ARCHITECTURE

FILE LOCATION:
C:\USERS\JOSE\VITAL ENGINEERING DROPBOX\JOSE RAMIREZ\PROJECTS\2021\21055 250 MERRICK RESIDENTIAL DEVELOPMENT\WORK DRAWINGS\E-5.00 ENLARGED PLANS TYPICAL UNITS
TYPE 'A'.DWG

PRINTED ON:10.10.2022
P L A N N I N G
GENERAL NOTES FOR APARTMENTS: I N T E R I O R S
1. ALL LIGHT FIXTURES LOCATIONS ARE TO BE COORDINATED WITH CERTIFICATIO N No. AA0002451
MECHANICAL TRADE PRIOR TO INSTALLATION.
2. ALL CONTROL WIRING FOR THERMOSTAT SHALL BE DONE BY THIS 4533 PONCE DE LEON BLVD.
CONTRACTOR PER UNIT MANUFACTURER WIRING DIAGRAM. Coral Gables, Florida 33146
3. CIRCUIT NUMBERS FOR LIGHTS AND RECEPTACLES AS SHOWN IS FOR TEL: (305) 740-5442
GUIDANCE ONLY. THIS CONTRACTOR MAY CHANGE CIRCUITING TO SUIT FIELD FAX: (305) 740-5443
CONDITIONS. HOWEVER, ALL CIRCUITING SHALL COMPLY WITH LATEST E-MAIL: info@beharfont.com
15 CODES AND STANDARDS. NOTIFY ENGINEER OF ANY CHANGE, AND IF
BALCONY ACCEPTABLE, DRAWINGS WILL BE REVISED. DIRECTORIES IN PANELS SHALL © 2019 BEHAR FONT & PARTNERS P.A.
S.05 DESCRIBE ROOMS AND APPLIANCES SERVED BY EACH CIRCUIT. THE DESIGN AND DRAWINGS FOR THIS
14 16 17 1 4. COORDINATE LOCATION OF OUTLETS FOR APPLIANCES WITH APPLIANCES PROJECT ARE THE PROPERTY OF THIS
GFI 13 ARCHITECT AND ARE PROTECTED UNDER THE
9 2 13 WP REPRESENTATIVE IN ORDER TO AVOID OUTLET'S PLUGS FROM PREVENTING COPYRIGHT PROTECTION ACT.

GFI GFI APPLIANCES FROM RESTING AGAINST REAR WALLS.


12" MIN. SEAL:
5. ALL APPLIANCES LOADS ARE NAMEPLATE RATING. IN CASE PURCHASED
12 8 GFI S.01 APPLIANCES ARE DIFFERENT, CALCULATIONS MUST BE CORRECTED TO
10 9 20,22 14 13 14 14

3'-0"
5 1 14 VERIFY SIZE OF CIRCUIT BREAKERS, CONDUCTORS, ETC.
S.01 12
1 6 . ALL OUTLET LOCATION AND HEIGHTS IN BATHROOMS & KITCHENS MUST BE
GFI A/C 15 S.02
1,3 A/C 12 1 COORDINATED WITH ARCHITECT AND SHALL COMPLY WITH ADA & FHA
6 8 12 13
12 DISTANCES AND HEIGHT REQUIREMENTS. ALL OUTLETS IN KITCHEN MUST BE
13 M BALCONY MASTER 14 COORDINATED WITH KITCHEN CABINETRY SHOP DWGS. CONTRACTOR MUST
6 M BATHROOM MASTER BEDROOM GFI 14 7 VERIFY EXACT DIMENSIONS ON SITE AND ADD RECEPTACLES AS REQUIRED.
2,4 1
12 3 BEDROOM 7. OUTLETS IN COMMON WALLS DIVIDING APARTMENTS SHALL NOT BE
50A 13 S.03 14 12" MIN.
GFI S.01 14 1 INSTALLED BACK TO BACK. THEY MUST BE INSTALLED AT A MINIMUM OF 24" OF
1 GFI
12 S.03 14 14 S.03 12 SEPARATION. EACH BOX SHALL BE WRAPPED WITH FIRE RETARDANT
8 12 1 S 5 MATERIAL APPROVED FOR THE PURPOSE. OUTLETS/JUNCTION BOXES
5 1 13 H S.01 12
10 S.04 S.01 1 JOSE A. RAMIREZ, P.E.
14 INSTALLED IN APARTMENT COMMON AREAS OR RATED WALL, SHALL NOT
GFI 1 12 1 W.L. P.E. 0060224
LIVING/DINING COMPROMISE THE WALL INTEGRITY. REFER TO INSTALLATION DETAIL ON
CONSULTANT:
4 GFCI 13 SHEET E-0.01.
GFCI 8. SMOKE DETECTORS ARE TO BE PHOTOELECTRIC TYPE AC-DC TYPE WITH
H 14 S.05 WP BATHROOM
KITCHEN 17 1 13 A BATTERY BACK-UP WITH CONTACTS FOR TANDEM CONNECTIONS TO OTHER
11 W/D GFI 14 D
7 8 13 12 DETECTORS WITHIN THE APARTMENT FOR SIMULTANEOUS ALARM AND FOR
GFI 30A 3 7 14 10
3 GFCI REMOTE ANNUNCIATION IN THE BUILDING SECURITY ALL SMOKE DETECTORS
GFI 10 16,18
8 S S GFI 13 AT EACH APT. UNIT SHALL BE INTERLOCKED SO THAT AUDIBLE ALARM IS
D S.01 S.01 SOUNDED AT ALL DETECTORS UPON ALARM IN ANY DETECTOR. INSTALL
12 13 1 12
5
12
3 GFI D D 12 B 1
SMOKE DETECTORS A MIN. OF 3'-0" FROM A/C DIFFUSERS, BATHROOMS AND
A
3 13 14 W.I.C.
14 B
12 8 W.L. 12 16 17 WITHIN 20'-0" OF COOK TOPS IN KITCHENS.
S.02 12
1 9.SMOKE DETECTORS WHEN WALL MOUNTED SHALL BE INSTALLED WITH TOP
11 10 14 14 11 30A 12
3 S.02 12 17 M 13 NOT LESS THAN 4 INCHES NOR MORE THAN 12 INCHES BELOW THE CEILING.
W.I.C. 8 S.03 M
7 1 10. LIGHT FIXTURES IDENTIFICATION AT UNITS SHALL BE SELECTED BY
GFI 10 1
3 14 8 5 GFCI 16,18 A/C 2 ARCHITECT AND/OR INTERIOR DESIGNER. THEY SHALL BE PROVIDED AND
12 14 3
12 3 3 GFI
13 W/D 1,3 A/C WIRED BY ELECTRICAL CONTRACTOR. PROVIDE KEYLESS PORCELAIN
10 D DA 13 20,22 LAMPHOLDER WITH 60 WATT LAMP ON A TEMPORARY BASIS.
B 10 4
GFI GFCI 30A 11. LIGHT FIXTURES SHALL NOT BE USED AS RACEWAY FOR CIRCUIT
S S 14 GFI
17 LIVING/DINING CONDUCTORS UNLESS MARKED FOR USE AS A RACEWAY.
14 3 16,18 S.04 10
1 GFCI 12. CIRCUIT BREAKER CONNECTORS AT APARTMENT LOAD CENTERS AND
GFCI 1 WIRING DEVICE CONTACTS SHALL BE RATED 75 DEGREES C.
W/D 12 11 S.01
7 3 1 13. ALL DISCONNECT SWITCHES IN APARTMENT UNITS FOR WATER HEATERS
13
14 W.L. 12 AND FAN COIL UNITS SHALL BE INSTALLED IN COMPLIANCE WITH N.E.C. ART.
12 12 110.26 WORKING CLEARANCES.
S.03 KITCHEN 8 5 13
S.03 1 12 14. CONTRACTOR SHALL VERIFY FAN COIL UNIT CIRCUIT BREAKER SIZE IN
GFI
1 13 14 S.01 S.01 50A APARTMENT ELECTRICAL PANELS WITH INFORMATION INCLUDED IN
MASTER 1 1 12 GFI S.04 3 INSTALLED FAN COIL UNIT NAMEPLATE AND MAKE ANY REQUIRED
LIVING/DINING 10 2,4 6 S 1
BEDROOM 12 MODIFICATION, INCLUDING CIRCUIT BREAKER AND WIRE SIZE, TO MATCH
1 6 D B GFI GFI INFORMATION SHOWN IN NAMEPLATE.
S.01 12
13 BB BATHROOM 1 10 8 15. ALL 125 VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER
1 10 9
1,3 RESISTANT RECEPTACLES TO COMPLY WITH NEC ARTICLE 406.12.
12 GFI 12 9
14 12 H GFI 16. ALL WIRING DEVICES SHALL BE WHITE COLOR, DECORA TYPE. RECEIVED

3'-0"
13 5 12 A/C
A/C 17. COMBINATION SMOKE/CARBON MONOXIDE DETECTORS AND INDIVIDUAL
14
S.01
12 20,22 3
9 8 12 8 KITCHEN CARBON MONOXIDE SENSORS ARE TO BE AC-DC TYPE WITH BATTERY
4/20/2023
1 GFI M
M GFI 3 4 BACK-UP WITH CONTACTS FOR TANDEM CONNECTIONS TO OTHER
GFI DETECTORS WITHIN THE APT. UNIT FOR SIMULTANEOUS ALARM. ALL
GFI WP S.05 12" MIN. 2 GFCI 8
COMBINATION SMOKE/CARBON MONOXIDE DETECTORS, INDIVIDUAL CARBON
13 1 10 GFI
13 13 9 14 14 MONOXIDE SENSORS AND/OR INDIVIDUAL SMOKE DETECTORS AT EACH APT.
16 17 8 10 7 11 6 2,4 8 UNIT SHALL BE INTERLOCKED SO THAT AUDIBLE ALARM IS SOUNDED AT ALL
15 GFI GFI GFI 12 DETECTORS UPON ALARM IN ANY DETECTOR. INSTALL SMOKE/CARBON
GFCI 50A

PROPOSED MIXED-USE RENTAL DEVELOPMENT:


3'-0" MONOXIDE DETECTORS A MIN. OF 3'-0" FROM A/C DIFFUSERS, BATHROOM
AND WITHIN 20'-0" OF THE COOK TOPS IN KITCHENS. COMBINATION
5 6 SMOKE/CARBON MONOXIDE DETECTORS AND INDIVIDUAL CARBON MONOXIDE
SENSORS DEVICE AND INSTALLATION SHALL COMPLY WITH LATEST THE
FLORIDA BUILDING CODE SECTION R314 AND R315.

4101 SALZEDO STREET CORAL GABLES, FLORIDA 33146


18. ELECTRICAL INSTALLATION FOR TYPICAL APARTMENT UNITS SHALL COMPLY
THE FLORIDA BUILDING CODE ENERGY SECTION 405.1.

ENLARGED PLAN - UNIT TYPE 'A-1' ENLARGED PLAN - UNIT TYPE 'A-1B' ENLARGED PLAN - UNIT TYPE 'A-2' 19. OUTLETS MUST BE LOCATED A MINIMUM OF 36 INCHES FROM AN INSIDE
CORNER OF A KITCHEN COUNTERTOP (OR A MINIMUM OF 12 INCHES FROM A
1 SCALE: 1/4"= 1'-0"
2 SCALE: 1/4"= 1'-0"
3 SCALE: 1/4"= 1'-0"
SIDE WALL OR OTHER VERTICAL OBSTRUCTION, SUCH AS COUNTERTOP
RETURN) TO BE CONSIDER ACCESSIBLE.
20. WALL MOUNTED OUTLETS ABOVE THE COUNTERTOPS SHALL BE MOUNTED

MERRICK 250
0 2' 4' 6' 8' 0 2' 4' 6' 8' 0 2' 4' 6' 8' NO MORE THAN 46 INCHES ABOVE THE FINISHED FLOOR, MEASURED TO THE
TOP OF ELECTRICAL BOX.
Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT 21. FIRE ALARM SYSTEM AUDIBLE SIGNAL UNIT SHALL PROVIDE A LOW
FREQUENCY ALARM SYSTEM AS REQUIRED TO COMPLY WITH N.F.P.A. 72
ARTICLE 18.4.5.3.
22. THE GROUNDED CIRCUIT CONDUCTOR SHALL BE PROVIDED AT THE
LOCATION WHERE SWITCHES CONTROL LIGHTING LOADS THAT ARE SUPPLIED
BY A GROUND GENERAL BRANCH CIRCUIT AS REQUIRED TO COMPLY WITH
N.E.C. ART. 402.(2) UNLESS THE LIGHT SWITCH JUNCTION BOX IS ACCESSIBLE
FOR THE INSTALLATION OF ADDITIONAL CABLES WITHOUT REMOVING
FINISHED MATERIAL OR RACEWAY CONNECTING TO LIGHT SWITCH JUNCTION
BOX IS LARGE ENOUGH FOR THE INSTALLATION OF ALL CONDUCTORS
INCLUDING THE GROUNDED CONDUCTOR.
23. PROVIDE DISCONNECT SWITCHES FOR APPLIANCES AS REQUIRED TO
COMPLY WITH NEC ART. 422.30.
24. ALL 120V SINGLE PHASE, 15 AND 20 AMP BRANCH CKTS. SUPPLYING
OUTLETS OR DEVICES SHALL BE ARC FAULT PROTECTED TO COMPLY WITH
14 14 NEC ARTICLE 210.12.
12
S.01 25. OUTLETS,(J/B),INSTALLED IN CEILING (BEDROOM, LIVING ROOM),SHALL
14 14 1 12 W.I.C. COMPLY WITH N.E.C. 314.27(A)(2).(AT LEAST 50 LBS.)
14
MASTER W.L. 14
W.I.C. BEDROOM 14 14
S.02 BATHROOM 14 S.02 MASTER
1 GFI 1 S
BEDROOM
14 D 12
14 GFI S.01
1 12 A 14
7
12"
S.03
1
H
7 KEY NOTES:
GFI S.03
S.01 MIN. 14 12" MIN. 1
12 1 BALCONY
5 5 8
12 14 15
GFI 1 2 30
0 BUILT-IN TO FAN COIL UNIT
16 17 12 30A 14
14 13
M
GFCI 3 14 14 14 2 2 30
0 AS REQUIRED FOR WATER HEATER.
S.05 17 16,18 7 12
1 M A/C 14 S.05
C/A

