You are on page 1of 36

House Control with

LOGO! 8 and
Weather Sensors

LOGO! 8, KTP400
Siemens
Set 11 Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/68585346 Support
Legal information

Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG (“Siemens”). They are non-
binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sublicensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.

Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
 Siemens AG 2018 All rights reserved

foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.

Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.

Security information
Siemens provides products and solutions with industrial security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit:
https://www.siemens.com/industrialsecurity
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 2
Table of Contents

Table of Contents
Legal information ......................................................................................................... 2
1 Task ..................................................................................................................... 4
2 Solution............................................................................................................... 5
2.1 Overview............................................................................................... 5
2.2 Hardware and software components ................................................... 6
2.2.1 Components used ................................................................................ 7
3 Mode of Operation ............................................................................................. 9
3.1 Weather sensors .................................................................................. 9
3.1.1 Wind sensor ......................................................................................... 9
3.1.2 Light sensor .......................................................................................... 9
3.1.3 Twilight sensor ................................................................................... 10
3.1.4 Rain sensor ........................................................................................ 10
3.1.5 Temperature sensor ........................................................................... 10
3.2 Configuration in network mode .......................................................... 11
3.2.1 Creating a project in network view and two-way programming.......... 11
4 Installation and Commissioning .................................................................... 14
4.1 Installing the hardware ....................................................................... 14
4.1.1 KTP400............................................................................................... 14
4.1.2 LOGO! 8 ............................................................................................. 14
 Siemens AG 2018 All rights reserved

4.1.3 Assigning IP addresses to LOGO and setting the master mode ....... 15
4.2 Software installation (download) ........................................................ 15
4.3 Commissioning ................................................................................... 16
4.3.1 Basic settings for the KTP400 ............................................................ 16
4.3.2 Settings in the operating system ........................................................ 19
4.3.3 Assigning devices and programs ....................................................... 20
4.3.4 Loading the programs into the KTP400 and KTP700 ........................ 20
4.3.5 Configuring dynamic warning messages for wind in the KTP700
WinCC project .................................................................................... 23
5 Operation .......................................................................................................... 27
5.1 Monitoring with the KTP400 ............................................................... 27
5.1.1 KTP400 screens ................................................................................. 27
5.1.2 Start screen ........................................................................................ 27
5.1.3 Overview of weather data................................................................... 28
5.1.4 System functions ................................................................................ 29
5.1.5 Online Support information................................................................. 30
5.2 Operator Control and Monitoring with KTP700 and KTP400 ............. 31
5.3 Operation via PC ................................................................................ 34
6 Appendix .......................................................................................................... 35
6.1 Service and Support ........................................................................... 35
6.2 Bibliographic references ..................................................................... 36
6.3 Internet link specifications .................................................................. 36
6.4 History ................................................................................................ 36

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 3
1 Task

1 Task
Note This LOGO! set expands the house control of LOGO! Set 9 "House Control with
Master-Slave Communication” or LOGO! Set 10 "House Control with
Touch Panel” by a weather station with a LOGO! 8 and a Basic Panel.
Further information on the functionalities of LOGO! Set 9 and LOGO! Set 10, and
the respective documentation for download is available in entry IDs 64143308
and 68585344.

Risk of property damage or personal injury


LOGO! Set 10 is based on LOGO! Set 9/10. In order to avoid property
damage and personal injury it is absolutely necessary to observe the
WARNING
precautions and warnings from LOGO! Set 9 and 10 for the hardware
installation, the handling of the blinds and how to operate the application.

Introduction
In a residential home, the following functions shall be controlled automatically using
weather sensors and the measuring values displayed on a Basic Panel:
 Blinds and Roof hatch (up/down)
 Interior and exterior lighting (on/off)
 Siemens AG 2018 All rights reserved

 Heating
 Garden watering

Figure 1-1

Blinds Roof hatch Interior light Blinds


(up/down) (up/down) (on/off) (up/down)

Heizung

PT 100
Exterior light Central light
(on/off) (on/off)

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 4
2 Solution

2 Solution
2.1 Overview
Schematic layout
The figure below shows a schematic overview of the most important components of
the solution:

Figure 2-1

3 1 2 4
 Siemens AG 2018 All rights reserved

PROFINET IE

Set 9/10 Set 11

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 5
2 Solution

In the automation solution, a weather station is connected to the LOGO! Set 9 /


Set 10 hardware setup. The weather station consists of a LOGO! 8 (1), a LOGO!
power supply (3), a Compact Switch module (2) and a SIMATIC HMI KTP400
Basic Panel (4). The SIMATIC HMI KTP400 Basic Panel will be called "KTP400”.

