Professional Documents
Culture Documents
BV-H2015 EN (V5)
PASS - Process Advanced Service System
Services and wearing parts for your applications.
Looking for after-sales solutions? Our comprehensive Process Advanced Service System (PASS) provides you with a customer-ori-
ented after-sales service tailored to your specific requirements.
Our experienced Schenck Process team will be happy to help you to create PASS packages that satisfy your needs. These packages
can consist of replacement and wear parts and a range of services and other components of the highest quality. We would be happy
to provide you with individual consultation - whether as part of a PASS contract or as an individual enquiry.
Contacts
Find your local contact on our Internet page:
http://www.schenckprocess.com/contact
Copyright
All rights reserved. Any reproduction of this documentation, regardless of method, without prior permission in writing, even by excerpt,
is prohibited. Subject to change without prior notice.
Contents
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
–i–
Schenck Process Group
Contents
List of figures........................................................................................................................................ 79
Index ...................................................................................................................................................... 81
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– ii –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
Basic function
▪ Digital display consoles without auxiliary energy
▪ Connection as for passive analogue displays, voltage drop approx. 1 V
▪ LC display with 30 / 50 mm digit height
▪ Scaling of values measured by keyboard and display
▪ Quick bar chart for following trend (41 segments, image build up 4 times per second)
▪ Bar chart is independently scalable (zoom function)
▪ Various housing designs (monitor panel and field housing)
Options
▪ Warning if limit values are exceeded with extra limit value bar chart on the display and two switching
outputs (limit value message)
▪ Limit value functions with switching hysteresis and time delay
▪ Field housing with extra (second) cable inlet
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
–1–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
Explosion Protection
Because of the different completion statuses, the details on the identification plate must be bindingly ob-
served when using the display consoles.
A distinction is made here between a version in category 2G and a different version in 2G/2D. All versions
are designed in Explosion Protection Class "i" and always have to be operated intrinsically safe.
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
–2–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
–3–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DANGER
Non-intrinsically safe connection in explosion protection
class "Ex i"
Danger to life from explosion.
– Operating equipment in Explosion Protection Class "Ex i" may only
be operated intrinsically safely.
> Only connect device to an intrinsically safe 4 … 20 mA measuring
circuit.
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
–4–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
–5–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
–6–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
NOTICE
Testing the display segments
Immediately after connecting the device, a test of the display segments
appears for one second. The version number of the device is displayed
for a further second.
The following parameters are set as standard after the first connection:
Scaling (display and bar Limit values Hysteresis/ Switching contacts Code words
chart) Time delay
4 mA measuring current – Lower: 4.00 mA 0.1 / 0 s Working current prin- CODE1: 0001
4.00 Upper: 20.00 mA ciple CODE2: 0002
20 mA measuring current –
20.00
NOTICE
Restore factory parameters (reset)
Simultaneously press the buttons [ENTER] and [MOVE-RIGHT] during
the switching-on to restore the factory settings of the parameters and the
factory-set calibration applies again.
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
–7–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
1.5 Operation
1.5.2 Keyboard
There are three membrane buttons with various function symbols on the front of the DLZ. With these keys,
the user can switch on and off all functions of the device and adjust all individual settings. The buttons are
named after their function:
Button Function
[ENTER]
Start input menu
Activate display menu item/confirm input
[UP]
Measuring currency check
Modification of the selected number
'Passing' menu items
[RIGHT]
Change to limit value display:
Displays the lower (Min) and upper (Max) limit value
Change the selected number
'Passing' menu items
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
–8–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
NOTICE
Display consoles without (optional) switching outputs
All the menu items, which contain the limit value input and output, are
omitted for this.
Displays (states), which are saved twice indicate that an input is made in these states
and the display changes with each press of the button.
> Perform 'Input of values' (see flow chart "Input of values").
Operating state
After clamping, the display consoles DLZ 030/050 start with the initialization of parameter and scaling data.
These are read from the internal EEPROM memory and come from the previous operation. This memory is
prepopulated with standard values when delivered new. The display console then starts to display the meas-
ured current signal on the digital display and in an analogue form in the bar charts. As a result, the device is
in working or operating mode and entries can be made (see flow chart in »Menu controls, flow
charts [➙21]«).
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
–9–
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
[MOVE RIGHT] button: Select limit value display. [limit high] appears.
Confirming by pressing the [ENTER] button displays the upper limit value.
