You are on page 1of 62

Cat C15 GC ®

DIESEL GENERATOR SETS

Standby: 60Hz, 480V & 600V


Engine Model Cat® C15 ACERTTM In-line 6, 4-cycle diesel
Bore x Stroke 137mm x 171mm (5.4in x 6.8in)
Displacement 15.2 L (928 in³)
Compression Ratio 16.1:1
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel Injection System MEUI
Governor Electronic ADEM™ A4

Standby Performance Strategy


EPA Certified for Stationary
500 ekW, 625 kVA
PACKAGE PERFORMANCE Emergency Application

Performance Standby
Frequency 60 Hz
Genset Power Rating 625 kVA
Gen set power rating with fan @ 0.8 power factor 500 ekW
Fuelling strategy TIER 3
Performance Number DM8155
Fuel Consumption
100% load with fan 137.0 L/hr 36.2 gal/hr
75% load with fan 110.5 L/hr 29.2 gal/hr
50% load with fan 71.3 L/hr 18.8 gal/hr
25% load with fan 41.9 L/hr 11.1 gal/hr
Cooling System 1

Radiator air flow restriction (system) 0.12 kPa 0.48 in. Water
Radiator air flow 720 m3/min 25426 cfm
Engine coolant capacity 20.8 L 5.5 gal
Radiator coolant capacity 54 L 14 gal
Total coolant capacity 75 L 20 gal
Inlet Air
Combustion air inlet flow rate 38.2 m³/min 1347.7 cfm
Max. Allowable Combustion Air Inlet Temp 49 ° C 120 ° F
Exhaust System
Exhaust stack gas temperature 531.1 ° C 988.0 ° F
Exhaust gas flow rate 102.1 m³/min 3605.5 cfm
Exhaust system backpressure (maximum allowable) 10.0 kPa 40.0 in. water
Heat Rejection
Heat rejection to jacket water 182 kW 10375 Btu/min
Heat rejection to exhaust (total) 493 kW 28039 Btu/min
Heat rejection to aftercooler 121 kW 6860 Btu/min
Heat rejection to atmosphere from engine 91 kW 5182 Btu/min
Heat rejection from alternator 29 kW 1655 Btu/min

LEHE2011-04 1/2
Cat C15 GC ®
DIESEL GENERATOR SETS

Emissions (Nominal)2 Standby


NOx 2129.1 mg/Nm³ 4.6 g/hp-hr
CO 301.5 mg/Nm³ 0.6 g/hp-hr
HC 8.8 mg/Nm³ 0.03 g/hp-hr
PM 9.5 mg/Nm³ 0.03 g/hp-hr
Alternator3 Standby
Voltages 480V 600V
Motor Starting Capability @ 30% Voltage Dip 1019 1103
Current 751.8 601.4
Frame Size M3154L4 M3136L4
Excitation Shunt Excitation AREP
Temperature Rise 105°C 189°F 130°C 234°F
WEIGHTS & DIMENSIONS – OPEN SET
Generator Set
Base Dim “A” Dim “B” Dim “C” Weight
mm (in) mm (in) mm (in) kg (lb)

Skid (Wide 4815 (189.6) 1630 (64.2) 2034 (80.1) 3756 (8280.6)
Base)

Integral Tank 4815 (189.6) 1630 (64.2) 2584 (101.7) 4693 (10346.3)
base

FUEL TANK CAPACITY

Total
Tank Useable Capacity
Capacity
Design

Litre Gallon Litre Gallon


Integral 3671 969.7 3323 877.8

DEFINITIONS AND CONDITIONS:


1
For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.

2
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO,
PM, NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb.
The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100%
load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.

3
UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise
is based on a 40° C ambient per NEMA MG1-32.

APPLICABLE CODES AND STANDARDS:


AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22, NEMA
MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for availability.

STANDBY: Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power
rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.

RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions.
Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29º C (85º F) and weighing 838.9 g/litre
(7.001 lbs/U.S. gal.). Additional ratings may be available for specific customer requirements, contact your Caterpillar representative for details. For information
regarding Low Sulfur fuel and Biodiesel capability, please consult your Cat dealer.

LEHE2011-04 (11-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their
respective logos, “Caterpillar Yellow”, the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without 2/2
permission.
Cat GC ®
Control Panel

Image shown might not reflect actual configuration

GCCP 1.2 - Control Panel


GCCP 1.2 is an auto Start Control Module suitable for a wide variety of diesel gen-
set applications. Monitoring an extensive number of engine parameters, the
modules will display warnings, shutdown and engine status information on the back-
lit LCD screen, illuminated LEDs and remote PC.

FEATURES
• 4-line back-lit LCD text display
• Multiple display languages
• Five-key menu navigation
• LCD alarm indication
• Customisable power-up text and images
• Data logging facility
• Internal PLC editor
• Protections disable feature
• Fully configurable via PC using USB & RS485 communication
• Front panel configuration with PIN protection
• Power save mode
• 3-phase generator sensing and protection
• Generator current and power monitoring (kW, kvar, kVA, pf)
• kW and kvar overload and reverse power alarms
• Over current protection
• Unbalanced load protection
• Breaker control via fascia buttons
• Fuel and start outputs configurable when using CAN
• Support for 0 V to 10 V & 4 mA to 20 mA sensors
• 8 configurable digital inputs (3 available for Customer use)
• 8 configurable digital outputs (5 available for Customer use)
• 4 configurable analogue outputs (3 available for Customer Use)
• CAN, MPU and alternator frequency speed sensing in one variant
• Real time clock
• Engine pre-heat and post-heat functions
• Engine run-time scheduler
• Engine idle control for starting &stopping
• Fuel usage monitor and low fuel level alarms
• 3 configurable maintenance alarms

BENEFITS
• Hours counter provides accurate information for monitoring and maintenance periods
• User-friendly set-up and button layout for ease of use
• Multiple parameters are monitored & displayed simultaneously for full visibility
• The module can be configured to suit a wide range of applications for user flexibility
• PLC editor allows user configurable functions to meet user specific application requirements .
• RS485 Communication port can be used for the Remote Monitoring Communication
(Compatible with Cat PLG)

LEHE2017-01 (11-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
 &-!&  $=> 2

? 8@ 88


    
  

  !   !"#$%!  


 
 
"&   '%   (&) 
'% !* & ("+)  + &$, 
' !* & *%$+ - ( .*)  - !* & (+) 
!& %! &$%!  %&$%!  
&$% '  /     -$ &!! & $0   
# 1# $%$0  -$ &!! & %&#%$ $0    
-#  $0  

 %  $  %-! %& $  (-) 
 %-! $0    2. $ *$ & $  (-) 
'!/ & !& $0 

 $#&"! ! -%'#&$%!   

+-$ $0      $#&"! 1# $%$0 


%' %$%! $0   $#&"!+&' & !     
% 2 $!& $0 
!  &$%-%$%! 0 & 
& - 3+ $. % $ & (% )  %$!  4 &$  '  (-$5% ) 
3 ! &$% ' $%$# (-$) 

% #$&0 #"% #$&0 %$%!




  "
    "#
 


      " !  "#
 


' 
 
 
6

'  $  & $ '% "&.   "&.   /! -#  %  $ - %  $ - 3+ - 3+ - '%
!* & *%$+ ! !* & -- &  -#  ! #$ &  $  $  &  !#$ $ $ 
- (" ) ! #$ (/-)
("-)

# $ %" " &%" % &%  % 
 ' 
 '  % 
 '
       (  ( 
(   ( ( (  (  ( 
(         ( 
      (    (
  (       ( 
  (  (    (  
      (   ( 
 (         
    (      (
          
          (
    (      (

'  $  & $ '% !& !& !& !& * $ %  $ %& '% * $ %  $ %& * $ 3+ ' * $ 3+ /! &0 3+ /!
!* & *%$+ ! !* & !#$ $ &  !#$ $ $  /! -!* !#$ $ * $  -!*  -!* -!* &$ (78 -!* &$
- &$ 3+ ' /! &$ &$  ' -   (78  ' -  
-!* &$ 89:9 % +') 89:9 % +')

# $ %"  % 
 ' ') ') &% &% ' &) ' &)
    ( (    ( (
(    ( (  (  ( 
(      (  (  
     (     
  ( (      (( (
  ( (    ( ((( ( 
      ( (  (( 
 (         
      ((    (
       ((  (( 
    (      (
     (( (  (( ( ((

+
6 &; 6< 
6

'  $  & $ '% & 2 $%! & 2 $%! & 2 $%! 3+#$ -&! !% -&! *!&. !* + $ +%'+ + $
!* & *%$+ ! !* & $! 2. $ $! $! 3+ & !/ &0 !! & -$ &!! & &'0 /# /#
- *$ & $!+ & $! 7- &'0 &'0
"*+,  -. 
 &-!&  $=> 2

? 8@ 88


# $ %"  !&)  !&)  !&)  !&)  !&)  !&)  !&)  !&)  !&)
       (    
(    ((       
(    ( (  (    (
    ( ( (   (  (
  (  ((   ( ( (  (
  ( ( ( ( (    ( (
    ( ( (    (( ((
 (  (       ( 
    ( (( ( (    
   (    (    
   ((( (       
       (  ( ( ((

<AA< A 
6

&$    !$ $% %$ /&%$%!   &

'  $ !* & *%$+ - .* : 7B: 8: 8: :


 & $ ! C  B  8 
'% !* & "+ BD8 B 798 8 9
  / 0 1 &%     
   &%     
  % &%  (   
" )
&%    ( (
  / 0 1 0 $ 1 )& )    ( 
   0 $ 1 )& )     (
  % 0 $ 1 )& )   (  
" )
0 $ 1 )& )  (  ( (
  / 0 1 0 $ 1 "")   (  (
   0 $ 1 "") ( ( (  
  % 0 $ 1 "")   (  
  / 0 1 &%" % ((  (  
   &%" %   ( ( (
  % &%" % (   ( 
" )
&%" %     
  / 0 1 &%   (  
   &%     
  % &%     
" )
&%     

&$    !%  $  &

'  $ !* & *%$+ - .* : 7B: 8: 8: :


 & $ ! C  B  8 
'% !* & "+ BD8 B 798 8 9
  / 0 1 &% (    (
   &% (    
  % &%  (   
   #&%     
" )
&%   (  
  / 0 1 0 $ 1 )& )     (
   0 $ 1 )& )  (  ( 
  % 0 $ 1 )& )     (
" )
0 $ 1 )& )   ( (( (
  / 0 1 0 $ 1 "")     
   0 $ 1 "") (    
  % 0 $ 1 "")   (  
  / 0 1 &%" % (  (  
   &%" %     
  % &%" %  ( (  
" )
&%" %     
  / 0 1 &%  (   (
   &%     ((
  % &% (  ( ( 
   &%   ( ( ((
" )
&% (    (
/

/% $   ( ( (

"*+,  -. 
 &-!&  $=> 2

? 8@ 88

&
6? % 
6<

 $% & 8 8D E 8



!
)    )
!
)
 " 2
  %

" 
 
 % %

 
 
" ( ' "  !"      ' )
!   %
 ")   / %
3)/ ) 3 % 
 

%
 
2

   
 )" 
 % %
 
!  

<6?  ? &
6< $<56
 
F < <6A E '5".* E +&
! 0  '1
"   
 4  5  %4 ( ")4 

  &' 0 $$%! &0 8 E EEEE



!
)    )
!
)
 " 2
  %

" 
 
 % %

 
 
" ( ' "  !"      ' )
!   %
 ")   / %
3)/ ) 3 % 
 

%
 
2

   
 )" 
 % %

)

     
!  

<6?  ? &
6< $<56
 
F < <6A E '5".* E +&
! 0  '1
"     
)

      4  5  %4 ( ")4 

6<6G 
6 
6

$%$# !&& $  !* & "%%$0 ("+)

"% $ 7   D B  9   8 7  !&


! &$% '
$  (-)
  !
0' 1
             
            (( 
         ( (   
             
(       (    (  
           (  
     (    ( ( (  
       (      
     (        
   (   (      (( ((
   (       (   
 (      (      
     (( ( (   ( ( ( 
 (  (     (( ( ( ( ( 
( (     ( ( ( ( ( (( (( (
   ( ( ( ( ( ( (( ( ( ( 

AA & 

$A6 H 66<  <  


  6 < <  G < <  G 6
6  6< <
 G  6< <

/A<    
# "" (  '
(
# "" ((  '
(


 

6 & 



6A & 9DE
 &-!&   -% %$%! 

"
' ) 

'    )
""  4

6+76, 8,9.-9:*6;, <-=,9*6;, >*=?,@ A,=-B *9, 9,89,@,6<*<7>, -. *


<C87;*= 89-D?;<7-6 ,6+76, <,@<,D 76 * ;*=7A9*<,D DC6*:-:,<,9 <,@<
;,== *< 
 @<*6D*9D 9,.,9,6;, ;-6D7<7-6@ *<,987==*9
:*76<*76@ 4 ;,9<7.7,D E?*=7<C :*6*+,:,6< @C@<,:@ .-9
,6+76, <,@< '*;7=7<7,@ <- *@@?9, *;;?9*<, ;*=7A9*<7-6 -. <,@<
,E?78:,6<
6+76, <,@< D*<* 7@ ;-99,;<,D 76 *;;-9D*6;, B7<F 

 DD7<7-6*= 9,.,9,6;, :*<,97*= 


 (  
( 4
 ( 4  (  *6D ( :*C *88=C 76
"*+,  -. 
 &-!&  $=> 2

? 8@ 88

8*9< -9 *9, @7:7=*9 <- 


 8,;7*= ,6+76, 9*<76+ 9,E?,@<
0
1 <,@< D*<* @F*== A, 6-<,D
"
' ) 
" )


 
'  4
"-B,9 & $
-9E?, & $

5F*?@< @<*;G <,:8,9*<?9, & $


6=,< *79.=-B & $
6<*G, :*67.-=D 89,@@?9, +*+, & $

5F*?@< .=-B & $


8,;7.7; .?,= ;-6@?:8<7-6 & $
'?,= 9*<, & $
8,;7.7; 
' ;-6@?:8<7-6 & $

' 9*<, & $
%,*< 9,H,;<7-6 & $
%,*< 9,H,;<7-6 ,5F*?@< -6=C & $
%,*< 9,H,;<7-6 
) -6=C & $
%,*< ,H,;<7-6 >*=?,@ A*@,D -6 ?@76+ <9,*<,D B*<,9
-9E?, 7@ 76;=?D,D .-9 <9?;G *6D 76D?@<97*= *88=7;*<7-6@ D- 6-<
?@, .-9 ,6 ,< -9 @<,*DC @<*<, *88=7;*<7-6@
6   ,6+76,@ *< @8,,D@ -.  ") *6D ?6D,9 <F,@, >*=?,@
*9, 89->7D,D .-9 9,.,9,6;, -6=C *6D :*C 6-< :,,< <F, <-=,9*6;,
=7@<,D
F,@, >*=?,@ D- 6-< *88=C <- & '-9 <F,@, :-D,=@ @,, <F,
<-=,9*6;,@ =7@<,D A,=-B
& %


  
 
'  4
%,*< 9,H,;<7-6 & $
%,*< 9,H,;<7-6 <- <:-@8F,9, & $
%,*< 9,H,;<7-6 <- ?A, 7= & $
%,*< 9,H,;<7-6 <- .<,9;--=,9 & $

 
  !