Advantages/benefits
 Weather dependent controlling and monitoring of a house control with
LOGO! 8, weather sensors and Touch Panel
 Individually setting each of the blinds also possible in automatic mode
 Minimizing wind damage at the blinds
 Cost reduction through efficient room temperature with internal and external
temperature comparison
 Additional option to control the functionalities of the application on the PC via
the WinCC Basic Panel simulation function

2.2 Hardware and software components

Note Please note that in this LOGO! Set, the LOGO! Set 9 and LOGO! Set 10
hardware setup is expanded by a weather station with a LOGO! 8 and a Basic
Panel.
 Siemens AG 2018 All rights reserved

Detailed information on the LOGO! Set 9 / Set 10 hardware setup can be found
in the LOGO! Set 9 documentation under entry ID 64143308 and in the LOGO!
Set 10 documentation under entry ID 68585344.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 6
2 Solution

2.2.1 Components used

The application example was created with the following components:

Hardware components
Table 2-1
No. Component Qty Article number Note
1. LOGO! 12/24RCE 1 6ED1052-1MD08-0BA0
2. LOGO! CSM 12/24 1 6GK7177-1MA20-0AA0 For the connection of the
COMPACT SWITCH MODULE application example to
LOGO! Set 9 or
LOGO! Set 10.
3. LOGO!POWER 24V/4 A 1 6EP1332-1SH52
4. SIMATIC HMI KTP400 BASIC 1 6AV2123-2DB03-0AX0
5. Rain sensor 1 Available from specialist e.g. Stengler rain sensor
retailers RS-600
 "1V output voltage
-> no rain
 9V output voltage
-> rain
 Output voltage: 0-10V DC
 Operating voltage: 12-24V
 Siemens AG 2018 All rights reserved

DC
6. Temperature sensor 1 Available from specialist e.g. Stengler
retailers temp. sensor TS-S
 Measuring range:
-20°C…+40°C
 Output voltage: 0-10V DC
 Operating voltage:12-24V DC
7. Twilight sensor 1 Available from specialist e.g. Stengler
 Measuring range: retailers twilight sensor DS-S
0…255 Lux (linear)
 Output voltage: 0-10V DC
 Operating voltage:12-24V DC
8. Light sensor 1 Available from specialist e.g.: Stengler
 Measuring range: retailers light sensor LE-S
0…40 kLux (linear)
 Output voltage: 0-10V DC
 Operating voltage: 12-24 V
DC
9. Wind sensor 1 Available from specialist e.g.: Ventus
 Measuring range: 0.8..40 m/s retailers Mini wind gage:
 Output signal: Frequency, Art. 200 430
max. 24 V DC, 100Hz=40m/s
 Supply Voltage:
max 24V DC

Software components
Table 2-2
Component Qty Article number Note
LOGO!Soft Comfort V8 1 6ED1058-0BA08-0YA1 Update V8.2 (Download)
SIMATIC WINCC BASIC V15 1 6AV2100-0AA05-0AA5

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 7
2 Solution

Example files and projects


The following list includes all files and projects that are used in this example.
Table 2-3
Component Note
68585346_LOGO!8_Set11_CODE_v21. ZIP This zip-file contains
 The enhanced LOGO! Soft Comfort project for the
master LOGO! from LOGO! Set 9/ LOGO! Set 10
 the LOGO!Soft Comfort project for the LOGO! 8 from
the weather station from LOGO! Set 11
 a revised WinCC V15 project for the KTP700 from
LOGO! Set 10
 a WinCC V15 project for the KTP400 of the weather
station from LOGO! Set 11
 A LOGO! Web project for the user defined
webserver

Note: Please note that the LOGO! program and the


WinCC project from LOGO! Set 10 have been expanded
here by the following functions:
 Weather sensor data processing
 Weather-dependent panel alarm messages
 Automatic mode for lighting
 Siemens AG 2018 All rights reserved

The LOGO! and the WinCC program from Set 10 are


replaced by the programs from Set 11.

