Professional Documents
Culture Documents
REF615 Appl 756378 ENe
REF615 Appl 756378 ENe
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, Finland
Telephone: +358 10 2211
Facsimile: +358 10 22 41094
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-6 and EN 60255-27 for the low
voltage directive. The IED is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................6
Product documentation set............................................................6
Document revision history.............................................................7
Related documentation..................................................................8
Document symbols and conventions..................................................8
Safety indication symbols..............................................................8
Document conventions..................................................................9
Functions, codes and symbols......................................................9
REF615 1
Application Manual
Table of contents
2 REF615
Application Manual
Table of contents
Applications.................................................................................93
Functions.....................................................................................93
Default I/O connections..........................................................94
Functional diagrams....................................................................95
Functional diagrams for protection.........................................96
Functional diagram for disturbance recorder and trip
circuit supervision.................................................................102
Functional diagrams for control and interlocking..................104
Section 6 Glossary.......................................................................121
REF615 3
Application Manual
4
1MRS756378 E Section 1
Introduction
Section 1 Introduction
This manual addresses the protection and control engineer responsible for
planning, pre-engineering and engineering.
REF615 5
Application Manual
Section 1 1MRS756378 E
Introduction
Decommissioning
Commissioning
Maintenance
Engineering
Operation
Installing
Engineering manual
Installation manual
Commissioning manual
Operation manual
Service manual
Application manual
Technical manual
Communication protocol
manual
en07000220.vsd
IEC07000220 V1 EN
Installation Manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in chronological order in which the IED should be installed.
6 REF615
Application Manual
1MRS756378 E Section 1
Introduction
Operation Manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for monitoring, controlling and
setting the IED. The manual also describes how to identify disturbances and how to
view calculated and measured network data to determine the cause of a fault.
Service Manual contains instructions on how to service and maintain the IED. The
manual also provides procedures for de-energizing, de-commissioning and disposal
of the IED.
Point List Manual describes the outlook and properties of the data points specific to
the IED. The manual should be used in conjunction with the corresponding
Communication Protocol Manual.
Download the latest documents from the ABB web site http://
www.abb.com/substationautomation.
REF615 7
Application Manual
Section 1 1MRS756378 E
Introduction
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
8 REF615
Application Manual
1MRS756378 E Section 1
Introduction
REF615 9
Application Manual
Section 1 1MRS756378 E
Introduction
10 REF615
Application Manual
1MRS756378 E Section 1
Introduction
REF615 11
Application Manual
12
1MRS756378 E Section 2
REF615 overview
2.1 Overview
REF615 is a dedicated feeder IED (intelligent electronic device) designed for the
protection, control, measurement and supervision of utility substations and
industrial power systems. REF615 is a member of ABB’s Relion® product family
and part of its 615 protection and control product series. The 615 series IEDs are
characterized by their compactness and withdrawable design.
Re-engineered from the ground up, the 615 series has been designed to unleash the
full potential of the IEC 61850 standard for communication and interoperability
between substation automation devices.
The IED provides main protection for overhead lines and cable feeders in
distribution networks. The IED is also used as back-up protection in applications,
where an independent and redundant protection system is required.
Depending on the chosen standard configuration, the IED is adapted for the
protection of overhead line and cable feeders in isolated neutral, resistance earthed,
compensated and solidly earthed networks. Once the standard configuration IED
has been given the application-specific settings, it can directly be put into service.
The 615 series IEDs support a range of communication protocols including IEC
61850 with GOOSE messaging, IEC 60870-5-103, Modbus® and DNP3.
REF615 13
Application Manual
Section 2 1MRS756378 E
REF615 overview
The IED consists of two main parts: plug-in unit and case. The plug-in unit content
depends on the ordered functionality.
14 REF615
Application Manual
1MRS756378 E Section 2
REF615 overview
1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and
featuring core-balance current transformers.
Rated values of the current and voltage inputs are basic setting parameters of the
IED. The binary input thresholds are selectable within the range 18…176 V DC by
adjusting the binary input setting parameters.
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and
the plug-in unit.
REF615 15
Application Manual
Section 2 1MRS756378 E
REF615 overview
B 4 1 11 (17)1) 10 (13)1)
C 4 - 4 6
D 4 - 12 (18)1) 10 (13)1)
E 4 52) 16 10
F 4 52) 16 10
A070704 V2 EN
Figure 2: LHMI
16 REF615
Application Manual
1MRS756378 E Section 2
REF615 overview
• Display
• Buttons
• LED indicators
• Communication port
2.4.1 LCD
The LHMI includes a graphical LCD that supports two character sizes. The
character size depends on the selected language. The amount of characters and
rows fitting the view depends on the character size.
3 4
A070705 V2 EN
1 Header
2 Icon
3 Content
4 Scroll bar (displayed when needed)
REF615 17
Application Manual
Section 2 1MRS756378 E
REF615 overview
2.4.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are also 11 matrix programmable alarm LEDs on front of the LHMI. The
LEDs can be configured with PCM600 and the operation mode can be selected
with the LHMI, WHMI or PCM600.
2.4.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. With push-buttons you can give open or close commands to one
primary object, for example, a circuit breaker, disconnector or switch. The push-
buttons are also used to acknowledge alarms, reset indications, provide help and
switch between local and remote control mode.
A071176 V1 EN
Figure 4: LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
The WHMI enables the user to access the IED via a web browser. The supported
web browser version is Internet Explorer 7.0 or later.
18 REF615
Application Manual
1MRS756378 E Section 2
REF615 overview
• Measurement display
• Disturbance records
• Phasor diagram
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
A070754 V3 EN
• Locally by connecting your laptop to the IED via the front communication port.
• Remotely over LAN/WAN.
2.6 Authorization
The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
REF615 19
Application Manual
Section 2 1MRS756378 E
REF615 overview
2.7 Communication
The IED supports a range of communication protocols including IEC 61850, IEC
60870-5-103, Modbus® and DNP3. Operational information and controls are
available through these protocols. However, some communication functionality,
for example, horizontal communication between the IEDs, is only enabled by the
IEC 61850 communication protocol.
The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.
20 REF615
Application Manual
1MRS756378 E Section 2
REF615 overview
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100BASE-TX) or the fibre-
optic LC connector (100BASE-FX). An optional serial interface is available for
RS-232/RS-485 communication.
REF615 21
Application Manual
22
1MRS756378 E Section 3
REF615 variants
Some of the functions included in the IED's standard configurations are optional at
the time of placing the order. The description of standard configurations covers the
full functionality including options, presenting the functionality, flexibility and
external connections of REF615 with a specific configuration as delivered from the
factory.