A 12 INSTALL UNDER SINK CABINET FOR DISHWASHER. COORDINATE


BATHROOM 14 1,3 1 W.I.C. W.L. 3
D S W/D 10 13 S.01
H GFI GFI 14 1 EXACT LOCATION IN FIELD.
2 20,22 B D S 13 13 WP
13 WP 12 4 INSTALL UNDER SINK CABINET UNDER THE SINK FOR GARBAGE
12 12 13 S.02
S.01 3 13 GFI 14 DISPOSAL. COORDINATE EXACT LOCATION IN THE FIELD
1 D S 13 MASTER 14 1
B 13 1 BEDROOM 5 INSTALL 44" A.F.F. TO CENTER.
W.L. 12 S.01
12 12 LIVING 1
16 17 12 BALCONY INSTALL 66" A.F.F. FOR MICROWAVE.
6
8 12 12 S.03 14
S.01 1
12 1 S.01 S.04 S.01 12 7 TELECOMMUNICATION DISTRIBUTION CABINET.
30A 1 1 13 1 12" MIN.
2 M 12 8 10 8
M 16,18 12 8 INSTALL 36" A.F.F.
GFI GFI 14 5
A/C
W/D 12 S.03 H BATHROOM
A/C 1,3 17 13 3 1 GFI 16 17 INSTALL 42" A.F.F.
S.03 30A 12 9
GFCI 1 KITCHEN 12 A 17 13
20,22
13 12 14 14 GFCI M 2 10 ELECTRICAL PANEL 'P1'
9 6 5 4 3 S.05 13 S D 16,18 M

C/A
1 1 A/C 20,22
12 11 CLOSED CABINET FLOOR TO CEILING
W/D 1,3 11
13 S.01 13 15
10 GFCI S D
1 11 13 INSTALL HORIZONTALLY NO MORE THAN 12" BELOW COUNTER
WP 12
12 12 9 8 6 2,4 10GFI 7 8 13
13 B 12
TOP. MOUNTING HEIGHT TO BE MEASURED TO BOTTOM OF
13 GFI GFCI GFI GFI 1 OUTLET.
50A 3
3 12 FCU-1
CLIENT INFORMATION:
12 S.01 13
1 CORAL GABLES
S.04 15 INSTALL AS REQUIRED FOR UNDER CABINET LIGHTING.
12 1 S.04 12 14 ALTA, LLC.
1 COORDINATE EXACT LOCATION WITH ARCH. AND/OR CABINETRY
12 10 2950 SW 27th AVE
SHOP DWGS.
11
9 8 10 3
SUITE 220
13 8 10 9 15 AT 5TH FLOOR APARTMENT UNITS ONLY
GFI GFI S.03 S.03 12 MIAMI, FL 33133
12 8 1 GFI GFI
9 1
GFI 13 9 INSTALL AS REQUIRED FOR MOTORIZE DAMPER. WIRE AS
16 DATE:

DINING REQUIRED FOR PROPER OPERATION. COORDINATE FINAL


GFI KITCHEN 22-MAR-2022 MTCI SUBMITTAL
4 LOCATION WITH MECHANICAL DRAWINGS IN THE FIELD
10 4 17-JUNE-2022 MTCI REVIEW
11 1/2"C TO FAN COIL UNIT STARTING CONTACTOR INTERLOCK WITH
14 17 COMMENTS
GFCI 10 GFCI GFI 14 RESPECTIVE FAN COIL UNIT AS REQUIRED FOR SIMULTANEOUS 29-JULY-2022 COORD.
GFI GFI 6 8 11 2,4 10 OPERATION REVISION
2,4 8 11 10 13 10 8 7 10 6 8
12 8 7 05-AUG-2022 PERMIT SET TO
10 50A GFI GFI GFCI GFI GFI 12
GFI GFCI 50A CITY
3'-0"

6 5 3 5 3 6
GENERAL NOTES:
1. SCHEDULES FOR PANEL 'P1' ARE SHOWN ON SHEET E-2.03
2. PANEL 'P1' FEEDERS ARE SHOWN ON METER CENTER SCHEDULES
SHOWN ON SHEETS E-2.03

ENLARGED PLAN - UNIT TYPE 'A-2.1' ENLARGED PLAN - UNIT TYPE 'A-3' ENLARGED PLAN - UNIT TYPE 'A-4'
4 SCALE: 1/4"= 1'-0"
5 SCALE: 1/4"= 1'-0"
6 SCALE: 1/4"= 1'-0"
0 2' 4' 6' 8' 0 2' 4' 6' 8' 0 2' 4' 6' 8'
PROJECT No. 19-017
Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT
DRAWN BY: JR/YG
CHECKED BY: JAR

E-5.00
ARCHITECTURE

FILE LOCATION:
C:\USERS\JOSE\VITAL ENGINEERING DROPBOX\JOSE RAMIREZ\PROJECTS\2021\21055 250 MERRICK RESIDENTIAL DEVELOPMENT\WORK DRAWINGS\E-5.01 ENLARGED PLANS TYPICAL UNITS
TYPE 'B'.DWG

PRINTED ON:10.10.2022
P L A N N I N G
GENERAL NOTES FOR APARTMENTS: I N T E R I O R S
1. ALL LIGHT FIXTURES LOCATIONS ARE TO BE COORDINATED WITH CERTIFICATIO N No. AA0002451
MECHANICAL TRADE PRIOR TO INSTALLATION.
2. ALL CONTROL WIRING FOR THERMOSTAT SHALL BE DONE BY THIS 4533 PONCE DE LEON BLVD.
CONTRACTOR PER UNIT MANUFACTURER WIRING DIAGRAM. Coral Gables, Florida 33146
12" MIN. 3. CIRCUIT NUMBERS FOR LIGHTS AND RECEPTACLES AS SHOWN IS FOR TEL: (305) 740-5442
GUIDANCE ONLY. THIS CONTRACTOR MAY CHANGE CIRCUITING TO SUIT FIELD FAX: (305) 740-5443
CONDITIONS. HOWEVER, ALL CIRCUITING SHALL COMPLY WITH LATEST E-MAIL: info@beharfont.com
5 GFI CODES AND STANDARDS. NOTIFY ENGINEER OF ANY CHANGE, AND IF
15 15 12
ACCEPTABLE, DRAWINGS WILL BE REVISED. DIRECTORIES IN PANELS SHALL © 2019 BEHAR FONT & PARTNERS P.A.
W.I.C. DESCRIBE ROOMS AND APPLIANCES SERVED BY EACH CIRCUIT. THE DESIGN AND DRAWINGS FOR THIS
S.01 PROJECT ARE THE PROPERTY OF THIS
15 1 12" MIN. 4. COORDINATE LOCATION OF OUTLETS FOR APPLIANCES WITH APPLIANCES
15 12 12 GFI REPRESENTATIVE IN ORDER TO AVOID OUTLET'S PLUGS FROM PREVENTING
ARCHITECT AND ARE PROTECTED UNDER THE
S.02 5 15 COPYRIGHT PROTECTION ACT.
1 15 APPLIANCES FROM RESTING AGAINST REAR WALLS.
S 12 5. ALL APPLIANCES LOADS ARE NAMEPLATE RATING. IN CASE PURCHASED SEAL:
BEDROOM S.01 W.L. S.01
1 W.I.C. APPLIANCES ARE DIFFERENT, CALCULATIONS MUST BE CORRECTED TO
15 3 W.L. 1
15 VERIFY SIZE OF CIRCUIT BREAKERS, CONDUCTORS, ETC.
BATHROOM 12 BEDROOM
12 15 6 . ALL OUTLET LOCATION AND HEIGHTS IN BATHROOMS & KITCHENS MUST BE
S.02
S.03 10 S.01 1 15 COORDINATED WITH ARCHITECT AND SHALL COMPLY WITH ADA & FHA
1 1 BATHROOM H
S.03 DISTANCES AND HEIGHT REQUIREMENTS. ALL OUTLETS IN KITCHEN MUST BE
3 H 16 17
16 17 1 COORDINATED WITH KITCHEN CABINETRY SHOP DWGS. CONTRACTOR MUST
GFCI 30A 3 15 VERIFY EXACT DIMENSIONS ON SITE AND ADD RECEPTACLES AS REQUIRED.
30A 12 M M 12 D S 7. OUTLETS IN COMMON WALLS DIVIDING APARTMENTS SHALL NOT BE
B 12 15 S.01 2 12 17 A
15 15 16,18 1 12 20,22 16,18 INSTALLED BACK TO BACK. THEY MUST BE INSTALLED AT A MINIMUM OF 24" OF
S D 8 M A/C 20,22 A/C

C/A
M

A/C
SEPARATION. EACH BOX SHALL BE WRAPPED WITH FIRE RETARDANT
17 W/D 1,3 W/D
3 12 MATERIAL APPROVED FOR THE PURPOSE. OUTLETS/JUNCTION BOXES
GFCI 8 3 15 JOSE A. RAMIREZ, P.E.
2 INSTALLED IN APARTMENT COMMON AREAS OR RATED WALL, SHALL NOT
12 D 1,3 P.E. 0060224
13 15 COMPROMISE THE WALL INTEGRITY. REFER TO INSTALLATION DETAIL ON
B 3 3 15 CONSULTANT:
12 1 13 3 SHEET E-0.01.
13 13 12 D B 8. SMOKE DETECTORS ARE TO BE PHOTOELECTRIC TYPE AC-DC TYPE WITH
1 S.01 13 BATTERY BACK-UP WITH CONTACTS FOR TANDEM CONNECTIONS TO OTHER
1 12 13 DETECTORS WITHIN THE APARTMENT FOR SIMULTANEOUS ALARM AND FOR
S.04 12 REMOTE ANNUNCIATION IN THE BUILDING SECURITY ALL SMOKE DETECTORS
1
3 AT EACH APT. UNIT SHALL BE INTERLOCKED SO THAT AUDIBLE ALARM IS
GFI GFI 3
SOUNDED AT ALL DETECTORS UPON ALARM IN ANY DETECTOR. INSTALL
UNIT 03
LIVING/DINING 8 10
12 SMOKE DETECTORS A MIN. OF 3'-0" FROM A/C DIFFUSERS, BATHROOMS AND
TYPE B-1 9 3
S.04 WITHIN 20'-0" OF COOK TOPS IN KITCHENS.
1,002 SF S.03 9.SMOKE DETECTORS WHEN WALL MOUNTED SHALL BE INSTALLED WITH TOP
KITCHEN 9 9 1 1
13 12 12 9 GFI GFI 15 NOT LESS THAN 4 INCHES NOR MORE THAN 12 INCHES BELOW THE CEILING.
S.03 10 8 UNIT 20
LIVING/DINING 10. LIGHT FIXTURES IDENTIFICATION AT UNITS SHALL BE SELECTED BY
1 11 4 3 12 13
TYPE B-2 ARCHITECT AND/OR INTERIOR DESIGNER. THEY SHALL BE PROVIDED AND
BALCONY 6
GFI 12 1,065 SF WIRED BY ELECTRICAL CONTRACTOR. PROVIDE KEYLESS PORCELAIN
12 BALCONY
11 8 LAMPHOLDER WITH 60 WATT LAMP ON A TEMPORARY BASIS.
13 GFI
B 12 KITCHEN 11. LIGHT FIXTURES SHALL NOT BE USED AS RACEWAY FOR CIRCUIT
13 10 7 8 6 2,4 8 GFI CONDUCTORS UNLESS MARKED FOR USE AS A RACEWAY.
S D 4 GFCI 10 10 5 4 3 13
3 GFI 6 12. CIRCUIT BREAKER CONNECTORS AT APARTMENT LOAD CENTERS AND
GFCI GFI GFI 12 13
50A 11 S.05 WIRING DEVICE CONTACTS SHALL BE RATED 75 DEGREES C.

3'-0"
WP GFI 3'-0" 1
S D 5 14 7 12 B 13. ALL DISCONNECT SWITCHES IN APARTMENT UNITS FOR WATER HEATERS
13 14 5 14 GFI
A 12 12 8 10 2,4 8 10 3 D 13 AND FAN COIL UNITS SHALL BE INSTALLED IN COMPLIANCE WITH N.E.C. ART.
14 H 14 6 S
GFI 12" MIN. S.01 GFCI 11 GFI 3 13 110.26 WORKING CLEARANCES.
1 WP
14 GFI GFI 50A GFI GFCI 14. CONTRACTOR SHALL VERIFY FAN COIL UNIT CIRCUIT BREAKER SIZE IN
APARTMENT ELECTRICAL PANELS WITH INFORMATION INCLUDED IN
S.01
1 14 5 GFI 14
A
D S 14 INSTALLED FAN COIL UNIT NAMEPLATE AND MAKE ANY REQUIRED
S.01 14
14 7 BATHROOM 1 14 H 12" MIN. 12
MODIFICATION, INCLUDING CIRCUIT BREAKER AND WIRE SIZE, TO MATCH
14 10 INFORMATION SHOWN IN NAMEPLATE.
15. ALL 125 VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER
RESISTANT RECEPTACLES TO COMPLY WITH NEC ARTICLE 406.12.
14 BATHROOM
GFI 7 16. ALL WIRING DEVICES SHALL BE WHITE COLOR, DECORA TYPE. RECEIVED
S.03 14 S.03
1 17. COMBINATION SMOKE/CARBON MONOXIDE DETECTORS AND INDIVIDUAL
14 S.01
1
1
CARBON MONOXIDE SENSORS ARE TO BE AC-DC TYPE WITH BATTERY
4/20/2023
MASTER 14 S.02
1 14 BACK-UP WITH CONTACTS FOR TANDEM CONNECTIONS TO OTHER
BEDROOM W.I.C. W.L. DETECTORS WITHIN THE APT. UNIT FOR SIMULTANEOUS ALARM. ALL
GFI
S.01 14 S.02 MASTER COMBINATION SMOKE/CARBON MONOXIDE DETECTORS, INDIVIDUAL CARBON
1
14
14 14 1 BEDROOM MONOXIDE SENSORS AND/OR INDIVIDUAL SMOKE DETECTORS AT EACH APT.
14 UNIT SHALL BE INTERLOCKED SO THAT AUDIBLE ALARM IS SOUNDED AT ALL
14 W.I.C. 14
W.L. DETECTORS UPON ALARM IN ANY DETECTOR. INSTALL SMOKE/CARBON

PROPOSED MIXED-USE RENTAL DEVELOPMENT:


14 MONOXIDE DETECTORS A MIN. OF 3'-0" FROM A/C DIFFUSERS, BATHROOM
14 AND WITHIN 20'-0" OF THE COOK TOPS IN KITCHENS. COMBINATION
SMOKE/CARBON MONOXIDE DETECTORS AND INDIVIDUAL CARBON MONOXIDE
SENSORS DEVICE AND INSTALLATION SHALL COMPLY WITH LATEST THE
FLORIDA BUILDING CODE SECTION R314 AND R315.