Unzip and load all contained programs from Set 11 to


the relevant LOGO!s and/or panels,
(see Table 4-2).
68585346_LOGO!8_Set11_DOC_v21_en.pdf This document.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 8
3 Mode of Operation

3 Mode of Operation

Note Detailed information on the house functions controlled in this application example
can be found in the LOGO! Set 9 documentation under entry ID 64143308.
It is also possible to use the LOGO! Set 11 individually as a mere weather station
or to control other devices.

3.1 Weather sensors


3.1.1 Wind sensor

The measured values from the wind sensor are processed in the LOGO! program
"68585346_LOGO!_Set11_LOGO!_8.lsc” in the "Blinds” program part.
In automatic mode, all blinds are raised in the event of "strong” wind via function
block "wind” (B183/analog threshold trigger).
For protecting the blinds, "strong wind” (here, 20 km/h) is given functional priority
over high solar irradiation (here, 20 kLux) and lowering via weekly timers.
The function block "wind” can be called up in parameter assignment mode with the
respective block name using the LOGO! display or LOGO! TDE. This makes it
 Siemens AG 2018 All rights reserved

possible to adjust the threshold values for the wind speed for opening the blinds.
When wind speeds fall below 18 km/h, the LOGO! program signals that the wind
has died down and the blinds can be moved down again.

Note For wind velocities below the limit value (here, 18 km/h), the blinds will be raised
in the morning and lowered in the evening automatically according to the set
times of the weekly timers.

3.1.2 Light sensor

The light sensor is processed in the LOGO! program in the blinds control. In
automatic mode, all blinds are lowered in the event of high solar irradiation (here,
20 kLux) via function block "sun” (B184/analog threshold trigger).
High solar irradiation takes priority over raising via weekly timers.
Manual switching of blinds takes highest priority, even if the automatic mode is
activated and high solar irradiation occurs.
The function block "sun” can be called up in parameter assignment mode with the
respective block name using the LOGO! display or LOGO! TDE. This makes it
possible to adjust the threshold values for sun irradiation for closing the blinds.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 9
3 Mode of Operation

3.1.3 Twilight sensor

The twilight sensor is processed in the LOGO! program in the lighting control.
In automatic mode, all exterior lights are automatically switched off at sunrise
(> 10 lux) and switched on at dusk (< 10 lux) via function block "twilight”
(B187/analog threshold trigger).
Manual switching of lights takes highest priority, even if the automatic mode is
activated.
The function block "twilight” can be called up in parameter assignment mode with
the respective block name using the LOGO! display or LOGO! TDE. This makes it
possible to individually adjust the threshold value for automatic switching off and on
of the lighting.

3.1.4 Rain sensor

The rain sensor is processed in the LOGO! program in the program parts garden
watering and roof hatch.
In automatic mode, if it does not rain, the garden watering is switched on
automatically in the morning at 09:00 a.m. and in the evening at 08:00 p.m. for 10
minutes via the function block "watering” (B104/Weekly Timer).
If automatic mode for the roof hatch has been activated, it will automatically close
 Siemens AG 2018 All rights reserved

when it rains. If it does not rain and the temperature is high, the roof hatch will
open.
The function block "watering” can be called up in parameter assignment mode with
the respective block name using the LOGO! display or LOGO! TDE. This makes it
possible to adjust days and times in the weekly timer for automatic garden
watering.

3.1.5 Temperature sensor

The temperature sensor is processed in the LOGO! program in the program part
roof hatch. In automatic mode, the roof hatch is opened via function block "auto
roof” (B105) at high temperature (here, >28 °C) and closed at low temperature
(here, <25°C).
In automatic mode, all heating is switched off via function block "temp out”
(B195/analog threshold trigger) with >22 °C outside temperature.
The function block "temp out” can be called up in parameter assignment mode with
the respective block name using the LOGO! display or LOGO! TDE. This makes it
possible to individually adjust the threshold value for automatic switching off of the
heating.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 10
3 Mode of Operation

3.2 Configuration in network mode


From LOGO! Soft Comfort V8 onwards, you are now able to interconnect several
LOGO! base modules with each other and with other devices (WinCC and S7-
CPUs) in the new network view.
Communication between the devices will be configured automatically.
In addition, it is possible to display three programs at once and to drag&drop
signals from one program to the other.

