Hisense DC INVERTER AIR CONDITIONER SERVICE MANUAL vss WNIT: AUD-18UX4SGKL AUD-24UX4SZLH AUD-36UX4SAMH AUD-48UX6SPHH AUD-60UX6SPHH AUD-18UX4SZKL1 AUD-24UX4SALH1 AUD-36UX4SAMH1 AUV-18UR4SZA1 AUV-24UR4SAA1 AUV-36UR4SAB1 AUV-48UR6SPC AUV-60UR6SPC AUC-18UX4SGAA AUC-24UX4SZEA AUC-36UX4SAEA AUC-48UX6SPFA AUC-60UX6SPFA AUC-18UR4SZAA1 AUC-24UR4SAEA1 AUC-36UR4SAEA1 Hisense Corporation 1. 2. 3. 4. 5. Table of Contents Page GENERAL - 1 ‘SPECIFICATION--- 15 OUTLINES AND DIMENSIONS -- 24 341 INDOOR ~ 24 3-2 OUTDOOR - 29 DIAGRAM&DATA - 33 4-1 Refrigerant Flow Diagranr 33 4-2MAX. Refrigerant Pipe Length and Height Difference -. 36 4-3 Electric Diagrams ~ aT 4-4Air flow and ESP Chart Diagrams(for duct type) -~ - 39 ELECTRICAL DATA -- 44 5-1 Electric Wiring Diagrams 44 5-2, Electric Control 57 5.3. Dip Switch Setting of Outdoor ~ - 68 5-4. Digital Display Switch of Outdoor ~ 5-5, Static Pressure Setting(only for duct type)- 69 5-6, Ambient Temperature Revise(INDOOR) -~ n 5-7 Sensor Parameter ~~ 72 CONTROL MODE --~ 80 6-1 Indoor Control Mode ~~ 80 6-2 Outdoor Control Mode ~~ TROUBLE SHOOTING-~ 86 7-4 Ertor Codes. ~~~ at CHECKING COMPONENTS 97 8-1 Check Refrigerant System 97 8-2 Check Parts Unit 4.GENERAL 1.1 Features Duct Type Air Conditioner Features > Save Installation Space The indoor unit can be installed inside the ceiling conveniently. > Optional Static Pressure 418k: optional 10Pa /30Pa, 24K/36K 50Pa/80Pa(For AUD-24UX4SALH1&AUD-36UX4SAMH1 freely changed betweent-80Pa), 48K/60K: 80Pa/120Pa static Pressure. ‘One unit, mute optional installation method. > High Efficiency and Environment Friendly New Refrigerant-R410A RA10A can protect the environment and do not harm to the ozone layer. > 24-hour Timer ON and OFF This Timer can be set to automatically turn the unit on or off within a 24-hour period. » Mute Operation The excellent fan design enable the airflow to be quiet and smooth with minimum noise. > Meeting Various Installation Requirements The back-air-inlet type is usually to be adopted according to the actual installation space. 1.GENERAL ‘The unit is also installed with down-air-inlet type and the noise will increase about 5-6 3B. Self Recovery of Power Break ‘When the power supply is recovered after break, all preset are still effective and the air-conditioner can run according to the original setting, Fault Self-diagnose Function When there is something wrong with the air-conditioner , the micro computer could diagnose the faults, which can be read from the display and is convenient for maintenance. Cassette Type 4.GENERAL Conditioner Features Save Installation Space ‘The indoor unit can be installed inside the ceiling conveniently. High Efficiency and Environment Friendly New Refrigerant-R410A R4A10A can protect the environment and do net harm to the ozone layer. 24-hour Timer ON and OFF This Timer can be set to automatically turn the unit on or off within a 24-hour period. ‘Mute Operation ‘The excellent fan design enable the airflow to be quiet and smooth with minimum noise. Self Recovery of Power Break When the power supply is recovered after break, all preset are still effective and the air-conditioner can run accerding to the original setting. Fault Self-diagnose Function When there is something wrong with the air-conditioner, the micro computer could diagnose the faults, which can be read from the display and is convenient for maintenance. 