Professional Documents
Culture Documents
Introduction.
Nowadays, we spend most of the day Ensuring adequate air exchange and
in closed rooms. This is why heat- thus determining the volume flow is an
ing, ventilation and air conditioning important quality factor when it comes
(HVAC) systems are installed which are to commissioning and operating HVAC
intended to ensure pleasant ambient systems. The reliable determination of
conditions indoors. Ventilation is of air velocity in ducts is one of the most
particular importance here. Firstly, it challenging measurements which a
is not only used to provide fresh air, ventilation and air conditioning techni-
but also for extracting pollutants, for cian has to carry out.
instance removing excess humidity
from rooms.
2
Contents:
3
Air flow measurements in ducts according to DIN EN 12599
1. Importance of
air velocity
In line with the motto: "The more, the On the other hand, too low a volume
merrier", HVAC systems are often flow can also be problematic. The
operated with air volumes that are too people in the room have too little
high. This excessive requirement leads fresh air to breathe in. The indoor air
to increased operating costs. Energy is "stale", because the CO2 content
expenditure for the fan rises, because in the room is too high. Low volume
a larger volume of air has to be moved flows can also have negative impacts
through the system. However, costs on the system's hygiene: there is the
are also incurred for conditioning risk of germ formation in the system
the air (cooling, heating, humidifying when movement of the humidified air
or dehumidifying) and these can be in the ducts is too slow. A correctly set
reduced when the system is set cor- HVAC system therefore not only helps
rectly. In addition, a high air exchange make the indoor climate comfortable,
often leads to draughts occurring in but also helps save costs.
the room, making people feel uncom-
fortable.
4
2. M
easurement of the
correct air velocity
The key parameter for evaluating the In order to meet quality requirements
functional capability of the HVAC when it comes to determining volume
system is the air volume flow. This is flow, there are different standards all
the product of flow velocity and duct over the world dealing with the correct
area. Since, in practice, flow velocity in measurement of flow velocities. In
the duct cross-section is not the same, addition to EN 12599, which is the
an individual point measurement leading standard in Germany and
does not suffice when it comes to large parts of Europe, there are also
determining the average air velocity. EN 16211 and ASHRAE 111. What all
Disruptors, such as dampers, elbows methods have in common is that the
and the like, have an influence on measuring points are distributed over
the velocity profile in the duct, which the duct cross-section according to
means a so-called grid measurement the size of the duct in line with defined
has to be carried out at several specifications, that a distinction
locations in the duct. is made between rectangular and
round ducts and that the readings are
averaged.
5
Air flow measurements in ducts according to DIN EN 12599
Round
Rectangular
Square
Dh = diameter
2×duct length×duct width
Dh = edge length Dh =
duct length+duct width
6
3.1. Flow profiles in the duct
7
Air flow measurements in ducts according to DIN EN 12599
Laminar Turbulent
Max
A(m2)
1/3D mean
Min
Laminar and turbulent air flow velocity. Different flow profiles are generated, depending on the flow velocity.
8
As a rule, return flows are diminished distorted that a large number of
after a distance of 2-times the measuring points are required to keep
hydraulic diameter from the disruption, the measurement uncertainty low.
however the flow profile is so strongly
10 m/s
10 m/s
10 m/s
5 m/s
5 m/s
5 m/s
Irregularities in the flow profile are diminished as the distance from the disruption increases. The greater the dis-
tance from the disruption, the more uniform the flow profile and the more precise the measurement or the smaller
the number of measuring points required.
9
Air flow measurements in ducts according to DIN EN 12599
Grid
A
yi
xi
Division of the duct cross-section according to the trivial method. The measuring points are at the centre points of
the areas.
10
4.1. Trivial method
The trivial method does not assume the number of measuring points has
any special velocity distribution in the to be increased accordingly. It is large
duct. The duct cross-section is simply enough when the reading fluctuations
divided into several measurement within a partial area are so small that
areas with an identical size. The the values measured at the centre
measuring point is in the middle of the points can be considered to be mean
partial area. values in the context of the specified
measuring accuracy.
