You are on page 1of 8

Research Note

Research Note
RN-2011-1

Tensile Strength of Lap Splices


in Reinforced Concrete Members
Introduction tonic tests conducted on beams with lap lengths
not exceeding 40 bar diameters (Orangun, et. al.
Current U.S. design provisions for lap splices 1977). But code design provisions often require
of deformed bars in tension were developed pri- splices to be longer than 40 bar diameters, as il-
marily from tests conducted on beam specimens lustrated in the previous examples. None of the
with lap lengths less than or equal to 40 bar di- failures described in the previous examples had
ameters (db). But design provisions often require the splices located in beams. In earthquakes,
splices to be longer than 40 bar diameters. Re- splices near critical sections are likely to experi-
cent structural failures have indicated the vulner- ence a stress equal to or exceeding their yield
ability of lap splices with splice length-to-bar-di- stress.
ameter (ℓs /db) ratios equal to or exceeding 40.
The available data from tests conducted until
In this study conducted at Purdue University, October 2001 on beams with lap splices of un-
the tensile strength of unconfined deformed-bar coated, deformed reinforcing bars were compiled
lap splices with different lengths was re-exam- by ACI Committee 408 (ACI 408, 2003). Until
ined. The focus was on lap splices with length- 2001, only 8 percent of the data came from tests
to-bar-diameter ratios of 40 or more (ℓs /db ≥ 40). of lap splices with lengths equal to or exceeding
The tensile strength of lap splices in configura- 40 bar diameters. Only after 2006, a significant
tions resembling those observed to have splice amount of data from tests of longer splices has
failures in the field was also examined. been published (El-Hacha, et. al. 2006; Seliem
et. al. 2009). Today, to the best of the researchers’
Background knowledge, only 14 percent of the available data
The tensile strength of lap splices of deformed comes from tests of splices with lengths equal
reinforcing bars in concrete has been studied ex- to or exceeding 40 bar diameters. This compiled
tensively in the past (ACI 408, 2003). Recent fail- test data is presented in Figure 1.
ures of deformed-bar lap splices in Turkey (Kilic
As shown in Figure 1, maximum steel stress
and Sozen, 2003), Japan (Kim and Shiohara, 
2012), and Chile (Song, et. al. 2012) have indi- developed (fsu) normalized by √fć in psi (where
fć is the concrete compressive strength in psi) is
cated the need to revisit the topic. These failures
had three commonalities: 1) the splice lengths plotted on the vertical axis and the splice length-
were equal to or exceeded 40 bar diameters; 2) to-bar diameter (ℓs /db) ratio is plotted on the hori-
the spliced bars were located in concrete sec- zontal axis. The available data from these refer-
tions entirely in tension (smoke stacks or chim- enced tests met the following five criteria:
neys) or concrete sections subjected to small ten-
1. Bottom-cast; in other words, the depth of
sile strain gradients, such as structural walls; and
concrete cast below bars did not exceed
3) they occurred during earthquakes.
12 in. [305 mm],
Current U.S. design provisions (ACI 318,
2. Minimum clear cover equal to or exceed-
2011) for lap splices of deformed bars in tension
ing 1 bar diameter (cmin ≥ 1db),
were developed primarily from static and mono-
3. Clear spacing between spliced bars equal to or Without more data from tests of splices meeting these
exceeding 2 bar diameters (csi ≥ db), criteria, it was difficult to confirm this conclusion. Thus,
the main objectives of this study were to contribute data
4. No transverse reinforcement was present (un- from tests of unconfined deformed-bar lap splices with
confined), and splice length-to-bar diameter ratios equal to or exceed-
ing 40, and to compare the strength of unconfined lap
5. Compressive strength of concrete (fć) not ex-
splices of different lengths.
ceeding 10,000 psi [69 MPa].

ACI 318 Design Provisions – The equation for de- Experimental Program
velopment length in Section 12.2.2 of the current U.S. Two series of tests were conducted at the Robert
design provisions (ACI 318, 2011) for #7 and larger bars L. and Terry L. Bowen Laboratory for Large-Scale Civil
is rearranged and simplified to Equation 1: Engineering Research, Purdue University in West La-

( )
 fayette, Indiana, to evaluate the tensile strength of de-

fsu = 20√fć ℓs
db
(1) formed-bar lap splices with lengths varying from 20 to 85
bar diameters. In Series 1 presented in Table 1, twenty-
seven (27) prismatic coupons were tested monotonically
Equation 1 was expected to provide a lower bound in tension to failure. In Series 2, fifteen (15) beams were
estimate to the maximum steel stress developed for the tested to failure; specimen information is presented in
data plotted in Figure 1. The provisions allow designers Table 2. The beam lap splices were located in a region
to increase this value by providing more concrete cov- of nearly constant bending moment. The tests are de-
er, adding transverse confinement reinforcement, or a scribed in greater detail in the research report (Richter,
combination of both. Figure 1 illustrates that, for the data 2012) and are summarized herein.
available until 2001, Equation 1 provided a reasonable
lower bound for splices meeting the five criteria listed
above. Only after 2006, data suggesting that Equation 1
was un-conservative became available.