1.GENERAL Ceiling &Floor Air Conditioner Features > Save Installation Space ness is only 230mm,can be installed inside the ceiling conveniently. > Flexible Installation Options ‘According to the actual installation space, The indoor unit can be installed in the ceiling cor on the floor. One unit, Two installation method. > High Efficiency and Environment Friendly New Refrigerant-R410A R410A can protect the environment and do not harm to the ozone layer. > 24-hour Timer ON and OFF This Timer can be set to automatically turn the unit on or off within a 24-hour period. > Mute Operation ‘The excellent fan design enable the airflow to be quiet and smooth with minimum noise. > Various Refrigerant Pipe Connect Methods ‘The refrigerant pipe can be connect from 3 different directions(rear,right or top) .More methods, more conveniently. > Self Recovery of Power Break When the power supply is recovered after break, all preset are still effective and the air-conditioner can run according to the original setting, 4 1.GENERAL > Fault Self-diagnose Function When there is something wrong with the air-conditioner, the micro computer could diagnose the faults, which can be read from the display and is convenient for maintenance. 1.GENERAL 1.2 Product Lineup Type Model 18 24 36 43 60 Duct Type | avD~ ° e Cassette Type | AUC e e connor av- | © ° ° e e 1.GENERAL 1.3 MODEL IDENTIFICATION AUC-18UR4 SZAA 1 serial number K:Outdoor Unit Indetification G:Indoor Unit Indetification S:Refrigement R410A F:Refrigement R22 4:220V-240V/S0HZ/1P _6:380V-415V/50HZ/3P X: Wire Romote Controller R:Wireless Romote Controller U:DC-Invert Heat Pump Type H:Heat Pump Type Cool Capacit Type:D-Duct Type,C-Cassette Type, V-Ceiling&Floor Type, W-Outdoor Unit Unit Air Conditioner 4.GENERAL 1.4 Product Picture Duct Type Mode? AuD-180KASGRL AuD-240xAsaL Indoor Outdoor AuD-$sUx6SPH Mode AuD-26uKASAMH AUD-48UN6SPIEA Indoor Outdoor 4.GENERAL Vode AUD-18UN4SZKL1 AUD-24UN4SALHL Indoor Outdoor Model AUD-S6UN4SAMEL Indoor ost g = 4.GENERAL Cassette Type Model AUC-ISUKASGAA ‘AUC-24UK4SZBA Indoor Outdoor AUC-48UX6SPFA Model AUC-26UKASABA AUC-6OUX6SPFA Indoor Outdoor 4.GENERAL Model AUC-18UR4SZAAL AUC-24UR4SAEAL AUC-36UR(SAEAL Indoor Outdoor a 1.GENERAL Ceiling &Floor Type Model AUV-18URASZAL ‘AUV-24URASAAL 1 1 1 - = Indoor : = utdoo AUv-48uRESPC Model AUV-36URASABL AUV-6OURESPC Indoor Outdoo 2 1.GENERAL DISPLAY PANEL: Cassette Type 18k 24K, 36K, 48K, 60K Emergency switch Signal receiving section @ © i Defrost Filter Timer 1.GENERAL Ceiling&Floor type fea ico 2.SPECIFICATIONS 2. Specifications Duct Type fre Ente aT ee any come we 2 ee a ‘ae a ae ea sy * z a * * - * * = 2 7 eaulea 7 woumaie [a [emrme | onmare | mien) [ones | om | ememer [ow ww 2.SPECIFICATIONS Serre Sas weeseeen [seers [rere reese essa cece eee errr ; oe | ec fre eet cana Se aceon | et La Leen [ere [ime [sores [rena [weer [een [res 2.SPECIFICATIONS one | tae | oe | oer on nape see | se eer |e commer | ramarce | avy | “asnne | cesssae | orssae |e so os “wo enti me | ress | sseweee | ener | erase | aoe | eee [wae | wae Ragone an . enor an ~ [ ve a 7m © = 5 = ey 0-38 2.SPECIFICATIONS Cassette type | Saiaray | waa) [waeormm| ee 7 a = = oa | scare | (meena | seo |e sow aia eee oe » wen) oO a ee ee 1 20 a i scope | ome er 2 a a eat ze 1s ae a nes a = 85 > ae Bs me oo 7 2.SPECIFICATIONS pee eee meer ene tee te eee ee Seetmamcoaiens | om | 2 @ 3 2 2 @ n 2.SPECIFICATIONS eing [Same | awe [om | vanes | orem [rien | aecmen | wate | rrenaina | jnweonae [Tew woe [omen [ecw [oe [eer a ane [se [ne rane ‘ewer ‘oer ens =| ams | aoe | some | ares | sem | wee | wave | wee gene [noc rtinanepeig [3 > > 2 = = = @ oo — = eset OE seme | seesate | sweats | teenth eae . ea Ceiling & Floor type 2.SPECIFICATIONS ma er 4 re =< os ee a a a a becroase ew 38 6 119) 153 25 ene [ar a a sa a sci | — fase —[ i a 7 7 m7 eras [ieaceraer sie [en 73 wT om a me ‘oe fa Foran | ozone, | uvamsuw 20% cement | sinromine | oo | wsscsans | saan | 2eueza a en ee emer | wr er ornare | serene | screnri | — wre — | —vemonr 2.SPECIFICATIONS ratmanee | wrerazescoasie |wzeoenzemaa.e| wrsasrs | wmrasnazozzen | MTSTASA2210 ateance | uzisawe | mreaaszsisscar | ansoracse ee Wes Ree ari J.05) --susouno powes) | -xsouno power | ~SKS2N® wss0ss 930s POWER! TRSGIND POWER) | ~RSSCUNO ROWER) | —ANSOUND =e = 2.SPECIFICATIONS Gestigws m= cr oo co oo ogee rare [teat 6 x” x” o 0 ing ot Ha atoenet init | 75 = = 20 aera 5) | 20 oar 1) Commcton | Powering [om Seon Towae Senora Senes Tomas wn ‘Sonal wiee | exons eon a7 oe “Koei con Regret rae) s 14 168 2 2 35 Tete Te Ey ev ev eer = zi 2 ng 168 eee ea 026 3. OUTLINES AND DIMENSION 3.OUTLINES AND DIMENSIONS 3-1 INDOOR Duct type = b + -_ LA Lt i Z bem f fo am HAO (Air Outlet) Le T [4 | U HG : L. a -| 1 ano (Air ota g . | [ «lr a/b c dje|f gi hjijj kil min 18K |1207|1170 154 447 |971 |117 1039170 |117 150 199 13 81 | 84 ¥ 3. OUTLINES AND DIMENSION BAO (hir Intake) i \ 24k | 934 |900 |669 |720 [805 | 222 |835 |228 |242 |294 |378 |405|25 |156 |202 214 36k {1334 1295 |669 |720 [1205 | 222 |1235 |228 |242 |294 |378 |405|25 |156 |202 214 éok [234 1295 [740 [796 [0s [zz hess 0s [as7 [312 [375 |405 [25. [208 [203 |aa2 3. OUTLINES AND DIMENSION Cassette type 18K 24K,36K 840 3. OUTLINES AND DIMENSION 48K,60K 298 3. OUTLINES AND DIMENSION Ceiling&Floor Type a 39 B 39 Blowout opening <> T q — O 4 (nit am) 36K 1285 48K, 60K 1580 1502 8. OUTLINES AND DIMENSION 3-2.0UTDOOR 18K(AUW-18U4SG) 32 0 3. OUTLINES AND DIMENSION 18K (MODEL: AUW-18U4SZ1 ) 24K(MODEL: AUW-24U4SZ) 9658 Tat Outlet o 3. OUTLINES AND DIMENSION 24836K (MODEL: AUW-24U4SA1, AUW-36U4SA1, AUW-36W4SA ) | 4 >100me 300mm Soe | 1386, 8. OUTLINES AND DIMENSION 48K&60K (MODEL: AUW-48U6SP, AUW-60U6SP SY SW SRW Se 380, 382.9 416.5 4 DIAGRAM&DATA 4. DiagramsaDATA 4.1 Piping Diagrams 18k type % | Diecharge outdoor exchanger ‘sep Vane anet Elcom expansonvahe stair Indoor Outdoor 4 DIAGRAM&DATA 24k &36K type StopVale ambent Ambient temperature temperature sensor =e os Outdoor heat exchanger stp Vale staner Electonc epanson vale ine Indoor Outdoor 4 DIAGRAM&DATA 48K&60K exchanger stp Vale saner Electonec epanaonvahe Sain Indoor outdoor a 4 DIAGRAM&DATA 4-2MAX. Refrigerant pipe length and height difference Indoor unit ; Height difference H Tube length L pe Outdoor unit pL Do your best to reduce the pipe length. Long pipe may cause capacity of the indoor unit incline. Outdoor unit precharged Total refrigerant pipe length om-Sm ‘5m~60m ‘AUW-18U45G 12708 0g AUW-24U4SZ_ 1500g Og Xg= 15g /m (Total pipe length(m) -5) AUW-36UASA 21008 og ‘AUW-1S1MSZ21 14008, 06 AUW-24U4SAL 16808 0g asa 21008 oe Xg=35g/m_ X (Total pipe length(m) -5) AUW-48U6SP 30008 08 AUW-60UBSP 35008 og 4 DIAGRAM&DATA 4-3ELECTRIC Diagrams Outdoor unit Indoor unit v 18K24K/36K Outdoor unt Indoor unit 48Ki60K Recommend Wire Size Porer Source | Tronsnitting Cable Model POWER SUPPLY Cable Size Size (a2) (m2) 18K 220-240¥, 50H 3X1. 40.75 248/368 220-240¥, 50H 32.5 40,75 486/608 380~415V,3N~,50HZ 5X2.8 40.75 © Use an ELB (Electric Leakage Breaker). If not used, it will cause an electric shock or a fire. * Do not operate the system until all the check points have been cleared. (A) Check to ensure that the insulution resistance is more than 1 megohm, by measuring the resistance between ground and the terminal of the electrical parts. If not, do not operate the system until the electrical leakage is found and repaired. ar 4 DIAGRAM&DATA (B) Check to ensure that the stop valves of the outdoor unit are fully opened and then start the system. # Pay attention to the following items while the system is running (A) Do not touch any of the parts by hand at the discharge gas side, since the compressor chamber and the pipes at the discharge side are heated higher than 90°C (B) DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH(ES). It will cause a serious Accident. NOTES: 1) Follow local codes and regulations when selecting field wires. 