SECONDARY DISTRIBUTION CUBICLES

cgm.3
Modular compact system
with full gas insulation
Up to 40.5 kV IEC Standards
Up to 38 kV ANSI / IEEE Standards
ormazabal.com
  Modular compact system with full gas insulation

The quality of the products designed,


manufactured and installed by Ormazabal is
backed by the implementation and certification
of a quality management system, based on In view of the constant evolution in standards
international Standard ISO 9001. and design, the characteristics of the elements
Our commitment to the environment is contained in this catalogue are subject to
reaffirmed with the implementation and change without prior notice.
certification of an environmental management These characteristics, as well as the availability
system as laid down in international standard of components, are subject to confirmation by
ISO 14001. Ormazabal.

2
cgm.3  

Table of Contents
1. Introduction 3. Technical
Ormazabal p. 5
characteristics
Benefits of our solutions p. 6
Functions p. 18
Feeder function p. 18
Fuse protection function p. 20
2. General product Circuit-breaker protection p. 24

characteristics Busbar switch function


Busbar rise function
p. 26
p. 28
Cable rise function p. 30
Introduction to cgm.3 p. 9 Metering function p. 32
Construction structure and Metering function or
components p. 10 auxiliary services p. 34
Standard p. 14 Two feeder and
Special applications p. 15 fuse protection functions p. 36
Outdoor p. 15 Double feeder and circuit-breaker
High Corrosion Resistant (HCR) p. 15 functions p. 38
Protection and automation p. 16 Rise functions in busbars,
feeder and circuit-breaker p. 40
Installation and connection p. 42

4. Services
Ormazabal Services p. 46

3
  Modular compact system with full gas insulation

1. Introduction
Ormazabal p. 5
Benefits of our solutions p. 6

4
cgm.3  

Ormazabal
We are experts in customised, high-tech We have a unique research and technology
electrical solutions, with more than 55 years’ centre and a team of more than 2400 highly
experience. qualified professionals, all with a common
purpose: to lead the technological evolution of
Our solutions are focused on digitalising the electricity grids and enable energy transition
electrical network in order to integrate more toward a sustainable model.
renewable energy generation, enable greater
sustainable mobility, and guarantee supply for We are the origin of Velatia, a family-run,
buildings and infrastructure with critical energy industrial and technology group with
needs. international standing made up of companies
offering advanced technological solutions in
Thanks to our permanent commitment to line with the development of smart cities.
technological and industrial innovation, we
have positioned our technology all round the Velatia is present in electrical networks,
world to become a global player. helping in the deployment of smart grids. It
16 industrial plants and a network of accompanies its customers in their digital
subsidiaries and distributors around the world transformation process and offers its expertise
help us serve our customers’ needs in over in sectors such as aeronautics, energy services,
50 countries. electromechanical engineering and the
manufacture of electronic components.

5
  Modular compact system with full gas insulation

Green
generation
and storage

• Distribution • Renewable energy


systems Green
• Energy storage
Smart and • Hydrogen production
digital grids
and networks generation
and storage

Benefits
of our Digitalisation
We respond to new requirements

solutions
in smart grids with native digital solutions.
Our equipment incorporates the sensors,
electronics and communications necessary to
ensure optimal network management:
• Greater safety
• Continuity of service
• Greater efficiency

6
cgm.3  

Sustainable
buildings and
infrastructure

Green
mobility

Smart and
digital grids

• Electric vehicle
• Data centres
• High-voltage shore
• Airports and tunnels
connection systems Sustainable
Green buildings and
• Hospitals, shopping centres, etc.
mobility • Railway and metro
infrastructure • Industry
• Hydrogen mobility

Efficiency Sustainability
We design flexible, compact equipment for We strive to ensure our environmental
easy handling, installation and replacement, footprint is as small as possible, which we
minimising the impact on the environment. achieve thanks to an ISO 14001-certified
environmental management system that
monitors our impact on the environment. That
Safety and reliability is why:
We care about the safety of all people coming • We rationalise our use of primary products,
into contact with our solutions. selecting those materials that can best be
All our equipment is validated in accordance recycled while continuously cutting down on
with the most important international the most harmful ones.
standards, thereby ensuring it works and • We certify the sealtight integrity of our
operates safely throughout its service life, products, minimising the risk of leakage to
while also helping to maintain continuity of the environment.
supply for the electrical network. • We apply eco-design criteria in all our
products.
• We optimise energy consumption for both
our equipment and the entire manufacturing
process.

7
  Modular compact system with full gas insulation

2. General
product
characteristics
Introduction to cgm.3 p. 9
Construction structure and
components p. 10
Standard p. 14
Special applications p. 15
Outdoor p. 15
High Corrosion Resistant (HCR) p. 15
Protection and automation p. 16

8
cgm.3  

Introduction to
cgm.3
Rated voltage cgm.3 cubicles up to
40.5 kV / 38 kV (IEC/IEEE) have a wide variety
of functions, both modular and compact,
designed according to the most important
international standards.
cgm.3 cubicles are designed with a
hermetically sealed stainless steel gas tank
throughout the product’s service life.

Resistance to internal arcing


Internal arc classification IAC AFL(R)
up to 25 kA - 1 s to ensure maximum safety.

Extensibility Designed for smart grids


cgm.3 cubicles are optionally extensible on Ormazabal offers a complete solution with the
both sides. Our ormalink connecting set makes integration of ekorsys automation, protection
cgm.3 easily scalable thanks to a simple and sensor systems in cgm.3 cubicles.
connection.

9
  Modular compact system with full gas insulation
Construction structure and

Construction
structure
components

1 Gas tank
The gas tank, sealed and gas-insulated,
contains the busbar, as well as the making and
breaking devices.

3
1 2 Cable compartment
The medium-voltage input/output cable
connection compartment is located at the
bottom of the cubicle and can be accessed by
removing the front cover.
This compartment houses the:
• Bushing
• Connectors and cables
• Cable clamp bracket
• Horizontal earthing bar

3 Control compartment
Area for making and breaking operations
in medium-voltage circuits. It includes the
following:
• Driving mechanism
• Single-wire diagram and position indicator
• Voltage indicator
• Protection, control and metering relay
• Pressure gauge

Optionally, a control box can be added in the


top of this compartment in order to install
protection relays and metering and
control devices.
3

10
cgm.3  

Components
Switches

3-position switch-disconnector
Switch-disconnector with load breaking
capacity.

a b c
a. Closed
b. Open
c. Earthed

Types:
B: basic mechanism with independent
manual drive
BM: basic mechanism with motorised
drive
BR-A: mechanism with manual operation
and latching on opening
BR-AM: mechanism with motorised operation
and latching on opening

Circuit-breaker
Vacuum circuit-breaker. Configurable reclosing
and mechanical endurance M1/M2 according
to IEC 62271-100.
Types:
AV: circuit-breaker
AVM: motorised circuit-breaker
RAV: circuit-breaker with reclosing
RAVM: circuit-breaker and motorised
reclosing

Interlocks
Mechanical and electrical interlocks that
guarantee optimum operation of the
equipment and all its elements.
• They make it impossible to close the switch-
disconnector and the earthing switch at the
same time.
• Allow safe opening of the cable
compartment access cover.