Figure 1 – Available data from tests conducted on beams with lap splices of uncoated, uncon-
fined, deformed reinforcing bars (adapted from the ACI 408 database)

2 Tensile Strength of Lap Splices in Reinforced Concrete Members [RN-2011-01]


Table 1 – Selected properties and results from Series 1 prismatic coupons

Table 2 – Selected properties and results from Series 2 beams

CRSI Research Note 3


Figure 3 Concrete Prism
Reinforcing Bar

Lap Splice

Figure 2 – Plan view of typical Series-1 prismatic coupon

cb
cso

Type A

Type C
Bottom

2csi
ct

Type B Type D Top

Figure 3 – Cross-sectional views of the Series-1 prismatic coupons. (Note the designations of “Top” and “Bottom” repre-
sent the bar position during concrete placement)

Test Series 1: Prismatic Coupons in Tension diameters. For Type D coupons, the side cover (cso) was
increased to 7.5db bar diameters, in addition to the top
Specimen Description – Each of the 27 specimens cover (ct) and one-half the clear spacing between bars
had two lap splices of #8 bars cast in a rectangular con- (csi). Nominal cross-sectional dimensions of the speci-
crete prism, as shown in Figure 2. Three splice lengths mens are shown in Table 1 and Figure 3.
were tested: 20db, 40db, and 60db. The reinforcing bars
extended past the ends of the concrete prisms to per- Grade 60, A706 bars (ASTM 2009) were used as the
mit load fixture attachment and were loaded in tension. main longitudinal reinforcement. Table 1 provides the
During testing, load was increased monotonically until relevant material properties and the specimen naming
failure. convention used.

Each test coupon had a minimum clear cover (cmin) Test Program – The specimens in Series 1 were de-
of 1.5db on at least one side. Type A coupons had all signed to investigate the effect of increasing the cover
three cover dimensions (cso, cb, and ct) and one-half the on one, two, and three sides of the splice, while keeping
clear spacing between bars (csi) equal to 1.5db. For Type the minimum bottom cover constant for different splice
B coupons, the cover dimension cast above the spliced lengths. By using tension coupons instead of beam
bars (ct) was increased to 7.5db. For Type C coupons, specimens, all three cover dimensions (cso, cb, and
both the top cover dimension (ct) and one-half the clear one-half the clear spacing between bars (csi) were made
spacing between bars (csi) were increased to 7.5db bar equal in Type A coupons, and varied for the other types.

4 Tensile Strength of Lap Splices in Reinforced Concrete Members [RN-2011-01]


Stirrup
Clamps Hyd. Ram
Load Cell
Lap Splice
Tube

Support Roller
Pedestal
T T

Figure 4 – Elevation view of the typical Series-2 beam specimen test setup

3" 6" 3"


No transverse reinforcement was provided in the nearly
#11 constant moment region of the beams. Reinforcement
5"
was Grade 60, A615 bars (ASTM 2009). Table 2 pro-
vides the relevant material properties and the specimen
naming convention used.

During testing, two loading procedures were used.


In the first procedure, load was increased monotonical-
30" ly to failure. During the second loading procedure, the
loading was incrementally stopped after pre-selected
24-1/4" loads were reached (Richter, 2012). Once these loads
were achieved, the load application was stopped, and
the specimen was unloaded. The specimen was then
reloaded monotonically until failure. Table 2 indicates
which loading procedure was used for each specimen.
The first loading procedure is referred to as “monotonic”
in Table 2, and the second loading procedure is “reload-
17-5/8" ed.”

Figure 5 – Typical Series-2 beam cross section


Test Program – The specimens in Series 2 were de-
signed to study the difference in behavior of lap splices
with different lengths using a traditional beam-type spec-
imen.

The Series-1 specimens were also designed to examine Results


the tensile strength of lap splices located in regions with
Strength of Prismatic Coupons in Tension – Fig-
small strain gradients.
ure 6 shows the average splice strengths (average maxi-