 
'  4
-9E?, & $
8,,D & $
'?,= .=-B & $
,:8,9*<?9, &   D,+9,,@
6<*G, :*67.-=D 89,@@?9, &  G"*

2


"
' ) 
 

  

'



   '!
    

'


 )"%
  

' 

   )


 ! .-9 :*976, ,6+76,@ *6D   ( .-9 -<F,9
,6+76,@ 9,.,9,6;, *<:-@8F,97; 89,@@?9, 7@  #" 0 76 F+1
*6D @<*6D*9D <,:8,9*<?9, 7@ D,+  0 D,+ '1 *< $ 9,=*<7>,
F?:7D7<C *< <F, @<*<,D *.<,9;--=,9 B*<,9 <,:8 -9 76=,< :*67.-=D
<,:8
' 



6+76, 9*<76+ -A<*76,D *6D 89,@,6<,D 76 *;;-9D*6;, B7<F  (&


*6D 
   ( 9,.,9,6;, *<:-@8F,97; 89,@@?9, 7@ 
#" 0 76 F+1 *6D @<*6D*9D <,:8,9*<?9, 7@ D,+  0 D,+ '1
*< $ 9,=*<7>, F?:7D7<C *6D ) *=<7<?D, *< <F, @<*<,D
*.<,9;--=,9 B*<,9 <,:8,9*<?9,
)
!
)
  '  

)"
 !

-;*<7-6 .-9 *79 <,:8,9*<?9, :,*@?9,:,6< *79 ;=,*6,9 76=,< *<


@<*A7=7I,D -8,9*<76+ ;-6D7<7-6@

'



/%!  # )


F, ,.,9,6;,
5F*?@< <*;G 7*:,<,9 8?A=7@F,D B7<F <F7@ D*<*@,<
7@ -6=C ?@,D .-9 <F, ;*=;?=*<7-6 -. :-G, 8*;7<C >*=?,@ D7@8=*C,D
76 <F7@ D*<*@,< F7@ >*=?, D-,@ 6-< 6,;,@@*97=C 9,89,@,6< <F,
*;<?*= @<*;G D7*:,<,9 -. <F, ,6+76, D?, <- <F, >*97,<C -. ,5F*?@<
@<*;G *D*8<,9 -8<7-6@ *>*7=*A=, -6@?=< <F, 897;, =7@< ,6+76,
-9D,9 -9 +,6,9*= D7:,6@7-6 D9*B76+@ .-9 <F, *;<?*= @<*;G D7*:,<,9
@7I, -9D,9,D -9 -8<7-6@ *>*7=*A=,

'


'!




,.,9,6;, .?,= 7@ J D7@<7==*<, D7,@,= B7<F * " +9*>7<CK
 =-B,9 F,*<76+ >*=?, 7@ ( # &# 0  !&1 BF,6 ?@,D *<
 D,+  0( D,+ '1 BF,9, <F, D,6@7<C 7@
 &7<,9 0 A@&*=1

,.,9,6;, 6*<?9*= +*@ .?,= F*@ * =-B,9 F,*<76+ >*=?, -. ( # &
0  !&! '<1 -B  ! 9*<76+@ *9, A*@,D -6 ( # & 0
 !&! ' 1 =-B,9 F,*<76+ >*=?, +*@ "9-8*6, 9*<76+@ *9, A*@,D -6
 # & 0  !&! '<1 =-B,9 F,*<76+ >*=?, +*@


"
0
1  %


 '%

 "
0 1 


/
 !/  

6+76, ;-99,;<,D +9-@@ -?<8?< 76;=?D,@ <F, 8-B,9 9,E?79,D <- D97>,
@<*6D*9D ,E?78:,6<K =?A, -7= @;*>,6+, =?A, -7= .?,= <9*6@.,9
;-::-6 9*7= .?,= @,8*9*<, ;79;?7< *.<,9;--=,9 *6D H*;G,< B*<,9
8?:8@
6+76, 6,< 8-B,9 *>*7=*A=, .-9 <F, ,5<,96*= 0.=CBF,,=1
=-*D 7@ ;*=;?=*<,D AC @?A<9*;<76+ <F, @?: -. *?57=7*9C =-*D .9-:
<F, ;-99,;<,D +9-@@ .=CBF,,= -?< 8?< 8-B,9 C87;*= *?57=7*9C
=-*D@ *9, 9*D7*<-9 ;--=76+ .*6@ FCD9*?=7; 8?:8@ *79 ;-:89,@@-9@
*6D A*<<,9C ;F*9+76+ *=<,96*<-9@ '-9 7,9 ( 9*<76+@ *DD7<7-6*=
"*9*@7<7; =-@@,@ B-?=D *=@- 76;=?D, 6<*G, *6D
5F*?@<
,@<97;<7-6@
  !
" 
=<7<?D, ;*8*A7=7<C 7@ <F, :*57:?: *=<7<?D, *A->, @,* =,>,= *<
@<*6D*9D <,:8,9*<?9, *6D @<*6D*9D 89,@@?9, *< BF7;F <F, ,6+76,
;-?=D D,>,=-8 .?== 9*<,D -?<8?< 8-B,9 -6 <F, ;?99,6< 8,9.-9:*6;,
"*+, ( -. 
 &-!&  $=> 2

? 8@ 88

D*<* @,<
<*6D*9D <,:8,9*<?9, >*=?,@ >,9@?@ *=<7<?D, ;-?=D A, @,,6 -6
)
F,6 >7,B76+ <F, *=<7<?D, ;*8*A7=7<C ;F*9< <F, *:A7,6< <,:8,9*<?9,
7@ <F, 76=,< *79 <,:8 *< <F, ;-:89,@@-9 76=,<

6+76,@ B7<F 
) )
! *6D %
! .?,= @C@<,:@ -8,9*<76+ *<
;-6D7<7-6@ *A->, <F, D,.76,D *=<7<?D, ;*8*A7=7<C D,9*<, .-9
*<:-@8F,97; 89,@@?9, *6D <,:8,9*<?9, ;-6D7<7-6@ -?<@7D, <F, >*=?,@
D,.76,D @,, )
),;F*67;*= +->,96-9 ;-6<9-==,D ?67< 76H,;<-9 ,6+76,@ 9,E?79, *
@,<<76+ ;F*6+, .-9 -8,9*<7-6 *< ;-6D7<7-6@ *A->, <F, *=<7<?D,
D,.76,D -6 <F, ,6+76, 8,9.-9:*6;, @F,,< ,, C-?9 *<,987==*9
<,;F67;*= 9,89,@,6<*<7>, .-9 6-6 @<*6D*9D 9*<76+@

!     " ! )" 

)
:7@@7-6@ 76.-9:*<7-6 7@ 89,@,6<,D *< L6-:76*=L *6D L"-<,6<7*=
7<, 2*97*<7-6L >*=?,@ .-9 @<*6D*9D 9*<76+@ - <-=,9*6;,@ *9,
*88=7,D <- <F, ,:7@@7-6@ D*<* F,@, >*=?,@ *9, @?AH,;< <- ;F*6+,
*< *6C <7:, F, ;-6<9-==76+ .,D,9*= *6D =-;*= ,:7@@7-6
9,E?79,:,6<@ 6,,D <- A, >,97.7,D AC C-?9 *<,987==*9 <,;F67;*=
9,89,@,6<*<7>,
?@<-:,9L@ :*C F*>, @8,;7*= ,:7@@7-6 @7<, 9,E?79,:,6<@ <F*< 6,,D
<- A, >,97.7,D AC <F, *<,987==*9 "9-D?;< 9-?8 ,6+76,,9

) 
) 4
C;=, ,:7@@7-6@ )*5 7:7<@ *88=C <- ;C;=, B,7+F<,D *>,9*+,@ -6=C

:7@@7-6@ *< 76D7>7D?*= =-*D 8-76<@ :*C ,5;,,D <F, ;C;=, B,7+F<,D
=7:7<

)  
'   4

:7@@7-6@ 4 )

) 

'   
 '-9 ;-6@<*6< @8,,D :*976, ,6+76,@ .-9 @F78 :*76 89-8?=@7-6
76;=?D76+D7,@,= ,=,;<97; D97>, <,@< ;C;=,
 @F*== A, *88=7,D
.-9 ;-6<9-==*A=, 87<;F 89-8,==,9 @,<@
<,@< ;C;=,
 @F*== A, *88=7,D
 '-9 89-8,==,9 =*B -8,9*<,D :*76 *6D 89-8,==,9 =*B -8,9*<,D
*?57=7*9C ,6+76,@ <F, <,@< ;C;=,
 @F*== A, *88=7,D
 '-9 ;-6@<*6< @8,,D *?57=7*9C ,6+76,@ <,@< ;C;=,  @F*== A,
*88=7,D
( '-9 >*97*A=, @8,,D >*97*A=, =-*D *?57=7*9C ,6+76,@ 6-<
76;=?D,D *A->, <,@< ;C;=,  @F*== A, *88=7,D
%


  
'   4
7,@,= 79;?7< C8, *6D %%2 *=*6;, 4 )
%% "
)
0%1 
'   4
4
)
   
'   4
+97;?=<?9, 4 )
'79, "?:8 4 )
,6,9*<-9 ,< 4 )
,6,9*<-9 0*@1 4 )(
6D?@<97*= 7,@,= 4 )
6D?@<97*= 0*@1 4 )(
997+*<7-6 4 )(
-;-:-<7>, 4 )
)*976, ?57=7*9C 4 )
)*976, "9-8 0
5;,8< 1 4 )(
)*976, "9-8 0 -6=C1 4 )(
)% 4 )(
7= '7,=D 0",<9-=,?:1 4 )
.. %7+FB*C 9?;G 4 )
6 %7+FB*C 9?;G 4 )
!  
'   4
-?6D "-B,9 4 )
-?6D "9,@@?9, 4 )
*<, ,=,*@,D 4 &&

"*+,  -. 
1/21/2020 Package Data Display

P D [C15DEPB] J 21, 2020


For Help Desk Phone Numbers Click here
Feature Code: C15DEPB Rating Type: STANDBY Sales model Package: D500GC
Engine Sales Model: C15 Engine Arrangement Number: 4206876 Hertz: 60
EKW W/F: 500.0 Noise Reduction: 0 dBA Back Pressure: 0.0 inH2O

Engine Package Information

Engine Package Data

Package Cooling Information

SA Level 2 Canopy Cooling Data


Airflow Ambient Ambient Ambient Ambient
%
Rate Capability Sea Capability 300 Capability 600 Capability 900
Load
scfm Level (Deg F) m (Deg F) m (Deg F) m (Deg F)
100.0 17692 122 118 114 111
75.0 17692 141 138 134 131
50.0 17692 159 156 152 149
25.0 17692 179 176 172 168

Package Sound Information

Sound Comments :

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&type=RNTMIRefNum&refno=&selection=&unitType=&system=tmiweb 1/3
1/21/2020 Package Data Display

Open Sound Data


Distance: 3.3 Feet
OVERALL OBCF OBCF OBCF OBCF OBCF OBCF OBCF OBCF
EKW %
SOUND 63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ 8000HZ
W/F LOAD
DB(A) DB DB DB DB DB DB DB DB
500.0 100.0 105.0 102.0 95.0 99.0 98.0 100.0 98.0 93.0 100.0
375.0 75.0 104.0 101.0 94.0 99.0 98.0 99.0 96.0 92.0 97.0

Distance: 23.0 Feet


OVERALL OBCF OBCF OBCF OBCF OBCF OBCF OBCF OBCF
EKW %
SOUND 63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ 8000HZ
W/F LOAD
DB(A) DB DB DB DB DB DB DB DB
500.0 100.0 95.0 92.0 85.0 89.0 88.0 90.0 88.0 83.0 90.0
375.0 75.0 94.0 91.0 84.0 89.0 88.0 89.0 86.0 82.0 87.0

Distance: 49.2 Feet


OVERALL OBCF OBCF OBCF OBCF OBCF OBCF OBCF OBCF
EKW %
SOUND 63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ 8000HZ
W/F LOAD
DB(A) DB DB DB DB DB DB DB DB
500.0 100.0 89.0 86.0 79.0 83.0 82.0 84.0 82.0 77.0 84.0
375.0 75.0 88.0 85.0 78.0 83.0 82.0 83.0 80.0 76.0 81.0

SA Level 2 Canopy Sound Data


Distance: 3.3 Feet
OVERALL OBCF OBCF OBCF OBCF OBCF OBCF OBCF OBCF
EKW %
SOUND 63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ 8000HZ
W/F LOAD
DB(A) DB DB DB DB DB DB DB DB
500.0 100.0 82.2 95.7 89.7 86.3 76.6 74.0 68.4 65.0 73.3
375.0 75.0 81.0 93.7 86.9 85.1 76.6 73.0 66.9 63.5 71.4
250.0 50.0 80.1 91.5 85.0 84.5 76.4 72.5 65.9 62.1 67.2
125.0 25.0 79.6 89.1 83.9 84.5 76.0 72.4 65.3 60.9 60.8

Distance: 23.0 Feet


OVERALL OBCF OBCF OBCF OBCF OBCF OBCF OBCF OBCF
EKW %
SOUND 63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ 8000HZ
W/F LOAD
DB(A) DB DB DB DB DB DB DB DB
500.0 100.0 72.6 89.4 80.8 78.2 66.6 64.4 59.4 55.1 61.2
375.0 75.0 71.5 87.2 78.6 78.5 66.1 62.7 57.0 52.8 58.9
250.0 50.0 70.6 85.2 77.1 77.9 65.6 61.7 55.4 51.1 55.0
125.0 25.0 69.9 83.4 76.2 76.5 65.2 61.4 54.7 50.0 49.6

Distance: 49.2 Feet


OVERALL OBCF OBCF OBCF OBCF OBCF OBCF OBCF OBCF
EKW %
SOUND 63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ 8000HZ
W/F LOAD
DB(A) DB DB DB DB DB DB DB DB
500.0 100.0 66.6 83.4 74.8 72.2 60.6 58.4 53.4 49.1 55.2