Pressing the [MOVE RIGHT] button ends the limit value display/'normal' mode is re-
stored.
Limit values can also be changed by pressing the [ENTER] button again.
The display switches to edit mode.
Edit mode
A flashing bar appears under the mathematical sign position.
[MOVE RIGHT] button: Select number
[MOVE UP] button: Increase value by 1
[ENTER] button (see value input flow chart in »Menu controls, flow charts [➙21]«).
Confirm limit value
Password query
In order to prevent unauthorized persons from modifying the limit values, a query of
password No. 2 is required. Entering an incorrect password immediately ends the limit
value entry. At delivery, password No. 2 is set to [0002].
NOTICE
Disable password query No. 2
Using the assigned password [0000].
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 10 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
Parametrization
Starting from the operating state: The [ENTER] button switches to the input menu.
Entering and manipulating the instrument adjustments should be reserved for the au-
thorized persons. Consequently, access to the input menu is protected by password
No. 1.
Factory settings: [0001].
The password query to access the input menu cannot be switched off.
Scaling menu:
The digital display with decimal point and the bar chart are scaled here (see scaling
menu flow chart in »Menu controls, flow charts [➙21]«).
Start the scaling menu: [ENTER] button
[MOVE RIGHT] button: Select next submenu (limit value menu) (only for devices with
switching output option).
Limit value menu: Enter the actual limit value, define a switching-off hysteresis/
switching-off delay/work principle for the switching outputs(see also limit value flow
charts in »Menu controls, flow charts [➙21]«).
Password No. 2 with reference [0000] is not queries for the limit value display.
The initial calibration takes place in the factory before delivery. Recalibration is generally not neces-
sary and may only be carried out by specially trained personnel.
This is the end of the input menu. Exiting from the menu is confirmed with the
[ENTER] button. The display console is then in operating mode.
The input menu can be repeated by pressing the [MOVE UP] button. The selection of
the scaling menu is displayed (see above).
If values were entered in the input menu that are outside their correct range, the input menu cannot
be exited. The display automatically changes to the valid value in edit mode.
Tab. 6: Parametrization
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 11 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
Fig. 3: Switching behaviour of the lower limit value at the switching output Min.
Fig. 4: Switching behaviour of the upper limit value at the switching output Max.
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 12 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
Switching delay
ON
OFF
Time
Measuring value
MAX limit value
Time
Limit value time exceeded for the first time
Vermax.cdr
The switching delay 'te' is the time between the first exceedance of the measured value above the limit value
and the switching time of the switching output Max. This applies correspondingly to the switching output Min.
If the measured value in the mean time is less than the limit value, the time delay waits for the entire
period 'te' again from the start.
Presets
▪ Good range: +10 °C … +20 °C
▪ Measuring range of the sensor: -20 °C … +30 °C
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 13 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
Settings
▪ Measuring range: -20 °C … +30 °C for 4 … 20 mA
▪ Bar chart: -5 °C … +25 °C
▪ Limit values: Lower limit value (min): +10 °C / Upper limit value (max): +20 °C
▪ Hysteresis: 0.5 °C
▪ Switching principle: Closed-current principle
▪ Switching delay: 5 seconds
Procedure
[ENTER] button: Exit operating display and enable input menu.
Enter the password using the arrow keys and press [ENTER].
Tab. 7: Procedure
Scaling starts with determining the position of the decimal point. The position
specified here
is binding for entries: Measured value scaling, bar chart scaling, limit values.
As [2000] is entered later for the upper scaling point, the decimal point has to
be set after the second position.
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 14 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
Press the [MOVE UP] button repeatedly until the digit '0' appears.
1. After the procedure described above, enter the sequence of figures [3000] for the upper scaling mark
30 °C.
2. Confirm with [ENTER].
NOTICE
Achieving the best possible precision for the display console
Enter the upper scaling mark 'as high as possible' so that the first digits
are never zeroes.
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 15 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
For the upper bar chart scaling mark, enter [2500] for +25 °C.
Confirm with the [ENTER] button and exit the scaling menu.
Press the [ENTER] button to enter the hysteresis of the lower limit value. Now
use the arrow keys to enter the value [0050] for +0.5 °C.
Confirm with [ENTER].
Press the [ENTER] button to enter the hysteresis of the upper limit value. Now
use the arrow keys to enter the value [0050] for 0.5 °C.
