You are on page 1of 6

Sinorix™

MANI50-DS, MANI50-EL90, MANI50-END, MANI50-T 222,


MANI50-NLxx
IG-01, IG-55, IG-100, IG-541, CO2

Fittings for DN50 high pressure manifolds and extension pipes


● Compatible with DN50 high pressure manifolds and extension pipes
● PN: 360 bar
● For use in Sinorix™ NXN, CDT, SDT, H2O Gas and CO2 automatic gas
extinguishing systems

Product codes:
MANI50-END - S54476-B710-A1
MANI50-DS - S54476-B716-A1
MANI50-EL90 - S54476-B722-A1
MANI50-T 222 - S54476-B728-A1
MANI50-NL Q2-M - S54476-B742-A1
MANI50-NL Q2-K - S54476-B742-A2
MANI50-NL F85 - S54476-B742-A3

A6V11849798_en--_b Smart Infrastructure


2022-06-28 Building Products
Use
These products must only be used with Sinorix™ fixed automatic extinguishing systems.

Functions
The fittings have been designed to be used in the high pressure network of a Sinorix™ gas
extinguishing system. They adapt the flow of extinguishant in high pressure manifolds and
extension pipes. They provide a flexible solution to meet any particular installation
specifications.

Type summary

Item Description Item Description

1 Coupling (S54476-B716-A1) 5 Thread union (S54476-B742-A1)

2 Elbow (S54476-B722-A1) 6 Manifold cap (S54476-B710-A1)

3 Swivel nut (S54476-B742-A3) 7 T-piece (S54476-B728-A1)

4 Seal head (S54476-B742-A2) - -

Equipment combinations

Reference Description Product code

MANI50-1-80-x 1-row DN50 manifold with 2 to 5 sockets for 80 l cylinders S54476-B754-A2


S54476-B754-A3
S54476-B754-A4
S54476-B754-A5

MANI50-2-80-x 2-row DN50 manifold with 4 to 10 sockets for 80 l cylinders S54476-B756-A4


S54476-B756-A6
S54476-B756-A8
S54476-B756-A10

MANI50-1-140-x 1-row DN50 manifold with 2 to 5 sockets for 140 l cylinders S54476-B750-A2
S54476-B750-A3
S54476-B750-A4
S54476-B750-A5

2
Siemens Schweiz AG A6V11849798_en--_b
Building Products 2022-06-28
Reference Description Product code

MANI50-2-140-x 2-row DN50 manifold with 4 to 10 sockets for 140 l cylinders S54476-B752-A4
S54476-B752-A6
S54476-B752-A8
S54476-B752-A10

MANI50-CUP QM-H Selector valve holder DN50 S54476-B734-A1

MANI50-OH QF-M Selector valve holder DN50 S54476-B706-A1

MANI50-OH QF-H Orifice holder S54476-B706-A2

MANI50-OH QM-M Selector valve holder DN50 S54476-B706-A3

MANI50-M85-G1 Selector valve holder DN25 S54476-B778-A1

MANI50-M85-G5/4 Selector valve holder DN32 S54476-B778-A2

MANI50-M85-G2 Selector valve holder DN50 S54476-B778-A3

MANI50-EXT116 High pressure extension pipe S54476-B700-A1

MANI50-EXT133 High pressure extension pipe S54476-B700-A3

MANI50-EXT277 High pressure extension pipe S54476-B700-A5

MANI50-EXT286 High pressure extension pipe S54476-B700-A7

MANI50-EXT311 High pressure extension pipe S54476-B700-A11

MANI50-EXT437 High pressure extension pipe S54476-B700-A15

MANI50-EXT750 High pressure extension pipe S54476-B700-A21

MANI50-EXT1200 High pressure extension pipe S54476-B700-A25

Product documentation

Type Title Document ref.

Mounting Sinorix™ NXN CDT-IG-x-300 A6V101065426


Sinorix™ CDT IG-100-300 NXN FR A6V12019059

Mounting Sinorix™ NXN SDT-IG-x-200, IG-x-300 A6V101065532

Mounting Sinorix™ NXN CO2 A6V101065538


Sinorix™ CO2 NXN FR A6V12019064

Notes
Safety
This product may only be installed by Siemens-authorized specialized installers, with
experience in the design, installation and maintenance of automatic extinguishing systems.
During installation, it must be ensured that:
● this product is installed in compliance with the accident prevention regulations and
national regulations in force,
● this product is used as intended,
● any danger is avoided,
● Siemens requirements are met (assembly instructions, technical instructions,
commissioning, and operating instructions),
● the operators have received and understood the information related to this product.
At commissioning, ensure compliance with the legislation in force, technical regulations and
safety instructions.

3
Siemens Schweiz AG A6V11849798_en--_b
Building Products 2022-06-28
Failure to comply with Siemens' instructions may result in serious bodily injury or significant
property damage, for which Siemens cannot be held liable.
Siemens reserves the right to make technical modifications and/or improvements at any
time.
Mounting

WARNING
Connection to the discharge piping
When connecting the high-pressure part to the discharge piping, always use a high-
pressure fitting with an internal thread. Remove the O-ring from the high-pressure fitting on
the discharge piping side at this connection point.

WARNING
No changes permitted
No product modifications permitted.

Using a light oil as a lubricant makes assembly, and particularly disassembly operations
easier.
Acid- and resin-free oil sprays, with or without PTFE additive, and recommended for use
with steel and elastomers (NBR) can be used.

Refer to the commissioning instructions for detailed assembly procedures.

Maintenance

Storage
● Store in its original packaging, protected from shocks.
● Store in a clean and dry location, protected from bad weather.

Transport
● During transport, use caps to protect the threads.

Inspection
● Check the good condition of the product.
● Check that each fitting has been properly tightened using the appropriate wrench. Re-
tighten if necessary.
● Check the integrity of the surface treatment.

The frequency of the product inspection is subject to applicable local regulations. For more
information, refer to the maintenance documentation.

4
Siemens Schweiz AG A6V11849798_en--_b
Building Products 2022-06-28
Technical data

Technical data

Nominal size DN50

Thread Female ISO 228-1 G 2" thread (Quantum)

Maximum operating pressure 360 bar

Gas IG-01, IG-55, IG-100, IG-541, CO2

Materials Galvanized steel, elastomer (NBR)

Operating temperature -20 °C to +50 °C, non-condensing

Transport and storage temperature -40 °C to +65 °C, non-condensing

Weight
MANI50-NL F85 1.6 kg
MANI50-NL Q2-K 1.1 kg
MANI50-NL Q2-M 0.8 kg
MANI50-DS 1.2 kg
MANI50-EL90 8.0 kg
MANI50-END 1.0 kg
MANI50-T 222 8.5 kg

OEM type

MANI50-NL F85 10050-9403


MANI50-NL Q2-K 10050-9402
MANI50-NL Q2-M 10050-9401
MANI50-DS 10050-1010
MANI50-EL90 10050-0606
MANI50-END 10050-1002
MANI50-T 222 10050-1131

Certifications and compliances

2014/68/EU (PED) Compliant

5
Siemens Schweiz AG A6V11849798_en--_b
Building Products 2022-06-28
Dimensions

Dimensions in mm

Issued by
© Siemens Switzerland Ltd, 2022
Siemens Switzerland Ltd
Technical specifications and availability subject to change without notice.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

Document ID A6V11849798_en--_b
Edition 2022-06-28