3.2.1 Creating a project in network view and two-way programming

Adding a device in network view


Table 3-1
No. Action/response LOGO!Soft Comfort V8
1. Start LOGO!Soft Comfort V8.

2. Click on "Network project” tab to


open the network project view.
 Siemens AG 2018 All rights reserved

3. Click on "Add new device”.


The subsequent window enables
you to add devices you want to
use to the network.

4. The network view gives you an


overview of the devices used in
your network.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 11
3 Mode of Operation

Two-way programming
If more than one LOGO! device is added to the network view, you can connect
individual function blocks with drag&drop and can exchange data between the
individual LOGO! devices.

Note Please note that two-way programming is only possible between LOGO! 0BA8
devices

Table 3-2
No. Action/response LOGO!Soft Comfort V8
1. A double-click on one of the
LOGO! base modules in the
network view automatically
opens the switching program
in the diagram editor of the
network project.
 Siemens AG 2018 All rights reserved

2. To exchange data between


two LOGO! devices, open the
switching programs of two
LOGO! devices.
3. Now click on the symbol for
dividing the diagram editor in
two windows in order that an
additional window in the
diagram editor opens.

4. Then, click on the bar with the


name of one of the two
switching programs and drag
the diagram into the second
window that has opened in the
diagram editor.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 12
3 Mode of Operation

No. Action/response LOGO!Soft Comfort V8


5. Move the mouse pointer to the
output connection of one of the
function blocks you want to
connect and keep holding the
mouse button down.

Then, move the mouse pointer


to the function block you want
to connect the first function
block with.
When you release the mouse
button, LOGO!Soft Comfort V8
will connect both function
blocks.
6. Once both function blocks are
connected, LOGO!Soft
Comfort V8 will create a
function block pair and an
Ethernet connection and a
data transfer mechanism.
When the function blocks are
displayed in green,
configuration of the
communication between the
 Siemens AG 2018 All rights reserved

two LOGO! devices is


complete.

Note:
If one of the two function
blocks is displayed in red,
configuration of the
communication between the
two LOGO! devices is not yet
complete.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 13
4 Installation and Commissioning

4 Installation and Commissioning


Note Please also observe the information on installation and commissioning in the
Set_9 and Set 10 documentation, unless you would like to operate Set 11
separately.

4.1 Installing the hardware


Table 4-1
Action Comment
1. Create Sets 9, 10 and 11 as shown in Figure  Set 11 can be used separately, without
2-1. connecting other sets.
 Set 11 can also be used only with Set 9.
For this, the LOGO! software from Set 11
must be used for house control
2. Connect the sets with LAN cables

4.1.1 KTP400

Note Observe the setup guidelines for the KTP400. Further information can be found
 Siemens AG 2018 All rights reserved

in the KTP400 Basic Panel "Manual".

IP addresses and subnet masks


Make sure that the KTP400, your PC and the hardware setup from LOGO! Set 9
and LOGO! Set 10 are in the same IP address range, as shown in the following
table.

Table 4-2
No. Device IP address Subnet mask
1. KTP400 weather station (Set 11) 192.168.1.80 255.255.255.0
2. KTP700 (Set 10) 192.168.1.20 255.255.255.0
3. LOGO! weather station (Set 11) 192.168.1.13 255.255.255.0
4. Master LOGO! (Set 9) 192.168.1.10 255.255.255.0
5. Slave LOGO! (Set 9) 192.168.1.11 255.255.255.0
6. LOGO! TDE (Set 9) 192.168.1.14 255.255.255.0
7. Network card or USB Ethernet Adapter for network 192.168.1.12 255.255.255.0
connection to PC

4.1.2 LOGO! 8

Note Changes of the IP address or the master-slave mode are only possible in
"STOP” mode.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 14
4 Installation and Commissioning

4.1.3 Assigning IP addresses to LOGO and setting the master mode

Table 4-3
No. Action/response LOGO! Display
1. Go to the "Network” item via the LOGO!
display using the arrow keys C1▲ or C2▼ of
the LOGO! 8 and press OK.

2. Select the "IP address” item.

3. Press the OK button of the LOGO! controller


and use the arrow keys C1▲, C2▼, C3 ◄ and
C4 ► to enter your LOGO!’s IP address (here:
192.168.1.13). Confirm with the OK button.

