within a public water distribution system. In this detailed incident, perchlorate (ClO4–) was
detected in the distribution system of Levelland, Texas, and was eventually isolated to one
tank. Because cathodic protection systems are widely used, this research confirms a
potentially troubling mechanism of ClO4– generation.
TECHNICAL NOTE:
electrochemical generation
of perchlorate
IN MUNICIPAL DRINKING WATER SYSTEMS
ontinued advances in sensitivity and reliability of analytical procedures
BY ANDREW JACKSON,
SANGEETHA ARUNAGIRI,
RICHARD TOCK,
TODD ANDERSON,
C now make detection of perchlorate (ClO4–) concentrations possible in the
microgram-per-litre range in water. Less than a decade ago these low-level
ClO4– concentrations would have gone undetected. Today increased
instrumental sensitivity has led to more frequent detections of ClO4– in
water resources. In most instances the ClO4– source can be traced to military,
industrial, or agricultural operations (Urbansky, 1998). In other instances it has
been suggested that ClO4– salts are generated by natural “oxidative weather-
AND KEN RAINWATER ing” phenomena, which involve pathways attributable to microbial activity,
ultraviolet radiation, or atmospheric generation of activated oxygen moieties,
such as ozone and peroxide complexes (Becking et al, 1958).
Even at the low microgram-per-litre levels, however, ClO4– contamination causes
concern for potential chronic ecological and human health effects (Greer et al,
2002). ClO4– is known to affect thyroid gland function, and numerous studies are
under way on the associated risk from ingestion of ClO4–. The current US Envi-
ronmental Protection Agency–recommended Interim Action Level is listed as 4–18
µg/L, whereas some state regulatory agencies have established a range of 1–18 µg/L.
In the spring of 2002, as part of its Uncontrolled Chemical Monitoring Program,
the Texas Commission on Environmental Quality (TCEQ) conducted sampling
E ve n a t t h e l ow m i c r o g r a m - p e r- l i t r e l eve l s , h oweve r , p e r c h l o r a t e c o n t a m i n a t i o n
causes concern for potential chronic ecological and human health effects.
The objectives of its research were to determine the most (2) reaction of a strong mineral acid with a chlorate to
probable cause of the ClO4– discovered in the Level- produce ClO4–, chloride, and chlorine dioxide;
land system and to estimate the potential for future (3) natural oxidative weathering or microbial oxidation
occurrences. Task assignments for this research included of chlorides;
the development of a summary of the known facts per- (4) electrolytic conversion of an aqueous chlorate to
taining to the Levelland incident, presentation of a the- ClO4– by anodic oxidation;
Even though elevated storage tanks are not designed as electrolytic cells , it is possible that the
use of internal cathodic corrosion protection systems and/or external lightning strikes could
promote electrochemical reactions within the tanks and generate perchlorate contamination.
eters as measured by the city of Levelland that could ous acid (HOCl) were present in the water being stored
affect the electrochemical processes. The city of Level- in the Lee Street EST.
land is one of the 11 member cities that make up the Initially both lightning strikes and internal cathodic
Canadian River Municipal Water Authority, and as protection were considered as possible energy sources to
such receives its primary drinking water supply from the drive the electrochemical processes. Lightning was sus-
city of Lubbock, whose water treatment plant handles pected to have struck the Lee Street EST sometime dur-
water from Lake Meredith on the Canadian River. Lub- ing the period in question. The lightning strike could have
80
with liberation of gaseous hydrogen
and free electrons to the anode. Equa-
60 tion 4 represents the final oxidation
step in which chlorate is electro-
40 chemically transformed into ClO 4 –
with additional release of protons to
solution and electrons to the anode
20
(Janssen & Vanderheyden, 1995;
Grotheer & Cook, 1968).