2) The wire sizes marked in the table are selected at the maxim current of the unit according to the European Standard ,En60 335-1. Use the wires which are not lighter than the ordinary tough rubber sheathed flexible cord (code designation HO7RN-F) or ordinary polychloroprene sheathed flexible cord (code designation HO7RN-F) 3) Use a shielded cable for the transmitting circuit and connect it to ground 4) In the case that power cables are connected in series, add each unit maximum current and select wires below. Selection According to EN60 335-1 Current i(A) Wire Size (mm?) is6 0.75 6 | oe Wed Cosy — Conver \ oe eo Par | Bou Temina| Panel nas) eos} 1004 ee an CNI(UN). ‘BRN—_[T(L}-paw- Cutie np cweaany i Eason Attention: 1. The fan motor connection mode has been setted by it's product factory. Please according to specification to connect diferent static pressure connector. a4 |. ELECTRICAL DATA AUD-24UX4SLH,AUD-36UX4SMH Electric wiring diagram 1812814. A xs 1 en} 2 o* can au fa} ex wa as Ss coun ‘NOTE: Fan motor connector in the diagram isthe factory default configuration. ‘In actual use,please select the right connector according to the the value of the static pressure, 45 5. ELECTRICAL DATA AUD-24U4SLH1,AUD-36U4SMH1 Electric wiring diagram 1806500. A — . Ys | ern Mainconrol = | He ~~ Wa at 7 board Tempe Tet exis 10. sy} nem su 00} coun sa. [a “TBO 46 5. ELECTRICAL DATA AUD-48UX4SHH,AUD-60UX4SHH Electric wiring diagram 1812823. A eons 1. a canny mw fy LAL exasy a oe sear "6 NOTE: Fan motor connector inthe diagram i the factory default configuration. In actual useplease select the right nnector aecording to the the value of the static pressure a7 |. ELECTRICAL DATA. Cassette type 18k Electric wiring diagram 1812538. B — “pas we My on Lent wae Main control Soon POO gg dq ou msc. pad | oe I J coe] us Fo “ xus9 |] ons — omc me 24K ,36K,48K,60K Electric wiring diagram 1812815.B 48 |. ELECTRICAL DATA Ceiling&Floor type 18K,48K,60K Electric wiring diagram 1806489. A oun oo sa] oh ay ay 2aK,36K Electric wiring diagram 1812833, A 49 |. ELECTRICAL DATA OUTDOOR UNIT 18K AUW-18U4SG_ wy, ELECTRIC WIRING DIAGRAM 1466720.B wo fem —] cn scour noses 2 = to a: a3 °5 2 scot erost wustaun Soe 50 |. ELECTRICAL DATA neon t+ nono BH ae aa PUBOG JONUOQ — mH yl oman? =| me om | (og WS Be La [eg999] 99905) Ge wn (iy i { tt wants “aNd cl ) as ‘ AS Sw) & @S968LS1 wesbeiq Bunny 9399/9 wossatianoo AUW-18U4SZ1 sl |. ELECTRICAL DATA 24K AUW-24U4SZ rg ELECTRIC WIRING DIAGRAM 1466882. PANEL, “ FuLTER fcefetn Ie | nw z an i - AM il B = E = el a = sacns - — ~ > sinonis) bow — Eee vale ® Louie) wc cM HENNA Kav) Pent) evacioene) fo ty owe ely 2 |. ELECTRICAL DATA AUW-24U4SA1 wwasa_ vn Peeters! 1707 = 25) weg) [e9) GYVOd TONLNOD © me exo F wot PRO IND 01ND ple iva) a y6961S1 wes6eig Bui 914399/5 33 |. ELECTRICAL DATA a'SeSlSrl weibeig Bun 9L398/9 AUW-36U4SA 36K st |. ELECTRICAL DATA AUW-36U4SA1 ole] /4] C 1 FIGS GS Jeo ¥eND—LZND LIND IND SIND. Mono CYVOE IONLNOD oan oO ene o non ND aN a waa ara unos facoal S995" Goong) EI woouga 2g 59 Lr @v6961S1 weibeig Bun o1}99/5 35 5. ELECTRICAL DATA AUW-48U6SP AUW-60U6SP 3 3 [a<] a) 2g 8) £ b 3 a. El Be = z € gi © 1 8 its él He oe D é re E& HERES = kK = a 2 Tr B [asses é iF ax—aqgs Main Control Board Ah Ben Bee Be fe 5. ELECTRICAL DATA 5-2. Electric control Board 4. Indoor control board Duct type 18K,48K,60K &AUD-24UX4SLH, AUD-36UX4SMH AUD-24UX4SLH1, AUD-36UX4SMH1 5. ELECTRICAL DATA CASETTE Type 18K 24K,36K,48K,60K 5. ELECTRICAL DATA Ceiling & Floor type 18k,48k,60k 24k,36k |. ELECTRICAL DATA 2.Comtrol board for outdoor unit 1) OUTDOOR CONTROL BOARD AUW-18U4SG 1) CONTROL BOARD (AUW-I8U4SG) CONTROL BOARD (AUW-24U4SZ) cy 5. ELECTRICAL