Functional diagrams
The functional diagrams describe the IED's functionality from the protection,
measuring, condition monitoring, disturbance recording, control and interlocking
perspective. Diagrams show the default functionality with simple symbol logics
forming principle diagrams. The external connections to primary devices are also
shown, stating the default connections to measuring transformers. The positive
measuring direction of directional protection functions is towards the outgoing feeder.
The functional diagrams are divided into sections which each constitute one
functional entity. The external connections are also divided into sections. Only the
relevant connections for a particular functional entity are presented in each section.
Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used
several times in the configuration. To separate the blocks from each other, the IEC
61850 name, IEC symbol and ANSI function number are appended with a running
number, that is an instance number, from one upwards. If the block has no suffix
after the IEC or ANSI symbol, the function block has been used, that is,
instantiated, only once. The IED’s internal functionality and the external
connections are separated with a dashed line presenting the IED’s physical casing.
REF615 23
Application Manual
Section 3 1MRS756378 E
REF615 variants
Signal Matrix
With Signal Matrix the user can modify the standard configuration according to the
actual needs. The IED is delivered from the factory with default connections
described in the functional diagrams for BI's, BO's, function to function
connections and alarm LEDs. Signal Matrix has a number of different page views,
designated as follows:
• Binary input
• Binary output
• Functions
The functions in different page views are identified by the IEC 61850 names with
analogy to the functional diagrams.
24 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
Functionality A B C D E F
Directional earth-fault protection, low stage, instance 2 ● ● - - ● ●
Directional earth-fault protection, high stage ● ● - - ● ●
Transient / intermittent earth-fault protection ● ● - - ● ●
Non-directional (cross-country) earth-fault protection, using calculated I0 ● ● - - ● ●
REF615 25
Application Manual
Section 3 1MRS756378 E
REF615 variants
Functionality A B C D E F
Fuse failure supervision - - - - ● ●
Measurement
Disturbance recorder ● ● ● ● ● ●
Three-phase current measurement ● ● ● ● ● ●
Sequence current measurement ● ● ● ● ● ●
Residual current measurement ● ● ● ● ● ●
Three-phase voltage measurement - - - ● ●
Residual voltage measurement ● ● - - ● ●
Sequence voltage measurement - - - - ● ●
Three-phase power and energy measurement - - - - ● ●
● = Included,○ = Optional at the time of the order
1) Note that all directional protection functions can also be used in non-directional mode.
2) Basic interlocking functionality: Closing of the circuit breaker can be enabled by a binary input signal. The actual interlocking scheme is
implemented outside the relay. The binary input serves as a "master interlocking input" and when energized it will enable circuit breaker
closing.
3) Extended interlocking functionality: The circuit breaker interlocking scheme is implemented in the relay configuration, based on primary
equipment position information (via binary inputs) and the logical functions available. The signal matrix of PCM600 can be used for
modifying the interlocking scheme to suit your application.
26 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
IECA070918 V5 EN
[1] Additional BIO-module (X110 in the diagram) is included in the IED variant B
REF615 27
Application Manual
Section 3 1MRS756378 E
REF615 variants
IECA070919 V5 EN
[2] Additional BIO-module (X110 in the diagram) is included in the IED variant D
28 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
GUID-FA7A5888-5288-4969-84D0-00354EAB3997 V3 EN
REF615 29
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071288 V5 EN
[3] Additional BIO-module (X110 in the diagram) is included in the IED variant B
30 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
A071290 V4 EN
[4] Additional BIO-module (X110 in the diagram) is included in the IED variant D
REF615 31
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-F7601942-ACF2-47E2-8F21-CD9C1D2BC1F0 V3 EN
32 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
GUID-5D0135B3-3890-497A-8AAA-0362730C8682 V1 EN
3.3.1 Applications
The standard configuration for directional earth-fault protection is mainly intended
for cable and overhead-line feeder applications in isolated and resonant-earthed
distribution networks.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
REF615 33
Application Manual
Section 3 1MRS756378 E
REF615 variants
3.3.2 Functions
Table 8: Functions included in the REF615 standard configuration with directional earth-fault
protection
Function IEC 61850 IEC ANSI
Three-phase non-directional overcurrent PHLPTOC1 3I> 51P-1
protection, low stage
Three-phase non-directional overcurrent PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent PHIPTOC1 3I>>> 50P/51P
protection, instantaneous stage
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Directional earth-fault protection, low stage, DEFLPDEF1 I0> → (1) 67N-1 (1)
instance 1
Directional earth-fault protection, low stage, DEFLPDEF2 I0> → (2) 67N-1 (2)
instance 2
Directional earth-fault protection, high stage DEFHPDEF1 I0>> → 67N-2
34 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings, thus
not included in the PCM600 functionality.
REF615 35
Application Manual
Section 3 1MRS756378 E
REF615 variants
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a core
balance current transformer. The signal marked with U0 represents the measured
residual voltage via open delta connected voltage transformers.
The functional diagrams describe the IED’s protection functionality in detail and
according to the factory set default connections.
A071316 V3 EN
36 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
Four overcurrent stages are offered for overcurrent and short-circuit protection.
The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary
input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and
NSPTOC2) are offered for phase unbalance protection. The inrush detection
block’s (INRPHAR1) output BLK2H enables either blocking the function or
multiplying the active settings for any of the described protection function blocks.
All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1
is used for overcurrent and LED 4 for negative-sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
There are four IED variant-specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The active setting
group can also be changed via a binary input if the binary input is enabled for this.
To enable the change of the active setting group via a binary input, connect a free
binary input with PCM600 to the ActSG input of the SGCB-block.
The active setting group defined by a parameter is overridden when a binary input
is enabled for changing the active setting group.
REF615 37
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071318 V4 EN
Three stages are offered for directional earth-fault protection. In addition, there is a
dedicated protection stage (INTRPTEF) either for transient-based earth-fault
protection or for cable intermittent earth-fault protection in compensated networks.
All operate signals are connected to the Master Trip and also to the alarm LEDs.
LED 2 is used for directional earth-fault and LED 3 for double earth-fault
protection operate indication.
38 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
A071320 V4 EN
Figure 15: Phase discontinuity, thermal overload and circuit breaker failure
protection
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker
position and the measured phase and residual currents. The breaker failure
protection has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for re-tripping its own breaker through the Master Trip 2. The TRBU
output is used to give a back-up trip to the breaker feeding upstream. For this
purpose, the TRBU operate output signal is connected to the output PO2 (X100:
8-9). LED 6 is used for back-up (TRBU) operate indication.
