Professional Documents
Culture Documents
MV SWITCHGEAR
( SPECIFICATION )
446554162.doc Page 1 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
CONTENTS
1 GENERAL......................................................................................................................3
1.1 Drawings..........................................................................................................................4
1.2 Equipment Identification and Color Codes.......................................................................4
2 TECHNICAL DESCRIPTIONS....................................................................................4
2.1 General.............................................................................................................................4
2.2 11 kV Switchgear..............................................................................................................5
2.2.1 General Arrangement and Construction............................................................................5
2.2.2 Busbars.............................................................................................................................7
2.2.3 Low Voltage Equipment Compartment.............................................................................7
2.2.4 Interfacing Cubicle...........................................................................................................9
2.2.5 Circuit Breaker.................................................................................................................9
2.2.6 Protection Schemes.........................................................................................................11
2.2.7 Isolator cum Earthing Switches (for GIS).......................................................................15
2.2.8 Interlock System (for GIS)..............................................................................................15
2.2.9 Locks and Padlocks........................................................................................................16
2.2.10 Floor Inserts....................................................................................................................16
2.2.11 Voltage and Current Transformers..................................................................................16
2.2.12 Cable Boxes....................................................................................................................16
2.2.13 Earthing of Metal Parts...................................................................................................17
2.2.14 Corona............................................................................................................................17
2.2.15 Switchgear Space Heater................................................................................................17
2.2.16 Labels.............................................................................................................................17
2.2.17 Fault Current Indicator....................................................................................................18
2.2.18 11 kV Voltage Detectors.................................................................................................18
2.3 11/0.4 kV Distribution Transformer................................................................................18
2.4 0.4 kV Distribution Board...............................................................................................18
2.5 Power Circuits, Control, Protection and Telecommunication Wiring..............................19
2.6 Corrosion Protection.......................................................................................................20
3 TESTING AND INSPECTION....................................................................................21
3.1 General...........................................................................................................................21
3.2 Factory Tests...................................................................................................................22
3.2.1 Type Tests (Only applicable for Pre-Qualification).........................................................22
3.2.2 Routine Tests..................................................................................................................22
3.2.3 Sample Tests...................................................................................................................23
3.3 Site Tests.........................................................................................................................23
446554162.doc Page 2 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
1 GENERAL
This specification covers the design, manufacturing, factory testing, marking, packing, shipping,
transportation to site, installation, site testing and commissioning of 11/0.4 kV Distribution
Substation equipped with the following equipment:
11 kV metal-clad air or SF6-insulated switchgear with fixed vacuum or SF6 circuit breakers
11/0.4 kV, 500,1000 or 1500 kVA transformers
CTs
VTs (if applicable)
0.4 kV Distribution Board
0.4 kV Station Cubicle (to be provided under Civil Works)
LV Energy Meter (if applicable)
Control and protection equipment
and only those general aspects, which are, considered minimum quality and performance
requirements by ADWEA/ADDC/AADC. Further detailed and specific data are contained in the
drawings, data sheets and other documents that form part of the Tender Document.
The 11/0.4 kV Distribution Substation equipment offered shall be complete in all respects
necessary for their effective and trouble free operation when connected to the distribution
system.
The 11/0.4 kV Distribution Substation equipment shall be installed indoor substations with
nature ventilation.
For applicable technical standards, tests, reference shall be made to:
S-AAA-SWG-MV-LV-GEN - General Requirements (MV/LV)
(Applicable Technical Standards, Tests, etc.)
For Specifications and Technical Data of associated equipment, reference shall be made to
Standard Technical Specification, Parts:
S-AAA-SWG-MV-VTCT - Voltage and Current Transformers for
MV Switchgear
S-AAA-SWG-MV-DIST-BOARD-0.4 - 0.4 kV Distribution Board
S-AAA-TRAFO-ATR - Distribution Transformers
446554162.doc Page 3 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
1.1 Drawings
Conceptual Design of 11/0.4 kV Distribution Substation Switchgear single-line diagrams
provided in the Drawings Section are as follows:
Drawing No. Title
DWG AAA SWG 02 04 05-1 Conceptual Design of 11/0.4 kV Distribution Substation, 11 kV
Fixed Type Circuit Breaker (Type 3)
Please note that number of feeders and feeder arrangement shown on above drawing shall be
subject the changes if required and requested by ADWEA/ADDC/AADC.
