Professional Documents
Culture Documents
Abstract— The changing nature of power flows from Increased reactive power requirements on the
unidirectional top-down approach to multi-level multi-directional distribution level will cause additional stress to the
generation and utilization, has led to creation of active distribution grid assets
networks. This shift in the generation structure poses different A change in consumption will cause a higher effect to
challenges to the transmission and distribution grids. With
efficiency, economics and coordinated operation of grids being the
the stability of the grid frequency due to decreasing
prime focus, voltage regulation and dynamic reactive power compensation by synchronous generators
compensation at generation, transmission and distribution level as High level of renewable generation is moving the
well as efficient evacuation of the generated power becomes operating point for conventional synchronous
critical. This paper briefs the existing voltage regulation practices generation units into economically unfavorable
in India as well as VAR exchange at the Interstate transmission regions with limited counteractions based on
system. and analyses the impact of renewable generation conventional infrastructure
integration on the voltage profile of the system.
Conventional infrastructure at the transmission level
For simulation, the 400 kV transmission network of the state of will cause service interruptions and frequent
Tamil Nadu has been modeled using DigSilent PowerFactory maintenance schedules due to dynamic fluctuations
considering all the major generation plants (greater than 100 and inadequate reactive power compensating
MW). Various operational scenarios were defined based on the equipment. This will dent the economics of power
hourly generation from wind and PV plants along with the load over lifetime of the equipment.
patterns throughout the year. The objective of this paper is to
evaluate the effect of large-scale integration of renewables and to
present technical solutions which would enable efficient,
economical, reliable and coordinated operation of the grid. Phase
shifting transformers and variable shunt reactor (a reactor, whose
inductance is varied using On Load Tap Changer (OLTC))
present dynamic solution to the challenges and these have been
validated by the simulation results. The simulation also
highlighted the importance of coordinated operation of
transformers.
I. INTRODUCTION
The Indian power network has evolved in terms of power flows
from a streamlined high voltage generation towards low voltage
consumption, to a decentralized generation and varying power
flow directions, as shown in Fig. 1 [1]. This varying nature of
power flows has an impact on the different parts of the power
system. The conclusions drawn from the evolution of such Figure 1: Evolution of the power grid from a inertia based
decentralized systems in the different parts of the world [2], will system to an inverter-based system [1]
serve as a guideline for the future grid planners and operators.
The exhaustive shift of generation capacity towards rural
Change of load balance and power flows cause an distribution grids is causing the physical effects of increased
increased requirement of reactive power and dynamic system voltage variation in the distribution grid, stress on
voltage fluctuations conventional infrastructure and increased reactive power
demand.
The overall objectives of this paper has been pictorially
represented in Fig. 2.
Fig. 4: Typical hourly wind generation pattern throughout a Based on the hourly load and generation patterns, shown in
year[14] Figures 4, 5, 6 and the characterizations of high and low
parameters in Table 2, the monthly and hourly occurrence of
the different highs are lows are derived and these are
summarized in Table 4 below.
The voltage at all the buses are within the permissible limits and
there are no line overloading in the system. This is shown in the Fig 8a: Kayathar grid in Scenario 3
network diagram shown in Fig. 7.
Fig. 7: Tamil Nadu Grid in base case Fig 8b: Kayathar grid in Scenario 3 with PST at bus 442004
ABISEK42 to bus 442072 SANKR2
5.2. Scenario 3 – High Wind, Low Solar and High Load
5.3. Operational scenarios 5-8
This scenario typically occurs during the evening hours of June-
October. High voltages are observed in 765 kV 447001 The 765 kV bus 447002 TRVLM is found to experience high
TRVLM and 400 kV 44024 TRVLM buses. Installing a 250 voltage in all the scenarios. Installation of a VSR of 250 MVAR
MVAR Variable Shunt Reactor (VSR) at 444024 TRVLM at the adjacent 440 kV bus 444024 TRVLM helps in bringing
helps in reducing the voltage at the 765 kV 447002 TRVLM down the voltage within limits.
bus. The usage of a Phase Shifting Transformers (PST) is
proposed as a solution to divert the flows through the congested During low wind and low load scenarios, there are occurrences
lines in the Kayathar grid during high wind and high load of high voltage at around 4-5 buses as discussed in the
scenarios. Here, a PST of 220kV and 600 MVA is introduced operational feedback and the scenarios simulated. Installation
at bus 442004 ABISEK 42 to line 18 (which goes to 442072 of VSR of 250 MVAR at the 444015 PUGALUR and 444030
UDAYATR2). The grid condition before and after the KAYATHAR sub-station along with the VSR at 444024
introduction of a PST is shown in Fig.8a and b. Loading of line TRVLM helps in bringing down the voltage at all the high
18 has been increased by 30% thereby reducing congestion in voltage nodes within operating limits as can be seen in Fig 9.
adjacent lines.
Table 6- Summary of the solutions for the different Operational ACKNOWLEDGEMENT
scenarios considered for simulation The authors acknowledge the Southern Regional Load Dispatch
Center (SRLDC), Bangalore, India for providing the data of the
Indian transmission network for research.
REFERENCES