REF615 39
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071322 V4 EN
The arc protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
40 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
control command to the circuit breaker, either local or remote, also blocks the
autoreclose function via the CBXCBR-selected signal.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
DISTURBANCE RECORDER
RDRE1
PHLPTOC1-start BI#1 TRIGGERED LED7 (DR TRIGGERED)
PHHPTOC1-start BI#2
PHHPTOC2-start BI#3
PHIPTOC1-start BI#4
NSPTOC1-start BI#5
NSPTOC2-start BI#6
DEFLPDEF1-start BI#7
DEFLPDEF2-start BI#8
DEFHPDEF1-start BI#9
INTRPTEF1-start BI#10
PHLPTOC1-operate
EFHPTOC1-start BI#11
PHHPTOC1-operate PDNSPTOC1-start BI#12
PHHPTOC2-operate OR T1PTTR1-start BI#13
BI 1 (Blocking)
BI 2 (CB Closed)
BI 3 (CB Open)
TCSSCBR1
TRPPTRC1- trip OR BLOCK ALARM
OR LED9 (TCS ALARM)
TRPPTRC2- trip
TCSSCBR2
BLOCK ALARM
A071324 V4 EN
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:16-19) and TCSSCBR2 for PO4 X100:20-23). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC1) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.
REF615 41
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071326 V4 EN
The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1-
open_cb are connected directly to the output PO3 (X100:16-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
42 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
A071328 V3 EN
The ENA_CLOSE input, that is, enable the closing of the circuit breaker, in the
breaker control function block CBXCBR is a combination of the status of the
Master Trip. The open operation is always enabled.
A071330 V3 EN
The signal outputs from the IED are connected to give dedicated information on:
REF615 43
Application Manual
Section 3 1MRS756378 E
REF615 variants
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.
3.4.1 Applications
The standard configuration for directional earth-fault protection is mainly intended
for cable and overhead-line feeder applications in isolated and resonant-earthed
distribution networks.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.4.2 Functions
Table 10: Functions included in the REF615 standard configuration with directional earth-fault
protection
Function IEC 61850 IEC ANSI
Three-phase non-directional overcurrent PHLPTOC1 3I> 51P-1
protection, low stage
Three-phase non-directional overcurrent PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent PHIPTOC1 3I>>> 50P/51P
protection, instantaneous stage
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Directional earth-fault protection, low stage, DEFLPDEF1 I0> → (1) 67N-1 (1)
instance 1
Directional earth-fault protection, low stage, DEFLPDEF2 I0> → (2) 67N-1 (2)
instance 2
Directional earth-fault protection, high stage DEFHPDEF1 I0>> → 67N-2
44 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
REF615 45
Application Manual
Section 3 1MRS756378 E
REF615 variants
The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings, thus
not included in the PCM600 functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a core
balance current transformer. The signal marked with U0 represents the measured
residual voltage via open delta connected voltage transformers.
46 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The functional diagrams describe the IED’s protection functionality in detail and
according to the factory set default connections.
A071332 V4 EN
Four overcurrent stages are offered for overcurrent and short-circuit protection.
The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary
input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and
NSPTOC2) are offered for phase unbalance protection. The inrush detection
block’s (INRPHAR1) output BLK2H enables either blocking the function or
multiplying the active settings for any of the described protection function blocks.
All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1
is used for overcurrent and LED 4 for negative-sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
The upstream blocking from the start of the overcurrent second high stage
(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used
REF615 47
Application Manual
Section 3 1MRS756378 E
REF615 variants
for sending a blocking signal to the relevant overcurrent protection stage of the
IED at the infeeding bay.
There are four IED variant-specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The active setting
group can also be changed via a binary input if the binary input is enabled for this.
To enable the change of the active setting group via a binary input, connect a free
binary input with PCM600 to the ActSG input of the SGCB-block.
Table 11: Binary input states and corresponding active setting groups
BI state Active setting group
OFF 1
ON 2
The active setting group defined by a parameter is overridden when a binary input
is enabled for changing the active setting group.
48 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
DEFLPDEF1
I 0 > (1)
67N-1 (1)
I0 START
U0 OPERATE
X110 BLOCK
3 BI 2 (BACTRL) ENA_MULT
RCA_CTL
4
DEFLPDEF2
I0 > (2)
67N-1 (2)
I0 START
U0 OPERATE
BLOCK
ENA_MULT
RCA_CTL
67N-2
I0 START
U0 OPERATE
BLOCK
ENA_MULT
RCA_CTL
INTRPTEF1
I0 >
67NIEF
I0 START
U0 OPERATE
BLOCK BLK_EF
EFHPTOC1
I0 >>
51N-2
I0 START
BLOCK OPERATE LED3 (NEF OPERATE)
ENA_MULTI
Calculated Io
A071334 V4 EN
Three stages are offered for directional earth-fault protection. In addition, there is a
dedicated protection stage (INTRPTEF) either for transient-based earth-fault
protection or for cable intermittent earth-fault protection in compensated networks.
REF615 49
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071320 V4 EN
Figure 23: Phase discontinuity, thermal overload and circuit breaker failure
protection
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker
position and the measured phase and residual currents. The breaker failure
protection has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for re-tripping its own breaker through the Master Trip 2. The TRBU
output is used to give a back-up trip to the breaker feeding upstream. For this
purpose, the TRBU operate output signal is connected to the output PO2 (X100:
8-9). LED 6 is used for back-up (TRBU) operate indication.
50 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
A071338 V5 EN
The arc protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
REF615 51
Application Manual
Section 3 1MRS756378 E
REF615 variants
The circuit breaker availability for the autoreclosure sequence is expressed with the
binary input 4 (X110:6-7) by connecting the input signal to the CB_RDY input. In
case this signal is completely removed from the autoreclose function block with
PCM600, the function assumes that the breaker is available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.4.3.2 Functional diagram for disturbance recorder and trip circuit supervision
DISTURBANCE RECORDER
RDRE1
PHLPTOC1-start BI#1 TRIGGERED LED7 (DR TRIGGERED)
PHHPTOC1-start BI#2
PHHPTOC2-start BI#3
PHIPTOC1-start BI#4
NSPTOC1-start BI#5
NSPTOC2-start BI#6
DEFLPDEF1-start BI#7
DEFLPDEF2-start BI#8
DEFHPDEF1-start BI#9
INTRPTEF1-start BI#10
PHLPTOC1-operate
EFHPTOC1-start BI#11
PHHPTOC1-operate PDNSPTOC1-start BI#12
PHHPTOC2-operate OR T1PTTR1-start BI#13
BI 1 (Blocking)
BI 2 (CB Closed)
BI 3 (CB Open)
TCSSCBR1
TRPPTRC1- trip OR BLOCK ALARM
OR LED9 (TCS ALARM)
TRPPTRC2- trip
TCSSCBR2
BLOCK ALARM
A071324 V4 EN
52 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
autorecloser, the ARC protection signals and the three binary inputs from X120 are
also connected.