mum steel stress developed normalized by √fć ) for each
Test Series 2: Rectangular Beams
splice length vs. the number of cover dimensions cso, cb,
Specimen Description – There were fifteen (15) ct, or csi (where half the clear bar spacing is considered
traditional beam specimens in the Series 2 tests, pre- as a fourth cover dimension) set equal to the minimum
sented in Table 2. Three splice lengths were tested in the cover of 1.5db bar diameters. Figure 6 illustrates that the
beams: 28db, 56db, and 85db. Each of the fifteen beams splice strength was reduced as an increasing number
was loaded in a four-point bending loading arrangement, of the cover dimensions were set equal to the minimum
as shown in Figure 4. Lap splices were located between cover.
supports in the region of nearly constant bending mo-
ment. Effect of Splice Length on Splice Strength – The
average splice strength is plotted against the ratio of
The beams had rectangular cross sections, as illus- splice length-to-bar diameter in Figure 7. The data are
trated in Figure 5. Longitudinal tension reinforcement presented for each prismatic coupon type and splice
consisted of two #11 bars. The minimum clear cover length in Series 1, and for each splice length in Series 2.
(cmin) was 3 in. [76 mm], which corresponds to 2⅛db. Figure 7 illustrates that the splice strength does increase

CRSI Research Note 5


Figure 6 – Average splice strength vs. number of cover dimensions equal to 1.5db for the Series-1 tests (refer-
ence Figure 3)

Figure 7 – Splice strength vs. splice length-to-bar diameter ratio (ls / db) for the Series-1 and -2 test specimens

6 Tensile Strength of Lap Splices in Reinforced Concrete Members [RN-2011-01]


with an increase in the splice length-to-bar diameter ra- These observations indicate a majority of the load
tio. But the strength does not increase proportionally to transfer in a spliced bar occurs near the ends of the two
the ratio of splice length-to-bar diameter, thus indicating bars being spliced. The non-uniform distribution of steel
a decrease in splice efficiency. The decrease in splice stress, which became more pronounced in longer splice
efficiency is more noticeable at lap lengths exceeding lengths, resulted in less efficient splices.
approximately 45db.
Conclusions and Recommendations
Comparison with Previous Tests of Deformed Bar
Lap Splices – The data from the Series 1 prismatic cou- 1) The Series 1 tests of prismatic coupons with ten-
pons and Series 2 beams are plotted with the available sion lap splices indicated that mean unit bond
ACI 408 data described previously in Figure 1. Figure 1 strength decreased as an increasing number of
illustrates the following: the side cover dimensions were set equal to the
minimum cover of 1.5 bar diameters (1.5db). For
1. Splice strengths reached in the Series 1 and Se- reference, the cover dimensions cso, cb, and ct
ries 2 tests with splice length-to-bar diameter (ℓs / are shown in Figure 3.
db) ratios between 20 and 60 fall within the scat-
ter of splice strengths reached in previous tests of 2) The results in this study indicated that increas-
lap splices with similar lap lengths, and ing the length of an unconfined lap splice beyond
approximately 45 bar diameters (45db) was an
2. Equation 1 can be un-conservative for splice inefficient way to increase the splice strength.
lengths exceeding approximately 45 bar diame- This inefficiency results from a non-uniform bond
ters. It is recommended that the steel stress pre- stress distribution along the lap splice length,

dicted by Equation 1 be capped at 900√fć . which is concentrated at the splice ends.

Bond Stress Distribution over the Lap Splice 3) For deformed-bar lap splices meeting the five cri-
Length – Bond stress distributions were inferred from teria addressed earlier, that is: 1) bottom-cast, 2)
concrete surface strains measured along the length of clear cover equal to or exceeding 1db, 3) clear
the lap splices in the Series-2 beams. The inferred distri- spacing between spliced bars equal to or exceed-
butions illustrated that bond stresses were concentrated ing 2db, 4) no transverse reinforcement (uncon-
near the ends of each splice. In the center portion of fined), and 5) compressive strength of concrete
each splice, the bond stresses were smaller. not exceeding 10,000 psi [69 MPa], Equation 2
below provides a conservative estimate of the
The widths of bursting cracks in the plane of the lon- steel stress that can be developed:
gitudinal reinforcement also indicated the relative mag-
nitude of bond stresses throughout the length of each
lap splice. Crack width measurements made during the

( ) 
fsu = 20√fć ℓs ≤ 900 √fć
db
(2)

beam tests showed that transverse crack widths due to


bursting were wider at the ends of each splice. Through- Equation 2 is similar to the expression in Section
out the center portion of each splice, the crack widths 12.2.2 of the ACI 318-11 design provisions for #7 and
were generally narrower. larger bars, except Equation 2 now includes an upper

limit of 900√fć (in psi) for the maximum steel stress that
The observation that unit bond stresses are not dis-
can be developed. According to Equation 2, increasing
tributed uniformly throughout the length of lap splices in
the lap splice length beyond 45db does not increase the
beams helps to explain the reduction in splice efficiency 
splice strength. If a steel stress exceeding 900√fć (in psi)
with an increase in splice length; this was clearly evident
is required, it is recommended the lap splice be moved
in the tests in this study. A comparison of the longitudinal
away from any critical sections or transverse reinforce-
concrete surface strain measurements and measure-
ment be provided to confine the splice region.
ments of transverse crack widths from bursting made in
the beam tests for different splice lengths showed the Acknowledgements
following trends:
This research was conducted by Purdue University
• The length at the end of each splice having a con- with the sponsorship of the Concrete Reinforcing Steel
centration of high bond forces remained nearly Institute (CRSI) and the National Institute of Standards
constant for each overall splice length, and and Technology (NIST). Reinforcing steel used in this
work was generously provided by ERICO International
• The length of the center portion of each splice
Corporation.
with relatively small bond stress increased as the
splice length increased.

