You are on page 1of 2

Page 1 Page 2 Page 3 Page 4

DESCRIPTION INSTALLATION INSTALLATION (continued) INSTALLATION (continued)

This manual describes the Bently Nevada™ 350800 The sensor may be ordered with or without a Flameproof Conduit Installations: Connect the sensor to the 3500/63 Hazardous
Hazardous Gas Sensor, a catalytic-bead gas sensor, (Ex d) housing. The application will determine the Gas Detection Monitor per the instructions in the
and contains instructions for its installation and sensor’s placement in conduit or a housing. The user System Operation and Maintenance Manual (Part
CONDUIT
maintenance. This manual is intended for use by those must evaluate the conditions at the site to determine the number 166848-01). Note that this monitor
experienced in the use of electronic instrumentation best sensor placement and installation. Some requires the use of an external power supply to
and machinery monitoring equipment. If you need considerations include: power the hazardous gas sensor (refer to the
350800 SENSOR
additional assistance contact the nearest GE Energy • Install sensors in areas where leaks may occur. system data sheet for ordering instructions).
office. • Recall that some gases are heavier than air when Install, configure, and calibrate the 350800
selecting locations of sensors. Hazardous Gas Sensor and 3500/63 Hazardous
WARNING: The Bently Nevada 350800 • Generally, orient sensors such that heads point Gas Monitor per the System Operation and
Hazardous Gas Sensor must be used only downward to prevent moisture from accumulating Maintenance manual, 166848-01.
WIND DIRECTION
with the Bently Nevada 3500/63 Hazardous on the sensor head.
Gas Detection Monitor to maintain • Position the sensor head facing the airflow if Housing Installations:
approvals from the proper agencies. airflow is over 2 meters/second.
• Sensor is approved for use in Zone 1 areas. Users
The 350800 Hazardous Gas Sensor, when used with must follow Zone 1 installation requirements
UP

the 3500/63 Hazardous Gas Detection Monitor, will where applicable. Also follow applicable laws and
detect the presence of hazardous gas from 0% LEL electrical wiring codes when installing sensor in NO CONNECT
(Lower Explosive Level) to 100% LEL of the hazardous conduit or Flameproof (Ex d) housing.
REFER TO 166848-01
FOR PROPER
gas for which it has been calibrated (methane or GROUND CONNECTIONS

hydrogen). The monitor’s Alert and Danger set point The following figures illustrate the recommended sensor
COLOR CODE
BLACK : - PWR
limits are configurable to alert the user to the conduit installations and sensor housing installations.
RED: CENTER
WHITE : +PWR
presence of specified levels of the hazardous gas. Note these examples assume hazardous gas density WIND DIRECTION

lighter than air.

Page 5 Page 6 Page 7 Page 8


CALIBRATION CALIBRATION (continued) CALIBRATION (continued) CALIBRATION (continued)