DATA igh pressere etch CONTROL BOARD (AUW-36U4SA) 61 5. ELECTRICAL DATA igh preture snitch wx CONTROL BOARD (AUW-48U6SP, AUW-60U6SP) Disctarse Sesce co/deront Sensor 5. ELECTRICAL DATA (AUW-ISU4SZ1, AUW-24U4SAL, AUW-36U4SA1) 6 5. ELECTRICAL DATA IPM Board aor Gl 307, ih prnere etch Communication IPM Board (AUW-18U4SG) ot 5. ELECTRICAL DATA To Electrol Capac LpaPover ‘To Compuesso W ToCompressor V ‘To Conuessor U ‘Te Elec 9 Main Cont Lia Nia Main Coatrl (AUW-ISUASZ1, AUW-24U4SAL, AUW-36U4SA1) 65 5. ELECTRICAL DATA 66 5. ELECTRICAL DATA 5-3. DIP SWITCH SETTING OF OUTDOOR AUW.-18U4SZ1,AUW-24U4SA1,AUW-36U4SA1 ,AUW-36W4SA, Dip Switch Setting of Outdoor Unit 1469538 .A TURN OFF all power sources before setting. Without turning OFF, the switches do not work and the contents of the setting are invalid. Mark of “™” indicates the position of dip switches. SH2 | Reigerant png Length Seting Ref. Cycle No.Setting seam] ‘Atal Ping Length im) 1a5 ei VRF: Indoor unit can indicate both indoor failure and outdoor failure .but outdoor only Indicate outdoor's. 7. TROUBLE SHOOTING —! —, —' —, — Va — ~ = a — DISPLAY ERROR CODES 3.Fault code display ( Driver Board ) Fault code display by indicate lamps of outdoor driver board. LED FALSH CONTROL: flash 200mS(T1), off 200mS(T2), after 900mS(T3)fault code repeat displays. (as shown below) Ti T2 13 7. TROUBLE SHOOTING The following is the fault code table of outdoor. Fault Fault description Fauit description REMARKS, code ‘Outdoor environment ‘Ourcoor environment temperature 1 ‘out ‘temperature sensor short Greut or open crit “The outdoor col temperate 2 The outdoor col sensor fault sensor short ccult or open chcult 3 Current protective device 4 Eprom Data eror Eprom Data error or EE chip faut Reigeration indoor cot Refrigeration and freezing or thermal overload 5 temperature Is o9 low er heating protection the indoor eal temperature too high 6 AC motor faut ‘Outdoor continuously fr 2 minutes 7 | indoor and outdoor communication fault without receipt of inoor communication data 8 Phase curtent imbalance Aenlication of tiree-phase Power supply models ° ‘Aoplicaton of tee: phase ‘current U phase Power supply models ‘Aoplication of tvee-phase 10 Current V phase Power supply models Appiicaion of| " Sequence enor Tice phase poe spel wing three-phase power line sequence error supely models ‘Application of| 2 Phase detection phase three-phase power ‘supply models ‘Compressor overheating protector 13.) Compressor everheat protection device "9 pot ‘pping oo high system pressure leads to high pressure switch tipping or | Were applied to have high High voltage swticn motor protecton'Pressure 14 | Honors pressure sensors to detect the pressure swich or 3 ‘Shutdown protection pressure too high to achieve pressure sensor ype shutdown protection pressure ‘System iow pressure causing low Were applied ta the low tg | Lowvollage swich protectonvLow pressure | pressure switch tipping er pressure pressure swich ora protection shutdown sensors to detect the pressure is too pressure sensor ype low to achieve the shutdown 2 7. TROUBLE SHOOTING Fault Expansion valve thick pipe sensor fault Fault description Fruit description REMARKS. code protection pressure “The outdoor coll emperature is 100 16 Refigeratian overload protection high to reach refrigeration temperature shutdown protection Exhaust temperature sensor short, 7 Exhaust temperature sensor fait Circuit er open circuit MUTLSPLIT TYPE te | AC voltage of high and iow voltage protection | Power input AC votage is too low or ‘onty Haute 10 high 10 Exhaust temperature sensor shor Intake ai temperature sensor fault circuit or open circuit ‘Condenser entrance temperature 20 | Condenser entrance temperature sensor fault pes sensor short