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:16-19) and TCSSCBR2 for PO4 X100:20-23). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC1) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.
A071326 V4 EN
The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1-
open_cb are connected directly to the output PO3 (X100:16-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
REF615 53
Application Manual
Section 3 1MRS756378 E
REF615 variants
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
A071344 V4 EN
There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
The remaining two not described in the functional diagram are available in
PCM600 for connection where applicable.
The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of
the line-side earth switch.
54 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector or breaker truck and earth switch position statuses and the statuses
of the master trip logics and gas pressure alarm and circuit-breaker spring charging.
This combination of interlocking conditions is called LOCAL_FEEDER_READY
and is transferred also to the remote end via binary signal transfer. The OKPOS
output from DCSXSWI defines if the disconnector or breaker truck is definitely
either open/in test position or close/in service position. This, together with the open
earth switch and non-active trip signals, activates the close-enable signal to the
circuit breaker control function block. The open operation is always enabled. The
auto-recloser close command signals are directly connected to the output contact
PO1 (X100:6-7).
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.
REF615 55
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071346 V4 EN
The signal outputs from the IED are connected to give dedicated information on:
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.
56 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
3.5.1 Applications
The standard configuration for non-directional earth-fault protection is mainly
intended for cable and overhead-line feeder applications in directly or resistance
earthed distribution networks.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.5.2 Functions
Table 13: Functions included in the REF615 standard configuration with non-directional earth-
fault protection
Function IEC 61850 IEC ANSI
Three-phase non-directional overcurrent PHLPTOC1 3I> 51P-1
protection, low stage
Three-phase non-directional overcurrent PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent PHIPTOC1 3I>>> 50P/51P
protection, instantaneous stage
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Non-directional earth-fault protection, low stage EFLPTOC1 I0> (1) 51N-1 (1)
Non-directional earth-fault protection, low stage EFLPTOC2 I0> (2) 51N-1 (2)
(Non-directional sensitive earth-fault)
Non-directional earth-fault protection, high stage EFHPTOC1 I0>> 51N-2
REF615 57
Application Manual
Section 3 1MRS756378 E
REF615 variants
58 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings, thus
not included in the PCM600 functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a
summation connection of the phase current transformers.
The functional diagrams describe the IED’s protection functionality in detail and
according to the factory set default connections.
REF615 59
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071348 V3 EN
Four overcurrent stages are offered for overcurrent and short-circuit protection.
The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary
input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and
NSPTOC2) are offered for phase unbalance protection. The inrush detection
block’s (INRPHAR1) output BLK2H enables either blocking the function or
multiplying the active settings for any of the described protection function blocks.
All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1
is used for overcurrent and LED 4 for negative-sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
There are four IED variant-specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The active setting
group can also be changed via a binary input if the binary input is enabled for this.
60 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
To enable the change of the active setting group via a binary input, connect a free
binary input with PCM600 to the ActSG input of the SGCB-block.
Table 14: Binary input states and corresponding active setting groups
BI state Active setting group
OFF 1
ON 2
The active setting group defined by a parameter is overridden when a binary input
is enabled for changing the active setting group.
EFLPTOC1
I0 >
51N-1
I0 START
BLOCK OPERATE
ENA_MULT
EFHPTOC1
I0 >>
51N-2
I0 START
BLOCK OPERATE
ENA_MULT
50N
I0 START
BLOCK OPERATE
ENA_MULT
EFLPTOC2
I0 >
51N-1
I0 START
BLOCK OPERATE LED3 (SEF OPERATE)
ENA_MULT
A071350 V4 EN
Four stages are offered for non-directional earth-fault protection. One stage is
dedicated to sensitive earth-fault protection.
All operate signals are connected to the Master Trip and also to the alarm LEDs.
LED 2 is used for directional earth-fault and LED 3 for the sensitive earth-fault
protection operate indication.
REF615 61
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071352 V4 EN
Figure 31: Phase discontinuity, thermal overload and circuit breaker failure
protection
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker
position and the measured phase and residual currents. The breaker failure
protection has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for re-tripping its own breaker through the Master Trip 2. The TRBU
output is used to give a back-up trip to the breaker feeding upstream. For this
purpose, the TRBU operate output signal is connected to the output PO2 (X100:
8-9). LED 6 is used for back-up (TRBU) operate indication.
62 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
A071354 V4 EN
The arc protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
REF615 63
Application Manual
Section 3 1MRS756378 E
REF615 variants
control command to the circuit breaker, either local or remote, also blocks the
autoreclose function via the CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the
CB_RDY input in DARREC1. In the configuration, this signal is not connected to
any of the binary inputs. As a result, the function assumes that the breaker is
available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.5.3.2 Functional diagram for disturbance recorder and trip circuit supervision
DISTURBANCE RECORDER
RDRE1
PHLPTOC1-start BI#1 TRIGGERED LED7 (DR TRIGGERED)
PHHPTOC1-start BI#2
PHHPTOC2-start BI#3
PHIPTOC1-start BI#4
NSPTOC1-start BI#5
NSPTOC2-start BI#6
EFIPTOC1-operate BI#19
EFLPTOC2-operate BI#20
PDNSPTOC1-operate BI#21
INRPHAR1-blk2h BI#22
T1PTTR1-operate BI#23
BI#24
DARREC1-unsuc_recl OR BI#31
BI#32
BI 1(Blocking)
BI 2 (CB Closed)
BI 3 (CB Open)
TCSSCBR1
TRPPTRC1- trip OR BLOCK ALARM
OR LED9 (TCS ALARM)
TRPPTRC2- trip
TCSSCBR2
BLOCK ALARM
A071356 V3 EN
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:16-19) and TCSSCBR2 for PO4 X100:20-23). Both functions are blocked
64 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
by the Master Trip (TRPPTRC1 and TRPPTRC1) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.