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&type=RNTMIRefNum&refno=&selection=&unitType=&system=tmiweb 2/3
1/21/2020 Package Data Display
375.0 75.0 65.5 81.2 72.6 72.5 60.1 56.7 51.0 46.8 52.9
250.0 50.0 64.6 79.2 71.1 71.9 59.6 55.7 49.4 45.1 49.0
125.0 25.0 63.9 77.4 70.2 70.5 59.2 55.4 48.7 44.0 43.6

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&type=RNTMIRefNum&refno=&selection=&unitType=&system=tmiweb 3/3
1/22/2020 Caterpillar Generator Data

G D J 22, 2020
For Help Desk Phone Numbers Click here

Selected Model
Engine: C15 Generator Frame: M3154L4 Genset Rating (kW): 500.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 5652331 Genset Rating (kVA): 625.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 751.8
Duty: STANDBY Connection: - STAR Application: EPG Status: Current
Version: 42423 /43607 /43655 /8556

Spec Information
Generator Specification
Generator Efficiency
Frame: M3154L4 Type: SR500 No. of Bearings: 1
Per Unit Load kW Efficiency %
Winding Type: RANDOM WOUND Flywheel: 14.0
0.25 125.0 93.3
Connection: - STAR Housing: 1
0.5 250.0 95.2
Phases: 3 No. of Leads: 6
0.75 375.0 95.4
Poles: 4 Wires per Lead: 0
1.0 500.0 95.1
Sync Speed: 1800 Generator Pitch: 0.6667

Reactances Per Unit Ohms


SUBTRANSIENT - DIRECT AXIS X''d 0.1161 0.0428
SUBTRANSIENT - QUADRATURE AXIS X''q 0.1571 0.0579
TRANSIENT - SATURATED X'd 0.1657 0.0611
SYNCHRONOUS - DIRECT AXIS Xd 2.9397 1.0837
SYNCHRONOUS - QUADRATURE AXIS Xq 1.4993 0.5527
NEGATIVE SEQUENCE X2 0.1364 0.0503
ZERO SEQUENCE X0 0.0068 0.0025

Time Constants Seconds


OPEN CIRCUIT TRANSIENT - DIRECT AXIS T'd0 1.7735
SHORT CIRCUIT TRANSIENT - DIRECT AXIS T'd 0.1000
OPEN CIRCUIT SUBSTRANSIENT - DIRECT AXIS T''d0 0.0142
SHORT CIRCUIT SUBSTRANSIENT - DIRECT AXIS T''d 0.0100
OPEN CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T''q0 0.0955
SHORT CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T''q 0.0100
EXCITER TIME CONSTANT Te 0.0220
ARMATURE SHORT CIRCUIT Ta 0.0150

Short Circuit Ratio: 0.4 Stator Resistance = 0.0087 Ohms Field Resistance = 0.5791 Ohms
Voltage Regulation Generator Excitation
Voltage level adjustment: +/- 5.0% No Load Full Load, (rated) pf
Voltage regulation, steady state: +/- 1.0% Series Parallel
Voltage regulation with 3% speed change: +/- 1.0% Excitation voltage: 10.64 Volts 46.58 Volts Volts
Waveform deviation line - line, no load: less than 2.0% Excitation current 1.0 Amps 3.6 Amps Amps
Telephone influence factor: less than 50

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 1/9
1/22/2020 Caterpillar Generator Data
Selected Model
Engine: C15 Generator Frame: M3154L4 Genset Rating (kW): 500.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 5652331 Genset Rating (kVA): 625.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 751.8
Duty: STANDBY Connection: - STAR Application: EPG Status: Current
Version: 42423 /43607 /43655 /8556

Generator Mechanical Information


Center of Gravity
Dimension X -511.0 mm -20.1 IN.
Dimension Y 0.0 mm 0.0 IN.
Dimension Z 0.0 mm 0.0 IN.
"X" is measured from driven end of generator and parallel to rotor. Towards engine
fan is positive. See General Information for details
"Y" is measured vertically from rotor center line. Up is positive.
"Z" is measured to left and right of rotor center line. To the right is positive.

Generator WT = 1240 kg * Rotor WT = 496 kg * Stator WT = 744 kg


2,734 LB 1,093 LB 1,640 LB

Rotor Balance = 0.0 mm deflection PTP


Overspeed Capacity = 125% of synchronous speed

Generator Torsional Data

J1 = Coupling J2 = Rotor J3 = Exciter


and Fan TOTAL J = J1 + J2 + J3 End
K1 = Shaft Stiffness between K2 = Shaft Stiffness between
J1 + J2 (Diameter 1) J2 + J3 (Diameter 2)
J1 K1 Min Shaft Dia 1 J2 K2 Min Shaft Dia 2 J3
17.5 LB IN. s2 52.0 MLB IN./rad 4.2 IN. 49.1 LB IN. s2 36.1 MLB IN./rad 4.5 IN. 1.9 LB IN. s2
1.979 N m s2 5.87638 MN m/rad 106.0 mm 5.546 N m s2 4.08 MN m/rad 115.0 mm 0.216 N m s2
Total J
68.5 LB IN. s2
7.741 N m s2

Selected Model
Engine: C15 Generator Frame: M3154L4 Genset Rating (kW): 500.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 5652331 Genset Rating (kVA): 625.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 751.8
Duty: STANDBY Connection: - STAR Application: EPG Status: Current
Version: 42423 /43607 /43655 /8556

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 2/9
1/22/2020 Caterpillar Generator Data

Generator Cooling Requirements -


Temperature - Insulation Data
Cooling Requirements: Temperature Data: (Ambient 40 0C)
Heat Dissipated: 25.8 kW Stator Rise: 105.0 0C
Air Flow: 66.0 m3/min Rotor Rise: 105.0 0C
Insulation Class: H
Insulation Reg. as shipped: 100.0 MΩ minimum at 40 0C

Thermal Limits of Generator


Frequency: 60 Hz
Line to Line Voltage: 480 Volts
B BR 80/40 552.0 kVA
F BR -105/40 627.9 kVA
H BR - 125/40 690.0 kVA
F PR - 130/40 690.0 kVA
H PR - 150/40 731.4 kVA
H PR27 - 163/27 759.0 kVA

Selected Model
Engine: C15 Generator Frame: M3154L4 Genset Rating (kW): 500.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 5652331 Genset Rating (kVA): 625.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 751.8
Duty: STANDBY Connection: - STAR Application: EPG Status: Current
Version: 42423 /43607 /43655 /8556

Starting Capability & Current Decrement


Motor Starting Capability (0.6 pf)

Percent
SKVA
Volt Dip
61 2.5
125 5.0
193 7.5
264 10.0
340 12.5
420 15.0
504 17.5
594 20.0
690 22.5
793 25.0
902 27.5
1,019 30.0
1,145 32.5
1,280 35.0
1,427 37.5
1,585 40.0

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 3/9
1/22/2020 Caterpillar Generator Data
Current Decrement Data

E Time
AMP
Cycle
0.0 6,441
1.0 4,242
2.0 3,372
3.0 2,821
4.0 2,385
5.0 2,017
7.5 1,316
10.0 845
12.5 529
15.0 346
20.0 190
25.0 135
30.0 115
35.0 106
40.0 102
45.0 101

Instantaneous 3 Phase Fault Current: 6441 Amps Instantaneous Line - Line Fault Current: 5126 Amps
Instantaneous Line - Neutral Fault Current: 8645 Amps

Selected Model
Engine: C15 Generator Frame: M3154L4 Genset Rating (kW): 500.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 5652331 Genset Rating (kVA): 625.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 751.8
Duty: STANDBY Connection: - STAR Application: EPG Status: Current
Version: 42423 /43607 /43655 /8556

Generator Output Characteristic Curves


Open Circuit Curve

Field Line -
Current Line Volt
0.0 0
12.7 288
14.8 336
17.0 384
19.2 432
21.5 480
23.9 528
26.6 576
29.6 624
33.3 672

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 4/9
1/22/2020 Caterpillar Generator Data
Short Circuit Curve

Field Armature
Current Current
0.0 0
37.2 451
43.3 526
49.5 601
55.7 677
61.9 752
68.1 827
74.3 902
80.5 977
86.7 1,052

Selected Model
Engine: C15 Generator Frame: M3154L4 Genset Rating (kW): 500.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 5652331 Genset Rating (kVA): 625.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 751.8
Duty: STANDBY Connection: - STAR Application: EPG Status: Current
Version: 42423 /43607 /43655 /8556

Generator Output Characteristic Curves


Zero Power Factor Curve

Field Line -
Current Line Volt
61.9 0
75.5 240
77.7 288
79.9 336
82.2 384
84.6 432
87.2 480
90.0 528
93.4 576
97.7 624

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 5/9
1/22/2020 Caterpillar Generator Data
Air Gap Curve

Field Line -
Current Line Volt
0.0 0
12.6 288
14.7 336
16.8 384
18.9 432
21.1 480
23.2 528
25.3 576
27.4 624
29.5 672

Selected Model
Engine: C15 Generator Frame: M3154L4 Genset Rating (kW): 500.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 5652331 Genset Rating (kVA): 625.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 751.8
Duty: STANDBY Connection: - STAR Application: EPG Status: Current
Version: 42423 /43607 /43655 /8556

Reactive Capability Curve

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 6/9
1/22/2020 Caterpillar Generator Data

Selected Model
Engine: C15 Generator Frame: M3154L4 Genset Rating (kW): 500.0 Line Voltage: 480
Fuel: Diesel Generator Arrangement: 5652331 Genset Rating (kVA): 625.0 Phase Voltage: 277
Frequency: 60 Excitation Type: Self Excited Pwr. Factor: 0.8 Rated Current: 751.8
Duty: STANDBY Connection: - STAR Application: EPG Status: Current
Version: 42423 /43607 /43655 /8556

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 7/9
1/21/2020 TMIWEB Production(a24-tc8-jdk8-tmi-prod)

January 21, 2020


Systems Data For Help Desk Phone Numbers
Reference Number: DM8155 Click Here

AIR INTAKE SYSTEM


THE INSTALLED SYSTEM MUST COMPLY WITH THE SYSTEM LIMITS BELOW FOR ALL EMISSIONS CERTIFIED ENGINES
TO ASSURE REGULATORY COMPLIANCE.
MAXIMUM ALLOWABLE INTAKE RESTRICTION WITH CLEAN
15 IN-H20
ELEMENT
MAXIMUM ALLOWABLE INTAKE RESTRICTION WITH DIRTY
25 IN-H20
ELEMENT
MAXIMUM PRESSURE DROP FROM COMPRESSOR OUTLET TO
4.4 IN-HG
MANIFOLD INLET (OR MIXER INLET FOR EGR)
COOLING SYSTEM
ENGINE ONLY COOLANT CAPACITY 5.5 GAL
MAXIMUM ALLOWABLE JACKET WATER OUTLET TEMPERATURE 219 DEG F
REGULATOR LOCATION FOR JW (HT) CIRCUIT OUTLET
MAXIMUM UNINTERRUPTED FILL RATE 5.0 G/MIN
ENGINE SPEC SYSTEM
CYLINDER ARRANGEMENT INLINE
NUMBER OF CYLINDERS 6
CYLINDER BORE DIAMETER 5.4 IN
PISTON STROKE 6.7 IN
TOTAL CYLINDER DISPLACEMENT 928 CU IN
STANDARD CRANKSHAFT ROTATION FROM FLYWHEEL END CCW
STANDARD CYLINDER FIRING ORDER 1-5-3-6-2-4
NUMBER 1 CYLINDER LOCATION FRONT
STROKES/COMBUSTION CYCLE 4
EXHAUST SYSTEM
THE INSTALLED SYSTEM MUST COMPLY WITH THE SYSTEM LIMITS BELOW FOR ALL EMISSIONS CERTIFIED ENGINES
TO ASSURE REGULATORY COMPLIANCE.
MAXIMUM ALLOWABLE SYSTEM BACK PRESSURE 40 IN-H20
MANIFOLD TYPE DRY
FUEL SYSTEM
MAXIMUM FUEL FLOW FROM TRANSFER PUMP TO ENGINE 69.2 G/HR
MAXIMUM ALLOWABLE FUEL SUPPLY LINE RESTRICTION 8.0 IN-HG
MAXIMUM ALLOWABLE FUEL TEMPERATURE AT TRANSFER PUMP
140 DEG F
INLET
MAXIMUM ALLOWABLE FUEL RETURN LINE RESTRICTION 14.8 IN-HG
NORMAL FUEL PRESSURE IN A CLEAN SYSTEM 90.1 PSI
FUEL SYSTEM TYPE MEUI
MAXIMUM TRANSFER PUMP PRIMING LIFT WITHOUT PRIMING
12.1 FT
PUMP
MAXIMUM ALLOWABLE FUEL TEMPERATURE AT ENGINE OUTLET 225 DEG F
LUBE SYSTEM
CRANKCASE VENTILATION TYPE TO_ATMOSPHERE

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&type=RNTMIRefNum&refno=&selection=&unitType=&system=tmiweb 1/2
1/21/2020 TMIWEB Production(a24-tc8-jdk8-tmi-prod)

MOUNTING SYSTEM
CENTER OF GRAVITY LOCATION - X DIMENSION - FROM REAR
22.2 IN
FACE OF BLOCK - (REFERENCE TM7077)
CENTER OF GRAVITY LOCATION - Y DIMENSION - FROM
9.4 IN
CENTERLINE OF CRANKSHAFT - (REFERENCE TM7077)
CENTER OF GRAVITY LOCATION - Z DIMENSION - FROM
0 IN
CENTERLINE OF CRANKSHAFT - (REFERENCE TM7077)
STARTING SYSTEM
MINIMUM CRANKING SPEED REQUIRED FOR START 115 RPM
LOWEST AMBIENT START TEMPERATURE WITHOUT AIDS 32 DEG F

https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&type=RNTMIRefNum&refno=&selection=&unitType=&system=tmiweb 2/2
AUTOMATIC VOLTAGE REGULATOR

D350 AVR
The D350, Digital Voltage Regulator is used to regulate
alternators with a field current of less than 5 A in continuous
operations, and 10 A maximum in the event of short-circuit
for 10 seconds maximum.

Its design is in accordance with mounting in a generator


terminal box or a control cabinet. It is required, at a
minimum, to follow the local protection and safety standards,
especially those specific to electrical installations for
voltages of 300 VAC phase-to-neutral maximum.

NFLink™ configuration module


The D350 is equipped with NFC technology for communication and configuration purposes. The
configuration module is placed over the two dedicated positioning holes on the plastic enclosure as shown
below. Once the configuration is done, the NF Link must be removed as it is not supposed to be left on the

LEHE1923-00
AUTOMATIC VOLTAGE REGULATOR

Technical characteristics
D350 regulator can be used to perform the following functions:

Voltage regulation

• With or without reactive droop compensation (Reactive droop to allow parallel operation)
• With or without line droop compensation.