4. Press the ESC key to return to the previous


menu item and select "Set M/S mode”.
 Siemens AG 2018 All rights reserved

5. For configuring the master LOGO!, select


"Master”.

6. The configuration of the IP address and the


mode for the LOGO! is now complete. Press
ESC to return to the main menu

4.2 Software installation (download)

Note It is assumed that the required software LOGO!Soft Comfort V8 and WinCC
have been installed on your PC. No previous experience with the software is
required.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 15
4 Installation and Commissioning

4.3 Commissioning

Note For the following points you find information in LOGO! Set 9:

 Download LOGO! program in LOGO! controller


 Settings for web server access
For LOGO! Set 9 refer to the following entry:
Building Automation Systems: House control with LOGO! and Master-Slave
communication (LOGO! Set 9)
https://support.industry.siemens.com/cs/ww/en/view/64143308

4.3.1 Basic settings for the KTP400

Note The IP address of the HMI panel can only be changed if Runtime has been
"stopped”.

Table 4-4
No. Action/response KTP400 display
7. Switch on the KTP400.
 Siemens AG 2018 All rights reserved

8. Press "Settings" to open the panel settings.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 16
4 Installation and Commissioning

No. Action/response KTP400 display


9. 1. Press "Network interface” to open the
dialog for changing the network settings.
2. Make your choice between automatic IP
address assignment via "DHCP” and
manual IP address assignment.
3. Touch the respective input fields and
enter the IP address and the subnet
mask with the screen keyboard, here:
 IP address: 192.168.1.80
 Subnet mask: 255.255.255.0

4. Under "Ethernet parameters” in the


"Mode and speed” selection field, tick
"Auto Negotiation”; this automatically
detects and sets the connection type
and the transmission rate in the
PROFINET network.
5. Activate the "LLDP” switch to enable the
operator panel to exchange information
with other operator panels. In this
example, "LLDP” can be activated or
deactivated.
 Siemens AG 2018 All rights reserved

6. Under "PROFINET” in the "Device


name” field, enter a network name for
your operator panel. The name must
meet the following requirements:
 Max. four blocks with max. 63
characters each. Example:
"Press1.Fender.
Bodywork.Hall3”
 Characters from "a” to "z”, numbers "0”
to "9”; special characters: "-” and ".

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 17
4 Installation and Commissioning

No. Action/response KTP400 display


4. Press "Settings” on the left side of the dialog
window for changing the network settings to
return to the panel settings window.

5. To load a project onto the HMI panel, a data


channel must be enabled:

1. Click the "Transfer settings” button to


open the "Transfer Settings” dialog box.
2. Activate "Enable transfer”.
3. Activate "Automatic” to enable automatic
transfer. When automatic transfer is
enabled, a transfer from the
configuration PC can be started while
the project is running. In this case, the
current project is stopped and the
transfer of the new project is carried out.
After the transfer, the new project is
started.

6. To return to the start center, press on the


 Siemens AG 2018 All rights reserved

symbol for minimizing the window on the


right side of the "Transfer Settings” dialog.
7. In the start center, you can start your project
any time by pressing "Start”.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 18
4 Installation and Commissioning

4.3.2 Settings in the operating system

Table 4-5
No. Action/response PC screen
1. In the operating system, navigate to:
"Start > Settings > Control Panel > Set PG/PC
Interface”.
2. In "Interface Parameter Assignment Used”,
select "TCP/IP(Auto) -> Name of your network
card or your USB Ethernet adapter” (without
the yellow warning sign) for the Ethernet
communication with LOGO!.
 In this example: TCP/IP(Auto)->Intel(R)
82577LM Gigab. network card)
Make sure that in the dropdown menu
"Access Point of the Application” "S7ONLINE
(STEP7) -> TCP/IP(Auto) -> Name of your
network card or your USB Ethernet adapter”
has been selected.
Click on OK to confirm the selection.
 Siemens AG 2018 All rights reserved

3. Alternatively the "Interface Parameter


Assignment Used” is displayed at "Control
Panel -> Set PG/PC Interface” for certain
operating systems.
As in the previous step 2, also select the
interface here and make sure that "Access
Point of the Application” "S7ONLINE (STEP7)
-> TCP/IP(Auto) -> Name of your network
card or your USB Ethernet adapter” has been
selected in the drop-down list.
Click on OK to confirm the selection.