11
  Modular compact system with full gas insulation

Technical characteristics
Electrical characteristics IEC ANSI/IEEE
Rated voltage Ud [kV] 36 38.5 40.5 38
Rated frequency fr [Hz] 50 60 50 50 60 50 60
Rated current Ir
Busbars and cubicle
[A] 400/630 630 630 600
interconnection
Feeder [A] 400/630 630 630 600
Transformer outgoing line [A] 200 200 200 200
Rated short-time withstand current
with tk= (x) s Ik [kA] 16/201)/25 (1/3 s) 201)/25 (1/3 s) 201) (1/3 s)/25 (1 s)
Peak value Ip [kA] 40/501)/62.5 41.6/521)/65 521)/62.5 521)/62.5 521)/65 52.5/62.5 54.6/65
Rated insulation level
Power frequency rated
Ud [kV] 70/80 80/90 95/118 70/77
withstand voltage [1 min]
Lightning impulse rated
Up [kV] 170/195 180/210 185/215 150/165
withstand voltage
Internal arc classification AF/AFL 16 kA 1 s/201) kA 1 s/25 kA 1 s AFL 201)kA 1 s/25 kA 1 s
IAC AFL2) 201)kA 1 s/25 kA 1
according to IEC 62271-200 AFLR 16/201)kA 1 s/25 kA 1 s AFLR 201)kA 1 s/25 kA 1 s
IP rating: Gas tank IP X8
IP rating: External enclosure IP2XD
Colour of equipment Grey 7035/blue 5005
Category of loss of service
RAL LSC2
continuity
Partition class LSC PM
1)
Tests conducted at 21 kA/52.5 kA 2)
Equivalent to IEEE C37.20.7 for 1D-S

Driving mechanism Three-position switch-disconnector Vacuum circuit-breaker


B BM B2M BR-A BR-AM BR-A2M AV AMV RAV RAMV
Tripping coils
Internal insulation [kV] 2 10 2
Tripping coil
Rated voltage [V] n/a 24/48/110 Vdc 220 Vac 24/48/110/220 Vdc 110/230 Vac
Max. consumption [W] n/a 56 < 56
Motorised units
Rated voltage [V] n/a 1) 2)
n/a 3) 3)
n/a 3)
n/a 3)

Rated current [A] n/a <4 n/a <4 < 4.5 n/a <4 n/a <4
Motor operation time [s] n/a 2.3 <3 n/a < 15 <3 n/a < 15 n/a < 15
Peak current [A] n/a < 14 n/a < 14 < 14 n/a < 15 n/a < 15
Indicating contacts
2NO + 2NC | 1NO //
1NO + 2NC | 2NO + 2NC |
Switch | Earthing 2NO + 2NC | 2NO/1NO + 1NC
1NO + 1NC 1NO + 1NC
1NO + 1NC 1NO + 1NC
Circuit-breaker n/a 2NO + 2NC 9NO + 9NC 2NO + 2NC 9NO + 9NC
Rated voltage [V] 250 250
Rated current [A] 16 10
1)
24/48/110/125 Vdc 110/220 Vac 2)
24/48/110 Vdc 3)
24/48/110/220 Vdc 110/230 Vac

Service conditions IEC ANSI/IEEE


Type of switchgear Indoor
Ambient temperature
Minimum | Maximum - 30 °C * | + 40 °C** - 40 °F * | 104 °F **
Maximum mean ambient temperature, measured over a 24-hour period + 35 °C 95 °F
Minimum storage temperature - 40 °C - 40 °F
Relative humidity
Maximum mean relative humidity, measured over a 24h/1 month period < 95 % < 90 %
Vapour pressure
Maximum mean vapour pressure, measured over a 24-hour | 1-month period 22 mbar | 18 mbar
Maximum height above sea level 2000 m** 6500 feet**
Solar radiation Negligible
Ambient air pollution (dust, smoke, corrosive and/or flammable gases, vapours or salt) acc. to normal service conditions indicated in IEC 62271-1.
Vibrations due to seismic movements or caused by causes external to the switchgear Insignificant**
* Check availability and other values ** For special conditions and altitudes, please check with Ormazabal

12
cgm.3  

cgm.3 system functions

Modular cubicles
l p v s

Feeder Fuse Circuit-breaker Busbar


function protection protection switch
function function function

rb rc m ma

Busbar rise Cable rise Metering Metering function


function function function and auxiliary services

Compact cubicles
2lp 2lv rlv

Double feeder and fuse protection functions Double feeder and circuit-breaker functions Rise functions in busbars, feeder and
circuit-breaker

13
  Modular compact system with full gas insulation

Standard
cgm.3 cubicles have been designed and certified according to the following international standards:

Applicable electrical standards


IEC
IEC 62271-1 Common specifications for high-voltage switchgear

IEC 62271-200 Alternating current metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV

IEC 62271-103 Switches for rated voltages above 1 kV up to and including 52 kV

IEC 62271-102 Alternating current disconnectors and earthing switches

IEC 62271-105 High-voltage alternating current switch-fuse combinations

IEC 62271-100 High-voltage alternating current circuit-breakers

IEC 60255 Electrical relays

IEC 60529 IP rating provided by enclosures

IEC 62271-206 Voltage presence indicating systems (vpis)

IEC 61243-5 Voltage detection systems (vds)

IEEE/ANSI
IEEE C37.74 IEEE Standard requirements for load break and fused under-pole, underground and subsurface load break switchgear for alternating current
systems up to 38 kV
IEEE C37.20.3 IEEE Standard for metal-enclosed interrupter switchgear

IEEE 1247 Standard for alternating current switches in the range above 1000 volts

IEEE C37.123 IEEE Guide to Specifications for Gas‑Insulated, Electric Power Substation Equipment

IEEE C37.20.4 IEEE Standard for indoor AC switches (1 kV‑38 kV) for use in metal-enclosed switchgear

IEEE C37.04 IEEE Standard Rating Structure for AC High‑Voltage circuit-breakers

IEEE C37.06 AC high-voltage circuit-breakers rated on a symmetrical current basis-preferred ratings and related required capacitances

IEEE C37.09 IEEE standard test procedures for AC high-voltage circuit-breakers with rated values based on a symmetrical current

IEEE C37.20.7 IEEE guide for testing metal‑enclosed medium-voltage switchgear for internal arc faults

IEEE C37.20.9 Standard for 1 kV to 52 kV metal-enclosed switchgear with gas insulation system.

(*) Check options and availability for other standards: SANS, HN, GB, SDMS...

14
cgm.3  

Special applications
Outdoor
cgm.3 outdoor cubicles are designed to
be installed outside, in service conditions,
including pollution, condensation and solar
radiation, as defined in normal outdoor service
conditions, according IEC 62271-1 or
IEEE C37.20.9.

There are two gas output options:


• Gas output to trench
• Upward gas output
Internal arc classification up to IAC AFLR 25 kA
- 1s, according to IEC 62271-200.

Outdoor Characteristics

IP rating IP54*

Impact protection IK10

Corrosion category C5H

* F or other options, please check with Ormazabal.

High Corrosion Resistant (HCR)


High corrosion resistant (HCR) cubicles have
been designed for harsh environmental
conditions, and are recommended for
installation in indoor applications with non-
standard environmental conditions such as
offshore or near-shore facilities, facilities in
tropical climates, or industrial environments
with high pollution levels.

Ormazabal has developed an in-house


testing procedure which guarantees corrosion
category C5-M, “High” durability according to
ISO 12944-2, and “Level 6” salinity according
to IEC 60068-2-52.

15
  Modular compact system with full gas insulation

Protection and
automation
Extensive range of ekorsys integrated equipment associated with cgm.3 cubicles, with protection, control and
automation functions to meet the needs of the electrical network.

Voltage sensing Voltage and current


units sensors
Voltage presence/absence sensing system, Toroidal current sensors and capacitive and
with the option to include high-frequency resistive voltage sensors for protection and
outputs for measuring signals associated with monitoring.
partial discharges.