Confirm with the [ENTER] button.
Now select the closed-current principle for the switching contact of the Min-
switching output.
Use the [MOVE UP] button to select closed-current principle [nc---] (normal
closed).
Confirm with [ENTER].
To conclude, activate the delay time with the [ENTER] button. Press the arrow
keys to set the value [0015]
(15 seconds) for the two limit values.
Confirm with the [ENTER] button and exit the limit value menu.
Miss out the following menu items of the input menu (set passwords and calib-
ration menu) with the [MOVE RIGHT] button. Then exit the input menu by
pressing the [ENTER] button.
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 16 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
The operating mode is restored. The inputs apply immediately and remain
saved after disconnecting the DLZ from the measuring voltage (DLZ is
switched off).
1.6 Appendix
4½ characters 3½ characters
Digit height 30 mm 30 mm 50 mm
Current control button Direct display of the current in the measuring circuit
Measuring circuit Intrinsically safe measuring circuit 4 ... 20 mA; Voltage drop approx. 1 V
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 17 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 18 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 19 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 20 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 21 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 22 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 23 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 24 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 25 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 26 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 27 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 28 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 29 –
Schenck Process Group
Display consoles DLZ 030 and DLZ 050
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 30 –
Schenck Process Group
Display consoles VLZ 20151 and VLZ 20250
Technical Data
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 31 –
Schenck Process Group
Display consoles VLZ 20151 and VLZ 20250
Menu items (1) - (4) Select the interface and the transmission parameters.
Must agree between display and DISOMAT.
Ignore (7) 05
Time-out (t) 0
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 32 –
Schenck Process Group
Display consoles VLZ 20151 and VLZ 20250
Call-up menu
> Press both menu buttons simultaneously for approx. 1 s.
u The left sign flashes in the display.
u The menu items can now be selected with the left button and the settings with the right button.
Short, repeated pressing of one button leads to the next menu item or to the previous setting.
If 'End' appears in the display, the menu can be ended with the left button. Altered settings are saved and
the device behaves in the same manner as after connecting the operating voltage.
Close menu
Closing the menu without saving is possible at any time by pressing both menu buttons at the same time. It
is not possible to control the device in menu mode.
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 33 –
Schenck Process Group
Display consoles VLZ 20151 and VLZ 20250
Menu table
Menu Item Display Setting
1 Interface 1 2 3 2 RS232C *
2 8 8 bit *
3 parity 3 0 none *
3 1 odd
3 2 even
4 Baud rate 4 1 2 0
4 2 4 0
4 4 8 0
4 9 6 0
5 Protocol 5 c r l f
5 S - E
6 1 XON/XOFF
6 2 ACK/NAK
6 3 Echo
etc. to
8 1 1 Position
8 2 2 Positions
8 3 3 Positions
9 Address 9 0 0 0 Address 0 *
9 0 0 1 Address 1
etc. to
9 9 9 9 Address 999
T Time-Out t 0 no Time-Out *
t 2 Time-out after 2 s
t 4 Time-out after 4 s
t 8 Time-out after 8 s
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 34 –
Schenck Process Group
Display consoles VLZ 20151 and VLZ 20250
etc. to
End E n d
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 35 –
Schenck Process Group
Display consoles VLZ 20151 and VLZ 20250
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 36 –
Schenck Process Group
Display console DLS
c
F
a E F –––––E
––––––––––––––––––––––––––––––––––––––––––––––
Seitenansicht
Maße in mm Rückansicht
E
–––––––––––
b–32
F
a–32
F E
––––––––––––––––––––––––––––––––––––––––––––
Sizes in brackets apply to types with 160 mm and 250 mm digit height.
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 37 –
Schenck Process Group
Display console DLS
Number of digits 5
Dimension sign g / kg / t
Legal-for-trade Yes
Pivoted No
Parameterization
For these displays, the DDP 8861 procedure has to be selected on the DISOMAT.
The following parameterisation is recommended:
Menu items (1) - (4) Select the interface and the transmission parameters.
Must agree between display and DISOMAT.
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 38 –
Schenck Process Group
Display console DLS
Start menu
> Press both menu buttons simultaneously (approx. 1 s).
u The first menu item appears in the menu display.
Quit menu
> Briefly press the [↕] key in the menu item U.
u Depending on the setting in menu item U, the completed settings will be saved (Set) or not (Escape)
or the factory settings will be reestablished (Default).