4. Acknowledge the warning prompt that


appears in certain operating systems with OK
to complete the selection.

5. The settings in the operating system required


for controlling the application example with the
Basic Panel or with the PC screen are now
complete.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 19
4 Installation and Commissioning

4.3.3 Assigning devices and programs

Table 4-6
No. Device Program for the device in the zip file
1. KTP400 weather station (Set 11) 68585346_LOGO!_Set11_weather_station_V21.ap15
2. KTP700 (Set 10) 68585346_LOGO!_Set11_HMI_WinCC_V21.ap15
3. LOGO! weather station (Set 11) 68585346_LOGO!_Set11_LOGO!8_weather_station.lsc
contained in the network project
68585346_LOGO!_Set11_LOGO!_8.lnp
4. Master LOGO! (Set 9) 68585346_LOGO!_Set11_LOGO!_8.lsc
5. Slave LOGO! (Set 9) contained in the network project
68585346_LOGO!_Set11_LOGO!_v20.lnp
6. LOGO! TDE (Set 9)

4.3.4 Loading the programs into the KTP400 and KTP700

Table 4-7
No. Action/response WinCC
1. Start WinCC and with "Browse”, open
the project "68585346_LOGO!_
Set11 _weather_station_V20”.
 Siemens AG 2018 All rights reserved

Then click "Open”.

Note:
Repeat the steps of this table for the
project "68585346_LOGO!_Set11_
HMI_WinCC_V20" of the KTP700,
unless you would like to operate
Set 11 separately.

2. Click on "Open the project view” to


open it.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 20
4 Installation and Commissioning

No. Action/response WinCC


3. In the project tree under "KTP400
[KTP400 Basic PN]" go to
"Connections” and select it with a
double click.

4. In "HMI device”, enter the IP address of


your Basic Panel (here: 192.168.1.80)
and press Enter to confirm.

Make sure that


 "S7ONLINE” is specified under
"Access point”.
 the master LOGO! IP address
is specified under "PLC” (here:
192.168.1.13).

 Siemens AG 2018 All rights reserved

the check box "Cyclic


operation” is ticked.
5. In the project tree, go to "Devices &
networks” and select it with a double
click.

6. Make sure a subnet has been added to


the network. To create a subnet in the
network, open the context menu with a
right click on the Ethernet interface and
click on "Add subnet”.

Note:
In this application example, the subnet
has already been added in the WinCC
project.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 21
4 Installation and Commissioning

No. Action/response WinCC


7. Click on the Ethernet interface and go
to the "Properties” tab.
Enter IP address and subnet mask of
your Basic Panel, here:
• IP address: 192.168.1.80
• Subnet mask: 255.255.255.0

8. In the project tree, select the folder


"KTP400 Basic PN” and click on "Load”
in the toolbar.

9. Select the Ethernet interface of your


network card or your USB-Ethernet
adapter with which you will connect
your PC to the Basic Panel. Then click
 Siemens AG 2018 All rights reserved

on "Load".

10. Then confirm the dialog and then click


on "Load".

11. As soon as the project download has


been completed, the project will
automatically start on the Basic Panel
and you can now operate the
application.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 22
4 Installation and Commissioning

4.3.5 Configuring dynamic warning messages for wind in the KTP700


WinCC project

In the WinCC project for the KTP700, 4 different dynamic warning messages for
wind have been configured. One of the 4 warning messages is displayed
depending on the wind speed:

Overview of warning messages


Table 4-8
No. Wind level Speed Warning message text Warning
message
color
1. Weak wind >= 1 km/h Weak wind:
(Wind speed) km/h
Blinds can still be operated!
2. Moderate wind >= 20 km/h Moderate wind:
(Wind speed) km/h!
Blinds will remain closed!
3. Fresh wind >= 30 km/h Fresh wind:
(Wind speed) km/h!
Blinds will remain closed!
4. Strong wind >= 40 km/h Strong wind:
 Siemens AG 2018 All rights reserved

(Wind speed) km/h!


Blinds will remain closed!

