You are on page 1of 20

Practical guide

Air flow measurements


in ducts according to
DIN EN 12599.
Air flow measurements in ducts according to DIN EN 12599

Introduction.

Nowadays, we spend most of the day Ensuring adequate air exchange and
in closed rooms. This is why heat- thus determining the volume flow is an
ing, ventilation and air conditioning important quality factor when it comes
(HVAC) systems are installed which are to commissioning and operating HVAC
intended to ensure pleasant ambient systems. The reliable determination of
conditions indoors. Ventilation is of air velocity in ducts is one of the most
particular importance here. Firstly, it challenging measurements which a
is not only used to provide fresh air, ventilation and air conditioning techni-
but also for extracting pollutants, for cian has to carry out.
instance removing excess humidity
from rooms.

2
Contents:

1. Importance of air velocity.......................................................................... 04

 easurement of the correct air velocity...................................................... 05


2. M

3. The right measuring location..................................................................... 06


3.1 Flow profiles in the duct....................................................................... 07
3.2 Distance from disruptions.................................................................... 08

4. The measurement method......................................................................... 10


4.1 Trivial method...................................................................................... 11
4.2 Centroidal axis method........................................................................ 12
4.3 Calculation of the volume flow............................................................. 13

5. Evaluation of the readings ........................................................................ 14


6. The measurement report .......................................................................... 20

3
Air flow measurements in ducts according to DIN EN 12599

1. Importance of
air velocity

In line with the motto: "The more, the On the other hand, too low a volume
merrier", HVAC systems are often flow can also be problematic. The
operated with air volumes that are too people in the room have too little
high. This excessive requirement leads fresh air to breathe in. The indoor air
to increased operating costs. Energy is "stale", because the CO2 content
expenditure for the fan rises, because in the room is too high. Low volume
a larger volume of air has to be moved flows can also have negative impacts
through the system. However, costs on the system's hygiene: there is the
are also incurred for conditioning risk of germ formation in the system
the air (cooling, heating, humidifying when movement of the humidified air
or dehumidifying) and these can be in the ducts is too slow. A correctly set
reduced when the system is set cor- HVAC system therefore not only helps
rectly. In addition, a high air exchange make the indoor climate comfortable,
often leads to draughts occurring in but also helps save costs.
the room, making people feel uncom-
fortable.

4
2. M
 easurement of the
correct air velocity

The key parameter for evaluating the In order to meet quality requirements
functional capability of the HVAC when it comes to determining volume
system is the air volume flow. This is flow, there are different standards all
the product of flow velocity and duct over the world dealing with the correct
area. Since, in practice, flow velocity in measurement of flow velocities. In
the duct cross-section is not the same, addition to EN 12599, which is the
an individual point measurement leading standard in Germany and
does not suffice when it comes to large parts of Europe, there are also
determining the average air velocity. EN 16211 and ASHRAE 111. What all
Disruptors, such as dampers, elbows methods have in common is that the
and the like, have an influence on measuring points are distributed over
the velocity profile in the duct, which the duct cross-section according to
means a so-called grid measurement the size of the duct in line with defined
has to be carried out at several specifications, that a distinction
locations in the duct. is made between rectangular and
round ducts and that the readings are
averaged.

We will now go into the correct


measurement of volume flow
according to EN 12599.

5
Air flow measurements in ducts according to DIN EN 12599

3. The right measuring location

The decisive factor when it comes to • Minimum distances from disruptions


meaningful measurements is selecting must be adhered to: at least 6-times
a suitable measuring point. This is the hydraulic diameter downstream,
already established by the system and 2-times the hydraulic diameter
planner in the execution plan (project upstream
plan). The following criteria must be • The measuring points must be
taken into account here: easily accessible and there must be
• Air flow measuring points must be enough space available for handling
allowed for on all main ducts and the measuring instrument.
on supply lines to rooms with high • The flow must be free of any return
requirements. flow or swirling

Round
Rectangular
Square

Dh = diameter
2×duct length×duct width
Dh = edge length Dh =
duct length+duct width

Calculation of the hydraulic diameter Dh for different duct shapes.

6
3.1. Flow profiles in the duct

Air which flows through a duct does Turbulent flow.


not have a uniform velocity. As a In this case, the flow velocities are to
rule, the air in the middle flows a large extent identical right across
faster than at the duct wall. There the duct diameter, but the velocity
are greater resistances at the duct does drastically fall at the duct wall.
wall due to friction and these have to However, the flow lines are non-
be overcome. A distinction is made directional, in other words the air
between two basic flow profiles: moves chaotically and with a high
degree of friction.
Laminar flow.
Laminar flow involves a uniform air
All mixed forms between these two
flow with the flow lines running parallel
ideal forms are possible, with every
to one another. There is no turbulence
disruptor (such as dampers, elbows,
and a distinct maximum velocity in the
valves, volume flow regulators, etc.)
middle of the duct. The average flow
changing the flow profile.
velocity is approximately at a third of
In practice, a so-called grid
the duct diameter. As soon as the air
measurement over the whole duct
velocity rises, laminar flow increasingly
cross-section is indispensable for
converts into turbulent flow.
reproducible results.

