Design Calculations (CAL)

Mechanical

Haykstep Station Firefighting Tank and Pump Room HVAC Calculation Notes.

Rev Date Description By CHK Approved

A 29/08/2019 Issued for Approval A.S. A.AD. N.E.

902-G2-DAR-038-CAL-910 REV A

E14155-0100D-PRC-EN-01 (F1) REV 1


Greater Cairo Metro Line 3 Phase 4B

Haykstep Station
Firefighting Tank and Pump Room
HVAC Calculation Report

902-G2-DAR-038-CAL-910-A

August 2019
Page 1 of 8
Greater Cairo Metro Line 3 Phase 4B

1 HVAC
Ventilation

1.1.1 Fans Air Flow Calculation


1.1.2 Fans Static Pressure Calculation

902-G2-DAR-038-CAL-910-A

August 2019
Page 2 of 8
Greater Cairo Metro Line 3 Phase 4B

1. HVAC

902-G2-DAR-038-CAL-910-A

August 2019
Page 3 of 8
Greater Cairo Metro Line 3 Phase 4B

1.1. VENTILATION

902-G2-DAR-038-CAL-910-A

August 2019
Page 4 of 8
Greater Cairo Metro Line 3 Phase 4B

1.1.1. FANS AIR FLOW CALCULATIONS

902-G2-DAR-038-CAL-910-A

August 2019
Page 5 of 8
Design calculation sheet
Project no: E14155-0100D Date: Sheet no. : 1 of 1 Computed by: A.S.
Subject : Fans Calculation Sheet Checked by: A.AD.
Firefighting Pump Room Approved by: N.E.

Fans Air Flow Calculation


Minimum Basic Design
Area Height No. of units Actual Exhaust air flow Total Exhaust
Fan Room name ACH L/s.m² L/s.unit Exhaust air flow Exhaust Notes
(m²) (m) (If applicable) (L/s) (L/s)
(L/s) (L/s)
Exhaust Air Fans
Basement Floor

1 Fan, 300 l/s


EF-01 PUMP ROOM 27.0 3.9 - 10 - - 293 300 - 300 to comply with civil
defense requirements

Page 6 of 8
Greater Cairo Metro Line 3 Phase 4B

1.1.2. FANS STATIC PRESSURE CALCULATIONS

902-G2-DAR-038-CAL-910-A

August 2019
Page 7 of 8
Design calculation sheet
Project no: E14155-0100D - Firefighting Pump Room Sheet no.: 1 of 1 Computed by: A.S.
Subject: EF-01 Checked by: A.E.
Static Pressure Calculations: Approved by: T.Z.
Note: To the exception of the airflows, only cells shaded cells are to be filled by user.
Total Exhaust
lps cfm
300 636

EXTERNAL PRESSURE LOSSES


Losses Low Pressure Low Velocity Exhaust Ducts:
Longest Duct Run 1 m = 3.28 ft
Safety Factor 1.1
Equivalent Length 1.1 m = 4 ft
Friction Factor 0.47 Pa/m = 0.057 "/100 ft in. mm
Exhaust
Friction loss 0.6 Pa 0.01 " = 0.01 0.26
Losses From Accessories and Outlets
Exhaust Outlet Fire Damper Volume Damper Other
in. mm in. mm in. mm in. mm in. mm
0 0 0 0 0 0 0.28 7.12 = 0.28 7.12
Balancing Factor : 1.20
Field Conditions : 1.15
Total P.D.
in. mm
0.4 10
Notes: Loss from Accessories and Outlets
which placed under (other) term in. mm
is defining losses from Total Calculated Static Pressure 0.4 10.0
(Exhaust & Intake Sand Trap Louvers) Static Pressure as Reported to Schedule : 0.4 10.0

Page 8 of 8