Medium-voltage
Protection, metering and control and automation,
control units units
Multifunction protection, including control and Remote control and automation of the
metering (with self-powering option). medium-voltage network.

Software
Configuration tools for ekorsys family
protection, control and metering units.

16
cgm.3  

3. Technical
characteristics
Functions p. 18 Two feeder and
Feeder function p. 18 fuse protection functions p. 36
Fuse protection function p. 20 Double feeder and circuit-breaker
Circuit-breaker protection p. 24 functions p. 38
Busbar switch function p. 26 Rise functions in busbars,
Busbar rise function p. 28 feeder and circuit-breaker p. 40
Cable rise function p. 30 Installation and connection p. 42
Metering function p. 32
Metering function or
auxiliary services p. 34

17
  Modular compact system with full gas insulation

cgm.3-l
Feeder function
Modular feeder cubicle, equipped with a three-
position switch-disconnector: closed, open or
Functions

earthed.

Electrical characteristics IEC ANSI/IEEE


Rated voltage Ur [kV] 36 38.5 40.5 38
Rated frequency fr [Hz] 50 60 50 50 60 50 60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630 630 630 600
Feeder Ir [A] 400/630 630 630 600
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth and between phases Ud [kV] 70 80 95 70
Across isolating distance Ud [kV] 80 90 118 77
Lightning impulse rated withstand voltage
Phase-to-earth and between phases Up [kV] 170 180 185 150
Across isolating distance Up [kV] 195 210 215 165
AF/AFL 16 kA 1 s/ AF/AFL 16 kA 1 s/
20* kA 1 s/25 kA 1 s AF/AFL 20* kA 1 s/25 kA 1 s 20* kA 1 s/25 kA 1 s
Internal arc classification IAC
AFLR ** 16 kA 1 s/ AFLR** 20* kA 1 s/25 kA 1 s AFLR** 20* kA 1 s/25
20 kA 1 s/25 kA 1 s kA 1 s
Withstand DC voltage [kV] 72 103

Switch-disconnector IEC 62271-103 + IEC 62271-102 IEEE C37.74


Admissible rated short-time withstand current (main circuit)
Value tk= (x) s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)/25 (1 s) 20* (1/3 s)/25 (1 s)
Peak value IP [kA] 40/50*/62.5 41.6/52*/65 52*/62.5 52*/62.5 52*/65 52.5/62.5 54.6/65
Mainly active current breaking capacity I1 [A] 400/630 630 600/800
Vacuum cable breaking capacity Ua [A] 50 50 20
Closed loop breaking capacity I2a [A] 400/630 630 600/800
Earth fault breaking capacity I6A [A] 160 160 n/a
Vacuum line and cable breaking capacity in earth I6b [A] 90 90 n/a
fault conditions
Main switch making capacity Ima [kA] 40/50*/62.5 41.6/52*/65 52*/62.5 52*/62.5 52*/65 52.5/62.5 54.6/65
(peak value)
Switch category
Mechanical endurance 1000-M1/5000-M2 1000/5000
Operations cycles (short-circuit making) - class 5-E3 3-E2 in 20 kA/5-E3 in 25 kA 3

Earthing switch IEC 62271-102 IEEE C37.74


Admissible rated short-time withstand current (earthing circuit)
Value tk= (x) s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)/25 (1 s) 20* (1/3 s)/25 (1 s)
Peak value Ip [kA] 40/50*/62.5 41.6/52*/65 52*/62.5 52*/62.5 52*/65 52.5/62.5 54.6/65
Earthing switch making capacity (peak value) Ima [kA] 40/50*/62.5 41.6/52*/65 52*/62.5 52*/62.5 52*/65 52.5/62.5 54.6/65
Earthing switch category
Mechanical endurance 1000-M0 *** 1000
Operations cycles (short-circuit making) - class 5-E2 3

* Tests conducted at 21 kA/52.5 kA ** With gas output through pressure relief duct *** As option, 2000-M1
Values for 50 Hz

18
cgm.3  

Dimensions 147/162 kg
324/357 Lb

IEC ANSI/IEEE

Configuration Standard Optional Type of side connection:


Female bushing
IAC Rating Right Left Both
Internal arc IAC AFLR Bushing
16 kA 1 s 20 kA 1 s Right Left Both
Internal arc IAC AF/AFL
16 kA 1 s 20 kA 1 s 25 kA 1 s Driving mechanisms
Internal arc: tank Actuating levers
16 kA 0.5 s 20 kA 0.5 s B type manual mechanism
16 kA 1 s 20 kA 1 s 25 kA 1 s BM type motorised mechanism

Cubicle height Additional interlocks:


1745 mm Electrical interlocks
1400 mm* Keylock interlocks
Padlocks
Gas tank
Gas pressure indicator: Indicators
Pressure gauge without contact Acoustic alarm ekor.sas
Pressure gauge with temperature Voltage presence capacitive indicator ekor.
compensation and contacts vpis
Voltage presence/absence capacitive
Front connection: indicator ekor.ivds
Cable bushing Voltage presence/absence capacitive
indicator ekor.ivds-pd with high-frequency
Extensibility: output (HF)
On both sides
To the left/right blind Gas pressure relief duct
To the right/left blind Rear duct

Some specific configurations may be incompatible with each other.


* IAC AFL 20 kA 1 s

19
  Modular compact system with full gas insulation

cgm.3-p
Fuse protection function
Fuse protection modular cubicle, equipped with a three-
position switch-disconnector: closed, open or earthed and
protection with limiting fuses.

Electrical characteristics IEC ANSI/IEEE


Rated voltage Ur [kV] 36 38.5 40.5 38
Rated frequency fr [Hz] 50 60 50 50 60 50 60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630 630 630 600
Feeder Ir [A] 200 200
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth and between phases Ud [kV] 70 80 95 70
Across isolating distance Ud [kV] 80 90 118 77
Lightning impulse rated withstand voltage
Phase-to-earth and between phases Up [kV] 170 180 185 150
Across isolating distance Up [kV] 195 210 215 165
AF/AFL 16 kA 1 s/
AF/AFL 16 kA 1 s/
AF/AFL 20*kA 1 s/25 kA 1 s 20* kA 1 s/25 kA 1 s
Internal arc classification IAC 20* kA 1 s/25 kA 1 s
AFLR** 16 kA 1 s/20* kA 1 s AFLR** 16 kA 1s/20*
AFLR** 16 kA 1 s/20 kA 1 s
kA 1 s
Withstand DC voltage [kV] n/a 103

Switch-disconnector IEC 62271-103 + IEC 62271-102 IEEE C37.74


Admissible rated short-time withstand current (main circuit)
Value tk= (x) s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)/25 (1 s) 20* (1/3 s)/25 (1 s)
Peak value IP [kA] 40/50*/62.5 40/52.5*/65 52*/62.5 52*/62.5 52*/65 52.5/62.5 54.6/65
Mainly active current breaking capacity I1 [A] 200 200 200
Main switch making capacity
Ima [kA] 40/50*/62.5 40/52.5*/65 52*/62.5 52*/62.5 52*/65 52.5/62.5 54.6/65
(peak value)
Switch category
Mechanical endurance 1000-M1 1000
Operations cycles (short-circuit making) - class 5-E3 3-E2 in 20 kA/5-E3 in 25 kA 3
Combined switch-relay take-over current (ekor.rpt)
Breaking Imax in acc. TDito IEC 62271-105 [A] 490 n/a
Switch-fuse combination transfer current
Breaking Imax in acc. TDitransfer IEC 62271-105 [A] 72 n/a