Regulation of the field current, or manual mode, which allows direct control of the field current.

The D350 can also be used to:

• Adjust the reference for the regulation mode in progress, using an analogue input (0-10V
• and potentiometer)
• Monitoring of temperature sensor (Pt100 or CTP)
• Limit the minimum field current delivered to the exciter field
• Monitoring of the maximum stator current limit
• Loss of voltage sensing
• Withstand a sudden short-circuit for 10 seconds maximum in AREP, PMG
• Signals monitoring (events logger).
• 2 digital outputs for various trip, regulation mode and measurement data

Alternator voltage sensing:


• 3 phases without neutral, 2 phases or 1 phase with neutral
• Three-phase range 0-530VAC
• Consumption < 2VA

Stator current measurement with CT:


• Range 0-1A or 0-5A
• Consumption < 2VA

Power supply:
• 4 terminals for PMG, AREP, SHUNT
• Range 50-277 VAC
• Consumption max < 3000VA

Field excitation:
• Rated 0-5 A
• Short-circuit 10A max.
• Field winding resistance > 4 ohms

Frequency:
• Range 10-100Hz

LEHE1923-00
AUTOMATIC VOLTAGE REGULATOR
• Regulation accuracy: +/-0.25% of the average of the three phases on a linear load, with
harmonic distortion less than 5%
• Voltage adjustment range: 0 to 150% of the rated voltage
• Quadrature droop adjustment range: -20% to 20%
• Under frequency protection: integrated, adjustable threshold, slope adjustable from 0.5 to
3V/Hz in steps of 0.1 V/Hz
• Excitation ceiling: adjustable by configuration at 3 points
• Environment: ambient temperature from -40°C to +65°C, relative humidity of less than 95%
non-condensing, mounted in a cabinet or in a terminal box

Easy Reg Advanced:


• All the D350 settings are entered / configured using the "EasyReg Advanced" software.
• This program is only compatible with computers running WINDOWS® versions
Windows 7 and Windows 10 operating systems.

Dimensions:
• Height : 52.9mm
• width : 125mm
• Length : 140mm

Mounting:
• Holes spacing on the Length : 115mm
• Holes spacing on the width: 100mm

Weight: 0.45kg

Conformity to standards
• EMC: IEC 61000-6-2, IEC 61000-6-4
• Humidity: IEC 60068-1 and test in accordance with IEC 60068-2-14
• Dry heat: IEC 60068-2-2
• Damp heat: IEC 60028-2-30
• Cold: IEC 600068-2-1

LEHE1923-00
AUTOMATIC VOLTAGE REGULATOR
D350 AVR and NFLink™ Dimensions

LEHE1923-00 (05-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos,
“Caterpillar Yellow”, the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Circuit Breakers
C9 ACERT TM, C13 ACERT, C15 ACERT,
C18 ACERT Circuit Breakers
Manually Operated Circuit Breakers
Current Fram e Num ber Interrupting Ratings (kA rm s)
(A) of Poles Trip (Lugs) Cable Size
Auxiliary Options
240V 480V 600V Units Range / Phase

100 H 3 65 35 18 8-30 AWG


Electronic Form C (1NO + 1NC)
LSI (2) 3/0 – 250 Shunt Trip 24VDC
250 J 3 65 35 18 kcmil
(2) 3/0 – 250 1 Form C + 1 Bell Alarm
400 T5N 3 65 25 18
kcmil 250VAC/VDC
Electronic (3) 2/0 – 400 Shunt Trip 24VDC
600 T6N 3 65 35 20 LS/I kcmil
(S or I)
(3) 2/0 – 400 1 Form C + 1 Bell Alarm
800 T6N 3 65 35 20 or
LSI kcmil 400VAC / 250VDC
1200 T7S 3 65 50 25 (4) 2/0 – 500 Shunt Trip 24VDC
kcmil

1600 R 3 65 35 18 BUS BAR

2000 R 3 65 35 18 BUS BAR


Electronic Form C (1NO + 1NC)
LSI Shunt Trip 24VDC
2500 R 3 65 35 18 BUS BAR

BUS BAR
3000 R 3 65 35 18

Electrically Operated Circuit Break ers


Current Fram e Num ber Interrupting Ratings (kA rm s) (Lugs) Cable
(A) of Poles Trip
Size Range / Auxiliary Options
240V 480V 600V Units
Phase
Electronic (4) 4/0 – 500 kcmil 2 Form C + 1 Bell Alarm
800 T 7M-S 3 65 50 25 LSI 24VDC

Electronic (4) 4/0 – 500 kcmil 2 Form C + 1 Bell Alarm


1200 T 7M-S 3 65 50 25
LSI 24VDC
Electronic BUS BAR 2 Form C + 1 Bell Alarm
2000 T8M-S 3 125 125 100 LSI 24VDC

Electronic BUS BAR 2 Form C + 1 Bell Alarm


3000 T8M-S 3 125 125 100 LSI 24VDC

LEHE0942-05 1/17
Circuit Breakers
Single Breaker Options (250 – 3000A)
Model Current (A) Operation

C9 ACERT™ 250 Manually Operated

C9 ACERT 400 Manually Operated

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 600 Manually Operated

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 800 Manually Operated or Electrically Operated

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 1200 Manually Operated or Electrically Operated

C13 ACERT, C15 ACERT, C18 ACERT 1600 Manually Operated

C15 ACERT, C18 ACERT 2000 Manually Operated or Electrically Operated

C18 ACERT 2500 Manually Operated

C18 ACERT 3000 Manually Operated or Electrically Operated

Multiple Breaker Options


Model Main Breaker Box Auxiliary Box
1st Breaker 2nd Breaker Breaker
(Am ps) (Am ps) (Am ps)
Manually Manually Manually Operated
Operated Operated

C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 250 250, 400, 600,
800, or 1200 3rd Breaker:
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 400
250 or 400 (Not
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 600
available if
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 800 1st & 2nd Breaker =
1200A)
C9 ACERT, C13 ACERT, C15 ACERT, C18 ACERT 1200

C13 ACERT, C15 ACERT, C18 ACERT 1600

C15 ACERT, C18 ACERT 2000


2nd Breaker:
Not Available
C18 ACERT 2500 250 or 400

C18 ACERT 3000

LEHE0942-05 2/17
Circuit Breakers

L EHE0942-05 3/17
Circuit Breakers

L EHE0942-05 4/17
Circuit Breakers
J-Frame 250 A Typical Peak Let-Through Curves

Figure 1

LEHE0942-05 5/17
Circuit Breakers
J-Frame 150-250 A (JD, JG, JJ, JL, and JR) Thermal-Magnetic
Trip

Figure 2

LEHE0942-05 6/17
Circuit Breakers
Ground Fault Module GFM250JD Trip Curve

Figure 3

LEHE0942-05 7/17
Circuit Breakers
T6 600 / 800 -PR221DS

LEHE0942-05 8/17
Circuit Breakers
T6 600 / 800 -PR221DS

LEHE0942-05 9/17
Circuit Breakers
Tmax T7 PR231/P Functions
L-S Functions

Figure 7

LEHE0942-05 10/17
Circuit Breakers
T6 800 - PR222DS and PR222DS/PD-A

LEHE0942-05 11/17
Circuit Breakers
T7 1000/1200 - PR232/P

Figure 9

LEHE0942-05 12/17
Circuit Breakers
T7 1000/1200 - PR332/P
L-S-I Functions

Figure 10

LEHE0942-05 13/17
Circuit Breakers
T8 1600/2000/2500/3000 – PR232/P-T8
L-S-I Functions

Figure - 11

LEHE0942-05 14/17
Circuit Breakers
P, R, NS-Frame Long-Short Trip Curve and NW-Frame Long-
Short Trip Curve

Figure - 12

LEHE0942-05 15/17
Circuit Breakers
P, R, NS-Frame Instant Curve and NW-Frame Instant Trip Curve

Figure 13

LEHE0942-05 16/17
Circuit Breakers
P, R, NS-Frame Ground Curve and NW-Frame Ground Fault Trip Curve

Figure - 14

LEHE0942-05 (10-19)

www.Ca t.com/electricpower
©2019 Caterpillar. All rights reserved. Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, ADEM, S•O•S, LET’S DO THE WORK, “Caterpillar Yellow”,
the “Power Edge” trade dress as well ascorporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
17/17
Note : The Information on this Document comesfroma Third Party Sup plier and isnot a Caterpillar Material
Attachments
AC SUPPLY
VOLTAGE RANGE 90 V to 305 V (L-N)

FREQUENCY RANGE
48 Hz to 64 Hz (L-N)

DC OUTPUT RATING
10 A DC at 24 V DC

RIPPLE AND NOISE


<1%

EFFICIENCY
>86%

REGULATION LINE
Image shown might not reflect actual configuration <0.5%

BATTERY CHARGER LOAD


2%
The intelligent battery charger has been developed with safety, usability, optimised TEMPERATURE SENSOR INPUT
battery performance and maximum battery lifetimes in mind. PT1000

A comprehensive range of input and output protections ensures a continued safe PROTECTIONS
charging environment also enabling the use of the charger as a power supply. Short Circuit
DC Over Voltage
DC Over Current
Reverse Polarity
FEATURES Over Temperature
• Intelligent two, three and four stage charging profiles AC Under & Over Voltage
• Configurable to suit most battery types (12V/24V)
• Adjustable current limit CHARGE FAILURE RELAY
3 A at 30 V DC volt free relay
• Can be used as a battery charger, power supply or both at the same time
• Automatic or Manual boost and storage charge functions to help maintain battery condition
DIMENSIONS OVERALL
• Digital Microprocessor Technology
70 mm x200 mm x 130 mm
• Temperature compensation for battery charging
2.7” x 7.9” x 5.1”
• Low Output Ripple and superb line regulation
• Three LED Indicators WEIGHT
• AC input Under voltage 0.75 kg
• AC input Over voltage
• Battery charger output Over voltage OPERATING TEMPERATURE RANGE
• Battery charger output Over current -30 °C to +80 °C
• Optional battery temperature compensation with over temperature protection -22 °F to +176 °F
• Output short circuit and Inversion polarity with auto recovery
• Configurable charge termination STORAGE TEMPERATURE RANGE
-40 °C to +70 °C
Automatic Boost Mode -22 °F to +158 °F
• Boosts and equalises cell charge improving battery performance and life

Power Save Mode


• Once the battery is fully charged the chargers switch to Eco-Power to save energy

Communication
• Can be integrated into external systems through MODBUS RTU using RS485
• Fully configurable via PC Software
• External remote LCD option

BENEFITS
• Fully flexible to maximise the life of the battery
• Suitable for a wide range of battery types
• Switched mode design
BENEFITS
• Minimum 86% efficiency throughout full operating range
• No external intervention for boost mode
• Multiple chargers can be linked together to provide larger current output
• Can be permanently connected to battery and mains (utility) supply. No need to disconnect
through high load conditions.

LEHE2022-01 (09-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Attachments

Jacket Water Heater (WHHH01)


Appropriate when the generator set is to be
sited in a low ambient environment, the heater
maintains the engine coolant at a temperature
[typically 38°C (100°F)] which facilitates rapid
starting and load acceptance. The heater
assembly uses UL compliant components (to
UL1030) and has CSA certification which is to
both CSA and UL Standards.
The heater itself is powered by a 240V for 60 Hz
AC auxiliary supply. A thermostatic controller is
included to regulate the output temperature to
within safe limits. When the generator set is not
running the heater is automatically connected to
the AC supply through a power relay mounted in
the control panel.

Features
• Uniform heat distribution
• Reduces wear from cold spots
• Improves startability
• Thermostatically controlled and protected
• 6’ (1.8m) cord
• Ensures generator is at optimal starting temperature and ready to accept load
• Durable pump with non-magnetic impeller that does not attract metal debris
• Robust die cast aluminum housing improves sealing of the hoses, eliminates leaking and breakage
• Corrosion resistant steel brackets for superior strength and durability
• Reduces thermal stress on coolant hoses
• Element designed for long life with maximum heat transfer
• IP44 Ingress Protection Rating
• No evaporation of coolant from hoses
• Reduces low coolant level alarms because coolant does not boil

Regulating Safety
Part No Outlet Location Watts Volts Amps Thermostat Thermostat
On 90°F (32°C)
577-1758/577-9355 Right 2700 240 11.25 Off 115°F (46°C) 210°F (98°C)

www.cat.com/electricpower
©2019 Caterpillar
All rights reserved.

Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Yellow,” the “Power Edge” and Cat
“Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks
of Caterpillar and may not be used without permission.
LEHE2077-00 (11/19)
100 Amp Load Centre

100 Amp Load Center

Image shown may not reflect actual package

Specifications

Number of spaces 6
Number of circuits 12
Number of tandem circuit breakers 6
System voltage 120/240VAC
NEMA degree of protection NEMA 3R outdoor
Electrical connection Lugs
Wiring configuration 3-wire
Material Tin plated aluminum busbar
Enclosure material Welded galvannealed steel
Cover finish Gray baked enamel
Product certifications UL E-6294

www.cat.com/electricpower
©2019 Caterpillar
All rights reserved.

Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, LET’S DO THE WORK, their respective logos, “Caterpillar Yellow,” the “Power Edge” and Cat
“Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks
of Caterpillar and may not be used without permission.
LEHE2075-00 (11/19)
Cat GC ®
Control Panel Options

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical
Business Equipment

TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 °C BS EN 60068-2-2
Bb/Be Dry Heat+70°C

VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn

SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 Ms

HUMIDITY
Remote Annunciator Module BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 °C @ 95% RH 48 Hours
It is an LED expansion module that can be used with compatible control BS EN 60068-2-78
Cab Damp Heat Static 40 °C @ 93% RH 48 Hours
modules. The module has been designed to display a maximum of eight
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES BS EN
individual LED indications up to a maximum distance of 1 KM (0.6miles). 60529
IP65 - Front of module when installed into the control panel with the
The Annunciator will consist of two modules to provide a 16 Channel supplied sealing gasket.
Fault annunciation.
It is presented in a vertical enclosure. It includes an alarm sounder that
is triggered when the host controller detects an alarm condition. The CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
alarm can be muted using the front push button.
CRANKING DROPOUTS
The Panels will be fitted with removable label cards which can be used Able to survive 0 V for 50 mS, providing supply was at least
10 V before dropout and supply recovers to 5 V. This is
to identify the standard NFPA alarms. If desired achieved without the need for internal batteries. LEDs and
backlight will not be maintained during cranking.
It includes individual LEDs for each channel and a ‘Power On’ LED that
MAXIMUM OPERATING CURRENT
flashes when the link with the host controller is lost. 112 mA at 12 V, 53 mA at 24 V

MAXIMUM STANDBY CURRENT


74 mA at 12 V, 35 mA at 24 V
• The Remote annunciator has an integral Sounder / Horn
DIMENSIONS OVERALL
• Eight configurable LEDs (per module) 275.5 mm x 214.2 mm x 108.8 mm
• Works up to 1 KM (0.6 miles) from the host controller
• A single Controller can support five Caterpillar Configured
remote annunciator control boxes 8 mm

LEHE2021-00 (08-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Cat GC ®
INTEGRAL FUEL TANKS

INTEGRAL FUEL TANKS


DE250 GC – DE600 GC

FEATURES

• UL Listed for United States (UL 142) and Canada INTEGRAL


(CAN/ULC S601)
• Facilitates compliance with NFPA 30 code, NFPA 37 and • Integral diesel fuel tank is incorporated into the
110 standards and CSA C282 code generator set base frame
• Robust base design includes linear vibration
• Dual wall
isolators between tank base and engine
• Low fuel level warning standard, customer configurable
generator.
warning or shutdown
• Primary tank leak detection switch in containment basin
• Tank design provides capacity for thermal expansion of OPTIONS
fuel
• Audio/visual fuel level alarm panel
• Fuel supply dip tube is positioned so as not to pick up
• 5gal (18.9 L) spill containment
fuel sediment
• Locking Fuel Fill
• Fuel return and supply dip tube is separated by an
• Overfill prevention Valve
internal baffle to prevent immediate re-supply of heated
return fuel
• Pressure washed with an iron phosphate solution
• Interior tank surfaces coated with a solvent-based thin-
film rust preventative
• Heavy gauge steel gussets with internal lifting rings
• Primary and secondary tanks are leak tested at 20.7 kPa
(3 psi) minimum
• Compatible with open packages and enclosures
• Gloss black polyester alkyd enamel exterior paint
• Welded steel containment basin (minimum of 110% of
primary tank capacity)
• Direct reading fuel gauge with variable electrical output
• Emergency vents on primary and secondary tanks are
sized in accordance with NFPA 30.

LEHE2015-00
Cat GC ®
INTEGRAL FUEL TANKS

Integral Fuel Tank Base Useable Capacities with Fuel Tank Dimensions & Weights
Standby Width Width
ekW mm in
250-300 1430 56.3
350-400 1630 64.1
450-500 1630 64.1
550-600 1865 73.4

WIDTH
HEIGHT
LENGTH

The heights listed above do not include lumber used during manufacturing and shipping

A. Open Set & Sound Attenuated Enclosure

Overall Package Height


Tank Only
Tank Total Useable with Tank
Feature Capacity Capacity
Design Dry
Code Height ‘H’ Length ‘L’ Open Enclosure
Weight
Litre Gallon Litre Gallon kg lb mm in mm in mm in mm in
FTDW035 2270.7 599.8 2059.9 543.9 970 2138 762.4 30.0 3958 155.8 2202 86.7 2487 97.9

Integral FTDW036 2820 744.9 2553 674.4 1165 2568 818.8 32.2 4815 189.5 2584 101.7 2644 104
Tank FTDW037 3671 969.7 3323 877.8 1331 2934 668.2 26.3 4622 181.9 2456 96.7 2644 104

FTDW038 4292 1133.8 3889 1027.3 1657 3653 816.4 32.1 4980 196 2560 100.7 2172 85.5

LEHE2015-00
Cat GC ®
INTEGRAL FUEL TANKS

B. Estimated Run Time (Hours)

Standby Ratings (kVA)

Tank Design Feature Code


ekW 100% 75% 50%
Hrs L/hr Hrs L/hr Hrs L/hr
250 28.1 73.3 35 58.8 47 43.8
FTDW035
300 24 86.0 30.8 66.8 40 51.5
350 27.1 94.3 31.2 81.9 42.4 60.2
FTDW036
400 24.1 105.9 28.1 90.7 38.6 66.2
Integral Tank
450 25.2 131.7 31.3 106.1 42.0 79.1
FTDW037
500 24.3 137 30.1 110.5 46.6 71.3
550 25.7 151.1 32.9 118.1 45.2 86.1
FTDW038
600 24.1 161.6 30.0 129.6 42.4 91.7

Tanks with full electrical stub-up area include removable end channel. Tanks with RH stub-up include stubup area directly below the
circuit breaker or power terminal strips.

Fuel tanks and applicable options facilitate compliance with the following United States NFPA Code and Standards:
NFPA 30: Flammable and Combustible Liquids Code
NFPA 37: Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines
NFPA 110: Standard for Emergency and Standby Power Systems

Fuel tanks and applicable options facilitate compliance with the following Canadian Standard and Code:
CSA C282 – Emergency Electrical Power Supply for Buildings
CSA B139-09 – Installation Code for Oil-Burning Equipment

LEHE2015-00 (07-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”, the
“Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Cat GC ®
ENCLOSURES

SOUND ATTENUATED LEVEL 2


ENCLOSURES
D250GC – D600GC
60 Hz

FEATURES

Robust / Highly Corrosion Resistant Construction Sound Attenuated Level 2


• Factory installed on skid base or tanks base • Caterpillar white paint
• Environmentally friendly, polyester powder baked paint • UL Listed integral fuel tank with 24 hours running time
• Enclosure constructed with 18-gauge steel capacity (Optional).
• Interior zinc plated fasteners • DC lighting package (Optional)
• Internally mounted exhaust silencing system
• Comply with ASCE /SEI 7 for Wind loads up to 100mph
• Designed and tested to comply with UL 2200 Listed
generator set package

Excellent Access
• Large cable entry area for installation ease.
• Accommodates side mounted single or multiple breakers.
• Two doors on both sides.
• Vertically hinged allow 180° opening rotation
• Radiator fill cover.

Security and Safety


• Lockable access doors which give full access to control
panel and breaker.
• Cooling fan and battery charging alternator fully guarded.
• Fuel fill, oil fill and battery can only be reached via
lockable access.
• Externally mounted emergency stop button (Optional).
• Designed for spreader bar lifting to ensure safety.
• Stub-up area is rodent proof.

LEHE2014-02
Cat GC ®
ENCLOSURES

Enclosure Package Operating Characteristics


Sound Pressure
Cooling Air Flow Ambient
Standby Levels (dBA) at
Enclosure Type Rate Capability*
ekW 7m (23 ft)
m3 /s cfm °C °F 100% Load
250 6.4 13561 57 135 74
300 6.4 13561 51 125 74
350 7.4 15680 57 134 71
400 7.4 15680 53 127 71
Level 2 Sound Attenuated Enclosure (Steel)
450 8.4 17692 54 130 73
500 8.4 17692 50 122 73
550 11.2 23731 56 133 73
600 11.2 23731 53 127 73
*Cooling system performance at sea level. Consult your Cat® dealer for site specific ambient and altitude capabilities.
Note: Sound level measurements are subject to instrumentation, installation and manufacturing variability, as well as ambient site conditions.

Sound Attenuated Enclosure on Skid Base

Sound Attenuated Enclosure on a UL Listed Integral Fuel Tank Base

Image shown might not reflect actual configuration

LEHE2014-02
Cat GC ®
ENCLOSURES

Standby
Length, L Width, W Height, H Package Weights
Enclosure Type Ratings,
ekW mm in mm in mm in kg lb
Sound Attenuated Enclosure on 250 2857 6298.6
3958 155.8 1440 56.7 1991 78.4
Skid Base 300 2945 6492.6
350 3983 8781.0
4633 182.4 1630 64.2 2227 87.7
400 4017 8856.0
450 4408 9718.0
4823 189.8 1630 64.2 2777 109.3
500 4457 9826.0
550 4754 10480.8
4980 196.1 1865 73.4 2723 107.2
600 4837 10663.8
Sound Attenuated Enclosure on 250 3497 7709.6
UL Listed Integral Fuel Tank 3958 155.8 1440 56.7 2487 97.9
300 3585 7903.6
Base 350 4765 10505.0
4633 182.4 1630 64.2 2644 104.1
400 4799 10580.0
450 5345 11783.7
4823 189.8 1630 64.2 2777 109.3
500 5394 11891.7
550 5973 13168.2
4980 196.1 1865 73.4 2723 107.2
600 6056 13351.2

LEHE2014-02 (09-19)
www.Cat.com/electricpower
©2019 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective logos,
“Caterpillar Yellow”, the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

L L

THIS DIAGRAM IS FOR GC GENSET MODELS (250kW to 600kW)


K
FOR USE WITH : C9, C13, C15 & C18 ENGINES K

6310 CONTROLLER

J J

I I

H H

SIGNAL NAMES SYMBOL LEGEND TABLE INDEX TABLE


SHEET INDEX DESCRIPTION
CIRCUIT_ID COLOR DESCRIPTION 1 CROSS REFERENCE SHEET INDEX, NOTES
MINIATURE CIRCUIT BREAKER
10 WH AVR_SUPPLY_X2_(SHUNT) 2 CONTROL SCHEMATIC
101 RD UNFUSED_BTRY_(+) WIRE NAME DEFINITION 3 POWER SCHEMATIC
105 WH (+24V_DC)_ECM_SUPPLY 4 OPTION SCHEMATIC
108 WH (+24V_DC_)_PANEL_SUPPLY EMERGENCY STOP PUSHBUTTON 5 OPTION SCHEMATIC (CONTINUED)
123 FUSED BTRY +
XXXX-XX# XX-XX
WH 6 CUSTOMER CONNECTIONS AND COMPONENT DETAILS .
14 WH AVR_SUPPLY_X1_(PMG)
G 148 WH (+24_VDC)_LIGHTING_SUPPLY G
15 WH AVR_SUPPLY_X2_(PMG)
16 WH AVR_SUPPLY_Z1_(PMG) WIRE GAUGE FUSED AUTOMOTIVE RELAY
200 GN-YL GROUND
208 WH BATTERY_(-)
229 CLEAN_GROUND WIRE COLOUR
WH
344 WH EMERGENCY_STOP
345 WH EMERGENCY_STOP WIRE NUMBER RESISTOR
346 WH EMERGENCY_STOP HARNESS LAYER TABLE
347 WH EMERGENCY_STOP HARNESS IDENT
348 WH EMERGENCY_STOP IDENT PART NO CHG LOC DESCRIPTION NOTE
5+ GENERATOR_EXCITATION_(+) HARNESS AS. - - - - -
WH
6- GENERATOR_EXCITATION_(-) CIRCUIT IDENT EARTH/GROUND A 572-5793 02 SH 2 MAIN HARNESS (C9-C13)
WH
879 WH REMOTE_START_INPUT A 572-5795 02 SH 2 MAIN HARNESS (C15-C18)
F F
892 BK CAT_DATA_LINK_(-) AN 578-6063 01 SH 4 ANNUNCIATOR HARNESS
893 WH CAT_DATA_LINK_(+) B 577-8429 01 SH 4 PLG 641 & 601 HARNESS (RS485)
9 WH AVR_SUPPLY_X1_(SHUNT) C 580-2678 00 SH 2 E-STOP LINK (OPEN SET)
951 WH MODBUS A CURRENT TRANSFORMER CE 581-0536 00 SH 5 LC BATTERY CHARGER
952 BK MODBUS B COLOUR ABBREVIATIONS CD 577-8711 00 SH 5 GFCI
953 CU MODBUS COM CF 581-0537 00 SH 5 LC ALT HEATER
1 1
954 WH DSENET A PANEL TERMINAL E 572-5798 02 SH 2 E-STOP HARNESS (ENCLOSED SET)
ABBREVIATION DESCRIPTION X
955 BK DSENET B 1 1 EL 580-3699 01 SH 4 CANOPY LIGHTS HARNESS
956 CU DSENET SCREEN
RD RED ER 578-7682 01 SH 5 BATTERY CHARGER HARNESS
WH WHITE TERMINAL GF 581-1932 SH 5 GROUND FAULT RELAY INDICATION HARNESS
SCR CU SCREEN 01
A309 WH DIGITAL_INPUT_(GENSET RUNNING) OR ORANGE GR 579-3092 00 SH 4 GENSET RUNNING & COMMON ALARM
A666 WH ENCLOSURE_LIGHTING YL YELLOW PG 443-0637 00 SH 4 PMG ADAPTOR
A774 WH EMERGENCY_STOP T 577-3930 00 SH 4 PLG 641 & 601 HARNESS (POWER)
E PK PINK CONNECTOR E
A775 WH EMERGENCY_STOP RC 580-8446 01 SH 5 ALTERNATOR HEATER HARNESS
AC101 FUSED BTRY CHARGER (L) BK BLACK AX TBA - SH3 1200A CB AUX CONTACT HARNESS
WH
AC102 BTRY CHARGER (L) GY GREY FF TBA - SH3 1200A CB SHUNT TRIP HARNESS
WH
AC103 WH ALT HEATER BREAKER PU PURPLE Y 586-4861 00 SH 5 PLG CANBUS HARNESS
+
AC104 WH ALT HEATER BREAKER BR BROWN BATTERY
AC199 BTRY CHARGER (N) WIRE AS. / CABLE AS. - - - - -
WH GN GREEN
AC703 ALT HEATER RELAY (11) N - - SH 2 BATTERY NEGATIVE
WH
AC719 ALT HEATER RELAY (12)
BU BLUE P - - SH 2 BATTERY POSSITVE
WH SPLICE
AC720 ALT HEATER TERM CU COPPER R - - SH 2 BATTERY LINK
WH
E486 SENSING_VOLTAGE-PHASE_A GN-YL GREEN-YELLOW SEE SHEET 3 - - SH 2 400A POWER CABLES
WH
E487 SENSING_VOLTAGE-PHASE_B WIRE SEE SHEET 3 - - SH 3 600A POWER CABLES
WH
E488 SENSING_VOLTAGE-PHASE_C SEE SHEET 3 - - SH 3 800A POWER CABLES
WH
E494 CT_SENSING-PHASE_A SEE SHEET 3 - - SH 3 1200A POWER CABLES
WH
D E495 WH CT_SENSING-PHASE_B SCREEN CABLE D
E496 WH CT_SENSING-PHASE_C
E498 WH CT_SENSING-COMMON
E600
E601
WH
WH
GROUND FAULT RELAY
GROUND FAULT RELAY
ABBREVIATIONS A FUSE
F409 WH SENSING_VOLTAGE-NEUTRAL
F430 DIGITAL_INPUT_(D) ABBREVIATIONS DESCRIPTION
WH
F434 GEN_PHASE_A AC ALTERNATING CURRENT
WH
F435 GEN_PHASE_B AVR AUTOMATIC VOLTAGE REGULATOR
WH
F436 GEN_PHASE_C BATT BATTERY
WH
N756 HORN_OUTPUT CR CONTROL RELAY
WH
P733 ANALOG_I/P_SIGNAL_(FUEL_LEVEL) DC DIRECT CURRENT
WH
P854 BREAKER_SHUNT_TRIP ECM ENGINE CONTROL MODULE
WH
R958 DIGITAL_OUTPUT_(SHUNT_TRIP) ECR ENGINE CRANK RELAY
C WH C
R959 DIGITAL_OUTPUT_(ENCLOSURE_LIGHTS) ELR EMNVLOSURE LIGHTS RELAY
WH
X861 STARTER_MAG_SWITCH E-STOP EMERGENCY STOP
WH
Y797 YL J1939_DATALINK_(CAN_+) FLS FUEL LEVEL SENDER
Y798 BK J1939_DATALINK_(CAN_-) GFR GERNERAL FAULT RELAY
Y799 CU J1939_DATALINK_(CAN_SHLD) GND GROUND
Y983 DIGITAL_INPUT_(LOW_COOLANT_LEVEL) GRR GENERATOR RUNNING RELAY
WH
Y984 DIGITAL_INPUT_(FUEL_LEAK) LCL LOW COOLANT LEVEL
WH
Y985 DIGITAL_INPUT__(ENCLOSURE_LIGHTS) MCB MINIATURE CIRCUIT BREAKER
WH
PMG PERMANENT MAGNET GENERATOR
STR SHUNT TRIP RELAY
TERM PANEL TERMINAL
VFC VOLT FREE CONTACT

