You are on page 1of 1

Modbus Hexa Codes for CUMARK Drive

Parametes Address
16-bit binary come from Postion of 06.05 as following:

Data Command Parameters Data


Definition Add Command 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Code (Hexa)
(Hexa) Code(DEC)
Forward Start: 882H 2178 0 0 0 0 1 0 0 0 1 0 0 0 0 0 1 0
Command for Reverse Start: 8882H 34946 1 0 0 0 1 0 0 0 1 0 0 0 0 0 1 0
Drive Stop: 881H 2177 0 0 0 0 1 0 0 0 1 0 0 0 0 0 0 1
(Refer to Fault Reset: 980H 0001 2432 0 0 0 0 1 0 0 1 1 0 0 0 0 0 0 0
Parameter Forward Jog: A80H 2688 0 0 0 0 1 0 1 0 1 0 0 0 0 0 0 0
06.05) Reverse Jog: 8A80H 35456 1 0 0 0 1 0 1 0 1 0 0 0 0 0 0 0
Emergency Stop: 885H 2181 0 0 0 0 1 0 0 0 1 0 0 0 0 1 0 1
Note: Need to reset after emergency stop before starting

VFD Parameters Parameters Attribute Value for the


Parameters Name Add Add
Parameter s Address
(Hexa) (DEC)
22.00 Acc Time1 1600 5632 RW 20
22.01 Dec Time1 1601 5633 RW 10
22.05 Jog Acc Time 1605 5637 RW
22.06 Jog Dec Time 1606 5638 RW
21.05 Speed Ref Jog1 1505 5381 RW
02.15 Filedbus Ref1 0002 2 RO
01.00 Motor Speed 0100 256 RO 1500
20.00 Max Speed 1400 5120 RW 1500