Earthing switch IEC 62271-102 IEEE C37.74


Admissible rated short-time withstand current (earthing circuit)
Value tk= 1 s Ik [kA] 1/3.15 1/3.15
Peak value Ip [kA] 2.5/7.8 2.6/8.2 2.5/7.8 2.5/7.8 2.6/8.2 2.5/7.8 2.6/8.2
Earthing switch making capacity (peak value) Ima [kA] 2.5 2.6 2.5 2.5 2.6 2.5 2.6
Earthing switch category
Mechanical endurance 1000-M0/2000-M1 1000
Operations cycles (short-circuit making) - class 5-E2 2-E1 for 7.8 or 8.2 kA 3

* Tests conducted at 21 kA/52.5 kA ** With gas output through pressure relief duct
Values for 50 Hz

20
cgm.3  

Dimensions 215/230 kg
474/507 Lb

IEC ANSI/IEEE

Configuration Standard Optional

IAC Rating
Internal arc IAC AFLR Extensibility: Additional interlocks:
20 kA 1 s On both sides Electrical interlocks
Internal arc IAC AF/AFL To the left/right blind Keylock interlocks
16 kA 1 s 20 kA 1 s To the right/left blind Padlocks
25*** kA 1 s
Internal arc: tank Type of side connection: Indicators
16 kA 0.5 s 20 kA 0.5 s Female bushing Acoustic alarm ekor.sas
16 kA 0.5 s 20 kA 0.5 s Right  Left Both Voltage presence capacitive
16 kA 1 s 20 kA 1 s 25 kA 1 s Bushing indicator ekor.vpis
Right  Left Both Voltage presence/absence
Cubicle height: capacitive indicator ekor.ivds
1745 mm Fuse compartment Voltage presence/absence
1400 mm* Fuse tripping: capacitive indicator ekor.ivds-pd
Via combined fuses with high-frequency output (HF)
Gas tank Via associated fuses
Gas pressure indicator: Gas pressure relief duct
Pressure gauge without contacts Fuse holder: Rear duct
Pressure gauge with temperature 36 kV
compensation and contacts 38-38.5 kV
40.5 kV
Front connection:
Cable bushing Driving mechanisms
Actuating levers
BR-A type manual mechanism
BR-AM type motorised mechanism
Tripping coil

Some specific configurations may be incompatible with each other.


* IAC AFL 20 kA 1 s

21
  Modular compact system with full gas insulation

Fuse compartment
Characteristics Type of protection
• Horizontal fuse holders In accordance with Standard IEC 62271-105,
• Front access the switch-fuse combination may be either
• Phase-independent compartments “associated” or “combined” type.
• Protected within the gas tank
• Insulation and sealing against external The combined switch-fuse option allows the
agents (pollution, temperature changes, opening of the switch-disconnector caused
adverse weather conditions, including floods) by an external signal, e.g. as sent by the
• Internal interlocks for safe access to the fuse transformer’s thermostat in the event of
holder area overheating.

Tripping of each of the fuses is shown on the


cubicle’s front mimic diagram.

HHD fuse selection according to IEC standards


Rated transformer power without overload [kVA]
Ur Network
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000
[kV]
Rated fuse current IEC 60282-1 [A]
25 6.3 10 16 16 16 16 20 31.5 31.5 40 40 50 63 80*

30 6.3 6.3 10 16 16 16 20 20 31.5 31.5 40 40 63 63

35/36 6.3 6.3 10 16 16 16 20 20 31.5 31.5 40 40 50 63

Fuse selection according to IEEE standards


Rated transformer power without overload [kVA]
Ur Fuse
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500
[kV]
Rated fuse current [A]
34.5 6.3 6.3 10 10 16 16 20 20 31.5 31.5 40 40 50 63 80*

22
cgm.3  

Remarks
• HRC fuses recommended: SIBA brand
with medium type striker, according to
IEC 60282-1 (low power loss fuses)
• The fuse-switch assembly has been
temperature-rise tested under normal
service conditions according to IEC 62271-1
• Changing all three units is recommended if
any of the fuses blow (according to
IEC 60282-1)
• For overload conditions of the transformer
or other brands of fuse, please check with
Ormazabal

23
  Modular compact system with full gas insulation

cgm.3-v
Circuit-breaker protection
Circuit-breaker protection modular cubicle, equipped with a
vacuum circuit-breaker in series with a three-position switch-
disconnector.

Electrical characteristics IEC ANSI/IEEE


Rated voltage Ur [kV] 36 38.5 40.5 38
Rated frequency fr [Hz] 50 60 50 50 60 50 60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630 630 600
Feeder Ir [A] 400/630 630 600
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth and between phases Ud [kV] 70 80 95 80
Across isolating distance Ud [kV] 80 90 118 88
Lightning impulse rated withstand voltage
Phase-to-earth and between phases Up [kV] 170 180 185 150
Across isolating distance Up [kV] 195 210 215 165
AF/16 kA 1 s/
AF/AFL 20* kA 1 s/25 kA 1 s AF/AFL 20*kA 1 s/25 kA 1 s
Internal arc classification IAC AFL 20* kA 1 s/25 kA 1 s
AFLR** 20* kA 1 s/25 kA 1 s AFLR** 20*kA 1 s/25 kA 1 s
AFLR** 20* kA 1 s/25 kA 1 s
Withstand DC voltage [kV] n/a 72 103
Circuit-breaker IEC 62271-100 IEEEC37.20.3
Admissible rated short-time withstand current (main circuit)
Value tk= (x) s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)/25 (1 s) 20* (1/3 s)/25 (1 s)
Peak value IP [kA] 40/50*/62.5 41.5/52*/65 50*/62.5 52*/62.5 52*/65 52.5/62.5 54.6/65
Rated making and breaking capacity
Mainly active current breaking capacity I1 [A] 400/630 630 600/800
Short-circuit breaking capacity Isc [kA] 16/20*/ 25 20*/25 20*/25
Main switch making capacity (peak value) Ima [kA] 40/50*/62.5 41.5/52*/65 50*/62.5 52*/62.5 52*/65 52.5/62.5 54.6/65
Capacitive current capacity (50 Hz). Capacitor bank [A] 400 n/a n/a
Rated operating sequence
CO-15 s-CO CO-15 s-CO
Without quick reclosing
O-3 min-CO-3 min-CO O-3 min-CO-3 min-CO
O-0.3 s-CO-15 s-CO O-0.3 s-CO-15 s-CO
With quick reclosing
O-0.3 s-CO-3 min-CO O-0.3 s-CO-3 min-CO
Circuit-breaker category
10,000 - M2 10000 - M2
Mechanical endurance (operations class)
2000 - M1 2000 - M1
Electrical endurance (class) E2-C2 E2-C2
Switch-disconnector IEC 62271-103 + IEC 62271-102 IEEE C37.74
Admissible rated short-time withstand current (main circuit)
Value tk= (x) s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)/25 (1 s) 20* (1/3 s)/25 (1 s)
Peak value IP [kA] 40/50*/62.5 41.5/52*/65 50*/62.5 52*/62.5 52*/65 40/50*/62.5 41.5/52*/65
Mainly active current breaking capacity I1 [A] 400/630 630 600/800
Main switch making capacity (peak value) Ima [kA] 40/50*/62.5 41.5/52*/65 52*/62.5 52*/62.5 52*/65 40/50*/62.5 41.5/52*/65
Switch category
Mechanical endurance 1000-M1/5000-M2 1000/5000
Operations cycles (short-circuit making) - class 5-E3 3-E2 in 20 kA/5-E3 in 25 kA 3
Earthing switch IEC 62271-102 IEEE C37.74
Admissible rated short-time withstand current (earthing circuit)
Value tk= (x) s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)/25 (1 s) 20* (1/3 s)/25 (1 s)
Peak value Ip [kA] 40/50*/62.5 41.5/52*/65 50*/62.5 52*/62.5 52*/65 40/50*/62.5 41.5/52*/65
Earthing switch making capacity (peak value) Ima [kA] 40/50*/62.5 41.5/52*/65 50*/62.5 52*/62.5 52*/65 40/50*/62.5 41.5/52*/65
Earthing switch category
Mechanical endurance 2000-M1 2000
Operations cycles (short-circuit making) - class 5-E2 3
* Tests conducted at 21 kA/52.5 kA ** With gas output through pressure relief duct
Values for 50 Hz

