4 A P P L I C AT I O N G U I D E A C H 5 8 0 O V E R R I D E M O D E
—
What is override mode?
Large buildings and other public facilities need and firefighting once a fire occurs. This increases
sophisticated heating, ventilation and air safety of the building’s occupants and minimizes
conditioning systems. It is absolutely critical for fire damage and restoration costs.
controlling the indoor microclimate not just in
everyday use but in extreme situations including The override mode is usually triggered with a
fire. special key at the firefighter’s control station.
Upon receipt of a signal (a contact closure) from
ABB HVAC drives bring enormous benefits to the building’s fire alarm system, the drive enters
buildings, whether commercial, residential, override mode and ignores all other irrelevant
industrial, educational, and other public inputs whether they be analog or digital, and
constructions. Yet many of these benefits haven’t serial communication signals as well as
been widely recognized. As a result, end-users commands from the drive’s keypad.
can be missing out on considerable cost and time
savings, but most importantly, life and property The drive may be programmed to ignore or reset
safety. A significant, built-in feature of the faults to ensure a “run at all costs” operation.
modern variable frequency drive ACH580 to Override mode cannot be triggered by any other
provide safety is override mode. signal: once override mode is activated, the drive
cannot exit this mode until the fire condition
Override mode (that is short for fireman’s signal is reset by opening the contact closure or
override mode) makes our HVAC products removing power from the variable frequency
respond properly in fire/life-safety situations. drive (VFD).
Thus, override mode in ACH580 allows the drive
to run a motor at an adjustable, predefined or PID IMPORTANT: Please check local regulations and
controlled speed in any direction to assist a requirements before using the system.
building smoke control system during evacuation
5
—
Override for ACH580
— During override operation, the ACH580 will be When override is no longer selected, the system
Figure 01. ACH580
control panel view able to control its relay outputs, digital outputs, will return to its operating state before override
for normal and and analog outputs in order to communicate its mode was activated:
override mode
status to the firefighter’s control station and the • Any external interlocks which might interrupt
building management system. These may be the operation of the system during normal
programmed for different functions during operation will again be able to provide the same
override mode than are used during normal function.
operation. • The system’s control state of HAND, OFF or
AUTO will return to the state it was in prior to
While the system will continue to communicate override being activated. If the system was
and provide status information to the building running in HAND mode from a LOCAL speed
control system via a fieldbus connection, reference, it will resume operation at the same
commands from the fieldbus or other speed reference.
connectivity are not able to impact the operation • If the system was in a faulted condition prior to
of the VFD System or write to any of its the activation of override mode, the fault will
parameters while override is active. initially be cleared. However, if the same fault
occurs once override mode has been disabled,
the fault will behave as programmed for normal
operation.
—
Figure 01.
7
—
Override application examples
— Most of the deaths or injuries that occur in a fire are In case of a fire in a large building, basically two
Figure 02. Smoke control
zones in buildings not caused by heat or flame, but instead are the functions of HVAC fans are required: to extract
result of smoke inhalation and intoxication due to smoke and to bring in and manage fresh air flows. It
high levels of carbon monoxide and nitrous oxides. must be ensured that no additional oxygen is being
Therefore, proper smoke management via airflow fed to the fire, while at the same time delivering air
control is critically important for keeping people’s to escape routes and safety zones.
injuries and deaths as well as building damage to a
minimum. Here we give some examples of factors to Smoke control strategy depends on numerous
be considered in fires regarding smoke and air factors such as the number of floors and the
control, and how the ACH580 override mode works construction of the building, but usually it implies
in such situations. pressurization technique in combination with
compartmentation. In such case a building is
HVAC units in residential and considered as a number of smoke control zones that
commercial buildings are separated from each other by walls, doors and
Proper integration of HVAC components including floors. Depending on building and HVAC system
VFDs into a building smoke control system is critical. design, a smoke control zone can include several
Modern smoke control systems can automatically floors and an individual floor may include several
identify the location of the fire, stop fresh air supply smoke control zones.
to the source of fire, exhaust smoke, prevent its fur-
ther spread and change the evacuation route de-
pending where the fire is detected. To accomplish
this advanced control, the VFD package must be
specified with care.
