Professional Documents
Culture Documents
Research Note
RN-2011-1
ACI 318 Design Provisions – The equation for de- Experimental Program
velopment length in Section 12.2.2 of the current U.S. Two series of tests were conducted at the Robert
design provisions (ACI 318, 2011) for #7 and larger bars L. and Terry L. Bowen Laboratory for Large-Scale Civil
is rearranged and simplified to Equation 1: Engineering Research, Purdue University in West La-
( )
fayette, Indiana, to evaluate the tensile strength of de-
fsu = 20√fć ℓs
db
(1) formed-bar lap splices with lengths varying from 20 to 85
bar diameters. In Series 1 presented in Table 1, twenty-
seven (27) prismatic coupons were tested monotonically
Equation 1 was expected to provide a lower bound in tension to failure. In Series 2, fifteen (15) beams were
estimate to the maximum steel stress developed for the tested to failure; specimen information is presented in
data plotted in Figure 1. The provisions allow designers Table 2. The beam lap splices were located in a region
to increase this value by providing more concrete cov- of nearly constant bending moment. The tests are de-
er, adding transverse confinement reinforcement, or a scribed in greater detail in the research report (Richter,
combination of both. Figure 1 illustrates that, for the data 2012) and are summarized herein.
available until 2001, Equation 1 provided a reasonable
lower bound for splices meeting the five criteria listed
above. Only after 2006, data suggesting that Equation 1
was un-conservative became available.
Figure 1 – Available data from tests conducted on beams with lap splices of uncoated, uncon-
fined, deformed reinforcing bars (adapted from the ACI 408 database)
Lap Splice
cb
cso
Type A
Type C
Bottom
2csi
ct
Figure 3 – Cross-sectional views of the Series-1 prismatic coupons. (Note the designations of “Top” and “Bottom” repre-
sent the bar position during concrete placement)
Test Series 1: Prismatic Coupons in Tension diameters. For Type D coupons, the side cover (cso) was
increased to 7.5db bar diameters, in addition to the top
Specimen Description – Each of the 27 specimens cover (ct) and one-half the clear spacing between bars
had two lap splices of #8 bars cast in a rectangular con- (csi). Nominal cross-sectional dimensions of the speci-
crete prism, as shown in Figure 2. Three splice lengths mens are shown in Table 1 and Figure 3.
were tested: 20db, 40db, and 60db. The reinforcing bars
extended past the ends of the concrete prisms to per- Grade 60, A706 bars (ASTM 2009) were used as the
mit load fixture attachment and were loaded in tension. main longitudinal reinforcement. Table 1 provides the
During testing, load was increased monotonically until relevant material properties and the specimen naming
failure. convention used.
Each test coupon had a minimum clear cover (cmin) Test Program – The specimens in Series 1 were de-
of 1.5db on at least one side. Type A coupons had all signed to investigate the effect of increasing the cover
three cover dimensions (cso, cb, and ct) and one-half the on one, two, and three sides of the splice, while keeping
clear spacing between bars (csi) equal to 1.5db. For Type the minimum bottom cover constant for different splice
B coupons, the cover dimension cast above the spliced lengths. By using tension coupons instead of beam
bars (ct) was increased to 7.5db. For Type C coupons, specimens, all three cover dimensions (cso, cb, and
both the top cover dimension (ct) and one-half the clear one-half the clear spacing between bars (csi) were made
spacing between bars (csi) were increased to 7.5db bar equal in Type A coupons, and varied for the other types.
Support Roller
Pedestal
T T
Figure 4 – Elevation view of the typical Series-2 beam specimen test setup
Figure 7 – Splice strength vs. splice length-to-bar diameter ratio (ls / db) for the Series-1 and -2 test specimens
Bond Stress Distribution over the Lap Splice 3) For deformed-bar lap splices meeting the five cri-
Length – Bond stress distributions were inferred from teria addressed earlier, that is: 1) bottom-cast, 2)
concrete surface strains measured along the length of clear cover equal to or exceeding 1db, 3) clear
the lap splices in the Series-2 beams. The inferred distri- spacing between spliced bars equal to or exceed-
butions illustrated that bond stresses were concentrated ing 2db, 4) no transverse reinforcement (uncon-
near the ends of each splice. In the center portion of fined), and 5) compressive strength of concrete
each splice, the bond stresses were smaller. not exceeding 10,000 psi [69 MPa], Equation 2
below provides a conservative estimate of the
The widths of bursting cracks in the plane of the lon- steel stress that can be developed:
gitudinal reinforcement also indicated the relative mag-
nitude of bond stresses throughout the length of each
lap splice. Crack width measurements made during the
( )
fsu = 20√fć ℓs ≤ 900 √fć
db
(2)
Contributors: The principal authors on this publication are Brian P. Richter and Santiago Pujol,
Ph.D., of Purdue University. This document represents a summary of their CRSI research project
on the subject topic; the final report should be referenced for more information on the research.
Keywords: Bond, development length, deformed bar, lap splice, reinforcement, reinforced concrete.
Reference: Concrete Reinforcing Steel Institute - CRSI [2014], “Tensile Strength of Lap Splices in
933 North Plum Grove Rd.
Reinforced Concrete Members,” CRSI Research Note RN 2011-1, Schaumburg, Illinois, 8 pp.
Schaumburg, IL 60173-4758
Note: This publication is intended for the use of professionals competent to evaluate the signifi- p. 847-517-1200 • f. 847-517-1206
cance and limitations of its contents and who will accept responsibility for the application of the www.crsi.org
material it contains. The Concrete Reinforcing Steel Institute reports the foregoing material as
a matter of information and, therefore, disclaims any and all responsibility for application of the Regional Offices Nationwide
stated principles or for the accuracy of the sources other than material developed by the Institute. A Service of the Concrete Reinforcing Steel Institute
©2014 This publication, or any part thereof, may not be
The opinions and findings expressed in this Research Note are those of the researchers and do not
reproduced without the expressed written consent of CRSI.
necessarily reflect the opinions or recommendations of the Concrete Reinforcing Steel Institute.