24
cgm.3  

Dimensions
240/255 kg
529/562 Lb

IEC ANSI/IEEE

Configuration  Standard  Optional

IAC Rating Driving mechanisms


Internal arc IAC AFLR Actuating levers
€
z 20 kA 1 s  25 kA 1 s B type switch mechanism
€
Internal arc IAC AF/AFL BM type motorised mechanism
z
z 20 kA 1 s  25 kA 1 s AV type manual mechanism
z
Internal arc tank RAV type manual mechanism with reclosing
z
z 16 kA 0.5 s  20 kA 0,5 s AVM type motorised mechanism
z
z 16 kA 0.5 s  20 kA 1 s  25 kA 1 s RAVM type motorised mechanism for reclosing
z
Tripping coil
z
Cubicle height Bistable coil
z
1745 mm
z
2nd tripping coil
z
1400 mm*
z
Closing coil
z
Gas tank Additional interlocks:
Gas pressure indicator: Electrical interlocks
z
z Pressure gauge without contacts Keylock interlocks
z
z Pressure gauge with temperature Padlocks
z
compensation and contacts
Indicators
Front connection:
Acoustic alarm ekor.sas
z
z Cable bushing Voltage presence capacitive indicator ekor.vpis
z
Extensibility: Voltage presence/absence capacitive
z

z On both sides indicator ekor.ivds


z To the left/right blind Voltage presence/absence capacitive
z

z To the right/left blind indicator ekor.ivds-pd with high-frequency


output (HF)
Type of side connection:
Female bushing Gas pressure relief duct
Right
z  Left  Both Rear duct
z
Bushing
Right  Left  Both

Some specific configurations may be incompatible with each other.


* IAC AFL 20 kA 1 s

25
  Modular compact system with full gas insulation

cgm.3-s
Busbar switch function
Busbar switch modular cubicle, equipped with a two-position
switch-disconnector (closed and open). Optional earthing
switch (s-pt).

Electrical characteristics IEC ANSI/IEEE


Rated voltage Ur [kV] 36 38
Rated frequency fr [Hz] 50 60 50 60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630 600
Feeder Ir [A] 400/630 600
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth Ud [kV] 70 70
Across isolating distance Ud [kV] 80 77
Lightning impulse rated withstand voltage
Phase-to-earth Up [kV] 170 150
Across isolating distance Up [kV] 195 165
Internal arc classification IAC AF/AFL 16 kA 1 s/20* kA 1 s AF/AFL 16 kA 1 s/20* kA 1 s
IEC 62271-103 +
Switch-disconnector IEEE C37.74
IEC 62271-102
Admissible rated short-time withstand current (main circuit)
Value tk = (x) s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)
Peak value Ip [kA] 40/50*/62.5 41.6/52*/65 52.5 54.6
Mainly active current breaking capacity I1 [A] 400/630 600/800
Vacuum cable breaking capacity Ua [A] 50 20
Closed loop breaking capacity I2a [A] 400/630 600/800
Earth fault breaking capacity I6a [A] 160 n/a
Vacuum line and cable breaking capacity I6b [A] 90 n/a
in earth fault conditions
Main switch making capacity (peak value) Ima [kA] 40/50*/62.5 41.6/52*/65 52.5 54.6
Switch category
Mechanical endurance 1000-M1/5000-M2 1000/5000
Operations cycles (short-circuit making) - class 5-E3 3
Earthing switch IEC 62271-102 IEEE C37.74
Admissible rated short-time withstand current (earthing circuit)
Value tk = (x) s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)
Peak value Ip [kA] 40/50*/62.5 41.6/52*/65 52.5 54.6
Earthing switch making capacity (peak value) Ima [kA] 40/50*/62.5 41.6/52*/65 52.5 54.6
Earthing switch category
Mechanical endurance (manual) 1000-M0/2000-M1 1000
Operations cycles (short-circuit making) - class 5-E2 3
* Tests conducted at 21 kA/52.5 kA
Values for 50 Hz

26
cgm.3  

143 kg
Dimensions 315 Lb

IEC ANSI/IEEE

Configuration Standard Optional

IAC Rating Driving mechanisms


Internal arc IAC AF/AFL Actuating levers
16 kA 1 s 20 kA 1 s B type manual mechanism
Internal arc tank BM type motorised mechanism
16 kA 0.5 s 20 kA 0,5 s
16 kA 0.5 s 20 kA 1 s Additional interlocks:
Electrical interlocks
Cubicle height Keylock interlocks
1745 mm Padlocks

Gas tank Indicators


Gas pressure indicator: Acoustic alarm ekor.sas
Pressure gauge without contacts Voltage presence capacitive indicator ekor.
Pressure gauge with temperature vpis (with earthing)
compensation and contacts Voltage presence/absence capacitive
indicator ekor.ivds (with earthing)
Side connection:
Two-side extensibility Gas pressure relief duct
Rear duct
Type of side connection:
Female bushing
Right Left Both
Bushing
Right Left Both

Earthing:
With earthing switch on left, s-pti*
With earthing switch on right, s-ptd

Some specific configurations may be incompatible with each other.


* Option only available with manual control.

27
  Modular compact system with full gas insulation

cgm.3-rb
Busbar rise function
Modular cubicle with gas insulation and busbar rise. Optional
earthing switch (rb-pt).

Electrical characteristics IEC ANSI/IEEE


Rated voltage Ur [kV] 36 38.5 40.5 38
Rated frequency fr [Hz] 50 60 50 50 60 50/60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630 630 600
Feeder Ir [A] 400/630 630 600
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth and between phases Ud [kV] 70 80 95 70
Across isolating distance Ud [kV] 80 90 118 77
Lightning impulse rated withstand voltage
Phase-to-earth and between phases Up [kV] 170 180 185 150
Across isolating distance Up [kV] 195 210 215 165
AF/AFL 20* kA 1 s/25*
AF/AFL 20*kA 1 s/25 kA 1 s AFL 20* kA 1 s/25 kA 1 s
Internal arc classification IAC kA 1 s
AFLR 20* kA 1 s/25 kA 1 s AFLR 20* kA 1 s/25 kA 1 s
AFLR 20* kA 1 s/25 kA 1 s
Earthing switch IEC 62271-102 IEEE C37.74
Admissible rated short-time withstand current (earthing circuit)
Value tk= 1 s Ik [kA] 16/20*/25 (1/3 s) 20* (1/3 s)/25 (1 s) 20* (1/3 s)/25 (1 s)
Peak value Ip [kA] 40/50*/62.5 41.6/52*/65 50*/62.5 50*/62.5 52*/65 50*/62.5 52*/65
Earthing switch making capacity (peak value) Ima [kA] 40/50*/62.5 41.6/52*/65 50*/62.5 50*/62.5 52*/65 50*/62.5 52*/65
Earthing switch category
Mechanical endurance 1000-M0** 1000
Operations cycles (short-circuit making) - class 5-E2 3