A071358 V4 EN
The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1-
open_cb are connected directly to the output PO3 (X100:16-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
REF615 65
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071360 V3 EN
The ENA_CLOSE input, that is, enable the closing of the circuit breaker, in the
breaker control function block CBXCBR is a combination of the status of the
Master Trip. The open operation is always enabled.
A071362 V3 EN
The signal outputs from the IED are connected to give dedicated information on:
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
66 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
ones not described in the functional diagram are available in PCM600 for
connection where applicable.
3.6.1 Applications
The standard configuration for non-directional earth-fault protection is mainly
intended for cable and overhead-line feeder applications in directly or resistance
earthed distribution networks.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.6.2 Functions
Table 15: Functions included in the REF615 standard configuration with non-directional earth-
fault protection
Function IEC 61850 IEC ANSI
Three-phase non-directional overcurrent PHLPTOC1 3I> 51P-1
protection, low stage
Three-phase non-directional overcurrent PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent PHIPTOC1 3I>>> 50P/51P
protection, instantaneous stage
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Non-directional earth-fault protection, low stage EFLPTOC1 I0> (1) 51N-1 (1)
Non-directional earth-fault protection, low stage EFLPTOC2 I0> (2) 51N-1 (2)
(Non-directional sensitive earth-fault)
Non-directional earth-fault protection, high stage EFHPTOC1 I0>> 51N-2
REF615 67
Application Manual
Section 3 1MRS756378 E
REF615 variants
68 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings, thus
not included in the PCM600 functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a
summation connection of the phase current transformers.
The functional diagrams describe the IED’s protection functionality in detail and
according to the factory set default connections.
REF615 69
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071364 V4 EN
Four overcurrent stages are offered for overcurrent and short-circuit protection.
The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary
input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and
NSPTOC2) are offered for phase unbalance protection. The inrush detection
block’s (INRPHAR1) output BLK2H enables either blocking the function or
multiplying the active settings for any of the described protection function blocks.
All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1
is used for overcurrent and LED 4 for negative-sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
The upstream blocking from the start of the overcurrent second high stage
(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used
for sending a blocking signal to the relevant overcurrent protection stage of the
IED at the infeeding bay.
There are four IED variant-specific setting groups. Parameters can be set
independently for each setting group.
70 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The active setting group (1...4) can be changed with a parameter. The active setting
group can also be changed via a binary input if the binary input is enabled for this.
To enable the change of the active setting group via a binary input, connect a free
binary input with PCM600 to the ActSG input of the SGCB-block.
Table 16: Binary input states and corresponding active setting groups
BI state Active setting group
OFF 1
ON 2
The active setting group defined by a parameter is overridden when a binary input
is enabled for changing the active setting group.
EFLPTOC1
I0 >
51N-1
I0 START
BLOCK OPERATE
ENA_MULT
EFHPTOC1
I0 >>
51N-2
I0 START
BLOCK OPERATE
ENA_MULT
50N
I0 START
BLOCK OPERATE
ENA_MULT
EFLPTOC2
I0 >
51N-1
I0 START
BLOCK OPERATE LED3 (SEF OPERATE)
ENA_MULT
A071350 V4 EN
Four stages are offered for non-directional earth-fault protection. One stage is
dedicated to sensitive earth-fault protection.
All operate signals are connected to the Master Trip and also to the alarm LEDs.
LED 2 is used for directional earth-fault and LED 3 for the sensitive earth-fault
protection operate indication.
REF615 71
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071352 V4 EN
Figure 39: Phase discontinuity, thermal overload and circuit breaker failure
protection
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker
position and the measured phase and residual currents. The breaker failure
protection has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for re-tripping its own breaker through the Master Trip 2. The TRBU
output is used to give a back-up trip to the breaker feeding upstream. For this
purpose, the TRBU operate output signal is connected to the output PO2 (X100:
8-9). LED 6 is used for back-up (TRBU) operate indication.
72 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
A071370 V4 EN
The arc protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
REF615 73
Application Manual
Section 3 1MRS756378 E
REF615 variants
The circuit breaker availability for the autoreclosure sequence is expressed with the
binary input 4 (X110:6-7) by connecting the input signal to the CB_RDY input. In
case this signal is completely removed from the autoreclose function block with
PCM600, the function assumes that the breaker is available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.6.3.2 Functional diagram for disturbance recorder and trip circuit supervision
DISTURBANCE RECORDER
RDRE1
PHLPTOC1-start BI#1 TRIGGERED LED7 (DR TRIGGERED)
PHHPTOC1-start BI#2
PHHPTOC2-start BI#3
PHIPTOC1-start BI#4
NSPTOC1-start BI#5
NSPTOC2-start BI#6
EFIPTOC1-operate BI#19
X110 EFLPTOC2-operate BI#20
DARREC1-unsuc_recl OR BI#31
BI#32
BI 1(Blocking)
BI 2 (CB Closed)
BI 3 (CB Open)
TCSSCBR1
TRPPTRC1- trip OR BLOCK ALARM
OR LED9 (TCS ALARM)
TRPPTRC2- trip
TCSSCBR2
BLOCK ALARM
A071372 V4 EN
74 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
autorecloser, the ARC protection signals and the three binary inputs from X120 are
also connected, as well as the autorecloser external start command from the binary
input 2 (X110:3-4).
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:16-19) and TCSSCBR2 for PO4 X100:20-23). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC1) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.
A071358 V4 EN
The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1-
open_cb are connected directly to the output PO3 (X100:16-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
REF615 75
Application Manual
Section 3 1MRS756378 E
REF615 variants
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
A071376 V4 EN
There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
The remaining two not described in the functional diagram are available in
PCM600 for connection where applicable.
The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of
the line-side earth switch.
76 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
the disconnector or breaker truck and earth switch position statuses and the statuses
of the master trip logics and gas pressure alarm and circuit-breaker spring charging.
This combination of interlocking conditions is called LOCAL_FEEDER_READY
and is transferred also to the remote end via binary signal transfer. The OKPOS
output from DCSXSWI defines if the disconnector or breaker truck is definitely
either open/in test position or close/in service position. This, together with the open
earth switch and non-active trip signals, activates the close-enable signal to the
circuit breaker control function block. The open operation is always enabled. The
auto-recloser close command signals are directly connected to the output contact
PO1 (X100:6-7).
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.
REF615 77
Application Manual
Section 3 1MRS756378 E
REF615 variants
A071378 V4 EN
The signal outputs from the IED are connected to give dedicated information on:
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.