2 TECHNICAL DESCRIPTIONS
2.1 General
The 11/0.4 kV Distribution Substation equipment ratings shall be as specified in the Technical
data Sheets.
The 11/0.4 kV Distribution Substation equipment shall be capable of withstanding the electrical
and mechanical stresses as specified in the Technical Data Sheets and in the Standard Technical
Specification, Part: General Technical Requirements.
The highest degree of uniformity and interchange ability shall be attained. The design shall
facilitate easy maintenance, fault diagnosis and repair of the components.
Cast iron shall not be used for any part, which may be subjected to mechanical shock.
446554162.doc Page 4 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
2.2 11 kV Switchgear
446554162.doc Page 5 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
The 11 kV Switchgear of similar ratings/model/type shall have the same dimensions and
components. The devices shall be interchangeable with those of other units.
The 11 kV Switchgear shall be equipped with one set of three phase busbars. The circuit breakers
shall be ‘VACUUM or SF6” and have approved means of isolation of circuit.
Where specified in Scope or shown on drawings, the 11 kV Switchgear shall also incorporate
earthing facilities for each set of busbars, achieved by either suitably interlocked earthing
switches/devices or other approved method.
The equipment shall be dust-proof, rodent and insect proof. It shall be capable of operating in
tropical and humid conditions and provision shall be made for electric heaters to prevent
condensation, particularly when the equipment is out of service.
The Switchgear shall be designed for automatic pressure relief in case of pressure build up due to
arcing, at the same time, ensuring that escaping gases are clear off the operating personal in the
front and rear of the Switchgear. Any devise for pressure relief shall under normal service be
absolutely vermin, dust and damp proof.
Complete protection shall be provided against approach to live parts or contact with internal
wiring parts. Particular attention shall be paid to drive linkages, bushings, earth bars and the like
to ensure that the enclosure classification is not reduced when these pass through compartments.
Adequate clearances and surface creepage distances shall be provided to ensure satisfactory
performance under service conditions.
In order to make the type of Switchgear compatible with the arrangements familiar to
ADWEA/ADDC/AADC, the busbars shall be contained in a busbar chamber, which shall be
positioned physically above the cable box.
Suitable potential indicators shall be provided at each feeder.
For busbar voltage measurement withdrawable busbar VTs shall be installed (top mounted).
Connection to busbar shall be through HV protection fuse. Secondary circuit shall be protected
through MCB. ADWEAs Standard Specifications for VT shall apply (if applicable & specified).
The 11 kV Switchgear shall not exceed Noise and Radio Influence Voltage Levels as specified in
Technical Data Sheets.
The 11 kV Switchgear shall be checked after assembly to ensure that no rattling of individual
components occur.
11 kV Switchgear shall be designed to ensure that thermal interaction does not unduly affect the
performance of any of the components.
446554162.doc Page 6 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
All 11 kV Switchgear metal works, including cable screens shall be securely bonded together in
such a way that a firm metallic connection exists between each component of the substation
metal work and the 11/0.4 kV Distribution Substation earthing system.
All wirings shall be labelled at the terminal and equipped with approved tags.
The following signalling facilities shall be incorporated in each switchgear compartment:
Earth Fault Protection TRIP
O/C Protection TRIP
MCB ALARM
SF6 ALARM
Bay Control LOCAL ALARM
CB control OPEN/CLOSE
CB position OPEN/CLOSE
Earth Fault Indication ALARM
2.2.2 Busbars
Each busbar shall be of hard drawn high conductivity copper and shall be covered with PVC
sleeves. Silicone rubber insulated Bus Bar is acceptable. The single busbars shall be arranged to
permit future extensions. The method of extension has to be described clearly and shall be shown
on a drawing. Provision shall be made for extending the busbar at either end without any need
for cutting or drilling the busbar. Bus Bar earthing facility is not required.