B B

M
A
T
NOTE A: FACTORY WIRING NOT PROVIDED AS STANDARD. REFER TO MANUFACTURER INSTALLATION INSTRUCTIONS. L
HT
TR

NOTE B: CONTACT OPEN IN DE-ENERGIZED STATE OR FAULT CONDITION. 1E5167A INT-PROP


1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
NOTE C: RESISTOR TO BE REMOVED IF ADDITIONAL EXPANSION MODULES ARE CONNECTED. 1E0012A INTERPRETATION
N 1E0011 INTPR & TOL
O
T
E Caterpillar: Confidential Yellow
PROD X OTHER
UNLESS OTHERWISE SPECIFIED
VERSION PRIMARY X
DIMENSIONS ARE IN mm
A DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 1 OF 6
PROJECTION
DWG CONTROL W591

THE INFORMATION HEREON IS THE PROPERTY OF CATERPILLAR INC. AND/OR ITS


SUBSIDIARIES. WITHOUT WRITTEN PERMISSION, ANY COPYING, TRANSMITTAL TO
OTHERS, AND ANY USE EXCEPT THAT FOR WHICH IT IS LOANED, IS PROHIBITED

DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 2X3
- 02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

L
CONTROL SCHEMATIC (DSE 6310) L

ADEM A4:E4
A-C3
ECM 160-7689

J1-PIN3 ANALOG RTN 3


J1-PIN2 5V ANALOG POWER 2
SPARE ANALOG INPUT
J1-PIN17 PROG. ANALOG 3 17 (NOTE A)
6310 CONTROLLER
J1-PIN67 BATT - 67
K 20 MPU + K
CUSTOMER TERMINALS
MAG PICKUP (NOT USED) 21 MPU -
(NOTE A)
22 MPU SCR
CBL-A2:Y799-A3 CU-20 A-T10 1 1 A-T16
CBL-A3:Y799-A3 CU-18 A-T25

25 ECU SCR (J1939)


CAN SH
J1-PIN42 CAN A SHIELD 42 A-T11
1 1 CBL-A3:Y797-A2 YL-18 A-T23

23 ECU + (J1939)
A-S3

J1-PIN50 CAN A + 50 Y797-A2 WH-18 CBL-A2:Y797-A2 WH-18 A-T12 1 1 A-T18


CBL-A3:Y798-A1 GN-18 A-T24

24 ECU - (J1939)
A-S4 CAN+
J1-PIN34 CAN A- 34 Y798-A3 WH-18 A-T13
1 1
120R
CBL-A2:Y798-A1 BK-18 A-T14 1 1

CAN-
Resistor_As_3_Nodes_1 A-T15
1 1 A-T17

134-2540 A-C2
155-2267
J J
A Y797-A20 WH-18 A-C1
265-4123
B Y798-A44 WH-18
CBL-A4:Y798-A1 BK-18 F
C REF [16,F] 208-A22 WH-18 A-T61

1 DC SUPPLY (-)
120 CBL-A4:Y797-A2 WH-18 G
ENGINE SERVICE E-STOP_PANEL REF [10,D] 108-A25 WH-18 A-T62
DC SUPPLY (+)
2
CBL-A4:Y799-A3 CU-20 C CONNECTOR 390--1209

J1-PIN8 ATA/CAT+ 8 CBL-A5:893-A2 WH-18 D


J1-PIN9 ATA/CAT- 9 CBL-A5:892-A1 BK-18 E 12 11
A-T19 A-T21
A775-A29 WH-18 A-T26

3 EMERGENCY STOP NC (POS)


A-CLIPPED_2

CBL-A5:200-A3 CU-20 A-CLIPPED_1

J 22 21
A-T20 A-T22

347-A28 WH-18 REF [7,E]


J1-PIN23 GND SW 2 E-STOP 23 A774-A32 WH-18 H
I REF [16,F] 208-A54 WH-18 B I
REF [10,D] 108-A55 WH-18 A
J1-PIN40 GND SW 3 RUN-STOP 40
OPEN SET LINK ENCLOSURE ESTOP
C-C32 E-STOP 4 OUTPUT A (NOT USED)
3E-3376 390--1209
REF [12,G] X861-A30 WH-18 A-T27

5 OUTPUT B (STARTER MOTOR)


1
12 11 E-C1 A-C5 6 CHARGE ALT EXCITE (NOT USED)
2 E-T1 E-T3
3E-3376 155-2272
CONNECT TO A-C5
22 21
344-C54 WH-18 3 E-T2 E-T4
A774-E4 WH-18 1
348-C55 WH-18 4 345-E3 WH-18 2 346-A46 WH-18
344-E1 WH-18 3 344-A27 WH-18 REF [6,E]
H 348-E2 WH-18 4 348-A26 WH-18 H

J1-PIN48 BATT + 48 105-A11 WH-16 OPTIONAL


J1-PIN52 BATT + 52 105-A10 WH-16
F5
AUDIBLE STR
352--2951
J1-PIN53 BATT + 415-2232 ALARM
53 105-A9 WH-16
241-3114
25A REF [16,F]
A-S7

J1-PIN70 KEY SW 70 105-A8 WH-16 105-A7 WH-14 A-T53 A-T63


101-A45 WH-14 Horn_1 208-A47 WH-18 A-T68 A-T67

R958-A50 WH-18 A-T66

7 OUTPUT C (SHUNT TRIP)


A2 A1

J1-PIN61 BATT - 61 208-A14 WH-16 A-T6

8 OUTPUT D (SPARE)
A-T7

J1-PIN63 BATT - 63 208-A12 WH-16 9 OUTPUT E (SPARE)


G J1-PIN65 BATT - 208-A13 WH-16 208-A56 WH-18 OUTPUT F (SPARE)
G
65 REF[16,E] 10
11 OUTPUT G (SPARE)
N756-A57 WH-18 A-T76

12 OUTPUT H (SPARE)
CUSTOMER TERMINALS
A-S2

208-A16 WH-10 208-A24 WH-18 X861-A30 WH-18 REF [3,I]


REF [13,A] 229-A58 WH-18 A-T78
1 1 A-T64
229-A53 WH-16 REF [12,E]
CLN_GND
REF [3,J] 208-A22 WH-18 1 1 A-T77
229-A59 WH-18 REF [5,E]
1 1
A-T1

879-A1 WH-18 A-T28

42 INPUT A (REMOTE START)


REF [5,G] 208-A47 WH-18 REM_STRT
REMOTE START 1 1 REF [13,C] Y983-A5 WH-18 A-T29
INPUT B (LOW COOLANT LEVEL)
43
REF [7,I] A-C4 REF [16,F]
208-A54 WH-18 230-4011
1 1 A-T2

208-A15 WH-16 REF [13,B] Y984-A52 WH-18 A-T74

44 INPUT C (FUEL LEAK)


21
BATT-
F 1 1
45 INPUT D (SPARE) F
REF [13,B] 208-A51 WH-18
1 1
46 INPUT E (SPARE)
BATT-
REF [12,C] 208-A18 WH-18 1 1
47 INPUT F (SPARE)
PROGRAMMABLE INPUTS
STARTER MOTOR 1 1 (NOTE A) 48 INPUT G (SPARE)
REF [7,F] 208-A15 WH-16 BATT-
1 1
49 INPUT H (SPARE)
G S LINK A
REF Sheet_3-[3,J] 208-A48 WH-18 1 1
A-T3

347-A28 WH-18 REF [4,I]


ESTOP_A
1 1
REF [8,G] 208-A56 WH-18 MOT BTRY A-T38
101-A31 RD-8
A-S5
REMOTE ESTOP (OPTIONAL)
NOTE: REMOVE LINKS A&B
G-T2

1 1
A-T4

344-A27 WH-18 REF [10,H] REF [7,F] 229-A59 WH-18 A-T9

15 ANALOG INPUT (GND)


ESTOP_B
101-P1 RD-2 1 1 REF [13,A] P733-A60 WH-18 A-T8

16 ANALOG INPUT A (SPARE)


M LINK B
E 1 1
17 ANALOG INPUT B (SPARE) E
A-T73

229-A53 WH-16 REF [7,G] BATT+


39
A-T

G-T
1

1 1
18 ANALOG INPUT C (SPARE)
F4 SPARE ANALOG INPUT
208-A19 BK-8 422-6095 1 1 (NOTE A) 19 ANALOG INPUT D (SPARE)
BATT+
10A
A-S6

101-A21 WH-14 A-T52 A-T54


108-A23 WH-16 108-A4 WH-16 A-T5
1 1
208-N1 BK-2

26 DSENET B
REF [3,J] 108-A25 WH-18 EXPANSION DATALINK 27 DSENET A
(NOTE A) 28 DSENET SCR
REF [7,I] 108-A55 WH-18

REF Sheet_3-[4,K] 108-A49 WH-18


D 101-R1 BK-2 D
50 RS485 SCR
Battery_1 Battery_2 RS485 CONNECTIONS 51 RS485 B
230-6368 230-6368 (NOTE A)
52 RS485 A
CHARGE ALT

ALT
A-T41
B+ A-T40
101-A43 WH-10

LOW COOLANT LEVEL A-C6


362-2913 155-2267
C C

A A 108-A6 WH-18
B B 208-A18 WH-18 REF [15,G]
C C Y983-A5 WH-18 REF [5,F]

FUEL LEAK SWITCH


A-C7
155-2269

1 Y984-A52 WH-18 REF [5,F]

B 2 208-A51 WH-18 REF [16,F] B

M
A
A-C8 T
L
FUEL LEVEL SENSOR 247-8195 HT
TR

1 1 1E5167A INT-PROP
1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
2 2 P733-A60 WH-18 REF [9,G] 1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
3 3 229-A58 WH-18 REF [5,E] T
E Caterpillar: Confidential Yellow
PROD X OTHER
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY X

A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 2 OF 6
PROJECTION
DWG CONTROL W591

THE INFORMATION HEREON IS THE PROPERTY OF CATERPILLAR INC. AND/OR ITS


SUBSIDIARIES. WITHOUT WRITTEN PERMISSION, ANY COPYING, TRANSMITTAL TO
OTHERS, AND ANY USE EXCEPT THAT FOR WHICH IT IS LOANED, IS PROHIBITED

DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

L
POWER SCHEMATIC L
CB SHUNT TRIP
STR
352--2951

21 24
22

REF Sheet_2-[10,D] 108-A49 WH-18 A-T69

11 14
A-T70

12

3 PHASE STAR
(6 WIRE) 1200A HARNESS
C2 C1
L1 (U)
L2 (V)
UF-T2

L1-UF1 BK-0 UF-T1


FF-T3 FF-T4

C1-FF1 WH-18 FF-T2


1 1
A-T72

P854-A62 WH-18
K CB1_Y0 CB1_ST+ K
T2
UG-T2

L1-UG1 BK-0 UG-T1 1 1

T1
EXCITER
UH-T2

L1-UH1 BK-0 UH-T1


CB2 OPTIONAL
C2 C1
ABB-T4 ABB-T3
C1-BK ABB-T2
1 1

T5
VF-T2

L2-VF1 BK-0 VF-T1

CB2_Y0 CB2_ST-
T4
VG-T2

L2-VG1 BK-0 VG-T1

T6
VH-T2

L2-VH1 BK-0 VH-T1

CONNECT TO CONNECT TO
ALTERNATOR
WF-T2

L3-WF1 BK-0 WF-T1

BREAKER
WG-T2

L3-WG1 BK-0 WG-T1


C2-BK ABB-T1
1
CB_BATT-
1
A-T71

208-A48 WH-18 REF Sheet_2-[16,E]


E
WH-T2

L3-WH1 BK-0 WH-T1


C2-FF2 WH-18 FF-T1
1 1

J T3 J
NF-T2

N-NF1 BK-0
NF-T1

L3 (W) NG-T2

N-NG1 BK-0
NG-T1

NH-T2
OPTIONAL OPTIONAL
N-NH1 BK-0
NH-T1

CB AUX CONTACTS CB AUX CONTACTS


(1200A) 1 1
(100A TO 800A) 1 1

41 95
41-AX1 WH-16 AX-T7
1 1 95-BK ABB-T21
1 1

PARALLEL STAR 600A/800A HARNESS CB TRIPPED/ 44


1

44
1
98
1

98
1

UNTRIPPED CB TRIPPED/
(12 WIRE) 44-AX2 WH-16 1 1 98-BK 1 1
AX-T1 AX-T6 ABB-T30 ABB-T25

(SY) 41 UNTRIPPED 95
UC-T1

L1-UC1 BK-0 UC-T2


AX-T11 AX-T12
1 1 (SY) ABB-T28 ABB-T29
1 1
L1 (U) 42 96
L2 (V) 42 96
I UE-T1

L1-UE1 BK-0 UE-T2


42-AX3 WH-16 AX-T5
1 1 96-BK ABB-T22
1 1
I
T7 T2
1 1 1 1

EXCITER T1 T8
VC-T1

L2-VC1 BK-0 VC-T2

11 11
11-AX4 WH-16 AX-T2
1 1 11-BK ABB-T24
1 1

T10 T5
VE-T1

L2-VE1 BK-0 VE-T2

CONNECT TO CONNECT TO 1 1 1 1
14 14 14 14
CB OPEN/CLOSED
T4 T11 ALTERNATOR WC-T1

L3-WC1 BK-0 WC-T2


BREAKER (Q/1)
AX-T10

14-AX5 WH-16 AX-T4


1 1
CB OPEN/CLOSED
ABB-T32
14-BK ABB-T23
1 1
11 11
WE-T1

L3-WE1 BK-0 WE-T2


AX-T8 AX-T9
1 1 (Q/1) ABB-T27 ABB-T31
1 1

T12 T6
12 12 12 12
12-AX6 WH-16 AX-T3
1 1 12-BK ABB-T26
1 1
NC-T1

N-NC1 BK-0 NC-T2

NE-T1

N-NE1 BK-0 NE-T2

E T9 T3
H H
L3 (W)