4101 SALZEDO STREET CORAL GABLES, FLORIDA 33146


18. ELECTRICAL INSTALLATION FOR TYPICAL APARTMENT UNITS SHALL COMPLY
THE FLORIDA BUILDING CODE ENERGY SECTION 405.1.
19. OUTLETS MUST BE LOCATED A MINIMUM OF 36 INCHES FROM AN INSIDE
CORNER OF A KITCHEN COUNTERTOP (OR A MINIMUM OF 12 INCHES FROM A
SIDE WALL OR OTHER VERTICAL OBSTRUCTION, SUCH AS COUNTERTOP
RETURN) TO BE CONSIDER ACCESSIBLE.
ENLARGED PLAN - UNIT TYPE 'B-1' ENLARGED PLAN - UNIT TYPE 'B-2' 20. WALL MOUNTED OUTLETS ABOVE THE COUNTERTOPS SHALL BE MOUNTED

MERRICK 250
1 SCALE: 1/4"= 1'-0"
2 SCALE: 1/4"= 1'-0"
NO MORE THAN 46 INCHES ABOVE THE FINISHED FLOOR, MEASURED TO THE
TOP OF ELECTRICAL BOX.
21. FIRE ALARM SYSTEM AUDIBLE SIGNAL UNIT SHALL PROVIDE A LOW
0 2' 4' 6' 8' 0 2' 4' 6' 8' FREQUENCY ALARM SYSTEM AS REQUIRED TO COMPLY WITH N.F.P.A. 72
ARTICLE 18.4.5.3.
Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT 22. THE GROUNDED CIRCUIT CONDUCTOR SHALL BE PROVIDED AT THE
LOCATION WHERE SWITCHES CONTROL LIGHTING LOADS THAT ARE SUPPLIED
BY A GROUND GENERAL BRANCH CIRCUIT AS REQUIRED TO COMPLY WITH
N.E.C. ART. 402.(2) UNLESS THE LIGHT SWITCH JUNCTION BOX IS ACCESSIBLE
FOR THE INSTALLATION OF ADDITIONAL CABLES WITHOUT REMOVING
FINISHED MATERIAL OR RACEWAY CONNECTING TO LIGHT SWITCH JUNCTION
BOX IS LARGE ENOUGH FOR THE INSTALLATION OF ALL CONDUCTORS
INCLUDING THE GROUNDED CONDUCTOR.
23. PROVIDE DISCONNECT SWITCHES FOR APPLIANCES AS REQUIRED TO
COMPLY WITH NEC ART. 422.30.
24. ALL 120V SINGLE PHASE, 15 AND 20 AMP BRANCH CKTS. SUPPLYING
OUTLETS OR DEVICES SHALL BE ARC FAULT PROTECTED TO COMPLY WITH
NEC ARTICLE 210.12.
25. OUTLETS,(J/B),INSTALLED IN CEILING (BEDROOM, LIVING ROOM),SHALL
COMPLY WITH N.E.C. 314.27(A)(2).(AT LEAST 50 LBS.)

13 GFI
14 14 13 BALCONY
WP 15
KEY NOTES:
13 13
15
1 2 30
0 BUILT-IN TO FAN COIL UNIT
9 16 17
2 2 2 30
0 AS REQUIRED FOR WATER HEATER.
14 GFI 12" MIN. MASTER LIVING INSTALL UNDER SINK CABINET FOR DISHWASHER. COORDINATE
GFI 3
GFI 12 BEDROOM 13 EXACT LOCATION IN FIELD.
12 10 8 9 20,22 S.01 13
3'-0"

3 1 14 4 INSTALL UNDER SINK CABINET UNDER THE SINK FOR GARBAGE


S.01 5 12
S.03 14 13 S.03 13 DISPOSAL. COORDINATE EXACT LOCATION IN THE FIELD
1 M
GFI A/C 12 12 1 2
1,3 A/C 5 INSTALL 44" A.F.F. TO CENTER.
6 8 12 M
6 12 6 INSTALL 66" A.F.F. FOR MICROWAVE.
BATHROOM 14
1 12
D 12 S.05 TELECOMMUNICATION DISTRIBUTION
2,4 8 13
A D 3 7
14 B CABINET.
50A 7 S 3 UNIT 02 13
5 GFI S.01 TYPE B-4 INSTALL 36" A.F.F.
GFI 1 8
12 3 1,141 SF
3 10 12 12 INSTALL 42" A.F.F.
KITCHEN S.01 W.L. GFI 9
1 S.02 14 15
10
4 1
7 GFI 10 ELECTRICAL PANEL 'P2'
12 GFCI 14 12" MIN. DINING
5 11 H 14
17 W.I.C. 11 CLOSED CABINET FLOOR TO CEILING
GFCI S.04 W/D
GFCI 1 8
16,18 INSTALL HORIZONTALLY NO MORE THAN 12"
8 GFI 30A GFI 12
H 5 S BELOW COUNTER TOP. MOUNTING HEIGHT
GFI 11 10
S.04 12 GFI TO BE MEASURED TO BOTTOM OF OUTLET.
15 13 1 8 FCU-2 CLIENT INFORMATION:
12 12 12 8 13
4 12 S.02 10
1 15 S.01 GFCI CORAL GABLES
10 13 1 12 7 INSTALL AS REQUIRED FOR UNDER CABINET
GFI 14
14 S 13 3
BATHROOM GFI
GFCI LIGHTING. COORDINATE EXACT LOCATION ALTA, LLC.
W.I.C. S.01 12 11 WITH ARCH. AND/OR CABINETRY SHOP 2950 SW 27th AVE
A S.01 3 W.L. D 3
D 1 1 B KITCHEN DWGS.
14 12 3 13 3 SUITE 220
14 B A 14 GFI 4
12" MIN. D D
12 15
3 10 15 AT 5TH FLOOR APARTMENT UNIT ONLY MIAMI, FL 33133
14 13 12 12
S S 3 1
DATE:
GFI 12 3 12
3 D B 5 16 INSTALL AS REQUIRED FOR MOTORIZE DAMPER. WIRE AS
H 5 GFI S.01 1,3 12 2,4 22-MAR-2022 MTCI SUBMITTAL
15
10
3
12
9 8 6 10 8 REQUIRED FOR PROPER OPERATION. COORDINATE FINAL
14 12 M GFI GFI 29-JULY-2022 COORD.
S.03 14 15 12 LOCATION WITH MECHANICAL DRAWINGS IN THE FIELD
13 13 A/C
A/C GFI 50A REVISION
1 3'-0"
14 S.01 M 1/2"C TO FAN COIL UNIT STARTING CONTACTOR INTERLOCK WITH
UNIT 09 13 20,22 15
17 05-AUG-2022 PERMIT SET TO
1 12 RESPECTIVE FAN COIL UNIT AS REQUIRED FOR SIMULTANEOUS
MASTER 7 13 TYPE B-3 S.03 13 CITY
14 1 9 6 OPERATION
BEDROOM BATHROOM 1,048 SF S.031 15
15
S.02 13
LIVING/DINING 2 D
1 BEDROOM W/D 4 D 12 15 A
S 16 17 15
W.I.C. B 12
14
15 12 15 13
16,18 17 12
14 13 S.03
S.01 30A GFCI 1
14
1 W.L. 13
13
15
15 15 GENERAL NOTES:
8 H
BEDROOM 1. SCHEDULE FOR PANEL 'P2' ARE SHOWN ON SHEET E-2.03
BATHROOM
15 15
WP 12 S.02 2. PANEL 'P2' FEEDERS ARE SHOWN ON METER CENTER SCHEDULES
S.05 GFI 1
1 13 13 W.I.C. SHOWN ON SHEETS E-2.03
W.L. 15
15 S.01 5
1 12
BALCONY S.01 15
1
12 GFI 12" MIN.

PROJECT No. 19-017


DRAWN BY: JR/YG
ENLARGED PLAN - UNIT TYPE 'B-3' ENLARGED PLAN - UNIT TYPE 'B-4' CHECKED BY: JAR
3 SCALE: 1/4"= 1'-0"
5 SCALE: 1/4"= 1'-0"
0 2' 4' 6' 8' 0 2' 4' 6' 8'

Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT


E-5.01
ARCHITECTURE

FILE LOCATION:

TYPE 'B' & TYPE 'C'.DWG

PRINTED ON:10.10.2022
C:\USERS\JOSE\VITAL ENGINEERING DROPBOX\JOSE RAMIREZ\PROJECTS\2021\21055 250 MERRICK RESIDENTIAL DEVELOPMENT\WORK DRAWINGS\E-5.02 ENLARGED PLANS TYPICAL UNITS
P L A N N I N G
GENERAL NOTES FOR APARTMENTS: I N T E R I O R S
1. ALL LIGHT FIXTURES LOCATIONS ARE TO BE COORDINATED WITH CERTIFICATIO N No. AA0002451
MECHANICAL TRADE PRIOR TO INSTALLATION.
2. ALL CONTROL WIRING FOR THERMOSTAT SHALL BE DONE BY THIS 4533 PONCE DE LEON BLVD.
12" MIN. CONTRACTOR PER UNIT MANUFACTURER WIRING DIAGRAM. Coral Gables, Florida 33146
GFI
15 15 3. CIRCUIT NUMBERS FOR LIGHTS AND RECEPTACLES AS SHOWN IS FOR TEL: (305) 740-5442
15
5 GUIDANCE ONLY. THIS CONTRACTOR MAY CHANGE CIRCUITING TO SUIT FIELD FAX: (305) 740-5443
15 W.L.
S.01 CONDITIONS. HOWEVER, ALL CIRCUITING SHALL COMPLY WITH LATEST E-MAIL: info@beharfont.com
W.I.C. 1 CODES AND STANDARDS. NOTIFY ENGINEER OF ANY CHANGE, AND IF
S.02 15 ACCEPTABLE, DRAWINGS WILL BE REVISED. DIRECTORIES IN PANELS SHALL © 2019 BEHAR FONT & PARTNERS P.A.
15 1 S.01 19 20 DESCRIBE ROOMS AND APPLIANCES SERVED BY EACH CIRCUIT. THE DESIGN AND DRAWINGS FOR THIS
15 BATHROOM 1 PROJECT ARE THE PROPERTY OF THIS
BEDROOM 4. COORDINATE LOCATION OF OUTLETS FOR APPLIANCES WITH APPLIANCES
H REPRESENTATIVE IN ORDER TO AVOID OUTLET'S PLUGS FROM PREVENTING
ARCHITECT AND ARE PROTECTED UNDER THE
COPYRIGHT PROTECTION ACT.
S 13 APPLIANCES FROM RESTING AGAINST REAR WALLS.
18 SEAL:
12 M 5. ALL APPLIANCES LOADS ARE NAMEPLATE RATING. IN CASE PURCHASED
15 S.03 12 S.01 APPLIANCES ARE DIFFERENT, CALCULATIONS MUST BE CORRECTED TO
1 D A 15 1 12 M 1 13
12 A/C
A/C VERIFY SIZE OF CIRCUIT BREAKERS, CONDUCTORS, ETC.
D
B 12 6 . ALL OUTLET LOCATION AND HEIGHTS IN BATHROOMS & KITCHENS MUST BE
1,3 14 COORDINATED WITH ARCHITECT AND SHALL COMPLY WITH ADA & FHA
16 15
3'-0" 15 20,22 DISTANCES AND HEIGHT REQUIREMENTS. ALL OUTLETS IN KITCHEN MUST BE
6 9 2 COORDINATED WITH KITCHEN CABINETRY SHOP DWGS. CONTRACTOR MUST
15 S.05
30A 15 2 VERIFY EXACT DIMENSIONS ON SITE AND ADD RECEPTACLES AS REQUIRED.
12
50A 16,18 BALCONY 7. OUTLETS IN COMMON WALLS DIVIDING APARTMENTS SHALL NOT BE
12 WP 14
5 GFI GFI GFI 12 INSTALLED BACK TO BACK. THEY MUST BE INSTALLED AT A MINIMUM OF 24" OF
10 6 8 9 W/D D B 13 GFI
2,4 12 17 S.01 12 SEPARATION. EACH BOX SHALL BE WRAPPED WITH FIRE RETARDANT
8 2
GFCI MASTER MATERIAL APPROVED FOR THE PURPOSE. OUTLETS/JUNCTION BOXES
JOSE A. RAMIREZ, P.E.
12 BEDROOM INSTALLED IN APARTMENT COMMON AREAS OR RATED WALL, SHALL NOT
3 P.E. 0060224
GFI 8 3 3 13 COMPROMISE THE WALL INTEGRITY. REFER TO INSTALLATION DETAIL ON
10 12 13 CONSULTANT:
4 3 SHEET E-0.01.
GFCI 8. SMOKE DETECTORS ARE TO BE PHOTOELECTRIC TYPE AC-DC TYPE WITH
11 12 15 S.03 14
KITCHEN 10 BATTERY BACK-UP WITH CONTACTS FOR TANDEM CONNECTIONS TO OTHER
7 14 1
12 S.01 BEDROOM DETECTORS WITHIN THE APARTMENT FOR SIMULTANEOUS ALARM AND FOR
1 REMOTE ANNUNCIATION IN THE BUILDING SECURITY ALL SMOKE DETECTORS
3 GFCI GFI 15 13
W.L. AT EACH APT. UNIT SHALL BE INTERLOCKED SO THAT AUDIBLE ALARM IS
10 8 10 15 LIVING/DINING
S.01 BATHROOM S.03 SOUNDED AT ALL DETECTORS UPON ALARM IN ANY DETECTOR. INSTALL
GFI 12 1 14
GFI 12 12 1 13 SMOKE DETECTORS A MIN. OF 3'-0" FROM A/C DIFFUSERS, BATHROOMS AND
S.04 S.03 WITHIN 20'-0" OF COOK TOPS IN KITCHENS.
15 15 1 S
1 S 9.SMOKE DETECTORS WHEN WALL MOUNTED SHALL BE INSTALLED WITH TOP
12 5 H 13 12 12
GFI D D A NOT LESS THAN 4 INCHES NOR MORE THAN 12 INCHES BELOW THE CEILING.
11 B 14
10. LIGHT FIXTURES IDENTIFICATION AT UNITS SHALL BE SELECTED BY
A 12 ARCHITECT AND/OR INTERIOR DESIGNER. THEY SHALL BE PROVIDED AND
12" MIN. 14 D S 3 WIRED BY ELECTRICAL CONTRACTOR. PROVIDE KEYLESS PORCELAIN
15 8
10 W.I.C. LAMPHOLDER WITH 60 WATT LAMP ON A TEMPORARY BASIS.
W.I.C. 11. LIGHT FIXTURES SHALL NOT BE USED AS RACEWAY FOR CIRCUIT
14 17 30A
CONDUCTORS UNLESS MARKED FOR USE AS A RACEWAY.
GFI S.02 15 S.02 16,18 CLOSET
3 1 GFCI 12. CIRCUIT BREAKER CONNECTORS AT APARTMENT LOAD CENTERS AND
1
12" MIN. W/D WIRING DEVICE CONTACTS SHALL BE RATED 75 DEGREES C.
14 13. ALL DISCONNECT SWITCHES IN APARTMENT UNITS FOR WATER HEATERS
12 3 14 14 S.02 AND FAN COIL UNITS SHALL BE INSTALLED IN COMPLIANCE WITH N.E.C. ART.
12
LIVING/DINING B D DA 1 110.26 WORKING CLEARANCES.
GFI H 3 B D 3 12 14
S S 14. CONTRACTOR SHALL VERIFY FAN COIL UNIT CIRCUIT BREAKER SIZE IN
7 12 12" MIN. GFI
5 12 13 3 APARTMENT ELECTRICAL PANELS WITH INFORMATION INCLUDED IN
S.04 GFI INSTALLED FAN COIL UNIT NAMEPLATE AND MAKE ANY REQUIRED
14 10 12
S.03 12 S.01 12 8 1 10
S.01 GFI MODIFICATION, INCLUDING CIRCUIT BREAKER AND WIRE SIZE, TO MATCH
S.03 1 12 1 2 5 H 7
1 14 12 12 1 INFORMATION SHOWN IN NAMEPLATE.
13 GFI
13 13 S.03 S.01 15. ALL 125 VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER
1 1 9 W.L. RESISTANT RECEPTACLES TO COMPLY WITH NEC ARTICLE 406.12.
13 12 14 S.01
1,3 9
14 BATHROOM 1 16. ALL WIRING DEVICES SHALL BE WHITE COLOR, DECORA TYPE. RECEIVED
2 20,22C/A M KITCHEN S.01 14
S.01 1 17. COMBINATION SMOKE/CARBON MONOXIDE DETECTORS AND INDIVIDUAL
1 A/C 12 BATHROOM
CARBON MONOXIDE SENSORS ARE TO BE AC-DC TYPE WITH BATTERY
4/20/2023
12 M
WP MASTER 12 13 BACK-UP WITH CONTACTS FOR TANDEM CONNECTIONS TO OTHER
W.L. GFCI 3 3
13 BEDROOM 10 DETECTORS WITHIN THE APT. UNIT FOR SIMULTANEOUS ALARM. ALL
18 14 8 7 10 8 6 2,4 GFI COMBINATION SMOKE/CARBON MONOXIDE DETECTORS, INDIVIDUAL CARBON
GFI 13 12 11 14
GFI MONOXIDE SENSORS AND/OR INDIVIDUAL SMOKE DETECTORS AT EACH APT.
BALCONY
14 GFI GFCI GFI 50A UNIT SHALL BE INTERLOCKED SO THAT AUDIBLE ALARM IS SOUNDED AT ALL
13 DETECTORS UPON ALARM IN ANY DETECTOR. INSTALL SMOKE/CARBON
13

