REPORT

3933 US ROUTE 11 CORTLAND, NEW YORK 13045

Order No. 104129960 Date: December 20, 2019

REPORT NO. 104129960CRT-003a

AIR PERFORMANCE-PRESSURE DROP TESTS


ON A ZAMZAM 50cm BY 50cm SAND TRAP LOUVER

RENDERED TO

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT
INTRODUCTION

This report gives the results of air performance-pressure drop tests conducted on a sand
trap louver. The sample was selected and supplied by the client and received at the
laboratories on November 5, 2019. The sample appeared to be in new, unused condition
upon arrival.

AUTHORIZATION

Signed Intertek SWA and P. O. No. Q6819PNA18221

TEST METHOD

Leakage and Air Performance-Pressure Drop testing were conducted in accordance with
AMCA Standard 500-L-2015 entitled, “Laboratory Methods of Testing Louvers for Rating”.

Air Performance – Pressure Drop tests were performed with the louver setup per Test
Figure 6.1 “Air performance-pressure drop test”.

Air Volume was measured employing metering stations containing appropriately sized
orifice plates.

This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are
limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss,
expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek
name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results
in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification
program. Measurement uncertainty budgets have been determined for applicable test methods and are available upon request.
DESCRIPTION OF TEST SPECIMEN

ZAMZAM 50cm BY 50cm SAND TRAP LOUVER


The sample consisted of a 50x50 cm sand trap louver. The sample was constructed from
aluminum. The sample measured 19 ¼ inches square at the inlet and 22 ¾ inches square
at the face. The louver had three openings in the face each measuring 2 inches by 20 3/8
inches.

PRESSURE DROP TEST RESULTS

ZAMZAM 50cm BY 50cm SAND TRAP LOUVER


Static Pressure (Inches of
Test Number Air Volume, SCFM
Water)
1 -0.20 1063
2 -0.25 1147
3 -0.30 1262
4 -0.35 1367
5 -0.50 1526
6 -0.65 1670
7 -0.93 1924
8 -1.25 2148
9 -1.55 2350
10 -1.75 2444

Report No. 104129960CRT-003a Page 2 of 4 December 20, 2019


PRESSURE DROP GRAPH

ZAMZAM 50cm BY 50cm SAND TRAP LOUVER

1.8
Negative Static Pressure, inches of water

1.6

1.4

1.2

0.8

0.6

0.4

0.2

0
1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
Air Volume, SCFM

Report No. 104129960CRT-003a Page 3 of 4 December 20, 2019


REMARKS

Ambient Temperature: 68º F


Relative Humidity: 28%
Barometric Pressure: 28.68 in. Hg

CONCLUSION

The test method employed for this test has no pass-fail criteria; therefore, the evaluation of
the test results is left to the discretion of the client.

Date of Test: December 12, 2019

Report Approved by: Report Reviewed By:

Brian Cyr James R. Kline


Engineer Engineer/Quality Supervisor
Acoustical Testing Acoustical Testing

Attachments: None

Report No. 104129960CRT-003a Page 4 of 4 December 20, 2019