You are on page 1of 4

TECHNICAL SPECIFICATION OF 2xHSYRaY (CWS)

1x500 rm 6/10 (12) kV Cable


TYPE & SIZE OF CABLE
2xHSYRaY(CWS)
1x500 rm (mm²)
VOLTAGE GRADE, U0/U (Um)
Permissible Service Voltage, U₀/U
6/10 (12) kV
6.35/11 kV
RELEVANT STANDARDS
IEC 60502-2, IEC 60228
TECHNICAL SPECIFICATION
Cross-sectional area of conductor, nominal 500 mm2
Number of core 1 core
Material Annealed Copper
Maximum conductor temperature in normal operation 900C
Conductor
Class of conductor Class 2
Shape of conductor Stranded Circular Compacted
Minimum number of wire (manufacturing) 53 (61) No.
Minimum and maximum diameter of conductor 25.3 – 27.6 mm
Material Semi-conducting XLPE
Conductor Screen
Thickness 0.6 mm
Material Crosslink polyethylene (XLPE)
Thickness, nominal 3.4 mm
Insulation
Thickness, minimum 2.96 mm
Color of insulation Natural
Material Semi-conducting XLPE
Insulation Screen
Thickness 0.7 mm
Material Copper Wire
Metallic Screen
Number & Diameter of wire 44/1.0 No./mm
Metallic Screen Binder Material Copper Tape
Dimension (W x T) 15x0.06 mm
Material PVC
Inner Covering Color Black
Thickness 1.4 mm
Material Round Aluminium Wire
Armour
Diameter of Armour wire 2.5 mm
Binder (Optional) Material Non-woven Tape
Material PVC (ST-2)
Color Red
Sheath Thickness, nominal 2.5 mm
Thickness, minimum 1.80 mm
Overall diameter, approximate 50.6 ± 3 mm
Electrical Characteristics Other Characteristics

D.C resistance of conductor at 200C, maximum 0.0366 ohm/km Minimum bending radius 20 x Overall diameter

A.C resistance of conductor at 900C, maximum 0.050 ohm/km Capacitance of cables 0.619 µF/km

Insulation resistance at ambient temperature 10+ G. Ohm Inductance of cables 0.319 mH/km

A.C. Voltage test for 05 minutes (3.5U₀ kV) 21 kV Operating temperature -15⁰C to 90⁰C

Conductor short circuit rating in 1 sec 71.5 kA Weight of cable, approximate 6660 kg/km

Metallic screen short circuit rating in 1 sec 5.07 kA Armour short circuit rating in 1 20.86 kA
sec

Earth fault capacity (Screen +Armour) in 1 sec 25.93 KA 500 Meter


Standard packing length/Drum
Returnable Steel Drum

Current carrying capacity- A K M Iftakher Ahmed


Signature
a. in ground at 20°C (Direct Buried) 672 A In Charge (QC & PD)

b. in free air at 30°C (Open) 938 A Date 21 March, 2023

Calculation of Short Circuit Capacity of Conductor for 1 sec.


Cable Size: 1x500 mm2 11 kV, Under Ground XLPE Copper Cable

Conductor Short Circuit Capacity for 1 sec:

1. Number of Copper wire for conductor = 61


2. Diameter of each copper wire = 3.231 mm (approx.)
3. Area of total conductor (A) = (0.7854 x 3.2312 x 61) = 500.14 mm2
4. Temperature prior for short circuit (T0) = 90°C
5. Temperature during for short circuit (Tmax) = 250°C
6. Value of “ K “ factor for above (T0) and (Tmax) = 0.143
7. Value of “ t “ duration of short circuit (second)

KA
Short circuit current for 1 sec. (kA) Isc =
√t

0.143 x 500.14
=
√1

= 71.5 kA / 1 sec.
Calculation for Metallic Screen of withstands required fault current for 1 sec.

Cable Size: 1x500 mm2 11 kV, Under Ground XLPE Copper Cable

Metallic Screen Short Circuit Capacity:

1. Number of Copper wire for Metallic Screen = 44


2. Diameter of each copper wire = 1.0 mm
3. Area of total Metallic Screen( Copper Wire+ Copper Tape )

(A) = (0.7854 x 1.02 x 44) + (15 x 0.06) = 35.46 mm2

4. Temperature prior for short circuit (T0) = 90°C


5. Temperature during for short circuit (Tmax) = 250°C
6. Value of “ K “ factor for above (T0) and (Tmax) = 0.143
7. Value of “ t “ duration of short circuit (second)

KA
Short circuit current for 1 sec. (kA) Isc ==
√t

0.143 x 35.46
=
√1

= 5.07 kA / 1 sec.

Note: This satisfies the required fault current of 5.07 kA / 1 sec.


Calculation of Short Circuit Capacity of Armour for 1 sec.

Cable Size: 1x500 mm2 11 kV, Under Ground XLPE Copper Cable

Armour Short Circuit Capacity:

1. Number of Aluminium Armour wire = 50±2


2. Diameter of each Aluminium wire = 2.5 mm
3. Area of total Armour (A) = (0.7854 x 2.52 x50) = 245.44 mm2
4. Temperature prior for short circuit (T0) = 80°C
5. Temperature during for short circuit (Tmax) = 200°C
6. Value of “ K “ factor for above (T0) and (Tmax) = 0.085
7. Value of “ t “ duration of short circuit (second)

KA
Short circuit current for 1 sec. (kA) Isc =
√t

0.085x245.44

=
√1

= 20.86 kA / 1 sec.

Calculation for Earth fault capacity for 1 sec.

Earth fault capacity = Screen short circuit capacity + Armour short circuit capacity

= (5.07 + 20.86) kA / 1 sec.

= 25.93 kA / 1 sec.

All design calculation are to be calculate as per International Standard of IEC 60228, IEC 60502-2 & IEC 60287.