Individually adjust and modify warning messages


Warning message texts, thresholds and colors can be modified and adjusted to the
requirements of the application at any time.
The table below shows which parameters to set in WinCC to change the warning
messages.

Table 4-9
No. Action/response WinCC Basic
1. 1. Start WinCC Basic V13
2. Select your unzipped
project "68585344_
LOGO!_Set11_HMI_
WinCC_V20" with
"Browse”.
3. Then click "Open”.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 23
4 Installation and Commissioning

No. Action/response WinCC Basic


2. Click on "Open the project
view” to open it.

3. In the project tree under


"KTP700 [KTP700 Basic PN]",
go to "HMI alarms” and select it
with a double click.
 Siemens AG 2018 All rights reserved

4. Navigate to the "Analog


alarms” tab. The following 1 2
options are provided:
1. "Trigger tag” allows you to
specify which tag to use for
monitoring the threshold
(here for wind).
2. Enter the limit value in
"Limit” to define when a
specific warning message
is displayed.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 24
4 Installation and Commissioning

No. Action/response WinCC Basic


5. You can display a value in the
warning message text (here,
e.g., the wind speed):
1. Double-click on one of the
warning messages to open
the text editing mode.
2. Now go to the place in the
text where you would like
to display a value.
3. Open the context menu
with a right click and select
the menu item "Insert tag
field”.

6. Now select the tag you would


like to display in the text and
specify the number of digits to
be displayed in the message.

Then click on the green


checkmark to close the
window.
 Siemens AG 2018 All rights reserved

7. Now, go to the "Alarm classes”


tab. Here you can assign user-
defined names to the individual
warning messages.

In addition, you can define the


background color of the
warning message.

8. Under "Screen management”,


go to "Global screen” and open
it with a double click.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 25
4 Installation and Commissioning

No. Action/response WinCC Basic


9. Proceed as follows:

1. Click on the "Alarm


window” to open its
properties.
2. Go to the "Properties" tab
and make sure that the
warning messages (here
for wind) which you have
configured, are enabled
under "Current alarm
states” and
"Unacknowledged alarms”.

10. Once you have completed all


changes and modifications of
the warning messages, click
"Load” in the toolbar to load the
 Siemens AG 2018 All rights reserved

project to the KTP700.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 26
5 Operation

5 Operation
Hinweis Operating via integrated and user defined webserver, the LOGO! display and
LOGO! TDE is described in LOGO! Set 9. For LOGO! Set 9 refer to the following
entry:
Building Automation Systems: House control with LOGO! and Master-Slave
communication (LOGO! Set 9)
https://support.industry.siemens.com/cs/ww/en/view/64143308

5.1 Monitoring with the KTP400


5.1.1 KTP400 screens

All KTP screens have a uniform toolbar on the right:


Press one of the buttons to go to the following screens:
 Start
 Weather
 System
 Support

 Siemens AG 2018 All rights reserved

Language switching

Note Synchronized language change from Basic Panel to LOGO! 8:


If the KTP400 is used to change the language with the button, the display
language on the LOGO! display and LOGO! TDE will also change.

5.1.2 Start screen

Figure 5-1

This screen is displayed right after system start.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 27
5 Operation

5.1.3 Overview of weather data

Figure 5-2
 Siemens AG 2018 All rights reserved

This figure displays the current measured values from the weather sensors.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 28
5 Operation

5.1.4 System functions

Figure 5-3
 Siemens AG 2018 All rights reserved

This screen provides system functions:

 Clean screen
 Calibrate
 (Data) transfer
 Runtime Stop

More information on the system functions can be found in the Basic Panel
manual \4\.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 29
5 Operation

5.1.5 Online Support information

Figure 5-4
 Siemens AG 2018 All rights reserved

Information on the Online Support can be found here.


The Home button (1) brings you back to the main menu.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 30
5 Operation

5.2 Operator Control and Monitoring with KTP700 and


KTP400
Table 5-1
No. Action/response KTP700 and KTP400
1. Verify on the KTP700 KTP700
(LOGO! Set 10) that
"Automatic mode” for
the blinds is activated.
 Siemens AG 2018 All rights reserved

2. The wind speed KTP400


exceeds 20 km/h.

3. All blinds move up and KTP700


stay in this final position
for as long as the wind
is strong (>20 km/h).

