WINDING DESIGN FOR 400 KVA COPPER

11/0.433 KV TRANSFORMER
TAPPING +10 % TO -10 % EACH 2.5 %
Sr. No. Partticulars Units LV Winding HV Winding
1 Conductor Material COPPER COPPER

2 Type of Winding Layer Cross-over

3 Bare Conductor Size mm (8.80x2.75)x6 2.2

4 Conductor Insulation DFG SEM

5 Insulation Thickness mils 24 4

6 Covered Conductor Size mm (9.40x3.35)x6 2.3

7 Conductor Arrangement 3Wx2D

8 Turns/Phase Nos. 23 1112

9 Coils/Phase Nos. 1 6
186x4(N),
10 Turns/Coils Nos. 23
184x2(T)
11 Turns/Layer Nos. 11.5 17

12 Layers Nos. 2 11

13 Inside Diameter mm 232 314

14 Outside Diameter mm 267 375

15 Axial Length mm 450 42

16 Transposition Center of each Layer

17 Oil Duct mm 6 6

18 Taps at 0-25-50-75-100------184(F)

19 Inter Layer Insulation mils 4x2 4x2


12x4(N)
20 Inter Coil Spacers mm
15x1(T)
21 Stack Height mm 495 315
Covered Conductoer
22 Kgs. 90 127
Weight per Transformer