7
Air flow measurements in ducts according to DIN EN 12599

Laminar Turbulent

Max
A(m2)

1/3D mean
Min

Laminar and turbulent air flow velocity. Different flow profiles are generated, depending on the flow velocity.

3.2. Distance from disruptions

Ideal flow profiles are almost can be considerably reduced.


exclusively found in very long ducts In practice, dampers, valves,
which run in a straight line and where elbows and other bends prevent the
there are no disruptions. For this development of a consistent flow.
reason, minimum distances from In unfavourable circumstances, this
disruptions have to be adhered to. results in the maximum of the flow
profile not being in the middle of
Where the distance from disruptions the duct, but being shifted towards
is sufficient, the number of measuring the edge, in more problematic
points which have to be measured circumstances there may also be
spread across the duct cross-section return flows or areas with no flow.

8
As a rule, return flows are diminished distorted that a large number of
after a distance of 2-times the measuring points are required to keep
hydraulic diameter from the disruption, the measurement uncertainty low.
however the flow profile is so strongly
10 m/s

10 m/s

10 m/s
5 m/s

5 m/s

5 m/s

Distance Distance Distance


7 x Dh 2 x Dh 1 x Dh

Balanced flow Distorted flow


profile profile
D=250
Flow profile with
return flow
AIR

Irregularities in the flow profile are diminished as the distance from the disruption increases. The greater the dis-
tance from the disruption, the more uniform the flow profile and the more precise the measurement or the smaller
the number of measuring points required.

9
Air flow measurements in ducts according to DIN EN 12599

4. The measurement method

The representative average flow round ducts. DIN EN 12599 envisages


value in the duct cross-section the following two measurement
has to be established to determine methods:
the air volume flow. To do this, the
• the trivial method for measurements
measurement area is split into partial
in air ducts with a rectangular or
areas and the velocity is determined
square cross-section
at the central point of the partial
• the centroidal axis method for
areas. This method is called grid
measurements in ducts with a
measurement. The method for dividing
circular cross-section
the duct cross-section into partial
areas is different for rectangular and

Grid
A

yi

xi

Duct Measurement plane B

Division of the duct cross-section according to the trivial method. The measuring points are at the centre points of
the areas.

10
4.1. Trivial method

The trivial method does not assume the number of measuring points has
any special velocity distribution in the to be increased accordingly. It is large
duct. The duct cross-section is simply enough when the reading fluctuations
divided into several measurement within a partial area are so small that
areas with an identical size. The the values measured at the centre
measuring point is in the middle of the points can be considered to be mean
partial area. values in the context of the specified
measuring accuracy.
Where there is a uniform velocity
profile, this enables a meaningful The reading for air volume flow for the
measurement result to be achieved whole duct is then calculated as an
even with a small number of arithmetic mean from the partial area
measuring points. Where there are readings.
larger differences in the flow velocities,

11
Air flow measurements in ducts according to DIN EN 12599

4.2. Centroidal axis method

The procedure for the centroidal axis axis is the radius (y) which bisects the
method which should be used in round partial area.
ducts is similar. It involves the circular
duct cross-section being divided into Since it cannot always be assumed
rings of an equal area and a circle in that the flow will move forwards in a
the middle. The measuring location in rotationally symmetrical way in the
the ring area and in the inner circle is duct, two measurement planes should
on the centroidal axis of each partial be selected for round ducts which are
area. In this respect, the centroidal at 90° angles to one another.

Measuring
Rings
points

Centroidal
axes

Determination of the measuring locations of a circular cross-section with the centroidal axis method.

12
4.3. Calculation of the volume flow

The velocity readings determined via


the trivial method or centroidal axis
method should be used to calculate
the average flow velocity, from which
the air volume flow should then be
calculated. The calculation is carried
out using the following formula:

V = A v 3600
V = volume flow in m³/h
v = mean flow velocity in m/s
A = flow cross-section in m²

Example:
A cross-section A of 0.5 m² and a
measured mean velocity of 4 m/s gives a
volume flow of 7200 m³/h