PROPOSED MIXED-USE RENTAL DEVELOPMENT:


MONOXIDE DETECTORS A MIN. OF 3'-0" FROM A/C DIFFUSERS, BATHROOM
19 20
16 5 4 3 6 AND WITHIN 20'-0" OF THE COOK TOPS IN KITCHENS. COMBINATION
18 SMOKE/CARBON MONOXIDE DETECTORS AND INDIVIDUAL CARBON MONOXIDE
13
S.05 SENSORS DEVICE AND INSTALLATION SHALL COMPLY WITH LATEST THE
2 FLORIDA BUILDING CODE SECTION R314 AND R315.

4101 SALZEDO STREET CORAL GABLES, FLORIDA 33146


18. ELECTRICAL INSTALLATION FOR TYPICAL APARTMENT UNITS SHALL COMPLY
THE FLORIDA BUILDING CODE ENERGY SECTION 405.1.

ENLARGED PLAN - UNIT TYPE 'B-5' ENLARGED PLAN - UNIT TYPE 'B-6' 19. OUTLETS MUST BE LOCATED A MINIMUM OF 36 INCHES FROM AN INSIDE
CORNER OF A KITCHEN COUNTERTOP (OR A MINIMUM OF 12 INCHES FROM A
1 SCALE: 1/4"= 1'-0"
2 SCALE: 1/4"= 1'-0"
SIDE WALL OR OTHER VERTICAL OBSTRUCTION, SUCH AS COUNTERTOP
RETURN) TO BE CONSIDER ACCESSIBLE.
20. WALL MOUNTED OUTLETS ABOVE THE COUNTERTOPS SHALL BE MOUNTED
0 2' 4' 6' 8' 0 2' 4' 6' 8'

MERRICK 250
NO MORE THAN 46 INCHES ABOVE THE FINISHED FLOOR, MEASURED TO THE
TOP OF ELECTRICAL BOX.
Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT 21. FIRE ALARM SYSTEM AUDIBLE SIGNAL UNIT SHALL PROVIDE A LOW
FREQUENCY ALARM SYSTEM AS REQUIRED TO COMPLY WITH N.F.P.A. 72
ARTICLE 18.4.5.3.
S.05 22. THE GROUNDED CIRCUIT CONDUCTOR SHALL BE PROVIDED AT THE
18 2 LOCATION WHERE SWITCHES CONTROL LIGHTING LOADS THAT ARE SUPPLIED
18 BY A GROUND GENERAL BRANCH CIRCUIT AS REQUIRED TO COMPLY WITH
13
N.E.C. ART. 402.(2) UNLESS THE LIGHT SWITCH JUNCTION BOX IS ACCESSIBLE
FOR THE INSTALLATION OF ADDITIONAL CABLES WITHOUT REMOVING
13
FINISHED MATERIAL OR RACEWAY CONNECTING TO LIGHT SWITCH JUNCTION
13 BALCONY BOX IS LARGE ENOUGH FOR THE INSTALLATION OF ALL CONDUCTORS
15 13 INCLUDING THE GROUNDED CONDUCTOR.
15
13 GFI 23. PROVIDE DISCONNECT SWITCHES FOR APPLIANCES AS REQUIRED TO
WP COMPLY WITH NEC ART. 422.30.
24. ALL 120V SINGLE PHASE, 15 AND 20 AMP BRANCH CKTS. SUPPLYING
18 OUTLETS OR DEVICES SHALL BE ARC FAULT PROTECTED TO COMPLY WITH
NEC ARTICLE 210.12.
BEDROOM 13 25. OUTLETS,(J/B),INSTALLED IN CEILING (BEDROOM, LIVING ROOM),SHALL
COMPLY WITH N.E.C. 314.27(A)(2).(AT LEAST 50 LBS.)
13
15
15 13 S.03 13
S.03 1
1 S.03
1
LIVING/DINING
15
S
S
12
KEY NOTES:
D B
15 12 3
D
A 1 2 30
0 BUILT-IN TO FAN COIL UNIT
3
GFI GFI 2 2 30
0 AS REQUIRED FOR WATER HEATER.
15
7 8 INSTALL UNDER SINK CABINET FOR DISHWASHER. COORDINATE
15 3
EXACT LOCATION IN FIELD.
12" MIN.
W.I.C. S.021 15 4 INSTALL UNDER SINK CABINET UNDER THE SINK FOR GARBAGE
S.04 DISPOSAL. COORDINATE EXACT LOCATION IN THE FIELD
12 1
GFI 12 GFI 5 INSTALL 44" A.F.F. TO CENTER.
5 10 15 15
H 10 INSTALL 66" A.F.F. FOR MICROWAVE.
8 3 6
S.01 12 GFCI
1 12 GFI GFI 7 W.I.C.
12 12" 7 TELECOMMUNICATION DISTRIBUTION
S.01 GFI
S.01 11 W.L. 1 MIN. CABINET.
GFCI W.L. 15
12 1 5 INSTALL 36" A.F.F.
11 KITCHEN 24 3 8
GFI 4 BATHROOM 12 S.02 15 BEDROOM
W.L. 12 8 1 INSTALL 42" A.F.F.
BATHROOM D 6 GFCI S.01 9
B BATHROOM S.01 1
12 3 W.L. S.01 17
12 1 S.03
5 1 W/D
15 1 10 ELECTRICAL PANEL 'P2'
10 16,18
9 2,4 GFI H
3 10 8 8 30A CLOSED CABINET FLOOR TO CEILING
1 6 H BATHROOM 11
3 12 GFI GFI 12 24
50A 15
15 1,3 12 M 3'-0" 12 INSTALL HORIZONTALLY NO MORE THAN 12" BELOW COUNTER
14 23 24 12 S.01 12 12
9 24 1 12 15 TOP. MOUNTING HEIGHT TO BE MEASURED TO BOTTOM OF
M D B OUTLET.
12 A/C
A/C 16 12 H 12
S.01 20,22 12 A 15 FCU-2
12 23 S.01 5 D S 15 13 CLIENT INFORMATION:
2 12 GFI
19 20 5 3 12 1
GFI
FCU-3
CORAL GABLES
14
23 D S 24 3 3 12" MIN. 3 3 ALTA, LLC.
8 17 D 12 12 D S 13
W/D A 12 12" MIN.
14
12 B B 12 15 ELECTRICAL PANEL 'P3' 2950 SW 27th AVE
S.03 23 13
16,18 12 1 S.02 SUITE 220
12" MIN. 17 23 W.I.C. 23 1 INSTALL AS REQUIRED FOR UNDER CABINET LIGHTING.
S.02 16
23 12 14 COORDINATE EXACT LOCATION WITH ARCH. AND/OR MIAMI, FL 33133
GFCI 30A 1 D 17 1
W.I.C. CABINETRY SHOP DWGS.
5 GFI 12 24 A D DATE:

B
D 24 12 A 1,3 17 2 60
0 AS REQUIRED FOR WATER HEATER.
S.01 GFI S A/C S.03 22-MAR-2022 MTCI SUBMITTAL
1 13 1
23
12 23 23 23 20,22 A/C M 12 18 AT 5TH FLOOR APARTMENT UNIT ONLY 17-JUNE-2022 MTCI REVIEW
BATHROOM
23 9 COMMENTS
S.02 S 11 INSTALL AS REQUIRED FOR MOTORIZE DAMPER. WIRE AS
3 1 14 23 M 19 29-JULY-2022 COORD.
12 23 12
CC W.I.C. 7 18 REQUIRED FOR PROPER OPERATION. COORDINATE FINAL REVISION
1 10
H LOCATION WITH MECHANICAL DRAWINGS IN THE FIELD 05-AUG-2022 PERMIT SET TO
14 GFI
23 LIVING/DINING CITY
14 14 14 23 GFI 20 1/2"C TO FAN COIL UNIT STARTING CONTACTOR INTERLOCK WITH
23 9 13 RESPECTIVE FAN COIL UNIT AS REQUIRED FOR SIMULTANEOUS
19 20 10
14 KITCHEN OPERATION
14 D S S.04 WP
23 A 12 6 6 12 1
S.01 GFI
W.L. 1 24 S.03 23 13
7 24 1 14
S.03 S.03 2,4 8
14 MASTER 1 BEDROOM 1
50A GFI S.03
BEDROOM 12 1
H MASTER
GFI
24 S.02 BEDROOM GFI
13 BALCONY
GENERAL NOTES:
BATHROOM 1
W.L. 14 10 4
14 1. SCHEDULES FOR PANELS 'P2' & 'P3' ARE SHOWN ON SHEET E-2.03
24 14 23
24 24 23 11 13
W.I.C. 14 2. PANEL 'P2' & 'P3' FEEDERS ARE SHOWN ON METER CENTER SCHEDULES
5 8 7 8 SHOWN ON SHEETS E-2.03
12 10 GFCI GFI 10
14 13 GFI
24 GFI 12" MIN. 3'-0" GFI GFI GFCI
18
16 3 13
5
PROJECT No. 19-017
18
DRAWN BY: JR/YG

ENLARGED PLAN - UNIT TYPE C-1' ENLARGED PLAN - UNIT TYPE "C-2' CHECKED BY: JAR

3 4 SCALE: 1/4"= 1'-0"


SCALE: 1/4"= 1'-0"
0 2' 4' 6' 8'
0 2' 4' 6' 8'
Scale: 1/4 INCH = 1 FOOT
Scale: 1/4 INCH = 1 FOOT
E-5.02
ARCHITECTURE

FILE LOCATION:
C:\USERS\JOSE\VITAL ENGINEERING DROPBOX\JOSE RAMIREZ\PROJECTS\2021\21055 250 MERRICK RESIDENTIAL DEVELOPMENT\WORK DRAWINGS\E-5.03 ENLARGED PLANS TYPICAL UNITS
TYPE 'L'.DWG