400A HARNESS

1 2
L1-UA1 BK-0 UA-T14

L1

A-T42

A-T43
G G
SERIES STAR 1 2
L2-VA1 BK-0 VA-T2

L2 CUSTOMER LOAD

A-T44

A-T45
(12 WIRE)
1 2
L3-WA1 BK-0 WA-T1

L3
A-T49

A-T46

A-T47
UA-
T6

T2
VA-

T4
A-T50

T1 T5
EXCITER
5+ T4
T8 N-NA1 BK-0 NA-T3

N
T7 T11
E494-A36 WH-18

E495-A35 WH-18

E496-A34 WH-18
E498-A37 WH-18
E498-A38 WH-18
E498-A39 WH-18
200-A63 GN-YL-16 A-T65

F T10
NA-T5
F
A-T
51

T12

GENERATOR GROUND
-6 T9 6310 CONTROLLER
200-A61 GN-YL-16 A-T75

T6

E 41 N/C

T3
CONTROL PANEL DOOR GROUND
E498-A33 WH-16 40 CURRENT SENSING COMMON
A-S1
WA-T3
A-T30
A-T48

E496-A34 WH-18 A-T31

39 CURRENT SENSING L3

E E
E495-A35 WH-18 A-T32

38 CURRENT SENSING L2

NE LINK CABLE
E494-A36 WH-18 A-T33
37 CURRENT SENSING L1
F1
GN/YL GN/YL 7W-0482

GN/YL F434-A17 WH-18 A-T34


2A A-T60

E486-A66 WH-18
A-T57

29 VOLTAGE SENSING L1

MAIN CUSTOMER GROUND


F2
7W-0482

F435-A42 WH-18 A-T35


2A A-T59

E487-A65 WH-18 A-T56

30 VOLTAGE SENSING L2
D D

BASEFRAME
F3
GROUND 7W-0482

F436-A40 WH-18 A-T36


2A A-T58
E488-A64 WH-18 A-T55

31 VOLTAGE SENSING L3

F409-A41 WH-18 A-T37

32 VOLTAGE SENSING N

C C

STANDARD
SHUNT EXCITATION
D350 AVR

6- 3 F-
0V
5+ 6 F+
AI1
CONNECT TO T7 9 4 X1
0V
B CONNECT TO T12 10 2 X2 B
RTD
5 Z1
0V
1 Z2
DI1
0V M
A
T
L
D02 HT
TR

D01
1E5167A INT-PROP
1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
CONNECT TO T1 U 1 U T
E Caterpillar: Confidential Yellow
PROD X OTHER

CONNECT TO T2 V 2 V S1
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY

A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
SHEET 3 OF 6
CONNECT TO T3 W 3 W S2
THIRD ANGLE
PROJECTION
DWG CONTROL W591

THE INFORMATION HEREON IS THE PROPERTY OF CATERPILLAR INC. AND/OR ITS


SUBSIDIARIES. WITHOUT WRITTEN PERMISSION, ANY COPYING, TRANSMITTAL TO
OTHERS, AND ANY USE EXCEPT THAT FOR WHICH IT IS LOANED, IS PROHIBITED

DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

L L

ADDITIONAL OPTIONS
OPTIONAL
VFC FOR GENSET RUNNING AND GENERAL FAULT

K K

GFR 6310 CONTROLLER


352-2951
A2 A1
208-GR2 WH-18 R958-GR1 WH-18 OUTPUT E (GENERAL FAULT)
GR-T4 GR-T2 GR-T1
1 1 GR-T3
9
BATT- GR-T5
1 1
14 11
12
24 21
22
J GRR J
352-2951
A2 A1
208-GR3 WH-18 R959-GR4 WH-18 OUTPUT F (GEN RUNNING)
GR-T7 GR-T6
GR-T8
10

14 11
12
24 21
22

I I

OPTIONAL
REMOTE ANNUNCIATOR
2548 CONTROLLER

108-AN1 WH-18 C-T1


1 BTRY -
H H
208-AN2 WH-18 C-T2
2 BTRY +

CBL-AN1 953-AN3 CU-20 C-T3 3 SCREEN

CBL-AN1 951-AN2 WH-18 C-T4


4 A

CBL-AN1 952-AN1 BK-18 C-T5


5 B

G G

120R

2548 CONTROLLER

108-AN1 WH-18 1 BTRY -


AN-T6
1 1 AN-T1

BATT+
1 1
F F
1 1
AN-T7

208-AN2 WH-18 AN-T2 2 BTRY +


BATT-
1 1

CUSTOMER CONNECTIONS: 1 1
AN-T8

CBL-AN1:956-AN3 CU-20 AN-T3


3 SCREEN
SCR
1 1

TO BE CONNECTED IN SERIES 1 1
AN-T9

CBL-AN1:954-AN2 WH-18 AN-T4


4 A
WITH DSENET CIRCUIT A
1 1

1 1
AN-T10

CBL-AN1:955-AN1 BK-18 AN-T5 5 B


B
1 1

E E

D D

C C

B B

M
A
T
L
HT
TR

1E5167A INT-PROP
1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
T
E Caterpillar: Confidential Yellow
PROD X OTHER
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY

A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 4 OF 6
PROJECTION
DWG CONTROL W591

THE INFORMATION HEREON IS THE PROPERTY OF CATERPILLAR INC. AND/OR ITS


SUBSIDIARIES. WITHOUT WRITTEN PERMISSION, ANY COPYING, TRANSMITTAL TO
OTHERS, AND ANY USE EXCEPT THAT FOR WHICH IT IS LOANED, IS PROHIBITED

DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

L L

ADDITIONAL OPTIONS
OPTIONAL
ALTERNATOR HEATER

AHR
352-2951
K K
REF [16,I] 208-RC36 WH-18 RC-T2 RC-T1

A309-RC35 WH-18 REF [14,H]


A2 A1
21 24 F7
22 190-2558
ALTERNATOR HEATER
HTR-H1 1 1
RC-T12

AC703-RC1 WH-18 RC-T11

11 14
1 AH_L1 12
RC-T10
AC719-RC39 WH-18 RC-T5
6A CF-T4
AC104-CF2 WH-14
1 1
2
F8
1 1 190-2558
AH_L2
HTR-H2 1 1 RC-T13
AC720-RC40 WH-18 RC-T6
6A CF-T3
AC103-CF1 WH-14

J J

OPTIONAL
BATTERY CHARGER

1 1 572-0792
BATTERY_CHARGER
BATT+
1 1 ER-T13
108-ER1 WH-14 ER-T1
OP+
1 1 ER-T12
208-ER2 WH-14 ER-T2

OP-
I BATT- I
REF [16,K] 208-RC36 WH-18 RC-T4
1 1

NC
COM
NO

NTC
NTC_1
6310 CONTROLLER
120R
8 OUTPUT D (GENSET RUNNING) RC-T3
A309-RC35 WH-18 REF [13,K] LK1
H NOTE C LK1_1 H

26 DSENET B ER-T16
CBL-ER1:B-1 GN-18 ER-T6
B
27 DSENET A ER-T17
CBL-ER1:A-2 YL-18 ER-T7

A
28 DSENET SCR ER-T18
CBL-ER1:SCR-3 CU-18 ER-T8

SCR

200-ER46 WH-14 ER-T19

GND_1
AC199-ER45 WH-14 ER-T20

N
1 1 F9 AC102-ER44 WH-14 ER-T21
L
GND 422-6095
G 200-CE3 GN-YL-14 CE-T8
1 1 ER-T26

G
ER-T23
10A ER-T22

1 1

AC199-CE2 WH-14 CE-T7


1 BC_N 1 ER-T25

1 1

BC_L1
AC101-CE1 WH-14 CE-T6
1 1 ER-T24
AC101-ER43 WH-14

F F

AC199-CE2 WH-14 AC199-CD3 WH-12 REF [11,D]

E OPTIONAL E
LOAD CENTER BOX
CE-T13

CD-T3

NEUTRAL
BATT_CHRG_BREAKER
508-6697
20A CE-T18
AC101-CE1 WH-14

ALT_HTRG_BREAKER
577-8557
AC103-CF1 WH-14
L1 CF-T2

CUSTOMER 15A
CF-T1

AC104-CF2 WH-14
D CONNECTION GFCI_RECEPTACLE D
240V 3WIRES 423-7031
GFCI_BREAKER
508-6697
BK (LINE)
L2 20A CD-T2
AC101-CD1 WH-12 CD-T4

WH (N) CD-T5
AC199-CD3 WH-12 REF [14,E]
JWH_BREAKER
577-8557
CONNECT
JACKET WATER GND
CD-T6

15A
HEATER WIRES
200-CE3 GN-YL-14 200-CD2 GN-YL-10
CE-T11

CD-T1

GROUND GFCI RECEPTACLE


CD-T8

C C
200-CD4 GN-YL-10
CD-T7

MAIN CUSTOMER
GROUND

B B

M
A
T
L
HT
TR

1E5167A INT-PROP
1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
T
E Caterpillar: Confidential Yellow
PROD X OTHER
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY

A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 5 OF 6
PROJECTION
DWG CONTROL W591

THE INFORMATION HEREON IS THE PROPERTY OF CATERPILLAR INC. AND/OR ITS


SUBSIDIARIES. WITHOUT WRITTEN PERMISSION, ANY COPYING, TRANSMITTAL TO
OTHERS, AND ANY USE EXCEPT THAT FOR WHICH IT IS LOANED, IS PROHIBITED

DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

L ADDITIONAL INFORMATION - COMPONENT DETAILS & CUSTOMER CONNECTIONS L

MAIN CUSTOMER RAIL


CIRCUIT BREAKER RAIL
(OPTIONS INCLUDED)
K

FUSE ID CURRENT RATING WIRE ID DESCRIPTION


(OPTIONS INCLUDED) K

F4 10A 101, 108 PANEL SUPPLY


F5 25A 101, 105 ECM POWER
F6 2A 148, 101 ENCLOSURE LIGHTS

DC FUSES

J J

GROUND FAULT

F1 F2 F3 F4 F5 F6 STR GFR GRR ELR

REM_STRT
CLN_GND

ESTOP_A

ESTOP_B

CAN_SH
BATT +

BATT +

CB2_95

CB2_96

CB2_98
BATT -

BATT -

BATT -

CB1_14

CB2_11

CB2_12

CB2_14
CB1_11

CB1_12

CB1_95
CB1_41
CB1_96
CB1_42
CB1_98
CB1_44
CAN +

CAN -
C1 C1 C2 C2
I I

H H

TERMINAL ID WIRE ID DESCRIPTION


CB1_ST+ C1 CB1 SHUNT TRIP
CB2_ST+ C1 CB2 SHUNT TRIP
BATT- C2 BATTERY NEGATIVE
AC FUSES CUSTOMER TERMINALS RELAY VFC CONNECTIONS GROUND FAULT RELAY 11 11 CB1 AUX COM
12 12 CB1 AUX NO
14 14 CB1 AUX NC
FUSE ID CURRENT RATING WIRE ID DESCRIPTION TERMINAL ID WIRE ID DESCRIPTION RAIL CURRENT RATING DESCRIPTION 95/41 95/41 CB1 AUX COM
F1 2A F434, E486 CLN_GND 229 CLEAN GROUND FOR ANALOG INPUTS STR 8A SHUNT TRIP RELAY
L1 SENSING AC 96/42 96/42 CB1 AUX NO
F2 2A F435, E487 REM_STRT 879 REMOTE START INPUT GFR 8A GENERAL FAULT RELAY
G L2 SENSING AC 98/44 98/44 CB1 AUX NC G
F3 2A F436, E488 BATT - 208 BATTERY NEGATIVE GRR 8A GENSET RUNNING RELAY
L3 SENSING AC 11 11 CB2 AUX COM
BATT - 208 BATTERY NEGATIVE ELR 8A ENCLOSURE LIGHTS RELAY 12 12 CB2 AUX NO
BATT - 208 BATTERY NEGATIVE
14 14 CB2 AUX NC
ESTOP_A 347 ECM ESTOP INPUT 95 95 CB2 AUX COM
ESTOP_B 344 GENSET CONTROLLER ESTOP INPUT 96 96 CB2 AUX NO
BATT + 108 BATTERY POSITIVE (10A FUSED) 98 98 CB2 AUX NC
BATT + 108 BATTERY POSITIVE (10A FUSED)
CAN + Y797 CAN + COMMS
CAN - Y798 CAN - COMMS
CAN SH Y799 CAN SH COMMS

F F

SHORE POWER RAIL


(OPTIONS INCLUDED)
E E

10A UL BATTERY CHARGER

D D
F7 F8 F9
AHR
BC_L1
AH_L1

AH_L2

BC_N
GND

C C

B COMPONENT DESCRIPTION B
AHR ALTERNATOR SPACE HEATER RELAY
AH_L1 ALTERNATOR HEATER AC SUPPLY L1
AH_L2 ALTERNATOR HEATER AC SUPPLY L2
F7 ALTERNATOR HEATER FUSE L1 (6A)
F8 ALTERNATOR HEATER FUSE L2 (6A) M
A
GND SHORE POWER GROUND T
L
HT
F9 BATTERY CHARGR FUSE L1 (10A) TR

BC_L1 BATTERY CHARGER AC SUPPLY L1


1E5167A INT-PROP
BC_N BATTERY CHARGER AC SUPPLY N 1E0198W BRAND MARKINGS
1E0013Y CONFIDENTIALITY
1E0012A INTERPRETATION
N
O 1E0011 INTPR & TOL
T
E Caterpillar: Confidential Yellow
PROD X OTHER
UNLESS OTHERWISE SPECIFIED VERSION PRIMARY

A DIMENSIONS ARE IN mm
DIMENSIONS W/O TOL ARE BASIC TYPE SECONDARY A
THIRD ANGLE SHEET 6 OF 6
PROJECTION
DWG CONTROL W591