Menu table
Menu item Settings Menu display
RS485 1 4 8 5
TTY 20 mA 1 t t y
3 parity no parity 3 n o n E
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 39 –
Schenck Process Group
Display console DLS
odd parity 3 a d d
even parity 3 E u E n
2400* 4 2 4 0 0
4800 4 4 8 0 0
9600 4 9 6 0 0
19200 4 1 9 2 0 0
DDP8 861 5 8 6 1
DISOMAT M1 5 d 1
AN5316 5 5 3 1 6
ACK/NAK 6 A c n C
Echo 6 E c h o
9 Address Address 0* 9 0
Address 1 9 1
¯ ¯
Address 9 9 9
t Time-out no time-out t 0
Time-out after 2 s t 2
¯ ¯
¯ ¯
Display pre-zeroing* C 0 0 0 0
Depending on the equipment design or settings, individual menu items or settings can be suppressed in an-
other menu item.
* Factory settings
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 40 –
Schenck Process Group
Display console DLS
Control computer
Power
supply
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 41 –
Schenck Process Group
Display console DLS
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 42 –
Schenck Process Group
Display consoles DLZ 055 and DLZ 111
STRICTLY OBSERVE
Damage to the device
Never use solvent to clean the device.
-0- = Zeroing
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 43 –
Schenck Process Group
Display consoles DLZ 055 and DLZ 111
Data word 1 Start bit, 7 Data bit, 1 Parity bit (even parity), 1 Stop bit
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 44 –
Schenck Process Group
Display consoles DLZ 055 and DLZ 111
2. Connect the DLZ 055/DLZ 111 to the selected interface according to the connection diagram in the relev-
ant manuals:
▪ DISOMAT B plus: BV-H2040
▪ DISOMAT Tersus: BV-H2334
▪ DISOMAT Opus: BV-H2310
Only the transmission line (Tx) of the interface is connected in each case.
3. Configure the selected interface in the relevant menu item of the DISOMAT to the values permanently
used by DLZ 055/111
▪ 1200 Bd, 7 Bit, even parity, 1 Stop bit.
DISOMAT B plus and DISOMAT Tersus: Additionally, set the interface type to RS232.
4. Configure the second display output in the relevant menu item of DISOMAT:
▪ Select the correct interface and the protocol DDP 8861
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 45 –
Schenck Process Group
Display consoles DLZ 055 and DLZ 111
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 46 –
Schenck Process Group
Display consoles DLZ 055 and DLZ 111
Then
If there are data telegrams Normal operation
If there are no data telegrams The central bar of the 7-segment display lights up cyc-
lically.
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 47 –
Schenck Process Group
Display consoles DLZ 055 and DLZ 111
more than 1 LED 1 column of the yellow status field self-activating switching-off of the
flashes at approx. 2 Hz: Entire dis- display
play is switching off
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 48 –
Schenck Process Group
Display consoles DLZ 055 and DLZ 111
4.9 Dimensions
Device A B C D F E G H K L M
DLZ 055 470 181 109 541 135 190 380 70 Ø 12 480 110
DLZ 111 945 181 109 1019 135 190 855 70 Ø 12 955 110
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 49 –
Schenck Process Group
Display consoles DLZ 055 and DLZ 111
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 50 –
Schenck Process Group
VLD 20100 Large Display
STRICTLY OBSERVE
Damage to the device
Never use solvent to clean the device.
-0- = Zeroing
= No-motion
If the measurement range of the weighing electronics is exceeded, the message "ooooo" is displayed in the
digit fields.
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 51 –
Schenck Process Group
VLD 20100 Large Display
The unit has an electronic brightness control, which automatically adjusts the display brightness depending
on ambient light. This not only enables a good readout to be obtained in all light conditions, but also provides
a significant increase in service life.
Baud rate, data format * 9600 Baud, 8 Data bit, 1 Stop bit, no parity
1200 Baud, 7 Data bit, 1 Stop bit, even parity
Baud rate/Data format and procedure are recognized automatically by the dis-
play.
:* If a value transmission format and a valid data protocol are identified, these set-
tings remain saved in the remote display until the next switching on. After chan-
ging to a different transmission format or another data protocol, the mains
voltage of the remote display must be switched off and on again so that the auto-
matic search for valid data protocols is restarted.
