Electrical protective signaling systems are configurations of components used to produce alarm signals indicative of fire, smoke,
sprinkler waterflow or other emergency and to produce supervisory signals indicative of conditions needing attention with respect to
protection equipment or watch service. System configurations are classified according to where and how the signals are received.
The categories are commonly designated as local, municipal, remote station, proprietary, emergency voice/alarm communication,
emergency communication, and central station. Auxiliary systems are either local or proprietary systems interconnected with a
municipal system.
This category presents the major system component categories and the integrated system configurations. The selection of
components to form a hybrid system should be made only by those skilled in system design. Also, the suitability of any system
application should be judged on the basis of the hazard(s) being protected.
Fire Detectors-Smoke
Models SD365, SD365-IV, SD-365A, SD365A-IV, SD365R, SD365R-IV, SD365RA, SD365RA-IV
and SD365T, SD365T-IV, SD365TA, SD365TA-IV
Models SD365, SD365-IV, SD-365A, SD365A-IV, SD365R, SD365R-IV, SD365RA, SD365RA-IV and SD365T, SD365T-IV, SD365TA,
SD365TA-IV are field programmable analog addressable photoelectric smoke detectors.
MS-5UD
MS-10UD
MS-9600LS
MS-9600LSE
Compatible Fire MS-9600UDLS
Alarm Panels MS-9600UDLSE
MS-9600LSC-FR
MS-9050UD
MS-9200UDLS
MS-9200UDLSE
B224RB, B224RBA, B300-6, B501, B300-6, B300-6-IS, B300A-6, B200S, B200SA, B200S-LF, B200SR,
B200SRA, B200SR-LF, B210LP, B210LPA, B224BI, B224BIA, B710LP, and B710LPA.(these models may
Compatible
also have a suffix of -IV (Ivory), -WH, -WHITE (White) or -BL (Black) designating their color)
detector bases
All models are also for use with the following Listed duct detector housing: System Sensor Models DNR,
DNRA, and DNRW; Silent Knight Model FHS-D; and Fire-Lite Model D355PL.
Sensitivity range 0.5%/ft. to 4.0%/ft.
Maximum spacing* 9m by 9m (30ft by 30ft) – if installed as a smoke detector*
Operating voltage
15 to 32Vdc
range
Operating
0° to 50°C, -20° to 70°C in duct applications;
temperature range