THE INFORMATION HEREON IS THE PROPERTY OF CATERPILLAR INC. AND/OR ITS


SUBSIDIARIES. WITHOUT WRITTEN PERMISSION, ANY COPYING, TRANSMITTAL TO
OTHERS, AND ANY USE EXCEPT THAT FOR WHICH IT IS LOANED, IS PROHIBITED

DIAGRAM-WIRING
(C9-C18) (DSE6310)
VER CHG
569-6011 - 2X3
02
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Effective with sales to the first user on or after August 1, 2016

CATERPILLAR LIMITED WARRANTY


Industrial, Petroleum, Locomotive, and Agriculture Engine Products and Electric Power
Generation Products
Worldwide
Caterpillar Inc. or any of its subsidiaries (“Caterpillar”) warrants new and Caterpillar Responsibilities • Travel or transporting costs, except as stated under “Caterpillar
remanufactured engines and new and rebuild electric power generation If a defect in material or workmanship is found during the warranty
Responsibilities.”
products sold by it (including any products of other manufacturers period, Caterpillar will, during normal working hours and at a place of • Premium or overtime labor costs.
packaged and sold by Caterpillar), to be free from defects in material business of a Cat dealer or other source approved by Caterpillar:
and workmanship. • Parts shipping charges in excess of those that are usual and
• Provide (at Caterpillar’s choice) new, Remanufactured, or customary.
This warranty does not apply engines sold for use in on-highway vehicle or Caterpillar approved repaired parts or assembled components
marine applications; engines in machines manufactured by or for Caterpillar; • Local taxes, if applicable.
needed to correct the defect.
C175, 3500 and 3600 series engines used in locomotive applications; 3000 • Costs to investigate complaints, unless the problem is caused by a
Family engines, C0.5 through C4.4 and ACERT™ (C6.6, C7, C7.1, C9, Note: New, remanufactured, or Caterpillar approved repaired parts or defect in Caterpillar material or workmanship.
C9.3, C11, C13, C15, C18, C27, and C32) engines used in industrial, mobile assembled components provided under the terms of this warranty
are warranted for the remainder of the warranty period applicable • Giving timely notice of a warrantable failure and promptly making
agriculture and locomotive applications; or Cat® batteries; or Electric Power
to the product in which installed as if such parts were original the product available for repair.
Generation Products manufactured or assembled in India. These products
are covered by other Caterpillar warranties. components of that product. Items replaced under this warranty • Performance of the required maintenance (including use of proper
become the property of Caterpillar. fuel, oil, lubricants, and coolant) and items replaced due to normal
This warranty is subject to the following:
• Replace lubricating oil, filters, coolant, and other service items wear and tear.
Warranty Period
made unusable by the defect. • Allowing Caterpillar access to all electronically stored data.
• For industrial engines, engines in a petroleum applications
• Provide reasonable and customary labor needed to correct Limitations
or Petroleum Power Systems (excluding petroleum fire
the defect, including labor to disconnect the product from and
pump application), or engines in a Locomotive application, or Caterpillar is not responsible for:
reconnect the product to its attached equipment, mounting, and
Uninterruptible Power Supply (UPS) systems, the warranty period • Failures resulting from any use or installation that Caterpillar
support systems, if required.
is 12 months after date of delivery to the first user. judges improper.
For new 3114, 3116, and 3126 engines and, new and Caterpillar rebuild
• For engines used in petroleum fire pump and mobile agriculture
electric power generation products (which includes the following: any • Failures resulting from attachments, accessory items, and parts
applications the warranty period is 24 months after date of delivery
new products of other manufacturers packaged and sold by Caterpillar) not sold or approved by Caterpillar.
to the first user.
• Provide travel labor, up to four hours round trip, if in the opinion • Failures resulting from abuse, neglect, and/or improper repair.
• For controls only (EPIC), configurable and custom switchgear
products, and automatic transfer switch products, the warranty of Caterpillar, the product cannot reasonably be transported to • Failures resulting from user’s delay in making the product available
period is 24 months after date of delivery to the first user. a place of business of a Cat dealer or other source approved by after being notified of a potential product problem.
Caterpillar (travel labor in excess of four hours round trip, and any
• For new CG132, CG170 and CG260 series power generation • Failures resulting from unauthorized repairs or adjustments, and
meals, mileage, lodging, etc. is the user’s responsibility).
products the warranty period is 24 months/16,000 hours, whichever unauthorized fuel setting changes.
comes first, after date of delivery to first user. For all other products:
• Damage to parts, fixtures, housings, attachments, and accessory
• For electric power generation products other than CG132, CG170 • Provide reasonable travel expenses for authorized mechanics, items that are not part of the engine, Cat Selective Catalytic
and CG260 series in prime or continuous applications the warranty including meals, mileage, and lodging, when Caterpillar chooses Reduction System or electric power generation product (including
period is 12 months. For standby applications the warranty period to make the repair on-site. any products of other manufacturers packaged and sold by
is 24 months/1000 hours. For emergency standby applications the User Responsibilities Caterpillar).
warranty period is 24 months/400 hours. All terms begin after date
The user is responsible for: • Repair of components sold by Caterpillar that is warranted directly
of delivery to the first user.
to the user by their respective manufacturer. Depending on type of
• For Caterpillar rebuild electric power generation products the • Providing proof of the delivery date to the first user.
application, certain exclusions may apply. Consult your Cat dealer
warranty period is 12 months, but not to exceed 24 months • Labor costs, except as stated under “Caterpillar Responsibilities,” for more information.
from shipment of rebuilt electric power generation product from including costs beyond those required to disconnect the product
Caterpillar. from and reconnect the product to its attached equipment,
• For all other applications the warranty period is 12 months after mounting, and support systems.
date of delivery to the first user. (Continued on reverse side…)

SELF5709
This warranty covers every major component of the products. Claims under this warranty should be submitted to a CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART
place of business of a Cat dealer or other source approved by Caterpillar. For further information concerning either OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES IN RESPECT OF THE
the location to submit claims or Caterpillar as the issuer of this warranty, write Caterpillar Inc., 100 N. E. Adams St., MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF SERVICES RELATING TO THE GOODS.
Peoria, IL USA 61629.
CATERPILLAR IS NOT LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES UNLESS IMPOSED UNDER
Caterpillar’s obligations under this Limited Warranty are subject to, and shall not apply in contravention of, the laws, MANDATORY RIGHTS.
rules, regulations, directives, ordinances, orders, or statutes of the United States, or of any other applicable jurisdiction,
IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE INTERNATIONAL SALE
without recourse or liability with respect to Caterpillar.
OF GOODS IS EXCLUDED IN ITS ENTIRETY.
A) For products operating outside of Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New Guinea, the
C) For products supplied in Australia:
Solomon Islands and Tahiti, the following is applicable:
IF THE PRODUCTS TO WHICH THIS WARRANTY APPLIES ARE:
NEITHER THE FOREGOING EXPRESS WARRANTY NOR ANY OTHER WARRANTY BY CATERPILLAR,
EXPRESS OR IMPLIED, IS APPLICABLE TO ANY ITEM CATERPILLAR SELLS THAT IS WARRANTED DIRECTLY I. PRODUCTS OF A KIND ORDINARILY ACQUIRED FOR PERSONAL, DOMESTIC OR HOUSEHOLD USE
TO THE USER BY ITS MANUFACTURER. OR CONSUMPTION; OR
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, II. PRODUCTS THAT COST AUD 40,000 OR LESS,
INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE,
EXCEPT CATERPILLAR EMISSION-RELATED COMPONENTS WARRANTIES FOR NEW ENGINES, WHERE WHERE THOSE PRODUCTS WERE NOT ACQUIRED FOR THE PURPOSE OF RE-SUPPLY OR FOR THE
APPLICABLE. REMEDIES UNDER THIS WARRANTY ARE LIMITED TO THE PROVISION OF MATERIAL AND PURPOSE OF USING THEM UP OR TRANSFORMING THEM IN THE COURSE OF PRODUCTION OR
SERVICES, AS SPECIFIED HEREIN. MANUFACTURE OR IN THE COURSE OF REPAIRING OTHER GOODS OR FIXTURES, THEN THIS SECTION
C APPLIES.
CATERPILLAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES.
THE FOLLOWING MANDATORY TEXT IS INCLUDED PURSUANT TO THE AUSTRALIAN CONSUMER LAW
CATERPILLAR EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART AND INCLUDES REFERENCES TO RIGHTS THE USER MAY HAVE AGAINST THE DIRECT SUPPLIER OF
OR ON THE PART OF ANY OF ITS EMPLOYEES, AGENTS OR REPRESENTATIVES IN RESPECT OF THE THE PRODUCTS: OUR GOODS COME WITH GUARANTEES THAT CANNOT BE EXCLUDED UNDER THE
MANUFACTURE OR SUPPLY OF GOODS OR THE PROVISION OF SERVICES RELATING TO THE GOODS. AUSTRALIAN CONSUMER LAW. YOU ARE ENTITLED TO A REPLACEMENT OR REFUND FOR A MAJOR
FAILURE AND COMPENSATION FOR ANY OTHER REASONABLY FORESEEABLE LOSS OR DAMAGE. YOU
IF OTHERWISE APPLICABLE, THE VIENNA CONVENTION ON CONTRACTS FOR THE INTERNATIONAL SALE
ARE ALSO ENTITLED TO HAVE THE GOODS REPAIRED OR REPLACED IF THE GOODS FAIL TO BE OF
OF GOODS IS EXCLUDED IN ITS ENTIRETY.
ACCEPTABLE QUALITY AND THE FAILURE DOES NOT AMOUNT TO A MAJOR FAILURE. THE INCLUSION
For personal or family use engines or electric power generation products, operating in the USA, its territories and OF THIS TEXT DOES NOT CONSTITUTE ANY REPRESENTATION OR ACCEPTANCE BY CATERPILLAR OF
possessions, some states do not allow limitations on how long an implied warranty may last nor allow the exclusion LIABILITY TO THE USER OR ANY OTHER PERSON IN ADDITION TO THAT WHICH CATERPILLAR MAY HAVE
or limitation of incidental or consequential damages. Therefore, the previously expressed exclusion may not apply to UNDER THE AUSTRALIAN CONSUMER LAW.
you. This warranty gives you specific legal rights and you may also have other rights, which vary by jurisdiction. To
TO THE EXTENT THE PRODUCTS FALL WITHIN THIS SECTION C BUT ARE NOT OF A KIND ORDINARILY
find the location of the nearest Cat dealer or other authorized repair facility, call (800) 447-4986. If you have questions
ACQUIRED FOR PERSONAL, DOMESTIC OR HOUSEHOLD USE OR CONSUMPTION, CATERPILLAR LIMITS
concerning this warranty or its applications, call or write:
ITS LIABILITY TO THE EXTENT IT IS PERMITTED TO DO SO UNDER THE AUSTRALIAN CONSUMER LAW
In USA and Canada: Caterpillar Inc., Engine Division, P. O. Box 610, Mossville, IL 61552-0610, Attention: Customer TO, AT ITS OPTION, THE REPAIR OR REPLACEMENT OF THE PRODUCTS, THE SUPPLY OF EQUIVALENT
Service Manager, Telephone (800) 447-4986. Outside the USA and Canada: Contact your Cat dealer. PRODUCTS, OR THE PAYMENT OF THE COST OF SUCH REPAIR OR REPLACEMENT OR THE ACQUISITION
OF EQUIVALENT PRODUCTS.
B) For products operating in Australia, Fiji, Nauru, New Caledonia, New Zealand, Papua New Guinea, the Solomon
Islands and Tahiti, the following is applicable: THE WARRANTY SET OUT IN THIS DOCUMENT IS GIVEN BY CATERPILLAR INC. OR ANY OF ITS
SUBSIDIARIES, 100 N. E. ADAMS ST, PEORIA, IL USA 61629, TELEPHONE 1 309 675 1000, THE USER IS
THIS WARRANTY IS IN ADDITION TO WARRANTIES AND CONDITIONS IMPLIED BY STATUTE AND OTHER RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH MAKING A CLAIM UNDER THE WARRANTY SET
STATUTORY RIGHTS AND OBLIGATIONS THAT BY ANY APPLICABLE LAW CANNOT BE EXCLUDED, OUT IN THIS DOCUMENT, EXCEPT AS EXPRESSLY STATED OTHERWISE IN THIS DOCUMENT, AND THE
RESTRICTED OR MODIFIED (“MANDATORY RIGHTS”). ALL OTHER WARRANTIES OR CONDITIONS, EXPRESS USER IS REFERRED TO THE BALANCE OF THE DOCUMENT TERMS CONCERNING CLAIM PROCEDURES,
OR IMPLIED (BY STATUTE OR OTHERWISE), ARE EXCLUDED. WITHOUT LIMITING THE FOREGOING CATERPILLAR RESPONSIBILITIES AND USER RESPONSIBILITIES.
PROVISIONS OF THIS PARAGRAPH, WHERE A PRODUCT IS SUPPLIED FOR BUSINESS PURPOSES, THE
CONSUMER GUARANTEES UNDER THE CONSUMER GUARANTEES ACT 1993 (NZ) WILL NOT APPLY. TO THE EXTENT PERMISSIBLE BY LAW, THE TERMS SET OUT IN THE REMAINDER OF THIS WARRANTY
DOCUMENT (INCLUDING SECTION B) CONTINUE TO APPLY TO PRODUCTS TO WHICH THIS SECTION C
NEITHER THIS WARRANTY NOR ANY OTHER CONDITION OR WARRANTY BY CATERPILLAR, EXPRESS APPLIES.
OR IMPLIED (SUBJECT ONLY TO THE MANDATORY RIGHTS), IS APPLICABLE TO ANY ITEM CATERPILLAR
SELLS THAT IS WARRANTED DIRECTLY TO THE USER BY ITS MANUFACTURER. ©2016 Caterpillar All Rights Reserved.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow" the "Power Edge" trade dress as well as corporate and
IF THE MANDATORY RIGHTS MAKE CATERPILLAR LIABLE IN CONNECTION WITH SERVICES OR GOODS, product identity used herein, are trademarks of Caterpillar and may not be used without permission.
THEN TO THE EXTENT PERMITTED UNDER THE MANDATORY RIGHTS, THAT LIABILITY SHALL BE LIMITED
AT CATERPILLAR’S OPTION TO (a) IN THE CASE OF SERVICES, THE SUPPLY OF THE SERVICES AGAIN OR
THE PAYMENT OF THE COST OF HAVING THE SERVICES SUPPLIED AGAIN AND (b) IN THE CASE OF GOODS,
THE REPAIR OR REPLACEMENT OF THE GOODS, THE SUPPLY OF EQUIVALENT GOODS, THE PAYMENT OF
THE COST OF SUCH REPAIR OR REPLACEMENT OR THE ACQUISITION OF EQUIVALENT GOODS.