0 The other most likely possible reac-
0 100 200 300 400 tion mechanisms for the production
Time—h
of chlorate and ClO4– would be the
following:
sent a surge of high voltage potential across the EST and OCl– + OCl– ↔ ClO2– + Cl– (5)
its cathodic protection circuit, damaging its rectifier. The
tank was examined for external evidence of a recent light- OCl– + ClO2– ↔ ClO3– + Cl– (6)
ning strike. Weather data sources from government mete-
orological agencies now compile records of the timing 2HClO3 ↔ HClO4 + HClO2 (7)
and locations of lightning strikes. It was documented that
the Lee Street EST had an active cathodic protection sys- Equation 5 represents the decomposition of hy-
tem mounted inside the EST beneath the water line. Active pochlorite to chlorite, and Eq 6 represents the further
cathodic protection systems use an impressed current to decomposition of chlorite to chlorate, which is known
force an anode to corrode and thus protect the steel tank to proceed at a faster rate (Weinberg et al, 2003; Kraft et
shell. Details of these systems can be found in National al, 1999). However, these reactions would be exceedingly
Association of Corrosion Engineers (NACE) Standard slow at neutral pH and temperatures less than 30oC
RP0388-2001 (NACE, 2001). (86oF). Equation 7 is the chemical decomposition of chlo-
Electrochemical production of chlorine, hypochlorous rate to ClO4–, which is only significant left to right at
acid, chlorate, and ClO4– has been understood and exploited elevated temperatures and under acidic conditions.
for more than a century. There are numerous possible reac- Equations 5–7 are important reactions for the manu-
tions that produce or consume the presence of the various facture of oxidized chlorine species and for storage of
oxidized states of chlorine. The primary electrochemically high-strength solutions of hypochlorite. However, in the
induced reactions that could occur in drinking water with absence of a lightning strike, which could produce local-
pH, temperature, and total dissolved solids similar to the ized high temperatures, these reactions most likely would
Levelland water supply as exposed to metal anodes are not have contributed significantly to the production of
ClO4– in the EST (Jonassen, 2002). This limitation leaves
2Cl– ↔ Cl2 + 2e- (1) the impressed-current corrosion protection system as the
more probable cause for the ClO4– contamination detected
Cl2(g) + H2O ↔ HCl + HOCl ↔ 2H+ + Cl– +ClO– (2) in the Lee Street EST. Therefore, to determine whether it
was possible that the cathodic protection system was
6ClO– + 3H2O ↔ 3ClO3– + 4Cl– + 1.5O2 + 6H+ + 6e- (3) responsible for the ClO4– presence in the EST, the fol-
lowing experiments were conducted.
ClO3– + H2O ↔ ClO4– + 2H+ + 2e– (4)
EXPERIMENTAL APPROACH
Equation 1 relates the dissolved chloride and chlorine Apparatus. The laboratory apparatus included com-
concentrations. Equation 2 represents the reaction of pletely mixed water baths in which a cathode and anode
The data supplied for the perchlorate incident in Levelland strongly suggests that it was produced
by the cathodic corrosion protection system.
cathode and no anode in the water bath. The circuits in of ClO4– in electrochemical systems. The chloride con-
Trials 1 and 2 were connected to a current/voltage power centration in the Lee Street EST (near 400 mg/L), although
source1 for a total of 338 h. Samples of water were taken high for drinking water, was much lower than that for typ-
from all four trials at periodic intervals over this time ical industrial generation of ClO4–. Higher concentra-
and analyzed for ClO4–. All samples were taken by glass tions of chloride increase the potential for ClO4– pro-
pipette and stored in 50 mL vials at 4oC until analysis. duction, and either chloride or OCl–/HOCl could have
Analytical instrumentation. A chromatograph2 equipped served as the feed material for the ClO4– production in the
with an oven3 maintained at 35oC and an autosampler4 Lee Street EST. The voltage potential reported for the
were used. A guard column5 (4 × 50 mm [0.16 × 2 in.]) Lee Street EST cathodic protection system was approxi-
was used in conjunction with an analytical column6 (4 × mately 6 V, which was about 1 V higher than those used
250 mm [0.16 × 10 in.]) for separation. The 100-mM in the cathodic protection systems in the other tanks. Cell
sodium hydroxide eluent was applied isocratically at a voltages higher than 6.3 were reported in the literature to
flow rate of 1.0 mL/min. A suppressor,7 operated at 300 be advantageous for the production of ClO 4 – . The
mA in the external water mode, was also used. A con- recorded pH levels (7.2 to 7.75) and temperatures (<30oC)
ductivity meter8 was used to measure the conductivity within the water storage tanks in the Levelland system
of samples before analysis. appear to be immaterial to the observed ClO4– contam-
ination, because neither is in the range known to pro-
RESULTS AND DISCUSSION mote nonelectrochemical mechanisms for the generation
ClO4– was generated in both replicates that received of ClO4–.