PRINTED ON:10.10.2022
P L A N N I N G
GENERAL NOTES FOR APARTMENTS: I N T E R I O R S
1. ALL LIGHT FIXTURES LOCATIONS ARE TO BE COORDINATED WITH CERTIFICATIO N No. AA0002451
MECHANICAL TRADE PRIOR TO INSTALLATION.
2. ALL CONTROL WIRING FOR THERMOSTAT SHALL BE DONE BY THIS 4533 PONCE DE LEON BLVD.
CONTRACTOR PER UNIT MANUFACTURER WIRING DIAGRAM. Coral Gables, Florida 33146
3. CIRCUIT NUMBERS FOR LIGHTS AND RECEPTACLES AS SHOWN IS FOR TEL: (305) 740-5442
GUIDANCE ONLY. THIS CONTRACTOR MAY CHANGE CIRCUITING TO SUIT FIELD FAX: (305) 740-5443
BALCONY BALCONY CONDITIONS. HOWEVER, ALL CIRCUITING SHALL COMPLY WITH LATEST E-MAIL: info@beharfont.com
13
GFI WP CODES AND STANDARDS. NOTIFY ENGINEER OF ANY CHANGE, AND IF
13 13 ACCEPTABLE, DRAWINGS WILL BE REVISED. DIRECTORIES IN PANELS SHALL © 2019 BEHAR FONT & PARTNERS P.A.
GFI WP GFI WP DESCRIBE ROOMS AND APPLIANCES SERVED BY EACH CIRCUIT. THE DESIGN AND DRAWINGS FOR THIS
PROJECT ARE THE PROPERTY OF THIS
4. COORDINATE LOCATION OF OUTLETS FOR APPLIANCES WITH APPLIANCES
ARCHITECT AND ARE PROTECTED UNDER THE
13 13 14 REPRESENTATIVE IN ORDER TO AVOID OUTLET'S PLUGS FROM PREVENTING COPYRIGHT PROTECTION ACT.
APPLIANCES FROM RESTING AGAINST REAR WALLS.
14 13 13 5. ALL APPLIANCES LOADS ARE NAMEPLATE RATING. IN CASE PURCHASED SEAL:
13 13 14 APPLIANCES ARE DIFFERENT, CALCULATIONS MUST BE CORRECTED TO
13 14
VERIFY SIZE OF CIRCUIT BREAKERS, CONDUCTORS, ETC.
14 LIVING/DINING MASTER 6 . ALL OUTLET LOCATION AND HEIGHTS IN BATHROOMS & KITCHENS MUST BE
13 BEDROOM
MASTER 14 COORDINATED WITH ARCHITECT AND SHALL COMPLY WITH ADA & FHA
MASTER DISTANCES AND HEIGHT REQUIREMENTS. ALL OUTLETS IN KITCHEN MUST BE
BEDROOM BEDROOM 13
LIVING/DINING 14 COORDINATED WITH KITCHEN CABINETRY SHOP DWGS. CONTRACTOR MUST
LIVING/DINING S S
14 13 VERIFY EXACT DIMENSIONS ON SITE AND ADD RECEPTACLES AS REQUIRED.
S.03 14 S.03 12 12 14 S.03
S.03 S.03 1 D D A 1 7. OUTLETS IN COMMON WALLS DIVIDING APARTMENTS SHALL NOT BE
1 S 1 B
S 13 13 1 INSTALLED BACK TO BACK. THEY MUST BE INSTALLED AT A MINIMUM OF 24" OF
14 12 13 S.03
12 D 1
14 SEPARATION. EACH BOX SHALL BE WRAPPED WITH FIRE RETARDANT
B 3
A D MATERIAL APPROVED FOR THE PURPOSE. OUTLETS/JUNCTION BOXES
JOSE A. RAMIREZ, P.E.
10 S S INSTALLED IN APARTMENT COMMON AREAS OR RATED WALL, SHALL NOT
3 10 7 P.E. 0060224
12 12 14 10 COMPROMISE THE WALL INTEGRITY. REFER TO INSTALLATION DETAIL ON
D D A GFI CONSULTANT:
10 B 7 14 SHEET E-0.01.
14 14
11 8. SMOKE DETECTORS ARE TO BE PHOTOELECTRIC TYPE AC-DC TYPE WITH
14 7 10 BATTERY BACK-UP WITH CONTACTS FOR TANDEM CONNECTIONS TO OTHER
13 3
14 11 11 GFI 12 GFCI DETECTORS WITHIN THE APARTMENT FOR SIMULTANEOUS ALARM AND FOR
14 5 12 GFI
GFI 17 14 REMOTE ANNUNCIATION IN THE BUILDING SECURITY ALL SMOKE DETECTORS
30A 8 12 12 8 14 S.02 8 W/D S.01 AT EACH APT. UNIT SHALL BE INTERLOCKED SO THAT AUDIBLE ALARM IS
GFI 5 8
16,18 GFI GFI 1 8 16,18 1 SOUNDED AT ALL DETECTORS UPON ALARM IN ANY DETECTOR. INSTALL
14
W/D 10 8 W.I.C. 3 30A S.02 SMOKE DETECTORS A MIN. OF 3'-0" FROM A/C DIFFUSERS, BATHROOMS AND
8 14 GFI
14 14 17 15 16 5 30A 17 7 13 14 1 WITHIN 20'-0" OF COOK TOPS IN KITCHENS.
GFI 8 S.04
GFCI 3 12 9.SMOKE DETECTORS WHEN WALL MOUNTED SHALL BE INSTALLED WITH TOP
W.I.C. 13 GFI GFCI 1 M 12 12 W.I.C.
7 16,18 GFCI NOT LESS THAN 4 INCHES NOR MORE THAN 12 INCHES BELOW THE CEILING.
7

A/C
11
M 12 S.04 GFCI GFCI GFCI 12 4 GFCI M 1,3 A/C 10. LIGHT FIXTURES IDENTIFICATION AT UNITS SHALL BE SELECTED BY
1 3 W/D 12 12 ARCHITECT AND/OR INTERIOR DESIGNER. THEY SHALL BE PROVIDED AND
14 12 12 10 15 16
C/A

14 20,22 A/C 11 10 12 2
M 11 GFCI W.L. 20,22 WIRED BY ELECTRICAL CONTRACTOR. PROVIDE KEYLESS PORCELAIN
4 S.04 GFI
12 12 S.01 5 LAMPHOLDER WITH 60 WATT LAMP ON A TEMPORARY BASIS.
4 1 11. LIGHT FIXTURES SHALL NOT BE USED AS RACEWAY FOR CIRCUIT
1,3 12 12 1 50A 10
W.L. 10 10 S.01 1 W.L.
1 GFI 2,4 GFI CONDUCTORS UNLESS MARKED FOR USE AS A RACEWAY.
GFI 5 5 1 12 H S.01
8 2,4 50A 10 12. CIRCUIT BREAKER CONNECTORS AT APARTMENT LOAD CENTERS AND
S.01 H 2 6 12 1
12
1 GFI 12 50A 2,4 GFI 12 6 KITCHEN S.01 12 S.01
WIRING DEVICE CONTACTS SHALL BE RATED 75 DEGREES C.
10 1 1 13. ALL DISCONNECT SWITCHES IN APARTMENT UNITS FOR WATER HEATERS
KITCHEN 6 KITCHEN 1
S.01 6 BATHROOM GFI AND FAN COIL UNITS SHALL BE INSTALLED IN COMPLIANCE WITH N.E.C. ART.
BATHROOM GFI 6 S.01 GFI
1 110.26 WORKING CLEARANCES.

3'-0"
6 GFI 1 8 14 3
10 1,3 20,22 H
10 12 BATHROOM 14. CONTRACTOR SHALL VERIFY FAN COIL UNIT CIRCUIT BREAKER SIZE IN
12 GFI GFI 12 12 10 9 APARTMENT ELECTRICAL PANELS WITH INFORMATION INCLUDED IN
3 8 14 S.01
8 14 3 12 C/A
M A/C 1 5 GFI INSTALLED FAN COIL UNIT NAMEPLATE AND MAKE ANY REQUIRED
12 S.01 9 10 12 9 12
1 12 10 12 GFI 12 MODIFICATION, INCLUDING CIRCUIT BREAKER AND WIRE SIZE, TO MATCH
GFI GFI M INFORMATION SHOWN IN NAMEPLATE.
5 12 9 11 12
GFI 2 S.01 5 15. ALL 125 VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER
3'-0" 3'-0" 15 16 13 11 1 GFI RESISTANT RECEPTACLES TO COMPLY WITH NEC ARTICLE 406.12.
11 9
9 16. ALL WIRING DEVICES SHALL BE WHITE COLOR, DECORA TYPE. RECEIVED
17. COMBINATION SMOKE/CARBON MONOXIDE DETECTORS AND INDIVIDUAL
CARBON MONOXIDE SENSORS ARE TO BE AC-DC TYPE WITH BATTERY
4/20/2023
C
BACK-UP WITH CONTACTS FOR TANDEM CONNECTIONS TO OTHER
DETECTORS WITHIN THE APT. UNIT FOR SIMULTANEOUS ALARM. ALL
COMBINATION SMOKE/CARBON MONOXIDE DETECTORS, INDIVIDUAL CARBON
MONOXIDE SENSORS AND/OR INDIVIDUAL SMOKE DETECTORS AT EACH APT.
UNIT SHALL BE INTERLOCKED SO THAT AUDIBLE ALARM IS SOUNDED AT ALL
DETECTORS UPON ALARM IN ANY DETECTOR. INSTALL SMOKE/CARBON

PROPOSED MIXED-USE RENTAL DEVELOPMENT:


MONOXIDE DETECTORS A MIN. OF 3'-0" FROM A/C DIFFUSERS, BATHROOM
ENLARGED PLAN - UNIT TYPE 'L-1' ENLARGED PLAN - UNIT TYPE 'L-2' ENLARGED PLAN - UNIT TYPE 'L-3' AND WITHIN 20'-0" OF THE COOK TOPS IN KITCHENS. COMBINATION

1 SCALE: 1/4"= 1'-0"


2 SCALE: 1/4"= 1'-0"
3 SCALE: 1/4"= 1'-0"
SMOKE/CARBON MONOXIDE DETECTORS AND INDIVIDUAL CARBON MONOXIDE
SENSORS DEVICE AND INSTALLATION SHALL COMPLY WITH LATEST THE
FLORIDA BUILDING CODE SECTION R314 AND R315.
0 2' 4' 6' 8' 0 2' 4' 6' 8' 0 2' 4' 6' 8'

4101 SALZEDO STREET CORAL GABLES, FLORIDA 33146


18. ELECTRICAL INSTALLATION FOR TYPICAL APARTMENT UNITS SHALL COMPLY
THE FLORIDA BUILDING CODE ENERGY SECTION 405.1.
Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT Scale: 1/4 INCH = 1 FOOT 19. OUTLETS MUST BE LOCATED A MINIMUM OF 36 INCHES FROM AN INSIDE
CORNER OF A KITCHEN COUNTERTOP (OR A MINIMUM OF 12 INCHES FROM A
SIDE WALL OR OTHER VERTICAL OBSTRUCTION, SUCH AS COUNTERTOP
RETURN) TO BE CONSIDER ACCESSIBLE.
20. WALL MOUNTED OUTLETS ABOVE THE COUNTERTOPS SHALL BE MOUNTED

MERRICK 250
NO MORE THAN 46 INCHES ABOVE THE FINISHED FLOOR, MEASURED TO THE
TOP OF ELECTRICAL BOX.
21. FIRE ALARM SYSTEM AUDIBLE SIGNAL UNIT SHALL PROVIDE A LOW
FREQUENCY ALARM SYSTEM AS REQUIRED TO COMPLY WITH N.F.P.A. 72
ARTICLE 18.4.5.3.
22. THE GROUNDED CIRCUIT CONDUCTOR SHALL BE PROVIDED AT THE
LOCATION WHERE SWITCHES CONTROL LIGHTING LOADS THAT ARE SUPPLIED
BY A GROUND GENERAL BRANCH CIRCUIT AS REQUIRED TO COMPLY WITH
N.E.C. ART. 402.(2) UNLESS THE LIGHT SWITCH JUNCTION BOX IS ACCESSIBLE
FOR THE INSTALLATION OF ADDITIONAL CABLES WITHOUT REMOVING
FINISHED MATERIAL OR RACEWAY CONNECTING TO LIGHT SWITCH JUNCTION
BOX IS LARGE ENOUGH FOR THE INSTALLATION OF ALL CONDUCTORS
INCLUDING THE GROUNDED CONDUCTOR.
23. PROVIDE DISCONNECT SWITCHES FOR APPLIANCES AS REQUIRED TO
COMPLY WITH NEC ART. 422.30.
24. ALL 120V SINGLE PHASE, 15 AND 20 AMP BRANCH CKTS. SUPPLYING
OUTLETS OR DEVICES SHALL BE ARC FAULT PROTECTED TO COMPLY WITH
NEC ARTICLE 210.12.
25. OUTLETS,(J/B),INSTALLED IN CEILING (BEDROOM, LIVING ROOM),SHALL
COMPLY WITH N.E.C. 314.27(A)(2).(AT LEAST 50 LBS.)

KEY NOTES:

1 2 30
0 BUILT-IN TO FAN COIL UNIT
2 2 30
0 AS REQUIRED FOR WATER HEATER.
3 INSTALL UNDER SINK CABINET FOR DISHWASHER. COORDINATE
EXACT LOCATION IN FIELD.
4 INSTALL UNDER SINK CABINET UNDER THE SINK FOR GARBAGE
DISPOSAL. COORDINATE EXACT LOCATION IN THE FIELD
5 INSTALL 44" A.F.F. TO CENTER.

6 INSTALL 66" A.F.F. FOR MICROWAVE.

7 TELECOMMUNICATION DISTRIBUTION CABINET.

8 INSTALL 36" A.F.F.

9 INSTALL 42" A.F.F.

10 ELECTRICAL PANEL 'P1'

11 CLOSED CABINET FLOOR TO CEILING

12 INSTALL HORIZONTALLY NO MORE THAN 12" BELOW COUNTER


TOP. MOUNTING HEIGHT TO BE MEASURED TO BOTTOM OF
OUTLET.
CLIENT INFORMATION:
13 FCU-1
CORAL GABLES
INSTALL AS REQUIRED FOR UNDER CABINET LIGHTING.
14
COORDINATE EXACT LOCATION WITH ARCH. AND/OR CABINETRY
ALTA, LLC.
SHOP DWGS. 2950 SW 27th AVE
SUITE 220
15 INSTALL AS REQUIRED FOR MOTORIZE DAMPER. WIRE AS
REQUIRED FOR PROPER OPERATION. COORDINATE FINAL MIAMI, FL 33133
LOCATION WITH MECHANICAL DRAWINGS IN THE FIELD DATE:

16 1/2"C TO FAN COIL UNIT STARTING CONTACTOR INTERLOCK WITH


22-MAR-2022 MTCI SUBMITTAL
RESPECTIVE FAN COIL UNIT AS REQUIRED FOR SIMULTANEOUS
17-JUNE-2022 MTCI REVIEW
OPERATION
COMMENTS
29-JULY-2022 COORD.
REVISION
05-AUG-2022 PERMIT SET TO
CITY

GENERAL NOTES:
1. SCHEDULES FOR PANEL 'P1' ARE SHOWN ON SHEET E-2.03
2. PANEL 'P1' FEEDERS ARE SHOWN ON METER CENTER SCHEDULES
SHOWN ON SHEETS E-2.03

PROJECT No. 19-017


DRAWN BY: JR/YG
CHECKED BY: JAR

E-5.03
ARCHITECTURE

FILE LOCATION:
C:\USERS\JOSE\VITAL ENGINEERING DROPBOX\JOSE RAMIREZ\PROJECTS\2021\21055 250 MERRICK RESIDENTIAL DEVELOPMENT\WORK DRAWINGS\E-0.00 SYMBOLS LEGEND, ELECTRICAL NOTES
& INDEX DRAWINGS.DWG