Only trained personnel should calibrate sensors. Step 1: Remove the gas regulator/calibration boot Step 3: Calibrate the sensor by using the
CAUTION: To ensure personal safety: assembly and calibration gas cylinder from the case. calibration procedure outlined in the System
Catalytic bead sensors will last for many years if not (NOTE: The 169038 & 175974 Calibration Gas Operation and Maintenance Manual, Part
exposed to adverse compounds or gases. Users must • Use safety glasses during the calibration Cylinders are sold separately.) Verify that the valve is number 166848-01.
calibrate new sensors, or sensors that have been in procedure. Refer to the MSDS that in the closed (fully clockwise) position. Inspect the
storage, to establish the operating parameters of the accompanies the test gas canister for any regulator and hose/cup assembly visually for cracks
sensor/monitor combination when first put into additional required PPE (Personal Protective and breaks. Replace if necessary.
service. Organic lead and silicon compounds can Equipment).
poison catalytic bead sensors resulting in an • Remove all ignition sources from the vicinity Step 2: Thread the regulator onto the calibration gas
irreversible loss of sensitivity. Also, certain other of sensor prior to performing the calibration cylinder. Verify that the regulator pressure gage
compounds, especially H2S and halogenated procedure. indicates at least ¼ full-scale pressure.
hydrocarbons, block reaction sites in the catalyst, • Review all local and national safety
which can cause a loss in sensitivity. This blocking is requirements before attempting to perform
temporary and in most cases a sensor will recover any operations with combustible gases.
after a period of operation in clean air. Additionally,
exposure of the sensor to salts, strong alkalis, acids or WARNING: To assure accuracy of calibration:
certain organics species can corrode elements of the
sensor and limit reliability and operating lifetime in an • The sensor channel must be calibrated using
unpredictable manner. For these reasons, GE Energy 50% LEL gas concentration of the gas to be Step 4: When the calibration procedure is
strongly recommends that calibration of the sensors detected to meet the performance complete, you will have turned the regulator
occur every 90 days. Also, if the sensor is knowingly specification. valve to the closed (fully clockwise) position and
exposed to gas, poisons or inhibitors, the user should • Sensor must be in the final installed removed the calibration cup from the sensor.
re-calibrate the sensor. Refer to the System Operation orientation and powered for a minimum of Unthread the regulator from the gas cylinder
and Maintenance manual, 166848-01, for a complete 30 minutes prior to calibration. and secure all calibration components in the
list of inhibitors and poisons, as well as for carrying case.
information on the process for calibrating sensors.
Page 9 Page 10 Page 11
SPECIFICATIONS1 SPECIFICATIONS (Cont.) SPECIFICATIONS (Cont.)

Operating temperature: Effect of humidity from 10% to 90% RH: 1 Applicable only when connected to the Bently

-40 °C to 200 °C (-40 °F to 392 °F) < ±5% LEL from baseline (baseline- room temperature, Nevada 3500/63 Hazardous Gas Monitor.
50% RH) Specifications subject to change without prior
Recommended storage temperature range: notification.
0 °C to 40 °C (32 °F to 104 °F) Response time to step change:
Sensor exceeds the approval agency requirements of: 2 As read from the verification screen in the

Sensitivity: ≤ 10s to reach 50% LEL reading when 100% LEL gas configuration software.
> 15 mV/% LEL CH42 applied (T50 time)
≤ 12s to reach 60% LEL reading when 100% LEL gas 3 GE Energy highly recommends recalibration of the

Accuracy (Room Temperature, calibrated with 50%LEL applied (T60 time) sensor every 90 days.
gas): ≤ 30s to reach 90% LEL reading when 100% LEL gas
±3% of full scale or applied (T90 time)
±10% of applied gas concentration, whichever is greater.
Long term zero drift (20C, 50% RH, 101 kPa):
Effect of temperature (zero gas) –40 °C to +200 °C: < ±2.5% LEL/month3
≤ ±5% LEL CH4
Long term sensitivity drift of output (20C, 50% RH, 101
kPa):
< 2.5 % Signal/month3

Poison resistance (T50 to 20ppm HMDS in 2.5% CH4 in


air):
> 75minutes. Refer to our Hazardous Gas Detection
System Operation and Maintenance manual, 166848-01
for list of possible poisons. *

Page 12 Page 13 Page 14


APPROVALS

Intentionally blank

PART No. 168724-01 REV J

NO CHANGES ALLOWED TO THIS DOCUMENT


WITHOUT PRIOR APPROVALS FROM APPLICABLE
APPROVALS AGENCIES

CONTACT INFORMATION * Denotes a trademark of Bently Nevada, Inc., a


wholly owned subsidiary of General Electric
Mailing Address: Company:
GE Energy Bently Nevada
1631 Bently Parkway South
Minden, NV 89423 © 2007-2011 Bently Nevada, Inc
USA All rights reserved.

Toll Free Telephone Number: Printed in the USA. Uncontrolled when transmitted
775.782.3611 electronically.
www.ge-mcs.com/bently

You might also like