4. The KTP700 displays a


warning message that
the wind speed has
increased.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 31
5 Operation

No. Action/response KTP700 and KTP400


5. Press the "Alarm KTP700
indicator” to open the
"Alarm window” with the
wind speed warning
messages.

6. A warning message is KTP700


displayed in the "Alarm
window” that the wind
has reached a
moderate speed.

Note:
 Siemens AG 2018 All rights reserved

A total of 4 different
warning messages have
been configured for
different wind speed
levels in the WinCC
project in this
application example.
Older warning
messages which have
not been acknowledged
remain on display in the
alarm window, even if
the wind speed has
changed or other
warning messages have
been activated.
7. Press the button for KTP700
acknowledging warning
messages until the
current warning
message is hidden. If
required, press the
acknowledgment button
several times to
acknowledge older
messages that may still
be listed.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 32
5 Operation

No. Action/response KTP700 and KTP400


8. Close the message KTP700
window after you have
cleared all warning
messages.

9. If the wind speed drops KTP400


below 18 km/h and at
the same time there is
high irradiation (>20
kLUX), all blinds will
automatically close.
 Siemens AG 2018 All rights reserved

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 33
5 Operation

5.3 Operation via PC

Note When using the application example with your PC, please make sure the
KTP400 or KTP700 is not connected with the other modules of the application
example (LOGO! modules, PC, etc.). It is recommended not to connect the Basic
Panel, if you already use your PC as a Basic Panel with the WinCC simulation.

For operating the application example with the PC, the same basic settings (chapter 4.3.1) in
the WinCC project apply as for direct operation with the Basic Panel. The only difference is that
you do not press the "Load” button, but the "Start simulation” button.

Table 5-2
No. Action/response WinCC
1. In the project tree, select the folder
"KTP400[KTP400 Basic PN]" and click on
"Start simulation” in the toolbar.
 Siemens AG 2018 All rights reserved

2. Press "OK” in the displayed message to


start the runtime simulator.

3. Then, the runtime simulator starts with the


project.
4. You can now operate the application
example via your PC with your mouse.

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 34
6 Appendix

6 Appendix
6.1 Service and Support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
https://support.industry.siemens.com

SITRAIN – Training for Industry


We support you with our globally available training courses for industry with
practical experience, innovative learning methods and a concept that’s tailored to
the customer’s specific needs.
For more information on our offered trainings and courses, as well as their
locations and dates, refer to our web page:
 Siemens AG 2018 All rights reserved

www.siemens.com/sitrain

Industry Online Support app


You will receive optimum support wherever you are with the "Siemens Industry
Online Support" app. The app is available for Apple iOS, Android and Windows
Phone: https://support.industry.siemens.com/cs/ww/en/sc/2067

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 35
6 Appendix

6.2 Bibliographic references


Table 6-1
Title
\1\ LOGO! 8
A Practical Introduction, with Circuit Solutions
and Example Programs
Author: Stefan Kruse
Published by: Publicis
ISBN: 9783895789267
\2\ LOGO!8 - MiniTrainerSchool
Author: Klaus Machalek
Product No.: LOGO! MTS

6.3 Internet link specifications


Table 6-2
Topic Link
\1\ Siemens Industry Online Support http://support.industry.siemens.com
\2\ Download page of the entry https://support.industry.siemens.com/cs/ww/en/view/68585
346
 Siemens AG 2018 All rights reserved

\3\ LOGO! 8 Manual https://support.industry.siemens.com/cs/ww/en/view/109741041


\4\ HMI KTP400 Manual https://support.industry.siemens.com/cs/ww/en/view/90114350
\5\ LOGO! http://w3.siemens.com/mcms/programmable-logic-
Software updates controller/en/logic-module-logo/demo-
software/Pages/Default.aspx
\6\ LOGO! http://w3.siemens.com/mcms/programmable-logic-
Application Examples controller/en/logic-module-logo/application-
examples/Pages/Default.aspx

6.4 History
Table 6-3
Version Date Modifications
V1.0 04/2013 First version
V1.1 03/2014 Layout modified and security note amended
V2.0 04/2016 Software and documentation revision with LOGO! 8
V2.1 08/2018 Changes in LOGO! 8 (user defined webserver)

House Control and Weather Sensors - LOGO! Set 11


Entry ID: 68585346, V2.1, 09/2018 36

You might also like