Zone
Pressurized Pressurized controller
stairwell
Zone
controller
Third Floor
Smoke extraction
Fresh air
Smoke zone
Zone
controller
Second Floor
Pressurized
Zone
controller FSCS
First Floor
—
Figure 02.
9
— When a fire occurs in a smoke control zone, all the Evacuation routes in buildings
Figure 03. Pressur-
ized stairwell (single adjacent zones get pressurized. The fireman’s Smoke management for stairwells applies
injection method) smoke control station (FSCS) may also pressurize pressurization technique to prevent smoke from
unaffected zones or leave them in normal operation. spreading through stairwells to other floors and to
Pressure produced by the fans limit smoke provide both safe evacuation routes for building
movement from a smoke control zone to adjacent occupants and staging area for a firefighting crew. In
and unaffected zones (figure 2). Some engineers call case of a fire, a stairwell becomes a high-pressure zone
this concept a pressure sandwich. The ACH580 and pressure difference across closed stairwell doors
override feature allows it to run some exhaust fans prevents smoke infiltration to the stairwell.
in reverse to provide additional pressurizing
capability that may be applicable in certain cases. Stairwell smoke control can use different air injection
Similarly, supply fans in reverse mode can help to and pressure compensation techniques, but the most
remove smoke from the building. reliable and efficient solution to the problems
associated with insufficient or excess pressure in
Consequently, the ACH580 override is able to ensure stairwells is the application of variable frequency
that in complex smoke and airflow situations in drives. VFDs allow to save a considerable amount of
large buildings the fans are running in the way energy by running the fan motor at the required speed
required by fire control. So it can be a very useful in normal mode, but the ACH580 is able to control the
tool in any smoke control strategy to extract the fan’s speed and therefore the pressurization rate even
smoke, while providing fresh air for people. during override mode.
—
Figure 04. Example of Tunnels to the VFD to select the various preset (constant)
override situation in
A road tunnel is a sophisticated engineering speeds or use floating point control.
tunnel ventilation
construction that has very strict requirements for air
quality. Special attention has to be paid to the design of The ACH580 allows to run fans at any speed in either
tunnel ventilation systems which control the direction to better manage the airflow and control
concentration of contaminants emitted by vehicles in smoke movement inside the tunnel. Depending on the
normal operation. However, the most important design location of a fire and its stage, fire control system
requirement is to extract smoke and provide defines airflow speed and direction by, for example,
evacuation routes with fresh air in case of a fire. placing air supply fans into reverse mode to provide
smoke extraction.
Smoke control in tunnels is typically achieved by either
extracting the smoke through air ducts or by pushing Another important feature of the ACH580 indirectly
it through the tunnel and out a portal. The choice of referring to override mode is the ability to handle a
smoke control strategy depends on the type of flying start. Wind in a tunnel often causes freewheeling
ventilation systems, the mode of traffic operation and of the fans. Override mode presumes fans reversing.
the surrounding environment. Thus, the drive that controls the fan motor, needs to be
able to handle a flying start by catching the speed – to
“Regardless ventilation system type, tunnels often ask either continue turning the fan in the same direction,
for more than one fan speed while in override mode,” or change it if necessary. A change of direction can
explains Simo Niskanen, Application Manager for cause a huge mechanical shock to the system. The
HVAC. Override mode in tunnels typically starts at a low advantage of flying start capabilities in the ACH580
speed to maintain stratification and provide escape drive is that it recognizes what is happening in the
routes under the smoke layer. The speed increases after particular situation and is able to quickly and smoothly
finishing the evacuation, to keep the smoke on the “catch the speed” to move the fan in the desired
downstream side of the fire and provide a staging area direction, without first having to take the speed down
for firefighters. In this case, the fireman’s smoke to zero. Flux braking is also possible, so an external
control station will provide individual contact closures braking resistor may not be needed.