78 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
3.7.1 Applications
The standard configuration for directional earth-fault protection is mainly intended
for cable and overhead-line feeder applications in isolated and resonant-earthed
distribution networks.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.7.2 Functions
Table 18: Functions included in the REF615 standard configuration including directional earth-
fault protection with phase voltage measurement
Function IEC 61850 IEC ANSI
Three-phase non-directional overcurrent PHLPTOC1 3I> 51P-1
protection, low stage
Three-phase non-directional overcurrent PHHPTOC1 3I>> (1) 51P-2 (1)
protection, high stage, instance 1
Three-phase non-directional overcurrent PHHPTOC2 3I>> (2) 51P-2 (2)
protection, high stage, instance 2
Three-phase non-directional overcurrent PHIPTOC1 3I>>> 50P/51P
protection, instantaneous stage
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Directional earth-fault protection, low stage, DEFLPDEF1 I0> → (1) 67N-1 (1)
instance 1
Directional earth-fault protection, low stage, DEFLPDEF2 I0> → (2) 67N-1 (2)
instance 2
Directional earth-fault protection, high stage DEFHPDEF1 I0>> → 67N-2
REF615 79
Application Manual
Section 3 1MRS756378 E
REF615 variants
80 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
freely selectable and a part of the disturbance recorder’s parameter settings, thus
not included in the PCM600 functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a core
balance current transformer. The signal marked with U0 represents the measured
residual voltage via open delta connected voltage transformers.
REF615 81
Application Manual
Section 3 1MRS756378 E
REF615 variants
The functional diagrams describe the IED’s protection functionality in detail and
according to the factory set default connections.
Four overcurrent stages are offered for overcurrent and short-circuit protection.
The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary
input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and
NSPTOC2) are offered for phase unbalance protection. The inrush detection
block’s (INRPHAR1) output BLK2H enables either blocking the function or
multiplying the active settings for any of the described protection function blocks.
Four overcurrent stages are offered for overcurrent and short-circuit protection.
The instantaneous stage (PHIPTOC1) can be blocked by energizing the binary
input 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and
NSPTOC2) are offered for phase unbalance protection. The inrush detection
block’s (INRPHAR1) output BLK2H enables either blocking the function or
multiplying the active settings for any of the described protection function blocks.
GUID-37D627C4-6097-4322-BACC-161CC6039EC5 V1 EN
All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1
is used for overcurrent and LED 4 for negative-sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
82 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The upstream blocking from the start of the overcurrent second high stage
(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used
for sending a blocking signal to the relevant overcurrent protection stage of the
IED at the infeeding bay.
There are four IED variant-specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The active setting
group can also be changed via a binary input if the binary input is enabled for this.
To enable the change of the active setting group via a binary input, connect a free
binary input with PCM600 to the ActSG input of the SGCB-block.
Table 19: Binary input states and corresponding active setting groups
BI state Active setting group
OFF 1
ON 2
The active setting group defined by a parameter is overridden when a binary input
is enabled for changing the active setting group.
REF615 83
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-1F3C1F26-6F11-4250-9476-82C47C3AC570 V1 EN
Three stages are offered for directional earth-fault protection. In addition, there is a
dedicated protection stage (INTRPTEF) either for transient-based earth-fault
protection or for cable intermittent earth-fault protection in compensated networks.
84 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
GUID-8BD4614B-2C4D-475E-ADC3-A376E213BF3C V1 EN
Figure 47: Phase discontinuity, thermal overload and circuit breaker failure
protection
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker
position and the measured phase and residual currents. The breaker failure
protection has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for re-tripping its own breaker through the Master Trip 2. The TRBU
output is used to give a back-up trip to the breaker feeding upstream. For this
purpose, the TRBU operate output signal is connected to the output PO2 (X100:
8-9). LED 6 is used for back-up (TRBU) operate indication.
REF615 85
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-86A27183-AE21-4420-AA8D-B53A43C77BBE V1 EN
The arc protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
86 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The circuit breaker availability for the autoreclosure sequence is expressed with the
binary input 4 (X110:6-7) by connecting the input signal to the CB_RDY input. In
case this signal is completely removed from the autoreclose function block with
PCM600, the function assumes that the breaker is available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.7.3.2 Functional diagram for disturbance recorder and trip circuit supervision
GUID-4BE45287-D708-41F3-851A-084A9AC3265E V1 EN
REF615 87
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-48DD2A49-CF29-4088-914B-7AE1629E18CA V1 EN
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:16-19) and TCSSCBR2 for PO4 X100:20-23). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC1) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.
88 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
GUID-4963C315-60C2-4C60-BE7F-B18D87A8D35E V1 EN
The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1-
open_cb are connected directly to the output PO3 (X100:16-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
REF615 89
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-4DED2926-A92A-4F6A-BCAA-7D9CD24ACFC8 V1 EN
There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
The remaining two not described in the functional diagram are available in
PCM600 for connection where applicable.
The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of
the line-side earth switch.
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
90 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
the disconnector or breaker truck and earth switch position statuses and the statuses
of the master trip logics and gas pressure alarm and circuit-breaker spring charging.
This combination of interlocking conditions is called LOCAL_FEEDER_READY
and is transferred also to the remote end via binary signal transfer. The OKPOS
output from DCSXSWI defines if the disconnector or breaker truck is definitely
either open/in test position or close/in service position. This, together with the open
earth switch and non-active trip signals, activates the close-enable signal to the
circuit breaker control function block. The open operation is always enabled. The
auto-recloser close command signals are directly connected to the output contact
PO1 (X100:6-7).
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.
REF615 91
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-572DA8CC-7A7D-4F9F-87C5-272A4283FB3E V1 EN
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.
The signal outputs from the IED are connected to give dedicated information on:
TPGAPC are timers and used for setting the minimum pulse length for the outputs.
There are four generic timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for
connection where applicable.