Where there is a uniform velocity
profile, this enables a meaningful The reading for air volume flow for the
measurement result to be achieved whole duct is then calculated as an
even with a small number of arithmetic mean from the partial area
measuring points. Where there are readings.
larger differences in the flow velocities,
11
Air flow measurements in ducts according to DIN EN 12599
The procedure for the centroidal axis axis is the radius (y) which bisects the
method which should be used in round partial area.
ducts is similar. It involves the circular
duct cross-section being divided into Since it cannot always be assumed
rings of an equal area and a circle in that the flow will move forwards in a
the middle. The measuring location in rotationally symmetrical way in the
the ring area and in the inner circle is duct, two measurement planes should
on the centroidal axis of each partial be selected for round ducts which are
area. In this respect, the centroidal at 90° angles to one another.
Measuring
Rings
points
Centroidal
axes
Determination of the measuring locations of a circular cross-section with the centroidal axis method.
12
4.3. Calculation of the volume flow
V = A v 3600
V = volume flow in m³/h
v = mean flow velocity in m/s
A = flow cross-section in m²
Example:
A cross-section A of 0.5 m² and a
measured mean velocity of 4 m/s gives a
volume flow of 7200 m³/h
13
Air flow measurements in ducts according to DIN EN 12599
14
a/Dh
10
Determination of the irregu-
8 larity U of the flow profile ac-
7 cording to the distance from
6 the disruption.
5
Example:
4
For a measurement at a
3
distance of two-times the
hydraulic diameter, U is 40%
(reading direction see yellow
2 arrows).
On the other hand, for a = 4
Dh, U is under 20% (green
arrows).
1
4 5 6 7 8 9 10 20 30 40 50 %
15
Air flow measurements in ducts according to DIN EN 12599
4 6 12 20 28 36 42
5 5 11 17 24 31 36
6 5 10 15 21 27 32
8 4 8 13 18 23 27
10 3 7 12 16 20 24
20 2 5 8 11 14 16
30 2 4 7 9 11 14
50 1 3 5 7 8 10
100 1 2 3 5 6 7
200 1 1 2 3 4 5
Example: For U = 40% and a specified measurement uncertainty of τU = ±15%, 20 measuring points are needed
(yellow marks, reading direction from top to bottom and then to the left). For U = 20%, 8 measuring points suffice
(green marks).
16
Tip: As you increase the measuring distance from the disruption, you can
reduce the number of required measuring points and thus the effort involved in
the measurement, without impairing the measuring accuracy.
17
Air flow measurements in ducts according to DIN EN 12599
x x x x
V1 V2
Division of the duct
x x x x cross-section into four
quadrants. A mean value
is generated in each of
x x x x the quadrants from the
measured flow velocities.
V3 V4
x x x x
The highest and lowest mean value will according to the following formula:
give the irregularity of the flow profile
vmax – vmin
U=
2v
U (*100) = irregularity of the flow profile
as a %
18
Step 4: Total error calculation Uncertainty due to influences at
according to DIN EN 12599 the measuring point and measuring
In addition to the measurement instrument errors (the accuracy of
uncertainty due to (flow) influences at the measuring instrument and/or the
the measuring point, there are other probes) have the greatest influence in
possible error sources which may this respect. With modern measuring
need to be taken into account: instruments, like the testo 400,
these are automatically taken into
• Measurement uncertainty when
account when the total uncertainty is
reading off
calculated, thus supporting standard-
• Measurement uncertainty of the
compliant performance of the
mean value (with fluctuating
measurement and documentation of
measurement parameter)
the results.
• Error of the measuring instrument
display (measuring instrument
error)
• Measurement uncertainties of the
material values, e.g. air density
• Uncertainties with conversion
19
Air flow measurements in ducts according to DIN EN 12599
www.testo.com