446554162.doc Page 7 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
The color shall be in the glass and not an applied coating and the different colored glasses shall
be interchangeable. Transparent synthetic materials may be used instead of glass, provided it can
be shown that such materials have fast colors and are completely suitable for operating in topical
climates.
MCBs shall be provided in indication circuits.
446554162.doc Page 8 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
The variety of indicating lamps provided shall be rationalized to reduce maintenance and spares
requirements.
2.2.5.1 General
The circuit breakers shall be of the fixed type with horizontal isolation from the fixed busbars
and outgoing circuit connections.
446554162.doc Page 9 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
If additional devices are required to limit over voltages caused during switching to a safe level,
these shall be supplied and the details shall be described in the Bid.
Contact material properties shall be such that the required dielectric strength across open
contacts is obtained at all times.
Transmission of high mechanical stresses to the vacuum enclosure during operation shall be
reduced to the minimum possible by the use of resilient mountings. Features to prevent the
application of abnormal stresses to the flexible seals shall be incorporated.
Means for measurement of contact wear without major dismantling shall be incorporated and an
appropriate gauge shall be provided.
The details of any vacuum monitoring facilities shall be described in the Bid.
If possible, any one vacuum or SF 6 bottle should be able to be removed without having to
remove any of those on the other two phases.
Facilities for SF6 gas insulated switchgear or circuit breaker such as gas leakage, pressure
monitoring, filling etc need to be described and confirmed.
446554162.doc Page 10 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
The operating mechanism shall be designed so that the circuit breaker is free to open
immediately when the trip coil is energized. A direct acting mechanical trip via an emergency
button shall be provided on each breaker.
Means shall be provided for the manual operation of all circuit breakers for maintenance
purposes.
An approved positively driven mechanically operating indicator shall be provided to show
whether the circuit breaker is open or closed.
In the event of failure to latch in the closed position it shall not be possible for the circuit breaker
to open except at normal speed. Means shall be provided for slow closing of the circuit breaker
for maintenance purposes. It shall not be possible to use this device when the circuit breaker is in
the service position. An approved arrangement shall be provided to prevent repeated reclosures
in the event of a permanent close signal being present.
It shall not be possible, without the use of special tools, to gain access to the tripping toggle or
any part of the mechanism, which would permit defeat of the mechanical tripping feature.
It shall not be possible to render the electrical protection tripping feature inoperative by any
mechanical locking device.
It shall be possible to complete the closing, tripping and interlock circuits when the circuit
breaker is isolated in order to permit operation for tests purposes. The interlocks of the circuit
breaker when in the isolated position shall be arranged to prevent interference with associated
interlocks on circuits in service.
A LOCAL/SUPERVISORY switch shall be provided for each circuit breaker.
Operating mechanism for feeder and transformer control switches shall include the following
electro-mechanical DMS interface facilities:
Internal ON/OFF position of all switches (feeder & transformer)
Switch for LOCAL & REMOTE Operation (ON/OFF) manually and electrically with the
provision for motor installation facility on the existing mechanism without any modification.
For feeder switches electrical ON/OFF control switches (local and remote positions) shall be
provided including all wirings.
Provision of lever switch/contacts incorporated with mechanism of feeder and transformer
switches for indicating ON/OFF positions.
2.2.6.1 11 kV
2.2.6.1.1 General
446554162.doc Page 11 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
Relays shall be of approved type and comply generally with the requirements of IEC 60255 and
other approved standards and shall be contained in dust proof, moisture proof flush-mounted
cases with transparent fronts and semi gloss black bezel; and shall be provided with breathers.
Test plugs to suit each different type of relay or test socket shall be provided for each
switchboard or set of relay panels. The test plugs shall have terminals for both the relay and
wiring side connections, which shall accept, both wires and plug connectors, and shall be
supplied with a flexible cable for connection to a portable relay test set.