PRINTED ON:10.10.2022
ELECTRICAL NOTES LEGEND OF SYMBOLS GENERAL NOTES FOR LIGHT FIXTURES P L A N N I N G
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE 2017 EDITION OF 26. CONTRACTOR'S WORK PRACTICES AND CONDITIONS MUST CONFORM WITH THE
SYMBOL DESCRIPTION SYMBOL DESCRIPTION 1. ALL WIRING CHANNELS (FLUORESCENT AND INCANDESCENT) AND BAFFLES I N T E R I O R S
1.
THE NATIONAL ELECTRICAL CODE (N.E.C.), 7TH EDITION OF THE 2020 FLORIDA OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970. LIGHTING:
SHALL BE COLD ROLLED STEEL OF MINIMUM GAUGE, OR AS REQUIRED BY
LOCAL CODE. CERTIFICATIO N No. AA0002451
BUILDING CODE (F.B.C.) AND ALL OTHER CODES AND ORDINANCES IN EFFECT AT 27. LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE TIME OF
THIS LOCATION. DESIGN. VERIFY ALL EQUIPMENT, PANEL AND WIRE SIZES BEFORE ORDERING. LIGHT FIXTURE, WALL MOUNTED AS INDICATED. 2. ALL SOCKETS SHALL BE OF THE PORCELAIN TYPE AND SHALL BE SECURELY
JUNCTION BOX. INSTALL AS SHOWN OR AS REQUIRED FOR MOTORIZED DAMPER. PROVIDE MOUNTED TO CHANNELS WITH SCREWS. SPRING MOUNTED SOCKETS ARE 4533 PONCE DE LEON BLVD.
2. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR EXACT CONTRACTOR MUST PROVIDE ALL REQUIRED MODIFICATIONS TO THE M
1/2"C TO FIRE ALARM SYSTEM FOR CONTROLS. WIRE AS REQUIRED PER SMOKE EVACUATION Coral Gables, Florida 33146
LOCATION OF EQUIPMENT. THESE DRAWINGS ARE NOT INTENDED TO SHOW ELECTRICAL INSTALLATION TO COORDINATE WITH ACTUAL EQUIPMENT LIGHT FIXTURE, RECESSED OR SURFACE MOUNTED. NOT ACCEPTABLE. FIXTURE MANUFACTURER IS RESPONSIBLE FOR
SEQUENCE OF OPERATION. COORDINATE WITH MECHANICAL DRAWINGS. TEL: (305) 740-5442
EVERY MINOR DETAIL, BUT THE CONTRACTOR SHALL FURNISH AND INSTALL ALL PURCHASED SHOP DRAWINGS AT NO ADDITIONAL CHARGES TO SUPPLYING CORRECT SOCKETS FOR LAMPS INDICATED FOR USE IN
ITEMS REQUIRED FOR A COMPLETE AND ACCEPTABLE WORKING SCHEDULE. LIGHT FIXTURE, WALL MOUNTED AT 8'-0"A.F.F. UNLESS OTHERWISE INDICATED. FIXTURE. FAX: (305) 740-5443
THE CONTRACT. FSD
JUNCTION BOX. INSTALL AS SHOWN OR AS REQUIRED FOR FIRE/ SMOKE DAMPER. PROVIDE E-MAIL: info@beharfont.com
3. CHECK EQUIPMENT FOR PROPER VOLTAGE, PHASE, AND AMP RATING BEFORE 28. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING; STRIP LIGHT FIXTURE, SURFACE MOUNTED. 3. ALL FIXTURE WIRING SHALL BE OF THE HEAT RESISTANT TYPE. AS
CONNECTION TO CIRCUITS. AND ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST 1/2"C TO FIRE ALARM SYSTEM FOR CONTROLS. WIRE AS REQUIRED PER SMOKE EVACUATION REQUIRED BY THE SPECIFICATIONS, OR AS REQUIRED BY LOCAL CODE.
PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. LIGHT FIXTURE IN EMERGENCY SYSTEM. SEQUENCE OF OPERATION. COORDINATE WITH MECHANICAL DRAWINGS. 4. FIXTURE MANUFACTURER AND CONTRACTOR SHALL BE RESPONSIBLE FOR © 2019 BEHAR FONT & PARTNERS P.A.
4. ALL CIRCUITS SHALL BE CLEARLY IDENTIFIED AND SHOWN ON PANEL THE DESIGN AND DRAWINGS FOR THIS
M.D. PROPER VENTILATION AND TEMPERATURE CONDITIONS OF LIGHT
DIRECTORIES. DO NOT CHANGE CIRCUIT ARRANGEMENT SHOWN ON THESE 29. JUNCTION BOXES SHALL BE GALVANIZED STEEL WITH SCREW OR HINGED JUNCTION BOX. INSTALL AS SHOWN OR AS REQUIRED FOR POWER EXTENSION TO OUTSIDE PROJECT ARE THE PROPERTY OF THIS

DRAWINGS. COVERS FOR INDOOR LOCATIONS AND WEATHER-PROOF WHERE EXPOSED TO AIR INTAKE MOTORIZED DAMPER. PROVIDE 1/2"C TO FAN COIL STARTING CONTACTOR. FIXTURES. ARCHITECT AND ARE PROTECTED UNDER THE
EMERGENCY LIGHTING UNIT, WALL MOUNTED. COPYRIGHT PROTECTION ACT.
WEATHER. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS. CAST INTERLOCK WITH RESPECTIVE FAN COIL UNIT AS REQUIRED FOR SIMULTANEOUS OPERATION. 5. ALL FIXTURES WITH REMOVABLE COVERS OR CONES SHALL BE SUPPLIED
5. ALL MATERIALS SHALL BE NEW AND SHALL BEAR THE UL LABEL WHEN
ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS AND SPECIAL LIGHT FIXTURE, RECESSED MOUNTED. COORDINATE WITH MECHANICAL DRAWINGS. WITH SAFETY CHAINS SECURELY ATTACHED TO MAIN HOUSINGS. THERE SEAL:
APPLICABLE.
ENCLOSURES FOR OTHER CLASSIFIED AREAS. SHALL BE A SUFFICIENT QUANTITY OF SAFETY CHAINS TO SUPPORT TOTAL
6. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF A/C JUNCTION BOX. INSTALL AS SHOWN AS REQUIRED FOR CONTROL INTERCONNECTION
30. OUTLETS SHALL BE FLUSHED WITH FINISHED SURFACES. TWO OR MORE LIGHT LIGHT FIXTURE, STEM MOUNTED. WEIGHT OF FIXTURE.
THE POWER, TELEPHONE AND CABLE T.V. COMPANIES. CONTRACTOR SHALL SWITCHES IN SAME WALL SHALL BE INSTALLED IN GANG-TYPE BOXES. BETWEEN A/C FAN COIL UNIT AND CONDENSING UNIT. PROVIDE 1/2"C AND CONNECT AS 6. THE CONTRACTOR SHALL VERIFY WITH THE ARCHITECT AND/OR ENGINEER
COORDINATE SERVICE REQUIREMENTS WITH THE UTILITY COMPANIES. LIGHT FIXTURE, SURFACED MOUNTED. REQUIRED. COORDINATE EXACT LOCATION WITH MECHANICAL DRAWINGS. THAT ALL LIGHTING EQUIPMENT MEETS ALL NATIONAL AND LOCAL CODES
COORDINATE ALL BOX LOCATION WITH BUILDING ARCHITECTURAL FEATURES.
7. ALL CONDUCTORS SHALL BE IN CONDUIT. ALL SECTIONS OF METALLIC CONDUIT AS APPLICABLE, E.G. THERMAL PROTECTION AND U.L. LABEL. FIXTURES
31. PANELBOARDS SHALL BE DEAD FRONT CIRCUIT BREAKER TYPE WITH COPPER LIGHT FIXTURE, PENDANT MOUNTED. MOTOR, SIZE AS INDICATED ON DRAWINGS.
SYSTEM SHALL BE GROUNDED AND ELECTRICALLY CONTINUOUS. INSTALLED IN WET AND/OR DAMP LOCATIONS SHALL BE PROVIDED WITH
BUS AND AS SCHEDULED ON DRAWINGS. EACH PANELBOARD SHALL BE
8. RACEWAYS INSTALLED UNDERGROUND IN CONCRETE SLABS, AND/OR LARGER PROVIDED WITH A SEPARATE GROUND BUS IN ADDITION TO THE NEUTRAL BUS. LIGHT FIXTURE, RECESSED MOUNTED WITH SOLID LENS. COMBINATION EXHAUST FAN AND LIGHT U.L. LABEL IDENTIFYING FIXTURE IS SUITABLE FOR USE IN THE INSTALLED
G
THAN 2" IN DIAMETER SHALL BE GALVANIZED RIGID STEEL. PVC PIPE SCHEDULE CIRCUIT BREAKERS SHALL BE BOLT-ON AND HAVE A MINIMUM INTERRUPTING LOCATION.
40 IS ACCEPTABLE FOR UNDERGROUND INSTALLATION ONLY, IF APPROVED BY LIGHT FIXTURE, WALL MOUNTED ABOVE DOOR OR 8'-0"A.F.F. UNLESS OTHERWISE INDICATED. 7. CONTRACTOR SHALL SUBMIT FOR ACCEPTANCE OF THE ARCHITECT AND
RATING OF 10,000 AMPERES AT 120 VOLTS, 14,000 AMPERES AT 277 VOLTS. ALL FIRE ALARM SYSTEM:
LOCAL AUTHORITIES, UDNER PAVED AREAS IT SHALL BE ENCASED IN CONCRETE PANELS SHALL HAVE SNAP CATCH DOORS WITH CLEAR PLASTIC ENCLOSED THE ENGINEER, MANUFACTURER'S CATALOGUE SPECIFICATION SHEETS
WITH 24" MIN. COVER. RACEWAY 2 INCHES AND SMALLER IN DIAMETER SHALL BE TYPEWRITTEN DIRECTORY INSIDE. FOR ALL STANDARD CATALOGUE LIGHT FIXTURES PRIOR TO FABRICATION
LIGHT FIXTURE, RECESSED WALL WASHWER. F PULL STATION. WALL M0UNTED AT 48" A.F.F. WP WHERE REQUIRED. SEE FIRE ALARM
I.M.C. IF EXPOSED TO WEATHER, E.M.T. ELSEWHERE. FLEXIBLE CONDUIT USED OF THE SAME.
32. DRY TYPE TRANSFORMER SHALL BE 480 VOLTS DELTA PRIMARY, 208Y/ 120 VOLTS SYSTEM DWG.
JOSE A. RAMIREZ, P.E.
WHERE INDICATED SHALL BE METAL FOR INDOOR LOCATIONS, LIQUID-TIGHT FOR SECONDARY. THREE-PHASE, 60 HERTZ WITH FOUR 2-1/2% FCBN TAPS AND TWO LIGHT FIXTURE, RECESSED MOUNTED ON CONCRETE WALL . 8. FIXTURE MANUFACTURER AND/OR CONTRACTOR SHALL SUBMIT FOR P.E. 0060224
OUTDOOR LOCATIONS. USE STEEL COMPRESSION TYPE FITTING. D IONIZATION SMOKE DETECTOR ANALOG TYPE, CEILING MOUNTED. SEE FIRE ALARM SYSTEM ACCEPTANCE OF THE ARCHITECT AND THE ENGINEER, DETAILED CONSULTANT:
2-1/2% FCAN TAPS. KVA RATING SHALL BE AS SHOWN ON DRAWINGS.
9. JUNCTION BOX FOR LIGHTING FIXTURE DWG. DRAWINGS OF ALL SPECIAL DESIGN FIXTURES PRIOR TO FABRICATION OF
RACEWAYS INSTALLED IN OR THRU ANY CONCRETE SLABS BE SPACED A 33. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK-MAKE, L
MINIMUM OF 3" DIA. OF THE LARGEST RACEWAY. METALLIC RACEWAYS SMOKE/HEAT PHOTOELECTRIC DETECTOR FOR ELEVATOR CAPTURE, CEILING MOUNTED. SEE THE SAME.
QUICK- BREAK, ENCLOSURE AS REQUIRED BY EXPOSURE. MOTOR STARTERS D
INSTALLED UNDERGROUND OR UNDER SLABS SHALL BE COATED WITH TWO E FIRE ALARM SYSTEM DWG. 9. ALL COMPONENT PARTS OF ARCHITECTURAL LIGHTING INSTALLATION
SHALL BE MANUAL OR MAGNETIC WITH OVERLOAD RELAYS IN EACH LEG. FUSES
COATS OF AN ASPHALTIC PAINT. SHALL BE PROVIDED BY GENERAL CONTRACTOR. COLOR AND FINISH
SHALL BE DUAL ELEMENT, COMBINING TIME DELAY WITH CURRENT LIMITING. L F JUNCTION BOX (LIGHTING AND FAN) D DUCT MOUNTED SMOKE DETECTOR. SEE FIRE ALARM SYSTEM DWG.
D SPECIFICATION SHALL BE BY THE ARCHITECT UNLESS OTHERWISE
10. CABLE AND WIRE INDICATED ON DRAWINGS SHALL BE 600 VOLT, COPPER, 34. ELECTRICAL CONTRACTOR SHALL PERFORM ALL NECESSARY WORK AND SHALL DESIGNATED IN THE LIGHTING FIXTURE SCHEDULE.
STRANDED, THHN/THWN INSULATION IN SIZES NO. 12 THRU NO. 8 AWG; AND PROVIDE ALL NECESSARY INSTRUMENTS AND SPECIAL APPARATUS TO CONDUCT
TAMPER SWITCH MONITOR MODULE. VERIFY QUANTITY AND LOCATION WITH MECHANICAL 10. THE CONTRACTOR SHALL VERIFY CEILING CONSTRUCTION FOR EACH
COPPER, STRANDED THW OR THWN INSULATION IN SIZES NO. 6 AWG AND ANY TEST THAT MAY BE REQUIRED TO INSURE THE SYSTEM IS FREE OF ALL TS
TRADE. SEE FIRE ALARM SYSTEM DWG. FIXTURE TYPE AND LOCATION AND SHALL COORDINATE TRIM DETAILS.
LARGER. MINIMUM SIZE WIRE SHALL BE NO. 12 AWG, MAXIMUM SIZE SHALL BE 600 IMPROPER GROUNDS AND SHORT CIRCUITS, AND THAT ALL FEEDERS ARE
MCM. PROPERLY BALANCED. FLOW SWITCH MONITOR MODULE.VERIFY QUANTITY AND LOCATION WITH MECHANICAL 11. BY SUBMITTING SHOP DRAWINGS, PRODUCT DATA, SAMPLES AND SIMILAR
TRACK LIGHT FIXTURE. FS
11. SEE MECHANICAL DRAWINGS FOR ELECTRICAL REQUIREMENTS AND LOCATION 35. WIRING DEVICES SHALL BE APPROVED SPECIFICATION GRADE. VERIFY LOCATION TRADE. SEE FIRE ALARM SYSTEM DWG. SUBMITTALS, THE CONTRACTOR REPRESENTS THAT THE CONTRACTOR
OF HVAC EQUIPMENT. THE CONTRACTOR SHALL PROVIDE ALL BRANCH CIRCUIT WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. WIRING DEVICES SHALL HAS DETERMINED AND VERIFIED MATERIALS, FIELD MEASUREMENTS AND
LIGHT FIXTURE, POLE MOUNTED. R RELAY MODULE. SEE FIRE ALARM SYSTEM DWG. FIELD CONSTRUCTION CRITERIA RELATED THERETO, OR WILL DO SO, AND
AND CONTROL WIRING AS INDICATED AND REQUIRED, AND IN CONFORMANCE BE WHITE COLOR, DECORA TYPE.
WITH NEC ARTICLES 440, AND 725.26 (SEPARATE RACEWAYS) AND HAS CHECKED AND COORDINATED THE INFORMATION CONTAINED WITHIN
36. ELECTRICAL CONTRACTOR SHALL PROVIDE OUTLETS TO MATCH EQUIPMENT POLE MOUNTED LIGHT FIXTURE. S FIRE ALARM SPEAKER, CEILING MOUNTED, SEE FIRE ALARM SYSTEM DWG.
MANUFACTURER'S RECOMMENDATIONS. THERMOSTAT LOCATIONS ARE SHOWN SUCH SUBMITTALS WITH THE REQUIREMENTS OF THE WORK AND OF THE
PLUGS.
ON MECHANICAL DRAWINGS. MAKE CONNECTIONS AS REQUIRED BY CONTROL S CONTRACT DOCUMENTS.
37. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID BOLLARD LIGHT FIXTURE. FIRE ALARM SPEAKER, WALL MOUNTED AT 84" A.F.F. SEE FIRE ALARM SYSTEM DWG.
WIRING DIAGRAM. 12. UNLESS OTHERWISE SPECIFIED, VOLTAGES OF ALL LAMPS SHALL BE
INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. DETERMINED BY ELECTRICAL ENGINEER. ELECTRICAL CONTRACTOR
12. CIRCUITS ON THE DRAWINGS ARE TO DETERMINE LOAD DATA AND PANEL SIZE. L FIRE ALARM STROBE LIGHT, WALL MOUNTED AT 80" TO BOTTOM. SEE FIRE ALARM SYSTEM
38. CONTRACTOR SHALL DO HIS OWN CUTTING OF FLOOR AND WALLS AND DO ALL EXIT SIGN WALL MOUNTED LIGHT FIXTURE. DWG. SHALL COORDINATE PROPER LAMP BASE TYPES WITH SOCKET PROVIDED
THE CONTRACTOR SHALL PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO
PATCHING ASSOCIATED WITH HIS/HER INSTALLATON. OBTAIN APPROVAL BEFORE IN SPECIFIED FIXTURE.
SUIT JOB CONDITIONS AND BALANCE THE JOB THROUGHOUT. SL FIRE ALARM SPEAKER/STROBE LIGHT COMBINATION. WALL MOUNTED AT 80" TO BOTTOM. SEE
DOING ANY CUTTING. REPAIR ANY DAMAGE DONE TO OTHER'S EQUIPMENT OR EXIT SIGN CEILING MOUNTED LIGHT FIXTURE (BOTH SIDE). 13. UNLESS OTHERWISE SPECIFIED, INITIAL PURCHASE OF LAMPS NOT EASILY
13. ROUTING OF RACEWAYS, INTERCONNECTING OUTLETS AND HOME-RUNS IS UP TO MATERIAL. FIRE ALARM SYSTEM DWGS.
THE ELECTRICAL CONTRACTOR, BUT AFTER COMPLETION OF THE INSTALLATION, AVAILABLE LOCALLY SHALL INCLUDE 100% SPARE QUANTITY OF LAMPS.
39. PROVIDE FIRE STOPPING MATERIAL AT ALL CONDUIT OPENINGS IN WALL AND SL FIRE ALARM SPEAKER/STROBE LIGHT COMBINATION. CEILING MOUNTED. SEE FIRE ALARM
CONTRACTOR SHALL SUBMIT TO THE OWNER AS-BUILT DRAWINGS OF THE EXIT SIGN CEILING MOUNTED LIGHT FIXTURE (ONE SIDE). 14. FIXTURE MANUFACTURER AND/OR CONTRACTOR SHALL BE RESPONSIBLE
FLOOR, AND OTHER LOCATIONS AS REQUIRED BY CODE TO PRESERVE FIRE SYSTEM DWGS.
ELECTRICAL WORK FOR FUTURE RECORD. THAT ALL FIXTURES SPECIFIED FOR EXTERIOR USE SHALL BE TREATED
RATING INTEGRITY.
WITH A WEATHER- RESISTANT CORROSION PROTECTIVE COATING.
14. CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND SUSPENSION SYSTEM 40. CORRECTIONS OF ANY DEFECTS SHALL BE COMPLETED WITHOUT CHARGE AND SWITCH: H HEAT DETECTOR, CEILING MOUNTED. SEE FIRE ALARM SYSTEM DWG.
FOR SELECTION OF THE PROPER TRIM AND SUPPORT ARRANGEMENTS OF THE SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE 15. ALL RECESSED LIGHT FIXTURES SHALL BE INSTALLED AT A MINIMUM OF 6"
FIXTURE. COORDINATE REQUIREMENTS WITH ARCHITECT. SINGLE POLE LIGHT SWITCH, QUIET TYPE, 120-277 VOLTS, 20 AMPS (15 AMPS FOR FIREFIGHTER'S TELEPHONE JACK, WALL MOUNTED AT 48" A.F.F. SEE FIRE ALARM SYSTEM AWAY FROM A/C DUCTS.
INSTALLATION WHICH MAY HAVE BEEN DAMAGED. F
NON-APPLIANCE CKTS. IN APT. UNITS). INSTALL 48"A.F.F. TO TOP. DWG. 16. RECESSED LIGHT FIXTURES INSTALLED IN 1-HOUR FIRE RATED CEILING
15. FURNISH AND INSTALL LIGHTING FIXTURES AND LAMPS AS CALLED FOR ON 41. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE OF
THESE DRAWINGS. DEFECT FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM THE DATE OF 3 THREE WAY LIGHT SWITCH, QUIET TYPE, 120-277 VOLTS, 20 AMPS (15 AMPS IN APT. UNITS). EWL ELEVATOR'S WARNING LIGHT, WALL MOUNTED AT 48" A.F.F. SEE FIRE ALARM SYSTEM DWG. SHALL BE PROTECTED IN ACCORDANCE WITH THE CEILING U.L. DESIGN
CLASSIFICATION. RECEIVED
ACCEPTANCE. INSTALL 48"A.F.F. TO TOP. FCC
16. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED FIRE COMMAND CENTER, SEE FIRE ALARM SYSTEM DWG.
AS REQUIRED IN ARTICLE 250 OF THE NEC. PVC CONDUITS TO HAVE EQUIPMENT 42. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ACCEPTANCE OF EVERY 4 FOUR WAY LIGHT SWITCH, QUIET TYPE, 120-277 VOLTS, 20 AMPS (15 AMPS IN APT. UNITS).
FTB FIRE/SMOKE DAMPER PROVIDE A RELAY CONTROL MODULE. SEE FIRE ALARM SYSTEM DWG.
4/20/2023
GROUND CONDUCTORS, AND WHEN CROSSING BUILDING EXPANSION JOINTS, EQUIPMENT AND MATERIAL USED, PRIOR TO ORDERING. INSTALL 48"A.F.F. TO TOP.
EXPANSION FITTINGS WITH BONDING JUMPERS SHALL BE USED. ALL GROUND 43. MOTORS: A. MOTORS 1/2 HORSEPOWER AND BELOW SHALL BE 120 VOLTS, SINGLE D DIMMER SWITCH, SINGLE POLE, WATT RATING TO MATCH LOAD. 120 VOLTS. INSTALL 48"A.F.F. FIRE TERMINAL BOX WITH CONTROL MODULES, SEE FIRE ALARM SYSTEM DWG.
CONNECTIONS TO BE DONE AS PER LATEST EDITION OF NATIONAL ELECTRICAL PHASE. B. MOTORS OF 1/2 HORSEPOWER AND LARGER SHALL BE AS SCHEDULED. TO TOP.
CODE. C. PROVIDE DISCONNECTS FOR ALL MOTORS TO BE INSTALLED. M MANUAL MOTOR STARTER SWITCH, SINGLE POLE WITH OVERLOAD PROTECTION. INSTALL D DUCT MOUNTED SMOKE DETECTOR. SEE FIRE ALARM SYSTEM DWG.
D
17. ELECTRICAL EQUIPMENT AIC RATING AND FEEDER SIZES SHOWN ON THESE 44. STANDARDS FOR MATERIALS. ALL MATERIALS SHALL BE NEW AND SHALL 48"A.F.F. OR AS REQUIRED.
PLANS ARE DESIGNED FOR MAXIMUM AVAILABLE FAULT CURRENT AND MAXIMUM
H FIXED TEMPERATURE (13DEGREES) HEAT DETECTOR. SEE FIRE ALARM SYSTEM DWG.
CONFORM TO THE APPLICABLE STANDARDS WHERE SUCH HAVE BEEN H
COMBINATION THERMOSTAT AND HUMIDITY CONTROL. INSTALL AT 48" A.F.F.