electrical power (trials 1 and 2, Figure 1). ClO4– genera-
tion was generally similar between replicates, although the CONCLUSIONS
absolute amount of ClO4– differed between each replicate, Primarily on the basis of documentation assembled
with maximum concentrations of 64 and 113 µg/L in tri- from the Levelland incident, experimental verification,
als 1 and 2, respectively. These experiments demonstrated and published literature, the cathodic protection system
it is feasible for impressed-current corrosion protection used in the Lee Street EST was the probable cause of in
systems to produce ClO4– in batch systems. ClO4– was not situ ClO4– contamination of the chlorinated drinking
detected in either the control (trial 3) or in the treatment water in the tank. Although it was originally speculated
with electrodes but no power (trial 4). that lightning adversely affected the cathodic corrosion
The investigation of a possible lightning strike as the system and that a malfunction of a rectifier in the im-
cause of the April 2002 ClO4– concentrations found no pressed-current system may have led to the generation of
evidence of a recent strike at or near the EST. Atmos- the ClO4– contamination, no evidence for that cause was
pheric generated flash data, which can be obtained from uncovered.
the US Lightning Detection Network, showed no lightning Fortunately it is unlikely that ClO4– production in
strikes within a 2 mi (3 km) radius of the storage tank for cathodically protected storage tanks is a common occur-
REFERENCES Grant, M.H., 1984. Kirk Othmer Encyclopedia Practice—Impressed Current Cathodic
of Chemical Technology (4th ed.), 5:934. Protection of Internal Submerged Sur-
Becking, L.; Haldane, A.; & Izard, D., 1958.
faces of Carbon Steel Water Storage
Perchlorate an Important Constituent of Janssen, L.J. & Vanderheyden, P.D., 1995. Tanks, Houston, Texas.
Seawater. Nature, 182:4636:645. Mechanism of Anodic Oxidation of Chlo-
Greer, M.A. et al, 2002. Health Effects Assess- rate to Perchlorate on Platinum Elec- Schilt, A., 2003. Perchloric Acid and Perchlo-
ment for Environmental Perchlorate Con- trodes. Jour. Applied Electrochem., rates. GFS Chemicals Inc., Powell, Ohio.
tamination: The Dose–Response for Inhi- 25:2:126.
Weinberg, H.; Delcomyn, C.; & Unnam, V.,
bition of Thyroidal Radioiodine Uptake in Kraft, A. et al, 1999. Electrochemical Water 2003. Bromate in Chlorinated Drinking
Humans. Envir. Health Persp., 110:9:927. Disinfection Part I: Hypochlorite Pro- Waters: Occurrence and Implications for
Grotheer, M. & Cook, E., 1968. Mechanism of duction From Very Dilute Chloride Solu- Future Regulation. Envir. Sci. & Technol.,
Electrolytic Perchlorate Production. tions. Jour. Applied Electrochem., 37:3104.
Electrochem. Technol., 6:5:221. 29:861.
Urbansky, E.T., 1998. Perchlorate Chemistry:
Jonassen, N., 2002. (2nd ed.) Electrostatics. National Association of Corrosion Engineers Implications for Analysis and Remedia-
Kluwer Academic, Boston, Mass. (NACE), 2001. Standard Recommended tion. Bioremediation Jour., 2:2:81.