1x500 RM 2xHSYRaY CWS 11 KV - Docxx
1x500 RM 2xHSYRaY CWS 11 KV - Docxx
D.C resistance of conductor at 200C, maximum 0.0366 ohm/km Minimum bending radius 20 x Overall diameter
A.C resistance of conductor at 900C, maximum 0.050 ohm/km Capacitance of cables 0.619 µF/km
Insulation resistance at ambient temperature 10+ G. Ohm Inductance of cables 0.319 mH/km
A.C. Voltage test for 05 minutes (3.5U₀ kV) 21 kV Operating temperature -15⁰C to 90⁰C
Conductor short circuit rating in 1 sec 71.5 kA Weight of cable, approximate 6660 kg/km
Metallic screen short circuit rating in 1 sec 5.07 kA Armour short circuit rating in 1 20.86 kA
sec
KA
Short circuit current for 1 sec. (kA) Isc =
√t
0.143 x 500.14
=
√1
= 71.5 kA / 1 sec.
Calculation for Metallic Screen of withstands required fault current for 1 sec.
Cable Size: 1x500 mm2 11 kV, Under Ground XLPE Copper Cable
KA
Short circuit current for 1 sec. (kA) Isc ==
√t
0.143 x 35.46
=
√1
= 5.07 kA / 1 sec.
Cable Size: 1x500 mm2 11 kV, Under Ground XLPE Copper Cable
KA
Short circuit current for 1 sec. (kA) Isc =
√t
0.085x245.44
=
√1
= 20.86 kA / 1 sec.
Earth fault capacity = Screen short circuit capacity + Armour short circuit capacity
= 25.93 kA / 1 sec.
All design calculation are to be calculate as per International Standard of IEC 60228, IEC 60502-2 & IEC 60287.