MAX4 - 4AFRC2pp

en en Arc fault detection RCBO (AFDD).

MFR9143700-00

PLEASE NOTE
b .
b All applicable local, regional and national regulations must be complied with during the installation and use of this device.
b This device should not be installed if, when unpacking it, you observe that it is damaged.
b Schneider Electric cannot be held responsible in the event of noncompliance with the instructions in this document and in the documents to which it refers.
b The service instruction must be observed throughout the product life time.

1 Installation - wiring

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
b
b Use a voltage tester with a suitable rated voltage, in order to check that all active conductors aren’t energized.
Failure to follow these instructions will result in death or serious injury.

en There is no insulation between the phase/Line and the neutral bottom terminals whatever the position of the toggles.

4AFRC225
Regular test
C25
230/240V~
AFDD

O OFF
14 mm 1...16 mm² 1...10 mm²

2 N.m 5.5 mm PZ2

MFR9143700-00
08/2019 1/4
2 Dielectric test

NOTICE
RISK OF DAMAGE TO THE AFDD
Disconnect all input and output wires to the AFDD before performing an insulation resistance test (dielectric test).
Failure to follow these instructions can result in equipment damage.

3 Testing

WARNING
FIRE HAZARD
Run a self diagnostic test of AFDD after installing it, and then at regular intervals by pressing the Test button (marked T) for 1 second. (see drawing below).
Failure to follow these instructions can result in death, serious injury, or equipment damage.

en After turning the AFDD on, wait 2 seconds before pressing the test button.

4AFRC225
Regular test
C25
230/240V~
AFDD

O OFF

≤1s
4AFRC225
Regular test
4AFRC225
Regular test Clack!
C25 C25
230/240V~ 230/240V~
AFDD AFDD

O OFF

30mA

4AFRC225
Regular test

2s
C25
230/240V~
AFDD

30mA

MFR9143700-00 2/4
4 Diagnosis

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Disconnect all output wires prior to the diagnostic steps.
Failure to follow these instructions will result in death or serious injury.

After 60 seconds, the blinking sequence stops and the LED is continuously switched OFF.
en
Diagnosis operations are similar whether in top feed or bottom feed.

en Top Feeding en Output wires

4AFRC225
Regular test
C25
4AFRC225
Regular test
230/240V~
C25
230/240V~ AFDD 4AFRC225
C25
230/240V~
Regular test

AFDD AFDD
4AFRC225
Regular test
C25
230/240V~
O OFF AFDD

O OFF O OFF

O OFF

en Output wires en Bottom Feeding

30mA

5s L
x2 2s x2
4AFRC225 4AFRC225 Load*

2
Regular test
C25 Regular test
C25
230/240V~
AFDD
230/240V~ N
AFDD

1 O OFF
x3 2s x3
L

Load*

N
30mA
3 L
x4 2s x4
Load*

L
x5 2s x5
U > 275 V Load*

x6 2s x6
Internal
en
< 50 s fault

5s
5s 0mA
4AFRC225

4
Regular test
C25
230/240V~
AFDD

5s

en Reset diagnosis mode


30mA
5
0mA

MFR9143700-00 3/4
5 Maintenance

4AFRC2pp

4AFRC225
Regular test
C25
230/240V~
AFDD

O OFF

Clipsal by Schneider Electric (Australia) Pty Ltd

Gepps Cross

Customer Care Centre

www.clipsal.com
MFR9143700-00 © 2019 Clipsal Australia Pty Ltd - All rights reserved. 4/4