* Tests conducted at 21 kA/52.5 kA ** As option, 2000-M1


Values for 50 Hz

28
cgm.3  

Dimensions Options
cgm.3-rb-pt

IEC ANSI/IEEE IEC 158 kg


348 Lb

Configuration Standard Optional

IAC Rating Type of side connection:


Internal arc IAC AFLR Female bushing
20 kA 1 s 25 kA 1 s Right Left Both
Internal arc IAC AF/AFL Bushing
16 kA 1 s 20 kA 1 s Right Left Both
25 kA 1 s
Internal arc: tank Earthing:
16 kA 0.5 s 20 kA 0.5 s With earthing switch
16 kA 1 s 20 kA 1 s
25 kA 1 s Driving mechanisms
B type manual mechanism
Cubicle height BM type motorised mechanism
1745 mm
1400 mm Additional interlocks:
Electrical interlocks
Gas tank Keylock interlocks
Gas pressure indicator: Padlocks
Pressure gauge without contacts
Pressure gauge with temperature Indicators
compensation and contacts Acoustic alarm ekor.sas
Voltage presence capacitive indicator ekor.
Front connection: vpis (with earthing)
Cable bushing Voltage presence/absence capacitive
indicator ekor.ivds (with earthing)
Extensibility: Other voltage capacitive indicators
On both sides: rba
To the right/left blind: (rbd/rbi) Gas pressure relief duct
Rear duct

Some specific configurations may be incompatible with each other.

29
  Modular compact system with full gas insulation

cgm.3-rc
Cable rise function
Cable rise modular air-insulated cubicle (through
to main busbar). Optional double cable rise
function (r2c)

Electrical characteristics IEC ANSI/IEEE


Rated voltage Ur [kV] 36 38.5 40.5 38
Rated frequency fr [Hz] 50/60 50 50 60 50/60
Rated current
Feeder Ir [A] 400/630 630 600
AF/AFL 20* kA 1 s/ 25
Internal arc classification IAC kA 1 s AFL 20* kA 1 s/25 kA 1 s AFL 20* kA/25 kA 1 s
AFL(R) 25 kA/1 s
* Tests conducted at 21 kA/52.5 kA
Values for 50 Hz

Configuration Standard Optional Options


IAC Rating cgm.3-r2c
IAC AFLR (without IAC class option)
20 kA 1 s 25 kA 1 s Double cable rise functional unit
IAC AFL (width=365 mm/1’ 2 3/8”,
16 kA 1 s 20 kA 1 s 25 kA 1 s weight=20 kg/44 Lb)

Cubicle height cgm.3-cl


1745 mm Side connection box
(width=550 mm/1’ 9 21/32”,
Extensibility weight=65 kg/143 Lb)
Right (rcd)
Left (rci)

Indicators
Voltage capacitive indicator ekor.vips
Voltage capacitive indicator ekor.ivds

30
cgm.3  

Dimensions 42 kg
93 Lb

IEC ANSI/IEEE

Options

Some specific configurations may be incompatible with each other.

31
  Modular compact system with full gas insulation

cgm.3-m
Metering function
Modular air-insulated metering cubicle.

Applications
Electrical characteristics IEC
Rated voltage Ur [kV] 36 38.5

Rated frequency fr [Hz] 50 60 50

Rated current

General busbar and cubicle interconnection Ir [A] 400/630 630

Rated short-time power frequency withstand voltage (1 min)

Phase-to-earth and between phases Ud [kV] 70 80 95

Lightning impulse rated withstand voltage

Phase-to-earth and between phases Up [kV] 170 180 185

Internal arc classification IAC AFL 16 kA 0.5 s/20* kA 0.5 s/16 kA 1 s/20* kA 1 s
16/20 (1/3 s)
Rated short-time withstand current Value tk = (x) s Ir [kA] 16/20*/25 (1/3 s)
25 (1 s)
* Tests conducted at 21 kA/52.5 kA
Values for 50 Hz

Configuration Standard Optional

IAC Rating Indicators


IAC AFL Voltage capacitive indicator ekor.vips
16 kA 0,5 s 20 kA 0,5 s Voltage capacitive indicator ekor.ivds
25 kA 0,5 s 20 kA 1 s
Optional elements
Busbar connections Heater element
Rigid unscreened top connection Protection mesh
Rigid unscreened bottom connection Keylocks/interlocks

Metering transformers
Current transformers installed (3 CTs)
Installed voltage transformers (3 VTs)
No transformers

Some specific configurations may be incompatible with each other.

32
cgm.3  

900 mm: 290 kg* / 639 Lb*


Dimensions 1100 mm: 520 kg* / 1146 Lb*
(*) Empty enclosure

IEC

Options
cgm.3-m-pt

Type* 03/07 Type** 22 Type 14 Type* 05/09 Type 11

Type 15 Type* 04/08 Type** 21 Type* 06/10

* Except for connection with cgm.3-l


** 1100 mm

33
  Modular compact system with full gas insulation

cgm.3-ma
Metering function or auxiliary services
Modular air-insulated metering cubicle.

Electrical characteristics IEC


Rated voltage Ur [kV] 36/40.5

Rated frequency fr [Hz] 50/60

Rated current

General busbar and cubicle interconnection Ir [A] 630

Rated short-time power frequency withstand voltage (1 min)

Phase-to-earth Ud [kV] 95

Lightning impulse rated withstand voltage

Phase-to-earth Up [kV] 185

Internal arc classification IAC up to AFL / AFLR 25 kA 1 s

Configuration Standard Optional

IAC Rating Control box


IAC AFL/AFLR Other metering and automation
16 kA 1 s 20 kA 1 s 25 kA 1 s components

Cable connections Optional elements


Cable connection Heater element
Protection mesh
Metering transformers Keylocks/interlocks
or auxiliary services
Voltage transformers (3 VTs) Gas output
Two-phase auxiliary services transformer To trench and upward (IAC AFL)
Upward with relief duct (IAC AFLR)

Some specific configurations may be incompatible with each other.

34
cgm.3  

125 kg*
Dimensions (*) Empty enclosure

IEC

Options

6MA type 7MA type


(13 MA if input on right) (14MA if input on right)

35
  Modular compact system with full gas insulation

cgm.3-2lp
Two feeder and
fuse protection functions
Compact cubicle (RMU) with two feeder
functions and one fuse protection function,
housed in a single gas tank.

Electrical characteristics IEC l-v


Rated voltage Ur [kV] 36
Rated frequency fr [Hz] 50 60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630
Feeder Ir [A] 400/630
Transformer outgoing line Ir [A] 200 (p)
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth and between phases Ud [kV] 70
Across isolating distance Ud [kV] 80
Lightning impulse rated withstand voltage
Phase-to-earth and between phases Up [kV] 170
Across isolating distance Up [kV] 195
Internal arc classification IAC AF/AFL 16 kA 1 s/20* kA 1 s

Switch-disconnector IEC 62271-103 + IEC 62271-102


Admissible rated short-time withstand current (main circuit)
Value tk= (x) s Ik [kA] 16/20*/25 (1/3 s)
Peak value IP [kA] 40/50*/62.5 41.6/52*/65
400/630
Mainly active current breaking capacity I1 [A]
(p) 200
Vacuum cable breaking capacity I4a [A] 50/1.5
Closed loop breaking capacity I2a [A] 400/630
Earth fault breaking capacity I6a [A] 160
Vacuum line and cable breaking capacity in earth fault conditions I6b [A] 90
Main switch making capacity (peak value) Ima [kA] 40/50*/62.5 41.6/52*/65
Switch category
Mechanical endurance 1000-M1/5000-M2
Operations cycles (short-circuit making) - class 5-E3
Combined switch-relay take-over current (ekor.rpt)
Breaking Imax in acc. TDito IEC 62271-105 [A] (p) 490
Switch-fuse combination transfer current
Breaking Imax in acc. TDitransfer IEC 62271-105 [A] (p) 820