All relays shall be arranged in such a way that any dust, which may have collected in or upon the
relay housing shall not fall on the relay mechanism when opening the housing.
Auxiliary relays shall also be mounted in dust proof cases.
All protective relays shall be provided with a name and data plate of approved standard, which
shall include the ratios of the associated current and/or voltage transformers.
All metal bases and frames of relays shall be earthed, except where the frame must be insulated
for special requirements. An earth terminal shall be provided on the back of the relay case.
Each relay which initiates tripping shall be provided with a trip isolation facility which should be
integrated into the relay in such a way that the tripping has to be isolated prior to withdrawal of
the relay from its housing.
All relays which are connected to the tripping circuit of a circuit breaker or to the coil circuit of
an auxiliary tripping relay shall be provided with approved operation indicators which, whenever
possible, shall be of the mechanically operated type. Indicators shall also be provided on such
additional relay elements to enable identification of the faulty phase.
Each indicator, whether of the electrically operated or mechanically operated type, shall be
capable of being reset by hand without opening the relay housing and relay operation shall not be
possible whilst resetting the operating indicator. Each indicator shall be so designed that the
status is not shown before the relay has completed its operation. Indicators shall not reset during
a failure of auxiliary power to the relay.
It shall not be possible to operate any relay by hand without opening the case.
Unless otherwise specified, the current circuit for the relays shall be suitable for 1 A, 50 Hz and
voltage circuit shall be rated for 63.5 V, 50 Hz (Ph-N) or 110 V by, 50 Hz (Ph-Ph).
The maximum ac fault voltage across any two points of a current circuit shall not exceed 3000
volt peak and non-linear resistors shall be included if necessary to achieve this limitation.
If bolts or nuts are so placed as to be inaccessible with an ordinary spanner, not less than 2
suitable special spanners shall be provided.
All calculations to determine relay settings and adequacy of CT and VT rating shall be submitted
to ADWEA/ADDC/AADC for approval. In the event that the rating of the VT or CT proposed is
insufficient to handle the connected burden in accordance with this specification, the
446554162.doc Page 12 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
Bidder/Contractor shall supply the CT and VT with the necessary increased capacity and ratio at
no extra cost.
The Bidder/Contractor shall provide electrical protection relay schedules including manufacturer,
type designation, characteristic details and ranges and actual protection settings to be used, on a
per circuit basis.
All protection relays offered shall have been fully type tested in accordance with the appropriate
standards and shall have had satisfactory operational service. Comprehensive data’s related to
these requirements shall be submitted with the Bid.
446554162.doc Page 13 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
The tripping energy for a circuit breaker shall be stored in a tripping energy storage capacitor
bank.
The energy storage capacitor bank shall be inside the relay casing and shall be charged by the
current transformers during a fault.
The Self-Powered O/C and E/F Protection Relay shall be designed to closely follow the
characteristics:
Withstand transformer inrush currents
Permit transformer overloads
To be co-ordinated with time/current characteristics of HRC fuses (if applicable) for down-
stream feeder protection.
Time/current characteristics and a schematic diagram shall be submitted with the Bid.
The O/C and E/F relay should be housed in a suitable housing shall have front connections and
shall be accessible from the front.
Alternatively a built in control supply arrangement may be provided to trip the breaker.
The protection curves and all other settings shall be adjustable through micro-switches which
when viewed from the front clearly show the unit settings.
The O/C and E/F relay shall provide local indication of a fault operation.
It should be possible for the relay to perform a self-check giving clear indication of the status of
the over current and earth fault elements.
The O/C and E/F relay shall have facility of historic fault information with time, date and fault
records. The CT circuits to the O/C and E/F relay shall be routed through the test terminal blocks
and also tripping circuits from O/C and E/F relay to the CB. DC supply for numerical O/C & E/F
relay to be routed through test block. The numerical O/C & E/F relay shall have output constants
as required by DMS signal list.
Other auxiliary relays with flag indication to give trip/alarm in case of transformer protections
such as oil temperatures etc. shall be provided.