Supply fan
Ventilation duct
Fresh air
Supply fan
Ventilation duct
Exhaust air
Fire
—
Figure 04.
11
—
Figure 05. An example Tunnel ventilation systems have sophisticated design for evacuation purposes. Therefore, exhaust fans
of a smoke exhaust-
and high installation and operational costs since they under the ceiling should remove smoke at a rate
ing technique in large
volume spaces consume a considerable amount of energy and require that is greater than or equal to the smoke
expensive, high- technology equipment. The ACH580 production rate, or at a rate that prevents smoke
meets the requirements of the tunnel ventilation layer descending and supports a safe evacuation.
system design while also decreasing power
consumption, boosting efficiency and increasing fire In certain cases, smoke extraction is followed up
and life safety. by introducing fresh air to the space. Fresh air
replaces the volume of smoke exhausted by fans
Malls, atriums, arenas and similar and keeps inner indoor pressure positive to
large volume spaces eliminate the process of smoke extraction.
Similar principles of smoke management apply to
long-span, large-volume buildings but it’s more A complex solution for HVAC systems in large
difficult to control smoke and air flows since such volume spaces is required to maintain
buildings are quite often oriented more comfortable environment during normal
horizontally than vertically. operation and react properly in emergencies.
The ACH580 is well equipped to meet airflow-
In case of fire in large volume spaces, a typical management challenges in malls, atriums,
strategy is to exhaust smoke through the top of arenas and similar buildings. The capabilities
the structure. Smoke management system must of bidirectional variable speed fan control, and
be able to maintain smoke layer above the the flexibility to change from normal mode to
occupiable zone of the highest floor that is used override, while ignoring all the low priority fault
signals make this drive excellent support for fire
control strategies.
Exhaust fan
Smoke layer
Plume
Clear height
Supply fan
Replacement air
Fire
—
Figure 05.
12 A P P L I C AT I O N G U I D E A C H 5 8 0 O V E R R I D E M O D E
—
Benefits for the owners
—
FAQs
What is Firefighter’s override mode? The mode is usually triggered with a special key
The override function is a function that aids at the firefighter’s control station and the drives
building services engineers in designing may then operate the HVAC motors in required
functioning escape routes and escape strategies direction to remove smoke from the building
within a building. It also allows emergency assisting with visibility and safety during
services to easily trigger these essential firefighting. The ACH580’s override mode also
functions to aid in the evacuation of residents or allows stairwell pressurization to be
whilst fighting fires. accomplished, which may require motors to be
run “overspeed” to keep escape routes free of
Variable speed allows more specific escape smoke.
routes to be designed by employing areas of
positive pressure to hold stairwells open, and Why is it not a feature of all drives?
because the speed can be variable and under PID The ACH580 has this feature as a standard
control, changing building conditions can be because of the HVAC industry requirements. The
accommodated. feature allows the drives to take control reducing
complicated wiring and central BMS control and it
Override mode should also ensure the drive can be activated regardless of the state in which
continues to run as long as possible (to the drive is currently in. Other industries do not
destruction if needed) prioritizing this mode and require this special function, so it is not included
giving maximum availability for the mode once with non-HVAC VFDs.
triggered.
What happens if there is no such a feature?
How does it work? Without Firefighter’s override mode built into the
Override mode is triggered by the emergency product, the function would have to be handled
services or the Fire Smoke Control Panel and puts by the building management system (BMS),
the drive into a pre- defined set of running making programming and installation more
instructions, including preset speeds and preset complex. Also, since the drive has to locally
control locations. control the motor so that it runs to destruction
ignoring most faults, this function could not be
The function can be protected by password. performed by the BMS on its own, as the drive
needs a special mode to ignore these issues
When in override mode, the VFD is programmed internally. Simpler systems would have to be
to ignore most of its trips and warnings that employed which would be less straightforward to
would normally stop the drive, ensuring control. As a result, modern high rise buildings
maximum availability during the emergency. would be harder to protect.
Why is it important?
Override mode is designed to allow fire
departments and other emergency responders to
use drives for assistance with smoke
management and to maintain escape routes.
—