92 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
3.8.1 Applications
The standard configuration is mainly intended for comprehensive protection and
control functionality of circuit breaker controlled asynchronous motors. With
minor modifications this standard configuration can be applied also for contactor
controlled motors.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.8.2 Functions
Table 21: Functions included in the REF615 standard configuration including directional
overcurrent protection with voltage protection
Function IEC 61850 IEC ANSI
Three-phase directional overcurrent protection, DPHLPDOC1 3I> → (1) 67-1 (1)
low stage, instance 1
Three-phase directional overcurrent protection, DPHLPDOC2 3I> → (2) 67-1 (2)
low stage, instance 2
Three-phase directional overcurrent protection, DPHHPDOC1 3I>> → 67-2
high stage
Three-phase non-directional overcurrent PHIPTOC1 3I>>> 50P/51P
protection, instantaneous stage
Arc protection ARCSARC1 ARC (1) 50L/50NL (1)
ARCSARC2 ARC (2) 50L/50NL (2)
ARCSARC3 ARC (3) 50L/50NL (3)
Directional earth-fault protection, low stage, DEFLPDEF1 I0> → (1) 67N-1 (1)
instance 1
Directional earth-fault protection, low stage, DEFLPDEF2 I0> → (2) 67N-1 (2)
instance 2
Directional earth-fault protection, high stage DEFHPDEF1 I0>> → 67N-2
REF615 93
Application Manual
Section 3 1MRS756378 E
REF615 variants
94 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed and changed with
PCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocks
inside the IED’s standard configuration. Exceptions from this rule are the 12
analog channels available for the disturbance recorder function. These channels are
REF615 95
Application Manual
Section 3 1MRS756378 E
REF615 variants
freely selectable and a part of the disturbance recorder’s parameter settings, thus
not included in the PCM600 functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents
and 3U the three phase voltages. The signal marked with I0 represents the
measured residual current via a core balance current transformer. The signal
marked with U0 represents the measured residual voltage via open delta connected
voltage transformers.
The functional diagrams describe the IED’s protection functionality in detail and
according to the factory set default connections.
Four overcurrent stages are available for overcurrent and short-circuit protection.
Three of them include directional functionality (DPHxPDOC). The non-directional
instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1
(X120:1-2). Two negative-sequence overcurrent stages (NSPTOC1 and
NSPTOC2) are available for phase unbalance protection. The inrush detection
block’s (INRPHAR1) output BLK2H enables either blocking the function or
multiplying the active settings for any of the shown protection function blocks.
96 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
GUID-F0BE506C-0A96-4AA2-AC55-FFD9BCD23951 V1 EN
All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1
is used for overcurrent and LED 4 for negative-sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
The upstream blocking from the start of the overcurrent second high stage
(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used
for sending a blocking signal to the relevant overcurrent protection stage of the
IED at the infeeding bay.
There are four IED variant-specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The active setting
group can also be changed via a binary input if the binary input is enabled for this.
To enable the change of the active setting group via a binary input, connect a free
binary input with PCM600 to the ActSG input of the SGCB-block.
Table 22: Binary input states and corresponding active setting groups
BI state Active setting group
OFF 1
ON 2
REF615 97
Application Manual
Section 3 1MRS756378 E
REF615 variants
The active setting group defined by a parameter is overridden when a binary input
is enabled for changing the active setting group.
GUID-F82FE8A6-6AA1-44D9-8FE2-8B2C51CEA7AA V1 EN
Three stages are offered for directional earth-fault protection. In addition, there is a
dedicated protection stage (INTRPTEF) either for transient-based earth-fault
protection or for cable intermittent earth-fault protection in compensated networks.
98 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
GUID-5F0B30AD-0B3F-4B6D-BFAC-7209FA9DAACD V1 EN
Figure 56: Phase discontinuity, thermal overload and circuit breaker failure
protection
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker
position and the measured phase and residual currents. The breaker failure
protection has two operating outputs: TRRET and TRBU. The TRRET operate
output is used for re-tripping its own breaker through the Master Trip 2. The TRBU
output is used to give a back-up trip to the breaker feeding upstream. For this
purpose, the TRBU operate output signal is connected to the output PO2 (X100:
8-9). LED 6 is used for back-up (TRBU) operate indication.
REF615 99
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-EC907A8E-9CF0-4150-A394-FFBAF30A8725 V1 EN
The arc protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the arc protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
100 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
The circuit breaker availability for the autoreclosure sequence is expressed with the
binary input 4 (X110:6-7) by connecting the input signal to the CB_RDY input. In
case this signal is completely removed from the autoreclose function block with
PCM600, the function assumes that the breaker is available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
GUID-BCEB1C2E-BC64-4E79-8329-A5D9FCD7AB2F V1 EN
REF615 101
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-A77D0608-E3F2-4D3D-8907-15034FC42D51 V1 EN
GUID-54404411-CD8E-4277-A0A1-80B31CBD45EC V1 EN
3.8.3.2 Functional diagram for disturbance recorder and trip circuit supervision
102 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
GUID-A2EBA677-AEF4-451B-807B-20F50D5894C7 V1 EN
REF615 103
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-F06A3FEF-2C72-49A4-928F-D301335EC2C6 V1 EN
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:16-19) and TCSSCBR2 for PO4 X100:20-23). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC1) and the circuit breaker open
signal. The TCS alarm indication is connected to LED 9.
104 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
GUID-300441A3-AE3C-4BBF-8C5A-B5CA8BA4EF53 V1 EN
The operate signals from the protections are connected to the two trip output
contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding Master
Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker
from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1-
open_cb are connected directly to the output PO3 (X100:16-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the
trip signal duration setting. If the lockout operation mode is selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
REF615 105
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-DE498CFB-A256-4275-9A1F-5EF3B09046F4 V1 EN
There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
The remaining two not described in the functional diagram are available in
PCM600 for connection where applicable.
The binary inputs 5 and 6 of the additional card X110 are used for busbar
disconnector (DCSXSWI1) or circuit-breaker truck position indication.
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of
the line-side earth switch.
The circuit breaker closing is enabled when the ENA_CLOSE input is activated.
The input can be activated by the configuration logic, which is a combination of
106 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
the disconnector or breaker truck and earth switch position statuses and the statuses
of the master trip logics and gas pressure alarm and circuit-breaker spring charging.
This combination of interlocking conditions is called LOCAL_FEEDER_READY
and is transferred also to the remote end via binary signal transfer. The OKPOS
output from DCSXSWI defines if the disconnector or breaker truck is definitely
either open/in test position or close/in service position. This, together with the open
earth switch and non-active trip signals, activates the close-enable signal to the
circuit breaker control function block. The open operation is always enabled. The
auto-recloser close command signals are directly connected to the output contact
PO1 (X100:6-7).
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.
REF615 107
Application Manual
Section 3 1MRS756378 E
REF615 variants
GUID-79EB68EE-F160-402E-A841-BC6D074E7294 V1 EN
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured
current levels. The function introduces various supervision methods. The
corresponding supervision alarm signals are routed to LED 8.
The signal outputs from the IED are connected to give dedicated information on:
108 REF615
Application Manual
1MRS756378 E Section 3
REF615 variants
TPGAPC 1...3 are timers used for setting the minimum pulse length for the
outputs. Four generic timers (TPGAPC1..4) are available in the IED. The
remaining one not described in the functional diagram is available in PCM600 for
connection where applicable.