circuit or open clei “The outlet ofthe condenser ‘The outlet ofthe condenser temperature a temperature sensor shor cicult or sensor faut open clrcut “The outlet ofthe condenser 2 “The defrosting sensor fait temperature sensor shor clcult or open circuit FOR MUTLSPLTAIMverer 2 expans ‘awe sensor ta Expansion valve A tube sensor : pansion valve A tube sensor unitary types ‘short cirult or open circu ny pes Expansion valve B tube sensor FOR MUTI-SPLIT 2 [Expansion valve B tube sensor faut vc shert circuit or opan circuit utdoor Expansion valve C tube sensor FOR MUTI-SPLIT 6 Expansion valve C tbe sensor fault ‘shot cult or open cicult outdoor Expansion valve D tube sensor FOR MUTI-SPLIT 6 Expansion valve D tube sensor fault shor cireult or open circu outdoor FOR MUTI-SPLIT Expansion valve A thick pipe sensor Sleverter unary a Expansion valve A thick pipe sensor fault ‘ype shert circuit or open cuit Expansion valve B thick pipe sensor FOR MUTI-SPLIT = Expansion valve B thick pipe sensor fault ws shert circuit or opan crit outdoor ~ Expansion valve C thick pe sensor FOR MUTI-SPLIT short ercut or open crcut cutoor 93 7. TROUBLE SHOOTING Fatt Fault description Fruit description REMARKS. code 0 Expansion valve D thick pipe sensor FOR MUTI-SPLIT Expansion valve D thick pipe sensor fault, outdoor short cirult or open circu a High discharge pressure fault RF outdoor 2 {Low suction pressure faut \VRF outdoor ‘Appicaton of| twee phase power “1 Current sensor faut supply ONIOFF tyes a Voltage sensor fault “ H Pressure sensor fault RF “4 | Pressure sensor fault 45 PM faut 46 IPM Communication faut a7 ‘Too high exhaust temperature shutdown 48 COursoor DC fan faut 49 COursoor DC fan faut 90 Forced expansion valve a IPM Temperature rise too high dowmtine 92 ‘Compression ratio is (00 large 0 top VRF TYPES . “The machine number and set the ‘umber of inconsistencies fault VRE 4 ‘outdoor acres confit VRE 95 Rerigerant serious excessive downtime VRE 6 Refigerant shortage downtime. Re FOR VRFainverter or Four way valve fault unitary pes 7. TROUBLE SHOOTING The following is the fault code table of indoor. FAULT cook FAULT DISCRIPTION REMARKS. 34 Panel key ADfauit (Only for MUTESPLIT The front panel fault is notin place 2 (0 upper and lower positon detecting switch and also putin (Only for MUTLSPLIT place or notin place) 2 Room Temperature Sensor Fault (Only for MUTL-SPLIT 4 Coll_ Temperature Sensor Fault (Only for MUTE-SPLIT Panel drive faut 35 (two upper and lower panel postion detection switch fs notin (Only for MUTESPLIT ‘accordance wth thereservation timing action) 26 ‘Communication between Indoor and Outdoor Fault Only for MUTESPLIT ar humiaty sensor fature (Only for MUTESPLIT 38 [Eprom Data error (nly for MUTESPLIT 2 Indoor Fan Motor Fault Only for MUTESPLIT 0 ‘Grd protection | (Only for MUTESPUT 5 Drainage Fault 2 Grd protection ‘The front panel fault is notin place a (two upper and lower poston detecting suftch and also putin place of notin place) contet Model Faut ‘ONLY FOR MUTLSPLIT & VRF TYPES Freeze Protection 7 (Overload Protection et Indoor address duplication For VRF 2 Remote address duplication For VRF o ‘Communication between Indoor & Outdoor unit Fault 6s ‘Communication between Indoor &Wiring remote controller Fautt For VRF nm “The Indoor zero crossing detection fault 7 Indoor Fan Motor Fault 7m [EEPROM Data Error Panel deve faut a (two upper and lower panel postion detection switch fs notin ‘accordance with there servation ting action) 0 Panel key faut a ‘Amtient Temperature Sensor Fault 2 Evaporator inlet Temperature Sensor Fauit 8 Evaporator Middle TemperatureSensor Fautt 4 Evaporaior outlet Temperature Sensor Faut °s Wiring Remote Controller Sensor Faut 95 7. TROUBLE SHOOTING 86 ‘Outlet temperature