446554162.doc Page 14 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
The IDMT and instantaneous functions provided for the earth fault protection also shall have
separate trip and alarm contacts and separate trip indicators.
The protection should be 230 Vac fed relays.
446554162.doc Page 15 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
446554162.doc Page 16 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
Cable glands shall be suitable for 11 kV, 3 Core, XLPE insulated, Double Steel Tape Armour,
PVC Served Cables, cable size range 95 to 300 mm 2 Copper. Gland plates, unless otherwise
specified, shall have glands pointing vertically downwards.
Each panel shall be supplied complete with Heat Shrinkable Termination Kit of an acceptable
and approved make, Cable Lugs support glands, etc. The termination kit shall be suitable for 95
mm2 for Transformer Feeder and 185, 240 or 300 mm2 for Cable Feeder.
Plug-In Type Cable Terminations are not acceptable.
2.2.14 Corona
The equipment shall be designed in such a way to minimise corona or other electrical discharge
and radio interference.
2.2.16 Labels
Each panel of each switchgear shall have a blank circuit label approximately 30 cm x 8 cm
mounted on the front of the panel in a prominent position. These labels shall be made of suitable
engraving material approximately 2 mm thick, white surface with black engraving. Small black
446554162.doc Page 17 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
labels of similar material shall be mounted on the rear of the panels. The circuit names will be
engraved at site by ADWEA/ADDC/AADC.
Fault Current Indicators shall have operating current setting range 40A to 80A.
446554162.doc Page 18 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
446554162.doc Page 19 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
imparted to the moving bundled conductors. Each bundle shall be anchored such that the moving
bundle length is the maximum available without loops.
Conductors between terminal blocks and apparatus shall be laid in plastic ducts or covered with
plastic bands.
All power circuits, control and protection wiring and low level signal wiring shall be physically
separated. Separate laying-way shall be provided for power cables, and the working voltage of each
power circuit shall be marked on the associated boards.
Conductor ends not connected to compression-type terminal blocks shall be provided with approved
claw-washers, which neatly retain all strands, "Push-on" or "quick" type connectors shall not be
used for current transformers and trip circuits. These connectors maybe used for alarm and control
system and within an equipment assembly only. Sample of any such connectors shall be submitted
for ADWEA/ADDC/AADC´s approval.
Wiring shall be arranged to give easy access to the terminal or relays and other apparatus.
Soldered or wire strapped connections shall only be inside electronic systems. Any wire
wrapping shall be in accordance with IEC Publication 60352.
As far as reasonably possible, all outgoing wiring shall be grouped by function (CT, VT, Trip,
Alarm, etc.) with those going to a common destination allocated to adjacent terminal blocks.
Terminal block configuration shall be submitted for ADWEA/ADDC/AADC’s approval. Labels
shall be provided on the fixed portion of the terminal boards showing the function of the group.
Insulating barriers shall be provided between each group of power circuit terminals and between
the terminal categories as applicable. The height and spacing between the barriers shall be such
as to give adequate protection to the terminals.
Connections for indicating instruments, and for the telecommunication circuits from transducers,
or modem outputs, shall use individually shielded wire pairs. One (1) extra terminal per pair of
terminals shall be provided to connect this shield to ground.
446554162.doc Page 20 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
For Corrosion Protection measures, reference shall be made to Standard Technical Specification,
Part:
S-AAA-CORR - Corrosion Protection and Painting Color Codes
446554162.doc Page 21 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
446554162.doc Page 22 of 23
MV SWITCHGEAR
11/0.4 kV Distribution Substation
(11 kV SWG Air or SF6 Insulated, Fixed CB)
3.2.3.1 General
The following sample (or quality acceptance) tests shall be carried out in the presence of
ADWEA/ADDC/AADC on the selected samples of 11 kV Switchgear.
Verification of dimensions of various components including thickness of mild steel sheets
and paint
Functional tests of all major components according to the Specifications and relevant IEC
standards.
446554162.doc Page 23 of 23