Earthing switch IEC 62271-102


Admissible rated short-time withstand current (earthing circuit)
(l) 16/20*/25 (1/3 s)
Value tk= (x) s Ik [kA]
(p) 1 (1 s)
(l) 40/52*/65
Peak value Ik [kA]
(p) 2.5
(l) 40/52*/65
Earthing switch making capacity (peak value) Ik [kA]
(p) 2.5
Earthing switch category
Mechanical endurance 1000-M0/2000-M1
Operations cycles (short-circuit making) - class 5-E2
* Tests conducted at 21 kA/52.5 kA
Values for 50 Hz

36
cgm.3  

490 kg
Dimensions 1080 Lb

IEC

Configuration  Standard  Optional

IAC Rating Driving mechanisms


Internal arc IAC AF/AFL Actuating levers
€
z 16 kA 1 s  20 kA 1 s B type manual mechanism
€
Internal arc: tank BM type motorised mechanism
z
z 16 kA 0.5 s  20 kA 0.5 s BR-A type manual mechanism
z
z 16 kA 1 s  20 kA 1 s BR-AM type motorised mechanism
z

Cubicle height Additional interlocks:


1745 mm
€ Electrical interlocks
z
1400 mm*
z Keylock interlocks
z
Padlocks
z
Gas tank
Gas pressure indicator: Indicators
€ Pressure gauge without contacts Acoustic alarm ekor.sas
€
z Pressure gauge with temperature Voltage presence capacitive indicator
€
compensation and contacts ekor.vpis
Voltage presence/absence
z
Front connection capacitive indicator ekor.ivds
€ Cable bushing Voltage presence/absence capacitive
z
Extensibility indicator ekor.ivds-pd with high-frequency
€ Two-side extensibility output (HF)
z Left extensibility/right blind Other voltage capacitive indicators
z

z Right extensibility/left blind


z Blind both sides

Type of side connection:


Female bushing
Right
z  Left  Both
Bushing
Right
z  Left  Both

Some specific configurations may be incompatible with each other.


* IAC AFL 20 kA 1 s

37
  Modular compact system with full gas insulation

cgm.3-2lv
Double feeder and circuit-
breaker functions
Compact cubicle with two feeder functions and
circuit-breaker protection, housed in a single gas
tank.

Electrical characteristics IEC l-v


Rated voltage Ur [kV] 36/40.5
Rated frequency fr [Hz] 50 60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630
Feeder Ir [A] 400/630
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth and between phases Ud [kV] 70
Across isolating distance Ud [kV] 80
Lightning impulse rated withstand voltage
Phase-to-earth and between phases Up [kV] 170
Across isolating distance Up [kV] 195
Internal arc classification IAC AF/AFL 20* kA 1 s/25 kA 1 s
Switch-disconnector IEC 62271-103
Admissible rated short-time withstand current (main circuit)
Value tk= (x) s Ik [kA] 20*/25 (1/3 s)
Peak value IP [kA] 50*/62.5 52/65
Mainly active current breaking capacity I1 [A] 400/630
Vacuum cable breaking capacity I4a [A] 50
Closed loop breaking capacity I2a [A] 400/630
Earth fault breaking capacity I6a [A] 160
Vacuum line and cable breaking capacity in earth fault conditions I6b [A] 90
Main switch making capacity (peak value) Ima [kA] 50*/62.5 52/65
Circuit-breaker category
Mechanical endurance (operations class) 1000-M1/5000-M2
Electrical endurance (class) 5-E3
Circuit-breaker IEC 62271-100
Admissible rated short-time withstand current (main circuit)
Value tk= (x) s Ik [kA] 20*/25 (1/3 s)
Peak value IP [kA] 50*/62.5 52/65
Rated making and breaking capacity
Mainly active current rated breaking capacity I1 [A] 400/630
Short-circuit breaking capacity Isc [kA] 20*/25
Circuit-breaker making capacity (peak value) Ima [kA] 50*/62.5 52/65
Capacitive current capacity (50 Hz). Capacitor bank [A] 400
Rated operating sequence
CO-15 s-CO
Without quick reclosing
O-3 min-CO-3 min-CO
O-0.3 s-CO-15 s-CO
With quick reclosing
O-0.3 s-CO-3 min-CO
Switch category
10,000 – M2
Mechanical endurance
2000 – M1
Operations cycles (short-circuit making) - class E2 – C2
Earthing switch IEC 62271-102
Admissible rated short-time withstand current (earthing circuit)
Value tk= (x) s Ik [kA] 20*/25 (1/3 s)
Peak value Ip [kA] 50*/62.5 52/65
Earthing switch making capacity (peak value) 50*/62.5 52/65
Earthing switch category
Mechanical endurance 1000-M0
Operations cycles (short-circuit making) - class 5-E2
* Tests conducted at 21 kA/52.5 kA
Values for 50 Hz

38
cgm.3  

Dimensions
547 kg
1206 Lb

IEC

Configuration  Standard  Optional

IAC Rating Driving mechanisms


Internal arc IAC AF/AFL Actuating levers
€
z 20 kA 1 s  25 kA 1 s B type manual mechanism
€
BM type motorised mechanism
z
Cubicle height AV type manual mechanism
z
1745 mm
€ RAV type manual mechanism with reclosing
z
AVM type motorised mechanism
z
Gas tank RAVM type motorised mechanism with
z
Gas pressure indicator: reclosing
€ Pressure gauge without contacts
z Pressure gauge with temperature Additional interlocks:
compensation and contacts z Electrical interlocks
z Keylock interlocks
Front connection z Padlocks
€ Cable bushing
Indicators
Extensibility Acoustic alarm ekor.sas
€
€ On both sides Voltage presence/absence capacitive
z
z To the left/right blind indicator ekor.ivds-pd with high-frequency
z To the right/left blind output (HF)
z Blind both sides Voltage presence capacitive indicator
€
ekor.vpis
Type of side connection: Voltage presence/absence capacitive
z
Female bushing indicator ekor.ivds
Right
z  Left  Both Other voltage capacitive indicators
z

Some specific configurations may be incompatible with each other.

39
  Modular compact system with full gas insulation

cgm.3-rlv
Rise functions in busbars, feeder
and circuit-breaker
Compact cubicle with busbar rise,
feeder and circuit-breaker function,
housed in a single gas tank.