PROPOSED MIXED-USE RENTAL DEVELOPMENT:


ALLOWABLE VOLTAGE DROP RESPECTIVELY. ESTABLISHED FOR THE PARTICULAR MATERIAL IN QUESTION. THE PUBLICATIONS SMOKE DETECTOR, WALL OR CEILING MOUNTED. 120 VOLTS AND BATTERY BACK UP, WHIT
D D
18. THE PROJECT IS "NEW CONSTRUCTION". THE CONTRACTOR SHALL VISIT THE JOB OS DECORA TYPE COMBINATION SINGLE POLE LIGHT SWITCH WITH INFRARED OCCUPANCY A
AND STANDARDS OF THE ORGANIZATIONS BELOW ARE APPLICABLE TO VISIBLE "POWER ON' INDICATOR, TEST BUTTON, SELF COTAINED, SOUNDING DEVICE (MIN.
SITE TO DETERMINE THE EXTENT OF WORK INVOLVED WITH THESE DOCUMENTS MATERIALS SPECIFIED HEREIN. SENSOR. WIRE TO LIGHT FIXTURE AS PER MANUFACTURER'S WIRING DIAGRAM, AS SHOWN RATING 85 dbA AT 10'-0"). SEE APARTMENT'S GENERAL NOTE #8.
AS SHOWN. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL A. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) AND AS REQUIRED. PROGRAM AUTOMATIC TIME SETTING TO TURN LIGHTING OFF WITHIN 30
D D COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, WALL OR CEILING MOUNTED, 120
EXISTING CONDITIONS AND ALLOW FOR ANY CHANGES THAT MAY BE MADE B. UNDERWRITER'S LABORATORIES, INC. (UL) MINUTES OF AN OCCUPANT LEAVING THE AREA WATT RATING TO MACH LOAD. LEVITON CAT. B VOLTS AND BATTERY BACKUP WITH VISIBLE POWER "ON" INDICATOR, TEST BUTTON AND

4101 SALZEDO STREET CORAL GABLES, FLORIDA 33146


DURING THE COMPLETION OF THE PROJECT. ANY ELECTRICAL WORK THAT MAY C. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) NO. OSSMT OR EQUAL INSTALL 48" A.F.F.
SELF-CONTAINED, SOUNDING DEVICE (MIN. RATING 85 DBA AT 10'-0"). SEE APARTMENT'S
HAVE TO BE DONE TO COMPLETE ANY ALTERATIONS SHOWN ON ANY PLAN SHALL D. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) OS DECORA TYPE COMBINATION SINGLE POLE FAN SWITCH WITH INFRARED OCCUPANCY GENERAL NOTE #17.
BE INCLUDED IN THIS CONTRACT WITH NO ADDITIONAL CHARGES TO THE OWNER E. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) F
AFTER THE CONTRACTS ARE LET. SENSOR. WIRE TO EXHAUST FAN AS PER MANUFACTURER'S WIRING DIAGRAM, AS SHOWN C0 C0 CARBON MONOXIDE DETECTOR, WALL OR CEILING MOUNTED, 120 VOLTS AND BATTERY
WHERE REFERENCE IS MADE TO TRADE NAMES OR NAMES OF MANUFACTURER'S
AND AS REQUIRED. PROGRAM AUTOMATIC TIME SETTING TO TURN EXHAUST FAN OFF WITHIN BACKUP WITH VISIBLE POWER "ON" INDICATOR, TEST BUTTON AND SELF-CONTAINED,
19. THE CONTRACTOR SHALL FURNISH ALL LABOR MATERIALS AND EQUIPMENT SUCH REFERENCES ARE MADE SOLELY TO DESIGNANTE AND TO IDENTIFY
30 MINUTES OF AN OCCUPANT LEAVING THE AREA WATT RATING TO MACH LOAD. LEVITON SOUNDING DEVICE (MIN. RATING 85 DBA AT 10'-0"). SEE APARTMENT'S GENERAL NOTE #17.
REQUIRED FOR A COMPLETE ELECTRICAL INSTALLATION IN ACCORDANCE WITH QUALITY OF MATERIALS OR EQUIPMENT TO BE FURNISHED AND DOES NOT
CAT. NO. OSSMT OR EQUAL INSTALL 48" A.F.F.
THESE DRAWINGS. PRECLUDE THE USE OF 'EQUAL' EQUIPMENT AS APPROVED BY THE ENGINEER. DH MAGNETIC DOOR HOLDER. SEE FIRE ALARM SYSTEM DWG.