sensor faut a “The waterside entrance temperature sensor fault oo “The waterside entrance temperature sensor faut 29 Humility sensor fate ‘Communication between maln control Board &Wiring remate controler Fault ( display on wing remote controller) Communication between maln control board splay board Fault (eisplays on eisplay board ) ER 8. CHECKING COMPONENTS 8-1. Check refrigerant system TEST SYSTEM FLOW Conditions: Compressor is running. ® The air condition should be installed in good ventilation, Tool: Pressure Gauge Technique: D see © teel © test SEE Tube defrost. FEEL The difference between tube’s temperature. TEST —~ Test pressure. i 7 8. CHECKING COMPONENTS Test system flow ‘ceatng mode Teteyiom rr rssute Does new = assure one pressure noma fon se ‘ence pat? charge regent Tnepemteonne ] fF [Te rescue onthe ae a pura wn jew oe pnpoes the oy ios a ‘The system wants ces T Ne coments \ 2 ( retgeranabout 009°), ‘ eanie csong erointg se ‘moose fsa tegnag tteew | fenarantsrten | faders?” | ‘Recharge retigerant ‘The remgerat system bdocked Pease sect ‘Me Capa Tubes or ‘destone expansion ‘aves tblecke? lcreck check vae nd jay vave Hesina mode Testojiem pessina the Frese sma Te pieaaure on he Recharge rfigaran fr stor arpugg oh Remove he back Jor grew one the vacuum anesthe Fre smd er ory tbe? Goan’ chosing? "Te ysor wants ee z 7 mace : ‘ Skee 4 peohee = ficckesUncaserte |e fsa tee ASS The fila tbat and cary fed 2 tlowm by frequency ste othe Figtpoeere risen ag mode? fstiorant om ochageroigrant Inthe proces cle lena eat xchange nt tostaepessue? “ sy ah ¥ ay va calle of pres exal fa " os 8. CHECKING COMPONENTS 8-2.Check parts unit 4. INDOOR FAN MOTOR Duct type 18K YSK110-40-4-A (HS16) uc ———4 puck g_______ ora NOT mn C=2. uF a Al AS ' um 94 ra me ane orice o—_— M1:146415% 2 M2: 33415% 0 M3: 43415% 2 AM: 63£15% 2 A2: 23£15% 0 AB: 119+15% 2 8. CHECKING COMPONENTS ‘AUD-24UX4SLH Y6S419C56 Hf oRG g & 4H 4 & BLUE BRN RED WHT srownewe 70.1 [ Q] +£12% Brown-onance7S,. 5 [QQ] +12% BROWNRED 49.3 [ OQ] +12% owe 11.4[ Q] £12% woitesack 16,1 [OQ] +£12% AUD-24UX4SLH1 Dc MOTOR ‘AUD-36UX4SMH1 Dc MOTOR 8. CHECKING COMPONENTS AUD-36UX4SMH Y7s4230024 BLUE BROWN prep WHITE BLACK M 23.78[Q] +12% A 21.48[1Q] +£12% Brown-RED 5.15 [Q] +12% RED-WHTE 2.66[Q] +12% WHITEBIACK 5,07 [Q] 412% ot 8. CHECKING COMPONENTS 48K,60K BLUE BROWN-RED RED-WHITE WHITE-BLACK BROWN pep WHITE BLACK 1.89(0] #1ib MALO] 1th 3.3510] 21h 41 G] +1 LMTO) tis 102 8. CHECKING COMPONENTS Cassette 18k IP WHT 2 @—______+ #EORG AL BLK at CRED a BLU YEL 2c M 240(Q) + 15% Al 60 (e158; Ay 33[M] 15% 5 AZ 143{9) = 15% ; 24K,36K,48K,60K Dc-MOTOR 103 8. CHECKING COMPONENTS Ceiling & Floor type 18K YSK110-22-4-4, 1P ia white ~ wy black biue i dif yettow M: 1879 At: 37.52 A2: 27.89 A3: 1460 24K--DC MOTOR SIC-70CW-F1100-6 36K--DC MOTOR SIC-70CW-F1140-3, 48K,60K 784230032 4 2 ifs # WHT BLK YEL WHITE-BLACK:42.69 BLACK-BLUE:9.19 BLUE-YELLOW:9.09 RED-BLACK:36.41 104 8. CHECKING COMPONENTS Test in resistance. TOOL: Muttimeter. Test the resistance of the main winding. The indoor fan motor is fault if the resistance of main winding O(short circuitjors> (open circuit) . Test in voltage TOOL: Multimeter. Insert screwdriver into to rotate indoor fan motor slowly for 1 revolution or over, and measure voltage “YELLOW” and “GND” on motor. The voltage repeat OV DC and SV DC. Notes: 1) Please don't hold motor by lead wires. 2) Please don't plug IN/OUT the motor connecter while power ON 3) Please don't drop hurt or dump motor against hard material. Malfunction may not be observed at early stage after such shock. But it may be found later, this type of mishandling void our warranty. 