CRSI Research Note 7


References Kim, S., and Shiohara, H. (2012), “Dynamic Re-
sponse Analysis of a Tall RC Chimney Damaged during
American Concrete Institute – ACI Committee 2007 Niigata-ken Chuetsu-Oki Earthquake,” Proceed-
318 (2011), Building Code Requirements for Structural ings of the Fifteenth World Conference on Earthquake
Concrete (ACI 318-11) and Commentary (ACI 318R-11), Engineering, Paper No. 3433.
Farmington Hills, Michigan, 503 pp.
Orangun, C.O.; Jirsa, J.O.; and Breen, J.E. (1977),
American Concrete Institute – ACI Committee 408 “A Reevaluation of Test Data on Development Length
(2003), Bond and Development of Straight Reinforcing and Splices,” ACI Journal, Proceedings (74) 3, pp. 114-
Bars in Tension (ACI 408-R03), Farmington Hills, Michi- 122.
gan, 49 pp.
Richter, B.P. (2012), “A New Perspective on the
ASTM International – ASTM A615 (2009), Standard Tensile Strength of Lap Splices in Reinforced Concrete
Specification for Deformed and Plain Carbon-Steel Bars Members,” MS Thesis, Purdue University, West Lafay-
for Concrete Reinforcement, ASTM A615 / A615M – 09b, ette, Indiana, 165 pp.
ASTM International, West Conshohocken, Pennsylva-
nia, 6 pp. Seliem, H.M.; Hosny, A.; Rizkalla, S.; Zia, P.; Briggs,
M.; Miller, S.; Darwin, D.; Browning, J.; Glass, G.M.;
ASTM International – ASTM A706 (2009), Standard Hoyt, K.; Donnelly, K.; and Jirsa, J.O. (2009), “Bond
Specification for Low-Alloy Steel Deformed and Plain Characteristics of ASTM A1025 Steel Reinforcing Bars,”
Bars for Concrete Reinforcement, ASTM A706 / A706M ACI Structural Journal, 106 (4), pp. 530-539.
– 09b, ASTM International, West Conshohocken, Penn-
sylvania, 6 pp. Song, C., Pujol, S., Lepage, A. (2012), “The Col-
lapse of the Alto Rio Building during the 27 February
El-Hacha, R., El-Agroudy, H., Rizkalla, S.M. (2006), 2010 Maule, Chile, Earthquake,” Earthquake Spectra,
“Bond Characteristics of High-Strength Steel Reinforce- 28 (S1), pp. S301-S334.
ment,” ACI Structural Journal, 103(6), pp. 771-782.

Kilic, S., and Sozen, M.A. (2003), “Evaluation of Ef-


fect of August 17, 1999, Marmara Earthquake on Two
Tall Reinforced Concrete Chimneys,” ACI Structural
Journal, 100(3), pp. 357-364.

Contributors: The principal authors on this publication are Brian P. Richter and Santiago Pujol,
Ph.D., of Purdue University. This document represents a summary of their CRSI research project
on the subject topic; the final report should be referenced for more information on the research.

Keywords: Bond, development length, deformed bar, lap splice, reinforcement, reinforced concrete.

Reference: Concrete Reinforcing Steel Institute - CRSI [2014], “Tensile Strength of Lap Splices in
933 North Plum Grove Rd.
Reinforced Concrete Members,” CRSI Research Note RN 2011-1, Schaumburg, Illinois, 8 pp.
Schaumburg, IL 60173-4758
Note: This publication is intended for the use of professionals competent to evaluate the signifi- p. 847-517-1200 • f. 847-517-1206
cance and limitations of its contents and who will accept responsibility for the application of the www.crsi.org
material it contains. The Concrete Reinforcing Steel Institute reports the foregoing material as
a matter of information and, therefore, disclaims any and all responsibility for application of the Regional Offices Nationwide
stated principles or for the accuracy of the sources other than material developed by the Institute. A Service of the Concrete Reinforcing Steel Institute
©2014 This publication, or any part thereof, may not be
The opinions and findings expressed in this Research Note are those of the researchers and do not
reproduced without the expressed written consent of CRSI.
necessarily reflect the opinions or recommendations of the Concrete Reinforcing Steel Institute.

Printed in the U.S.A.

You might also like