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 52 –
Schenck Process Group
VLD 20100 Large Display
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 53 –
Schenck Process Group
VLD 20100 Large Display
PE (protective earth)
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 54 –
Schenck Process Group
VLD 20100 Large Display
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 55 –
Schenck Process Group
VLD 20100 Large Display
5.8 Dimensions
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 56 –
Schenck Process Group
VLZ 20100 Large Display
T Tare is shown
g, kg, t, lb Dimension character. The dimension character is only shown when the scale is in the
no-motion state.
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 57 –
Schenck Process Group
VLZ 20100 Large Display
Connection to a DISOMAT:
NOTICE
DISOMAT does not start when the VLZ is connected
The starting current of the display may prevent DISOMAT Tersus from
starting.
> This can be remedied with 10 W series resistance per unit length in
the feed line (at least 1 W).
Please see the respective manuals when selecting the correct interface and connection to a DISOMAT:
▪ BV-H2310 DISOMAT Opus
▪ BV-H2331 DISOMAT Satus
▪ BV-H2334 DISOMAT Tersus
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 58 –
Schenck Process Group
VLZ 20100 Large Display
Color Signal
Pink Supply +
Black RS485 A
Violet RS485 B
Blue RS232 Rx
Function Lettering
Supply +V - 0V
RS485 AB
RS232 + RxD -
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 59 –
Schenck Process Group
VLZ 20100 Large Display
The interface of the display automatically adjusts to the preset values for the interface in the DISOMAT. If it
is necessary to adjust the display to fixed parameters or if the large display is offset, the following steps are
necessary:
Adjusting the interface to the large display (points 5 to 7 only necessary according to factory settings):
1. Unscrew cover (1)
2. Hold the "OK" button down and then press the "BACK" button
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 60 –
Schenck Process Group
VLZ 20100 Large Display
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 61 –
Schenck Process Group
VLZ 20100 Large Display
6.5 Dimensions
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 62 –
Schenck Process Group
VLZ 20100 Large Display
6.6 Assembly
The VLZ can be mounted directly to a wall. The positions of the screw holes are shown in the dimension
drawing.
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 63 –
Schenck Process Group
VLZ 20100 Large Display
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 64 –
Schenck Process Group
VLZ 20045 Type Secondary Display
NOTICE
An event message appears on the DISOMAT
The VLZ 20045 remains dark.
Digit size 45 mm
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 65 –
Schenck Process Group
VLZ 20045 Type Secondary Display
NOTICE
DISOMAT does not start when the VLZ is connected
The starting current of the display may prevent DISOMAT Tersus from
starting.
> This can be remedied with 10 W series resistance per unit length in
the feed line (at least 1 W).
There is a 9-pole sub-D plug on the display with the following pin assignment:
1 5
6 9
TTY- GND (0 V)
TTY+ V+
TxD Prog
B- A+
RxD
Fig. 17: VLZ 20045, Sub-D, plug, 9-pole
The following pins are used for displaying the data:
▪ Pin 2: RS232, TxD
▪ Pin 3: RS232, RxD
▪ Pin 5: 0 V, for feed and RS232
▪ Pin 7: RS485, B
▪ Pin 8: RS485, A
▪ Pin 9: Feed +
The plug achieves protection class IP65 through the provided hood.
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 66 –
Schenck Process Group
VLZ 20045 Type Secondary Display
7.5 Dimensions
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 67 –
Schenck Process Group
VLZ 20045 Type Secondary Display
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 68 –
Schenck Process Group
VAG 20200-D Type Secondary Display
g, kg, t, lb = Dimension character. The dimension character is only shown when the scale is in
the no-motion state.