Determination of the volume flow based on the mean


flow velocity and the duct cross-section

13
Air flow measurements in ducts according to DIN EN 12599

5. Evaluation of the readings

There is a requirement in DIN EN therefore always be seen in connection


12599 for the accuracy of the air with the distance from disruptions,
volume flow to be determined with a because these are decisive when it
measurement uncertainty of ±10%. comes to irregularity in the profile.
Here, the question that now has to
be asked is how accurate was the Step 1: Determining the
measurement which has just been irregularity of the flow profile
carried out. DIN EN 12599 also The required number of measuring
provides answers to this. points in a specified duct cross-
section depends on the irregularity
In addition to the uncertainty of the (distortion) of the flow profile. The
measuring instrument and the probe diagram below shows an empirical
used, the irregularity of the flow profile relationship between the relative
is a crucial factor for determining distance a/Dh (distance from the
the total error. Where there is a disruption expressed as quantity
large profile irregularity, the required of hydraulic diameters) and the
measurement uncertainty of ±10% irregularity U of the flow profile (as a
can only be achieved with a number percentage). It can be seen that the
of measuring points that is just as profile irregularity diminishes as the
large, but this is very time-consuming. distance increases.
The number of measuring points must

14
a/Dh

10
Determination of the irregu-
8 larity U of the flow profile ac-
7 cording to the distance from
6 the disruption.
5

Example:
4
For a measurement at a

3
distance of two-times the
hydraulic diameter, U is 40%
(reading direction see yellow
2 arrows).
On the other hand, for a = 4
Dh, U is under 20% (green
arrows).

1
4 5 6 7 8 9 10 20 30 40 50 %

15
Air flow measurements in ducts according to DIN EN 12599

Step 2: Determining the number of read off the number of necessary


required measuring points measuring points required to adhere
With the value for U which has been to a particular specified measuring
determined using the diagram, from accuracy.
the following table you can now

Number of Uncertainty of the measurement τu as a %


measuring Irregularity of the profile U as a %
points
2 10 20 30 40 50

4 6 12 20 28 36 42

5 5 11 17 24 31 36

6 5 10 15 21 27 32

8 4 8 13 18 23 27

10 3 7 12 16 20 24

20 2 5 8 11 14 16

30 2 4 7 9 11 14

50 1 3 5 7 8 10

100 1 2 3 5 6 7

200 1 1 2 3 4 5

Uncertainty of the measurement depending on the number of measuring points.

Example: For U = 40% and a specified measurement uncertainty of τU = ±15%, 20 measuring points are needed
(yellow marks, reading direction from top to bottom and then to the left). For U = 20%, 8 measuring points suffice
(green marks).

16
Tip: As you increase the measuring distance from the disruption, you can
reduce the number of required measuring points and thus the effort involved in
the measurement, without impairing the measuring accuracy.

Step 3: Calculating the irregularity duct cross-section into four quadrants


of the flow profile with an equal area and determine the
Using your readings, you can now arithmetic mean of the readings for
check the irregularity of the flow profile each of the quadrants.
arithmetically. To do this, split the

17
Air flow measurements in ducts according to DIN EN 12599

x x x x
V1 V2
Division of the duct
x x x x cross-section into four
quadrants. A mean value
is generated in each of
x x x x the quadrants from the
measured flow velocities.
V3 V4

x x x x

The highest and lowest mean value will according to the following formula:
give the irregularity of the flow profile

vmax – vmin
U=
2v
U (*100) = irregularity of the flow profile
as a %

 aximum of the arithmetic


Vmax (m/s) = m
mean of all four quadrants

 inimum of the arithmetic


Vmin (m/s) = m
mean of all four quadrants

V (m/s) = arithmetic mean of the velocity


in the whole cross-section

18
Step 4: Total error calculation Uncertainty due to influences at
according to DIN EN 12599 the measuring point and measuring
In addition to the measurement instrument errors (the accuracy of
uncertainty due to (flow) influences at the measuring instrument and/or the
the measuring point, there are other probes) have the greatest influence in
possible error sources which may this respect. With modern measuring
need to be taken into account: instruments, like the testo 400,
these are automatically taken into
• Measurement uncertainty when
account when the total uncertainty is
reading off
calculated, thus supporting standard-
• Measurement uncertainty of the
compliant performance of the
mean value (with fluctuating
measurement and documentation of
measurement parameter)
the results.
• Error of the measuring instrument
display (measuring instrument
error)
• Measurement uncertainties of the
material values, e.g. air density
• Uncertainties with conversion

19
Air flow measurements in ducts according to DIN EN 12599

6. Evaluation of the readings

A full measurement report must


be issued to the client, at the
latest at the time of handover. This
measurement report covers details
of the building and project name,
the specific measuring location, the
agreed target value, the measuring
instrument used, the recorded
readings and the uncertainty of the
measurement results, along with the

Subject to change, including technical modifications.


date and place of the measurement.
The testo 400 enables you to
complete this measurement report
directly in the measuring instrument
and to send it by e-mail. It can’t get
any more effective than that.

www.testo.com

You might also like