MERRICK 250
20. PROVIDE TEMPORARY POWER AND LIGHT OUTLETS AND ALL REQUIRED CONNEC- OS CEILING OR WALL MOUNTED MULTI-TECHNOLOGY OCCUPANCY SENSOR RATED AT 24 VOLTS.
OS
45. WORKMANSHIP. ALL WORK SHALL BE INSTALLED IN A NEAT, ORDERLY MANNER.
TIONS FOR USE BY OTHER TRADES. WIRE IN SERIES WITH LIGHT SWITCHES LIGHT FIXTURES CONNECTED TO NORMAL POWER DC DOOR CONTACT SWITCH.
DEVICES, PLATES, EXPOSED. RACEWAYS, ENCLOSURES, COVERS, FIXTURES, ETC
21. OUTDOOR UNDERGROUND CONDUITS SHALL BE SCHEDULE 40 PVC. UNDER ONLY IN RESPECTIVE AREAS AND AS PER MANUFACTURER'S WIRING DIAGRAM. LEVITE
SHALL BE ALIGNED PERPENDICULAR TO/OR PARALLEL WITH THE PRINCIPAL KP KEY PAD. INSTALL 48" A.F.F.
PAVED AREAS IT SHALL BE ENCASED IN CONCRETE, MINIMUM COVER SHALL BE STRUCTURE MEMBERS. THE EDGES OF THESE COVERS, PLATES, ENCLOSURES, CATALOG NO. OSC20-MOW OR EQUAL. PROVIDE POWER PACK RATED AT 13 AMPS, QUANTITY
24". AS REQUIRED. LEVITE CATALOG NO. OSP20-120 OR EQUAL. PROGRAM AUTOMATIC TIME DOOR CHIME. INSTALL 7'-6" A.F.F. UNLESS OTHERWISE INDICATED.
ETC. SHALL BE IN VERTICAL OR HORIZONTAL PLANE, AS APPLICABLE FOR THE RECEPTACLES:
22. ELECTRICAL INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF N.E.C. SETTING TO TURN LIGHTING OFF WITHIN 30 MINUTES OF AN OCCUPANT LEAVING THE AREA.
PARTICULAR ITEM INVOLVED. EXPOSED RACEWAYS SHALL BE OFFSET WHERE PUSH BUTTON. INSTALL 48" A.F.F.
110-26 (A)(1) "WORKING SPACES" AND N.E.C. 408 "SWITCHBOARDS AND THEY ENTER SURFACE-MOUNTED EQUIPMENT. WIRING INSTALLED IN PLANELS
PANELBOARDS" INCLUDING SPACES ABOVE THE EQUIPMENT. AND OTHER ENCLOSURES SHALL BE NEATLY LOOPED AND LACED AND NOT I INTERCOMM. INSTALL 48" A.F.F.
23. PROVIDE FIELD MARKING TO WARM PERSONNEL OF POTENTIAL ELECTRIC ARC WADDED OR BUNDLED. DUPLEX RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE TAMPER RESISTANT, 20
FLASH HAZARDS IN ACCORDANCE WITH N.E.C. ART. 110-16. AMPS (15 AMPS FOR NON-APPLIANCE CKTS. IN APT. UNITS). INSTALL 18"A.F.F. TO CENTER MISCELLANEOUS:
46. COORDINATED SHOP DRAWINGS: SUBMIT COORDINATED SHOP DRAWINGS AT UNLESS OTHERWISE INDICATED.
24. PRIOR TO INSTALLATION OF ROUGH ELECTRIC WIRING CHECK NAMEPLATE DATA 1/2-INCH SCALE, NOT REDUCED, USING ACTUAL SIZES AND WEIGHTS OF CONDUIT RUN CONCEALED IN CEILING OR WALL.
OF A/C EQUIPMENT, HOT WATER HEATERS, ELEVATORS AND OTHER EQUIPMENT DUPLEX RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE RESISTANT, 20 AMPS (15
VENDOR'S EQUIPMENT. PLANS SHALL CONSIST OF FLOOR PLAN AND ELEVATIONS AMPS FOR NON-APPLIANCE CKTS. IN APT. UNITS). INSTALL 44"A.F.F. TO CENTER. CONDUIT RUN UNDERGROUND OR IN FLOOR SLAB.
TO OBTAIN CORRECT WIRE SIZES AND OVERCURRENT DEVICE SIZES. OF EACH SIGNIFICANT WALL. DUCTS OR FOREIGN PIPES MAY NOT ENCROACH
OVER PANELS AND SWITCHBOARDS. SHOW NEC REQUIRED CLEARANCES. UPON SINGLE RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE, 20 AMPS. INSTALL CONDUIT UP.
25. IF, THROUGH ERRORS OR OMISSIONS, THE INTENT TO THE ARCHITECT/ENGINEER
COMPLETION OF THE PROJECT THE PLANS SHALL BE UPDATED WITH INCIDENTAL 18"A.F.F. TO CENTER UNLESS OTHERWISE INDICATED.
WITH REGARD TO ANY DETAIL IS NOT CLEAR, OR IS CAPABLE OF MORE THAN ONE CONDUIT DOWN.
INTERPRETATION, SUCH MATTERS SHALL BE BROUGHT TO THE ATTENTION OF ITEMS SUCH AS RELAYS, TIME CLOCKS, CONTACTORS, ETC. DUPLEX RECEPTACLE OUTLET WITH TOP RECEPTACLE SWITCHED, 120 VOLTS, 3-WIRE,
GROUNDING TYPE TAMPER RESISTANT, 15 AMPS. INSTALL 18"A.F.F. TO CENTER. FLEXIBLE CONDUIT.
ARCHITECT/ENGINEER IN WRITING BEFORE THE SUBMISSION OF BIDS, AND THE
ARCHITECT/ENGINNER SHALL MAKE CORRECTION OR EXPLANATION IN WRITING. 47. ALL EMERGENCY SYSTEM, DISCONNECTS FEEDERS, BRANCH CIRCUITS SHALL HOME-RUN TO ELECTRIC PANEL. HATCH MARKS INDICATE NUMBER OF WIRES, - DENOTES
USB CHARGER/DUPLEX RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE 20AMPS
OTHERWISE, NO EXTRA CHARGE WILL BE ALLOWED FOR THE WORK OR MATERIAL COMPLY WITH NEC 700.10(A)(B)(C)(D).” GROUND WIRE.
(15 AMPS FOR NON-APPLIANCE CKTS. IN APT. UNITS). INSTALL 44"A.F.F. TO CENTER.
WHICH THE ARCHITECT/ENGINEER WILL REQUIRE, PROVIDED THAT IT COMES 2 60
0 DISCONNECT SWITCH. 2-NUMBER OF POLES; 60-FRAME SIZE; 0-NO FUSE (FUSE SIZE).
QUADRUPLEX RECEPTACLE OUTLET, 125 VOLTS, 3-WIRE, GROUNDING TYPE TAMPER
WITHIN A RESONABLE INTERPRETATION OF THE DRAWINGS AND SPECIFICATIONS.
RESISTANT, 20 AMPS. INSTALL 18"A.F.F. TO CENTER UNLESS OTHERWISE INDICATED. A
LIGHTING FIXTURE IDENTIFICATION. A-DENOTES TYPE; 3-DENOTES QUANTITY OF FIXTURES IN
3 THE AREA.
SPECIAL RECEPTACLE OUTLET, 250 VOLTS, 4-WIRE, GROUNDING TYPE, AMPS AS SHOWN.
INSTALL 18" A.F.F. TO CENTER UNLESS OTHERWISE INDICATED. VFD MOTOR STARTER, BY MECHANICAL CONTRACTOR OR LIGHTING CONTRACTOR.
LIST OF DRAWINGS DUPLEX RECEPTACLE. INSTALL FLUSH AT FLOOR. TIME CLOCK. INSTALL AS REQUIRED.
01 E-0.00 SYMBOLS LEGEND, ELECTRICAL NOTES & INDEX DRAWINGS GENERAL NOTE FOR OCCUPANCY SENSORS FOR LIGHTING: EV1 W/P SINGLE PORT ELECTRIC VEHICLE CHARGING STATION; W/P- DENOTES (W) WALL MOUNTED OR
ELECTRICAL PANEL.
02 E-0.01 MISCELLANEOUS DETAILS (P) BOLLARD FLR. MOUNTED
03 E-0.02 MISCELLANEOUS DETAILS 1- OCCUPANCY SENSORS FOR LIGHTING ON ALL FLOORS NEED TO MEET THE PLYWOOD BOARD FOR TELEPHONE AND CABLE T.V. SYSTEMS.
REQUIREMENTS OUTLINED IN NFPA 101, 7.8.1.2.2 AND NEED TO BE TIED IN TO EV2 W/P DUAL PORT ELECTRIC VEHICLE CHARGING STATION; W/P- DENOTES (W) WALL MOUNTED OR
04 E-0.03 MISCELLANEOUS DETAILS THE FIRE ALARM SYSTEM. (P) BOLLARD FLR. MOUNTED STRIP HEATER.
05 E-0.04 EMERGENCY GENERATOR SPECIFICATIONS AND DETAILS
2- OCCUPANCY SENSORS SHALL ONLY CONTROLLED LIGHT FIXTURES ABBREVIATIONS:
06 E-1.00 ELECTRICAL SITE PLAN DATA:
CONNECTED TO NORMAL POWER. EMERGENCY LIGHTS AND EXIT LIGHTS
07 E-1.01A GROUND LEVEL SECTOR 'A' ELECTRICAL PLAN CONNECTED TO GENERATOR SYSTEM SHALL NOT BE CONTROLLED BY
M MAIN TELEPHONE OUTLET. A.F.F. ABOVE FINISHED FLOOR.
08 E-1.01B GROUND LEVEL SECTOR 'B' ELECTRICAL PLAN OCCUPANCY SENSORS.
09 E-1.01C RESERVED TELEPHONE OUTLET. INSTALL 18"A.F.F. TO CENTER UNLESS OTHERWISE INDICATED. W.P. WEATHER PROOF.
10 E-1.02A SECOND LEVEL SECTOR 'A' ELECTRICAL PLAN CABLE T.V. OUTLET. INSTALL 18"A.F.F. TO CENTER UNLESS OTHERWISE INDICATED. W.R. WEATHER RESISTANT.
11 E-1.02B SECOND LEVEL SECTOR 'B' ELECTRICAL PLAN COMBINATION TELEPHONE/COMPUTER DATA AND T.V. OUTLET. INSTALL 18" A.F.F. TO CENTER G.F.I. GROUND FAULT INTERRUPTER.
12 E-1.03A THIRD LEVEL SECTOR 'A' ELECTRICAL PLAN UNLESS OTHERWISE INDICATED.
V.P. VAPOR PROOF.
13 E-1.03B THIRD LEVEL SECTOR 'B' ELECTRICAL PLAN COMPUTER DATA OUTLET. INSTALL 18" A.F.F. TO CENTER UNLESS OTHERWISE INDICATED. W.T. WATER TIGHT
14 E-1.04A 4TH LEVEL SECTOR 'A' ELECTRICAL PLAN COMBINATION TELEPHONE OUTLET AND COMPUTER DATA OUTLET. INSTALL 18" A.F.F. TO E.W.C. ELECTRIC WATER COOLER.
15 E-1.04B 4TH LEVEL SECTOR 'B' ELECTRICAL PLAN CENTER UNLESS OTHERWISE INDICATED.
P.H. PHOTOCELL.
16 E-1.05A 5TH LEVEL SECTOR 'A' ELECTRICAL PLAN JUNCTION BOX. INSTALL AS SHOWN OR AS REQUIRED.
17 E-1.05B 5TH LEVEL SECTOR 'B' ELECTRICAL PLAN A.F.C.I. ARC FAULT CIRCUIT INTERRUPTER.
18 E-1.06 TYPICAL LEVEL (FROM 6TH THRU 12TH LVS.) ELECTRICAL PLAN W.L. DENOTES WITH WET LOCATION LABEL.
19 E-1.07 ROOF LEVEL ELECTRICAL PLAN E.C. EMPTY CONDUIT.
20 E-1.08 LIGHTNING PROTECTION SYSTEM
21 E-1.09 GROUND LEVEL PHOTOMETRIC PLAN
22 E-1.10 SECOND LEVEL PHOTOMETRIC PLAN
23 E-1.11 THIRD LEVEL PHOTOMETRIC PLAN
24 E-1.12 FOURTH LEVEL PHOTOMETRIC PLAN CLIENT INFORMATION:
25 E-1.13 RESERVED CORAL GABLES
26 E-2.00 PANEL SCHEDULES
ALTA, LLC.
27 E-2.01 PANEL SCHEDULES
28 E-2.02 PANEL SCHEDULES
2950 SW 27th AVE
29 E-2.03 PANEL SCHEDULES SUITE 220
30 E-2.04 RESERVED MIAMI, FL 33133
31 E-3.00 HOUSE LOAD ELECTRICAL RISER DIAGRAM DATE:
32 E-3.00A RESERVED
22-MAR-2022 MTCI SUBMITTAL
33 E-3.01 APARTMENT LOAD ELECTRICAL RISER DIAGRAM
17-JUNE-2022 MTCI REVIEW
34 E-3.01A RESERVED COMMENTS
35 E-3.02 FIRE ALARM SYSTEM RISER DIAGRAM 29-JULY-2022 COORD.
36 E-3.03 TELEPHONE AND CABLE TV SYSTEM RISER DIAGRAM REVISION
37 E-3.04 BI-DIRECTIONAL DISTR. ANTENNA SYST. RISER DIAGRAM 05-AUG-2022 PERMIT SET TO
CITY
38 E-4.00 ENLARGED PLANS - ELECTRICAL ROOMS
39 E-4.01 ENLARGED PLANS - ELECTRICAL ROOMS
40 E-4.02 ENLARGED PLANS - ELECTRICAL ROOMS
41 E-4.03 ENLARGED PLANS - 'ELEVATORS', NOTES AND DETAILS
42 E-4.04 ENLARGED PLAN - LOBBY AREA (LIGHTING)
43 E-4.05 ENLARGED PLAN - LOBBY AREA (POWER)
44 E-4.06 ENLARGED PLANS - GROUND LEVEL (LIGHTING AND POWER PLANS)
45 E-4.07 ENLARGED PLANS - SECOND LEVEL (LIGHTING)
46 E-4.08 ENLARGED PLANS - SECOND LEVEL (POWER)
47 E-4.09 ENLARGED PLANS - MULTIPURPOSE( LIGHTING AND POWER PLANS)
48 E-5.00 ENLARGED PLANS - TYPICAL UNITS
49 E-5.01 ENLARGED PLANS - TYPICAL UNITS
50 E-5.02 ENLARGED PLANS - TYPICAL UNITS
51 E-5.03 ENLARGED PLANS - TYPICAL UNITS
52 E-6.00 250 BIRD ROAD OFFICE BUILDING - ELECTRICAL RISER DIAGRAM (FOR
REFERENCE ONLY)
53 E-6.01 250 BIRD ROAD OFFICE BUILDING - PANEL SCHEDULES (FOR REFERENCE PROJECT No. 19-017
ONLY)
DRAWN BY: JR/YG
CHECKED BY: JAR

E-0.00