REF615 109
Application Manual
110
1MRS756378 E Section 4
Requirements for measurement transformers
The selection of a CT depends not only on the CT specifications but also on the
network fault current magnitude, desired protection objectives, and the actual CT
burden. The protection relay settings should be defined in accordance with the CT
performance as well as other factors.
The rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primary
current to the rated primary current. For example, a protective current transformer
of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For
protective current transformers, the accuracy class is designed by the highest
permissible percentage composite error at the rated accuracy limit primary current
prescribed for the accuracy class concerned, followed by the letter "P" (meaning
protection).
Table 24: Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class Current error at Phase displacement at rated primary Composite error at
rated primary current rated accuracy limit
current (%) minutes centiradians primary current (%)
5P ±1 ±60 ±1.8 5
10P ±3 - - 10
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent
protection. The 5P class provides a better accuracy. This should be noted also if
there are accuracy requirements for the metering functions (current metering,
power metering, and so on) of the relay.
REF615 111
Application Manual
Section 4 1MRS756378 E
Requirements for measurement transformers
The CT accuracy primary limit current describes the highest fault current
magnitude at which the CT fulfils the specified accuracy. Beyond this level, the
secondary current of the CT is distorted and it might have severe effects on the
performance of the protection relay.
In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy
limit factor (Fn) and is proportional to the ratio of the rated CT burden and the
actual CT burden.
Sin + Sn
Fa ≈ Fn ×
Sin + S
A071141 V1 EN
The nominal primary current I1n should be chosen in such a way that the thermal
and dynamic strength of the current measuring input of the relay is not exceeded.
This is always fulfilled when
The saturation of the CT protects the measuring circuit and the current input of the
relay. For that reason, in practice, even a few times smaller nominal primary
current can be used than given by the formula.
112 REF615
Application Manual
1MRS756378 E Section 4
Requirements for measurement transformers
The factor 0.7 takes into account the protection relay inaccuracy, current
transformer errors, and imperfections of the short circuit calculations.
The adequate performance of the CT should be checked when the setting of the
high set stage O/C protection is defined. The operate time delay caused by the CT
saturation is typically small enough when the relay setting is noticeably lower than
Fa.
When defining the setting values for the low set stages, the saturation of the CT
does not need to be taken into account and the start current setting is simply
according to the formula.
With definite time mode of operation, the saturation of CT may cause a delay that
is as long as the time the constant of the DC component of the fault current, when
the current is only slightly higher than the starting current. This depends on the
accuracy limit factor of the CT, on the remanence flux of the core of the CT, and
on the operate time setting.
With inverse time mode of operation, the delay should always be considered as
being as long as the time constant of the DC component.
With inverse time mode of operation and when the high-set stages are not used, the
AC component of the fault current should not saturate the CT less than 20 times the
starting current. Otherwise, the inverse operation time can be further prolonged.
Therefore, the accuracy limit factor Fa should be chosen using the formula:
The Current start value is the primary pickup current setting of the relay.
The following figure describes a typical medium voltage feeder. The protection is
implemented as three-stage definite time non-directional overcurrent protection.
REF615 113
Application Manual
Section 4 1MRS756378 E
Requirements for measurement transformers
A071142 V1 EN
The maximum three-phase fault current is 41.7 kA and the minimum three-phase
short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is
calculated to be 59.
The start current setting for low-set stage (3I>) is selected to be about twice the
nominal current of the cable. The operate time is selected so that it is selective with
the next relay (not visible in the figure above). The settings for the high-set stage
and instantaneous stage are defined also so that grading is ensured with the
downstream protection. In addition, the start current settings have to be defined so
that the relay operates with the minimum fault current and it does not operate with
the maximum load current. The settings for all three stages are as in the figure above.
For the application point of view, the suitable setting for instantaneous stage (I>>>)
in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the
criteria given by the current transformer selection formula is fulfilled and also the
relay setting is considerably below the Fa. In this application, the CT rated burden
could have been selected much lower than 10 VA for economical reasons.
114 REF615
Application Manual
1MRS756378 E Section 5
IED physical connections
5.1 Inputs
X120-9, 10 IL2
X120-11, 12 IL3
REF615 115
Application Manual
Section 5 1MRS756378 E
IED physical connections
Terminals X120/1-4 are binary input terminals. In the IED variants C and D, there
are additional binary inputs X120/5-6 included. In the IED variants B and D, an
additional BIOB01A-module is included in slot X110. Optional BIO-module
BIOB02A for slot X130 can be included at the time of order.
116 REF615
Application Manual
1MRS756378 E Section 5
IED physical connections
Terminal Description
X110-8 BI5, +
X110-9 BI5, -
X110-9 BI6, -
X110-10 BI6, +
X110-11 BI7, +
X110-12 BI7, -
X110-12 BI8, -
X110-13 BI8, +
Table 33: Binary input terminals X130-1...9, optional for configurations B and D
Terminal Description
X130-1 BI1, +
X130-2 BI1, -
X130-2 BI2, -
X130-3 BI2, +
X130-4 BI3, +
X130-5 BI3, -
X130-5 BI4, -
X130-6 BI4, +
X130-7 BI5, +
X130-8 BI5, -
X130-8 BI6, -
X130-9 BI6, +
REF615 117
Application Manual
Section 5 1MRS756378 E
IED physical connections
The IED is provided with connection sockets X13, X14 and X15
only if the optional communication module with light sensor inputs
has been installed. If the arc protection option is selected when
ordering an IED, the light sensor inputs are included in the
communication module.
5.2 Outputs
118 REF615
Application Manual
1MRS756378 E Section 5
IED physical connections
Output contacts of slot X110 are available only with configurations B and D.
Output contacts of slot X130 are available in the optional BIO module (BIOB02A).
REF615 119
Application Manual
Section 5 1MRS756378 E
IED physical connections
5.2.3 IRF
The IRF contact functions as an output contact for the self-supervision system of
the protection IED. Under normal operating conditions, the IED is energized and
the contact is closed (X100/3-5). When a fault is detected by the self-supervision
system or the auxiliary voltage is disconnected, the output contact drops off and the
contact closes (X100/3-4).
120 REF615
Application Manual
1MRS756378 E Section 6
Glossary
Section 6 Glossary
REF615 121
Application Manual
Section 6 1MRS756378 E
Glossary
122 REF615
Application Manual
123
Contact us
www.abb.com/substationautomation