Electrical characteristics IEC l-v


Rated voltage Ur [kV] 36/40.5
Rated frequency fr [Hz] 50 60
Rated current
General busbar and cubicle interconnection Ir [A] 400/630
Feeder Ir [A] 400/630
Rated short-time power frequency withstand voltage (1 min)
Phase-to-earth and between phases Ud [kV] 70
Across isolating distance Ud [kV] 80
Lightning impulse rated withstand voltage
Phase-to-earth and between phases Up [kV] 170
Across isolating distance Up [kV] 195
Internal arc classification IAC AF/AFL 20* kA 1 s/25 kA 1 s
Switch-disconnector IEC 62271-103
Admissible rated short-time withstand current (main circuit)
Value tk= (x) s Ik [kA] 20*/25 (1/3 s)
Peak value IP [kA] 50*/62.5 52/65
Mainly active current breaking capacity I1 [A] 400/630
Vacuum cable breaking capacity I4a [A] 50
Closed loop breaking capacity I2a [A] 400/630
Earth fault breaking capacity I6a [A] 160
Vacuum line and cable breaking capacity in earth fault conditions I6b [A] 90
Main switch making capacity (peak value) Ima [kA] 50*/62.5 52/65
Circuit-breaker category
Mechanical endurance 1000-M1/5000-M2
Operations cycles (short-circuit making) - class 5-E3
Circuit-breaker IEC 62271-100
Admissible rated short-time withstand current (earthing circuit)
Value tk= (x) s Ik [kA] 20*/25 (1/3 s)
Peak value IP [kA] 50*/62.5 52/65
Rated making and breaking capacity
Mainly active current rated breaking capacity I1 [A] 400/630
Short-circuit breaking capacity Isc [kA] 20*/25
Circuit-breaker making capacity (peak value) Ima [kA] 50*/62.5 52/65
Capacitive current capacity (50 Hz). Capacitor bank [A] 400
Rated operating sequence
CO-15 s-CO
Without quick reclosing
O-3 min-CO-3 min-CO
O-0.3 s-CO-15 s-CO
With quick reclosing
O-0.3 s-CO-3 min-CO
Switch category
10,000 – M2
Mechanical endurance (operations class)
2000 – M1
Electrical endurance (class) E2 – C2
Earthing switch IEC 62271-102
Admissible rated short-time withstand current (earthing circuit)
Value tk= (x) s Ik [kA] 20*/25 (1/3 s)
Peak value Ip [kA] 50*/62.5 52/65
Earthing switch making capacity (peak value) 50*/62.5 52/65
Earthing switch category
Mechanical endurance 1000-M0
Operations cycles (short-circuit making) - class 5-E2
* Tests conducted at 21 kA/52.5 kA
Values for 50 Hz

40
cgm.3  

547 kg
Dimensions 1206 Lb

IEC

Configuration  Standard  Optional

IAC Rating Driving mechanisms


Internal arc IAC AF/AFL Actuating levers
€
z 20 kA 1 s  25 kA 1 s B type manual mechanism
€
BM type motorised mechanism
z
Cubicle height AV type manual mechanism
z
1745 mm
€ RAV type manual mechanism with reclosing
z
AVM type motorised mechanism
z
Gas tank RAVM type motorised mechanism with
z
Gas pressure indicator: reclosing
€ Pressure gauge without contacts
z Pressure gauge with temperature Additional interlocks:
compensation and contacts z Electrical interlocks
z Keylock interlocks
Extensibility z Padlocks
€ On both sides
z To the left/right blind Indicators
z To the right/left blind Acoustic alarm ekor.sas
€
z Blind both sides Voltage presence capacitive indicator
€
ekor.vpis
Type of side connection: Voltage presence/absence capacitive
z
Female bushing indicator ekor.ivds
Right
z  Left  Both Voltage presence/absence capacitive
z
Bushing indicator ekor.ivds-pd with high-frequency
Right
z  Left  Both output (HF)
Other voltage capacitive indicators
z

Some specific configurations may be incompatible with each other.

41
  Modular compact system with full gas insulation

Installation and
connection
Handling and transport
• Dimensions compatible with road,
sea or air container transport
• Reduced size and weight
• Adapted packing:
• Vertical plastic on pallet protected with
polystyrene.
• Pallet pack with reinforced cardboard box
• Wooden box.

Handling methods (up to 5 functional units):


• Elevation: Forklift truck or manual pallet jack
• Lifting: Slings and lifting beams

For handling and installation instructions, check


with Ormazabal.

Installation
• Indoor, outdoor installation, transformer
substations, wind power applications (on/
offshore), etc.
• Easy handling (passes through standard
doors and elevators)
• Operation, extensibility and removal in
reduced space
• Ergonomic design for easy cubicle
connection and floor fastening
• No gas handled on site
• Installation on auxiliary profiles in the case
of uneven floors or to avoid digging cable
trenches

42
cgm.3  

Installation distances
cgm.3 family cubicles can be configured to
best suit your needs and available space. It is
important to take into account the minimum
installation distances, which are defined
by accessibility and the required protection
conditions (IAC classification, gas output, etc.).

Minimum installation distances [mm] (feet/inches)

Side wall (a) [100] (4)


Roof (b) [550] (1' 9.65")
Front clearance (c) [500] (1’ 7.69”)
Rear wall (d) [> 100] (> 4”) *
* Except for cgm.3-p and cgm.3-2lp (0 mm/inches)
In the case of rear duct = 0 mm/inches. The space required to extend the assembly with an additional cubicle is 200 mm / 7 7/8" plus the
width of the new cubicle.

Gas output
Configurable gas relief according to the
characteristics of the facility:
• Downward gases, directing gases into the
trench
• Upward gases, directing gases from the rear
to the top of the cubicle

For other configurations, please check with


Ormazabal.

Trench dimensions
The recommended minimum dimensions
for the trench are defined on the basis of
those used in IEC/IEEE standard tests. These
dimensions may vary, in accordance with the
radius of curvature of the cables.

For specific dimensions for your product, check


with Ormazabal.

43
  Modular compact system with full gas insulation

Cable connection
Screw-in or plug-in epoxy resin bushing, IEC or
IEEE type. Complaint with dielectric and partial
discharge tests.

There are three types:


• Plug-in up to 250 A (IEC) and 200 A (IEEE)
• Plug-in up to 400 A
• Screw-in up to 630 A (IEC) and 600 A (IEEE)

Located in the cable compartment. Optionally,


they can be located in the side of the cubicles
for direct supply to the main busbar.

Option to install more than one connector per


phase, depending on the model and manufacturer.
Check with Ormazabal for availability.

Distance (d)
[mm] [430]
cgm.3-l/rb
(feet/inches) (1’-4.93”)
[mm] [500]
cgm.3-v
(feet/inches) (1’ 7.69”)
[240]
cgm.3-p -
(9.45”)

Option to extend the available distance using the extended cover option [+ 165 mm] (+ 6.5”).

IEC type cable IEEE type cable Extended cover


cgmcosmos cable + surge
plug-in screw-in screw-in 2 cables/phase
arrester
-l
-p - -
-v
-s - - - - -
rb - -
-rc * -
-ma - - -
-m - - - - -
-2lp - ** **
-2lv -
rlv -
* cgm.3-r2c: double cable rise functional unit.
** Configurable option for feeder function only.

44
cgm.3  

4. Services
Ormazabal Services p. 46

45
  Modular compact system with full gas insulation

Ormazabal Services

Engineering and Assembly and Training and


technical commissioning certification
advice
Advice during the project’s initial We accompany our customers at Continuous personalised training for
stages, providing solutions tailored all times, from equipment factory our customers, with official operation
to our customers’ needs through acceptance tests through to delivery and maintenance certification for our
innovative, efficient, sustainable and commissioning on site. equipment.
products.

46
cgm.3  

Ormazabal provides a wide range of services For further information, please check with
and support for its customers throughout the Ormazabal.
product's service life: from preliminary design
and customisation, through to end of service
life.

Inspection and Manage parts and Modernisation and


maintenance accessories digitalisation
Predictive, preventive and corrective Availability of spare parts and Upgrade equipment to the latest
inspections and maintenance accessories in order to offer technologies in order to improve
of equipment in order to ensure a quick response on site and performance and extend service
maximum efficiency and optimal reduce downtime. life, as well as providing remote
service life. monitoring and support for your
facility.

47
Parque Científico y More info
Tecnológico de Bizkaia, Edif. 104.
48170 Zamudio. Spain
CA-112-EN-02

Tel.: +34 94 431 77 77


2023

ormazabal@ormazabal.com

48

You might also like