10s 8 CHECKING COMPONENTS 2, OUTDOOR FAN MOTOR MOTOR EXAMINE AND REPAIR Circuit diagram AUW-18U4SZ1, AUW-24U4SA18AUW-36U4SA1—DC MOTOR 18K-MOTOR MODEL:ARW4401QH 24K--MOTOR =MODEL-SIC-71FW-08121-1 36K-MOTOR MODEL:SIC-71FW-D8121-1 Circuit diagram AUW-18U4SG YDK29-61-22: aus O28) OQ ent 9 ? Te tag ag A ) cE IL comcitar G2) or Protectar 120 au T . ? 8 Winding resistance ( at 20°C) M: 283.59 A: 1809 AUW-24U48Z, YDK70-6H-3: en WINDING BLACK— “M’The main winding "A" The auxiliary winding Capacitor Hot protector 130°C WHITE BLUE RED Winding resistance ( at 20°C) M:782 A: 802 Winding resistance ( at 20°C) M: 28352 A: 1809 AUW-36U4SA YDK95-6-9043 105 8 CHECKING COMPONENTS Brow’) | YELLOW an) ie eoeiveg © asa ne om 1 a J ~ | D— oer wate AK BLE = Winding resistance ( at 20°C) M1:59.19 M2:2030 M3:1530 A: 85.80 48K,60K YDK65-6-9024, YDK65-6-9061 WINDING —~ Willain vinding Asduxiliary winding AK Capacitor —®> Hot protector Winding resistance ( at 20°C) M8300 A1:23.40 2:14.00 3:63.50 Test in resistance, TOOL: Multimeter. Test the resistance of the main winding. The outdoor fan motor is fault if the resistance of main winding O(short circuitjor=> (open circuit) Notes: 1) Please don't hold motor by lead wires. 2) Please don't plug INIOUT the motor connecter while power ON. 3) Please don't drop hur! or dump motor against hard material. Malfunction may not be observed at early stage after such shock. But it may be found later, this type of mishandling void our warranty. 107 8. CHECKING COMPONENTS 3. COMPRESSOR COMPRESSOR EXAMINE AND REPAIR AUW-18U4SG: DA130S1C-20FZ Thermal Sensor a = DC inverter Power e Controller | AUW-18U4SZ1 7 DA13181B-28FZ Thermal Sensor _—eas ~ DC inverter Power & Controller AUW-24U4SZ WIRING DIAGRAM aa SM pore source © si CHECKING COMPONENTS AUW-24U4SA1 DA230S2C-31MT ‘Thermal Sensor ~ DC Inverter Controller AUW-36U4SA / AUW-36U4SA1 DAz50S2C-30MT 1/338 Thermal Sensor DC 242 — B o | Blas “an i ~ DC Inverter Power & Controller ite FR4i#L Compressor AUW-48U6SP (TNB306FPNMC) eR Sw rower 8. CHECKING COMPONENTS ‘AUW-60U6SP (LNB42FSAMC) CL were THERMO SENSER OR THERMAL SWTCH i] — ! ‘SHUNT BI RESISTANCE & Power — ——" source CONVERTER oo POSITION DETECTOR Test in resistance. TOOL: Multimeter. Test the resistance of the winding. The compressor is fault if the resistance of winding O(short circuitjors> (open circuit) Familiar error: 1) Compressor motor lock 2) Discharge pressure value approaches static pressure value 3) Compressor motor winding abnormality. Notes: 1) Don't put a compressor on its side or turn over. 2) Please assembly the compressor in your air conditioner rapidly after removing the plugs. Don't place the comp. In air for along time. 3) Avoiding compressor running in reverse caused by connecting electrical wire incorrectly. 4) Warning! In case AC voltage is impressed to compressor, the compressor performance will below because of its rotor magnetic force decreasing. no 8 CHECKING COMPONENTS INDUCTANCE Familiar error: 1) Sound abnormality 2) Insulation resistance disqualification. 5. STEP MOTOR 1 Test in resistance. TOOL: Muttimeter. Test the resistance of winding. The stepper motor is fault if the resistance of winding O(short Circuitjorse (open circuit) . 6. FUSE Checking continuity of fuse on PCB ASS'Y. 1) Remove the PCB ASS'Y from the electrical component box. Then pull out the fuse from the PCB ASS'Y (Fig.1) SS . SRB? Se | et 2) Check for continuity by a multimeter as shown in Fig.2. Fig.2 T.CAPACITOR 1) Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig.3. 2) Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value. m CHECKING COMPONENTS The capacitor is “good” if the pointer bounces to @ great extent and then gradually returns to its original position. The range of deflection and deflection time differ according to the capacity of the capacitor. cate Fig? na

You might also like