Culture Documents
2003-28
for:
Kloben
Brand Name:
Kloben SP14 CPC Diffusion
Date:
6th October 2003
Address:
Fraunhofer-Institute for Solar Energy Systems ISE
Heidenhofstraße 2
D-79110 Freiburg
Tel.: +49-761-4588-5354; Fax.: +49-761-4588-9000
E-mail: arim.schaefer@ise.fhg.de
Test facility certified by DIN CERTCO
Contents
1 Summary 4
1.1 Boundary conditions for the efficiency curve . . . . . . . . . . 4
1.2 Collector parameters determined . . . . . . . . . . . . . . . . 4
1.3 Incidence angle modifier - IAM (measured at the outdoor test
facility (tracker)) . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Pressure drop . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Effective thermal capacity . . . . . . . . . . . . . . . . . . . . 5
1.6 Summary statement . . . . . . . . . . . . . . . . . . . . . . . 5
2 Test Center 6
3 Orderer 6
7 Pressure drop 16
9 Summary statement 18
Test conditions:
Mean irradiation : 974 W/m
Mean wind speed: 3 m/s
Mean flow rate: 156 kg/h
Kind of fluid: water
Period: September 2003
transversal: longitudinal:
= 1.019 = 0.957
20 50
= 0.985
40
60 = 1.061
3 Orderer
Kloben
Francesco Fontana
Via Rizzotti 1, 37064 Povegliano Veronese , Verona, Italy
Tel: +39 045 7971966
Fax: +39 045 7971866
4.4 Limitations
Maximum pressure: 600 kPa (MS)
Operating pressure: 300 kPa(MS)
Maximum temperature: not measured
Flow range recommendation: 30 l/m h (MS)
8 8 :8 8
97
+*-,/.0*21 1 m a m 79 a;
m 3 a 465 0 7 1a 7 2a (1)
*1 1
< > 5
with: m = e in
@ 0 : Efficiency without heat losses, which means that the mean collector
fluid temperature is equal to the ambient temperature:
B
< CE < e D
= <
in
a
The coefficients A 1a und A 2a describe the heat loss of the collector. The
temperature depedency of the collector heat loss is described by:
B
A 1a C A 2a F < m G < aD
Boundary conditions:
Test method: outdoor, steady state
Latitude: 48.0
Longitude: 7.8
Collector tilt: tracked between 40 and 50
Collector azimuth: tracked
Test conditions:
Mean irradiation : 974 W/m
Mean wind speed: 3 m/s
Mean flow rate: 156 kg/h
Kind of fluid: water
Period: September 2003
B
? ? dH ? m < in < e <eG < in < m < a < m G < a < m G < aD H ? @ a
[W/m ] [-] [kg/h] [ C] [ C] [K] [ C] [ C] [K] [K m /W] [-]
990 0.11 155.1 19.16 26.82 7.66 22.99 22.76 0.23 0.0002 0.633
984 0.11 155.1 19.18 26.79 7.61 22.98 23.23 -0.25 -0.0003 0.633
979 0.11 155.2 19.21 26.77 7.56 22.99 23.45 -0.46 -0.0005 0.633
979 0.11 155.2 19.24 26.76 7.52 23.00 24.10 -1.10 -0.0011 0.629
1048 0.15 155.3 41.99 49.67 7.68 45.83 20.00 25.84 0.0246 0.600
971 0.13 155.0 41.99 49.20 7.21 45.60 19.85 25.74 0.0265 0.607
956 0.13 154.8 42.00 49.12 7.12 45.56 20.15 25.41 0.0266 0.608
946 0.13 155.0 42.01 49.05 7.04 45.53 20.12 25.40 0.0268 0.608
946 0.14 154.9 42.01 48.99 6.99 45.50 20.47 25.03 0.0264 0.603
959 0.11 156.6 66.77 73.33 6.56 70.05 24.04 46.02 0.0480 0.566
954 0.11 156.7 66.79 73.30 6.51 70.04 24.60 45.44 0.0476 0.564
942 0.11 156.6 66.82 73.30 6.47 70.06 24.58 45.48 0.0483 0.569
924 0.11 156.6 66.81 73.19 6.37 70.00 24.88 45.12 0.0488 0.571
917 0.11 156.3 66.82 73.13 6.31 69.98 24.10 45.87 0.0500 0.569
1017 0.12 155.9 91.92 98.35 6.43 95.13 19.99 75.15 0.0739 0.523
1022 0.11 156.1 91.98 98.44 6.47 95.21 21.11 74.10 0.0725 0.524
1025 0.11 156.1 91.97 98.46 6.49 95.21 21.60 73.61 0.0719 0.525
0.9
Efficiency η (based on aperture area)
0.8
0.7
0.6
I 0.5
0.4
0.3
0.2
0.1
0
-0.01 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
2
∆T/G [K*m /W]
Figure 2: Efficiency curve with measurement points based on aperture area 2.202 mJ
Results:
based on aperture area based on absorber area
(2.202 m ): (2.359 m ):
@ 0a = 0.632 @ 0A = 0.590
A 1a = 0.936 W/m K A 1A = 0.874 W/m K
A 2a = 0.0076 W/m K A 2A = 0.007 W/m K
0.9
Efficiency η (based on aperture area)
0.8
0.7
0.6
I 0.5
0.4
0.3
0.2
0.1
0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
∆T/G [K*m2/W]
Figure 3: Efficiency curve scaled to 800 W/mJ based on aperture area 2.202 mJ
80
70
Pressure drop ∆p [mbar]
60
50
40
30
20
10
0
0 50 100 150 200 250 300 350 400 450 500
Mass flow [kg/h]
Figure 4: Measured pressure drop of the collector Kloben SP14 CPC Diffusion
87.8 kJ/K
The effective thermal capacity based on the aperture area 2.202 m is:
39.9 kJ/K m