SECONDARY CHILLED WATER PUMP H
Section Description Pipe Size in Inches Length (m) Length (ft) L/s Flow (GPM)
Pipe 5 20.12 66 30.28 480
Gate Valve 5 0.00 0 30.28 480
Butterfly Valve 5 0.00 0 30.28 480
A-I Strainer 5 0.00 0 30.28 480
Elbow 5 0.00 0 30.28 480
NRV 5 0.00 0 30.28 480
DRV 5 0.00 0 30.28 480
I-J Pipe 5 3.66 12 22.71 360
PIpe 5 4.27 14 15.14 240
J-K Reducer 5 0.00 0 15.14 240
No Reduction Tee 5 0.00 0 15.14 240
Pipe 5 4.88 16 7.57 120
Gate Valve 5 0.00 0 7.57 120
K-L
Strainer 5 0.00 0 7.57 120
Reducer 5 0.00 0 7.57 120
ONDARY CHILLED WATER PUMP HEAD CALCULTION
Friction (ft/100ft) Equivalent legnth (ft) No Of Fittings Total Equivalent Length in Straight Pipe (ft)
3.895 0 0 66.0
3.895 6 1 6.0
3.895 6 2 12.0
3.895 80 1 80.0
3.895 8.2 5 41.0
3.895 50 1 50.0
3.895 58 1 58.0
2.261 0 0 12.0
3.255 0 0 14.0
3.255 3.8 1 3.8
3.255 6.7 1 6.7
3.433 0 0 16.0
3.433 3.2 1 3.2
3.433 42 1 42.0
3.433 2.6 1 2.6
Pump Head (ft)
Pump Head (m)
S.F (15%) (ft)
S.F (15%) (m)
Total Head Loss (ft)
Total Head Loss (m)
Head Loss (ft)
2.57
0.23
0.47
3.12
1.60
1.95
2.26
0.27
0.46
0.12
0.22
0.55
0.11
1.44
0.09
15.45
4.71
2.32
0.71
17.77
5.42