Panel 2 / 4 / 8 zone
For Fire detection purpose, the panel has On panel board are available: two
input terminals (Zones, 2,4 or 8 depending on the supervised output (NAC : Notification Appliance
model) for conventional detectors connection. Circuit) for alarm signalling devices (sirens,
These detectors behave as an open contact in beacon etc.), one not supervised relay output
stand by condition and become resistor equivalent activated when alarm is detected, one not
in alarm state. supervised relay output activated when a fault is
Moreover devices with same characteristic detected . the above mentioned not supervised
can be connected (e.g. manual call Point, gas relay are capable to switch loads up to 5A.
detectors etc.). The [DL] terminal (supervised open
Do not connect more than 30 devices on collector output) can be used to drive an external
each zone input. dialler, this terminal must be terminated with a
3900 Ώ end of line resistor for circuit supervision.
The [OC] output (not supervised open
collector) can be activated by one or more signals
selected by the installer among the ones
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 available.
Z1 R1 Z2 R2 Z3 R3 Z4 R4 Z5 R5 Z6 R6 Z7 R7 Z8 R8
For external device feeding are available
two terminals pair : [24V] which supply a
continuous voltage of 24V (1A), [24R] which
Input zones need a 3900Ώ end of line supply 24V (1A) switched off for few seconds
resistor and are capable to detect alarm, short during the reset.
circuit or open circuit conditions.
Wiring
Power Supply SOUNDER BEACON
Gas GAS
Closing DETECTOR
Valve -
S + +
+24V
rosso
+24V
nero
MANUAL + -
CALL POINT
C 1N4002
601CH 601H-R 601PH
3K9 1N4002
3K9
L2 L2 L2
3K9
L1 L L1 L L1 L
- End Of Line Resistors (3K9)
- Activation resistors (680 ohm)
- Call Point Activation resistors on the-
MANUAL
CALL
se lines with
POINT
MOTHER
BOARD
-
+
3K9
L1 L L1 L L1 L
HOLDER
DOOR
L2 L2 L2
+
3K9 -
Power Supply 12V
L1 L L1 L L1 L BAQ35T12
3K9 -
+
BEAM
DETECTOR RX
11 12 13 12 10 12 11 10 9 4 6 8 7 6 4
System
1 Housing for extinguishing module
2 Control Board
3 Mother board 2/4/8 zones The following figure shows the panel with
4 Holes for wall mounting all devices which can be connected: detectors,
5 Switching power supply Manual Call Points, dialler, Sounders, Extinguish
6 Batteries (2) 12 V / 7 Ah (not supplied) module, additional power supply (only for J408-8).
7 Wires entry point
8 thermal probe (optional)
9 Flat cable for extinguish module
connection (supplied with extinguishing
module kit)
10 Guides for the fixing cables
11 Supports for extinguishing module
12 Pins for extinguishing module housing
13 extinguishing module (optional)
Power Supply