Digit size 20 mm
Weight 0.35 kg
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 69 –
Schenck Process Group
VAG 20200-D Type Secondary Display
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 70 –
Schenck Process Group
VAG 20200-D Type Secondary Display
8.5 Dimensions
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 71 –
Schenck Process Group
VAG 20200-D Type Secondary Display
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 72 –
Schenck Process Group
VAG 20200-D Type Secondary Display
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 73 –
Schenck Process Group
VAG 20200-D Type Secondary Display
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 74 –
Schenck Process Group
Disposing of electrical and electronic devices
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 75 –
Schenck Process Group
Disposing of electrical and electronic devices
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 76 –
Schenck Process Group
List of tables
List of tables
Tab. 1 Initial connection parameter............................................................................................................. 7
Tab. 2 Key function ..................................................................................................................................... 8
Tab. 3 Limit value display ........................................................................................................................... 10
Tab. 4 Edit mode......................................................................................................................................... 10
Tab. 5 Password query ............................................................................................................................... 10
Tab. 6 Parametrization................................................................................................................................ 11
Tab. 7 Procedure ........................................................................................................................................ 14
Tab. 8 Measured values and bar chart scaling ........................................................................................... 14
Tab. 9 Limit values, hysteresis and time delay ........................................................................................... 16
Tab. 10 Menu table ....................................................................................................................................... 34
Tab. 11 Mains plug ....................................................................................................................................... 46
Tab. 12 Data plug ......................................................................................................................................... 46
Tab. 13 Error messages ............................................................................................................................... 48
Tab. 14 Connecting cable strand assignment of Secondary display VLZ..................................................... 59
Tab. 15 VLZ printed circuit board labelling ................................................................................................... 59
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 77 –
Schenck Process Group
List of tables
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 78 –
Schenck Process Group
List of figures
List of figures
Fig. 1 Field housing DLZ 030 EF connections........................................................................................... 6
Fig. 2 Field housing DLZ 050 EF connections........................................................................................... 6
Fig. 3 Switching behaviour of the lower limit value at the switching output Min. ....................................... 12
Fig. 4 Switching behaviour of the upper limit value at the switching output Max....................................... 12
Fig. 5 Panel-mounting housing dimensional drawing ................................................................................ 19
Fig. 6 Field housing dimensional drawing.................................................................................................. 20
Fig. 7 Operating mode flow chart............................................................................................................... 21
Fig. 8 Limit value display flow chart ........................................................................................................... 22
Fig. 9 Input menu flow chart ...................................................................................................................... 23
Fig. 10 Scaling menu flow chart................................................................................................................... 24
Fig. 11 Value input flow chart ...................................................................................................................... 25
Fig. 12 Limit value flow chart ....................................................................................................................... 26
Fig. 13 Limit value flow chart ....................................................................................................................... 27
Fig. 14 Full limit value flow chart.................................................................................................................. 28
Fig. 15 Calibration menu flow chart ............................................................................................................. 29
Fig. 16 VLZ 20100 ....................................................................................................................................... 62
Fig. 17 VLZ 20045, Sub-D, plug, 9-pole ...................................................................................................... 66
Fig. 18 VLZ 20045 ....................................................................................................................................... 67
Fig. 19 Front view ........................................................................................................................................ 71
Fig. 20 Back view......................................................................................................................................... 72
Fig. 21 Side view ......................................................................................................................................... 73
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 79 –
Schenck Process Group
List of figures
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 80 –
Schenck Process Group
Index
Index
Symbols F
VAG 20200-D Type Secondary Display .................................. 69 Field device DLZ 030 EF and DLZ 050 EF ............................... 3
Field Housing ............................................................................ 6
Fixing in the control panel ......................................................... 3
A Front view ............................................................................ 8, 71
Appendix ................................................................................. 17
Assembly ................................................................................. 63
Assembly and connection ......................................................... 2 G
Assembly in zone 1 or 2 ............................................................ 3 General equipment description ................................... 43, 65, 69
Assembly in zone 21 or 22 ........................................................ 4 General Equipment Description ............................................. 57
General Equipment Description ............................................. 51
B
Basic function ............................................................................ 1 K
Brief description of the display consoles ................................... 1 Keyboard ................................................................................... 8
C L
Call-up menu ........................................................................... 33 Limit value display ................................................................... 10
Close menu ............................................................................. 33 Limit values, hysteresis and time delay ............................. 16, 17
Close menu without saving ..................................................... 39
Configuration of the interface ...................................... 60, 66, 70
Connecting and commissioning ................................................ 4
M
Connecting up to Schenck Process DISOMAT and INTECONT Measured values and bar chart scaling............................. 14, 15
type weighing electronics .................................................. 58 Measuring current display ......................................................... 9
Connecting up to Schenck Process DISOMAT type weighing Mechanical mounting .............................................................. 55
electronics ....................................................... 45, 53, 65, 70 Menu controls .......................................................................... 33
Connection assignment ..................................................... 46, 54 Menu controls, flow charts....................................................... 21
Connection assignment on the side of the VAG...................... 70 Menu structure, Parameter input ............................................... 9
Connection to a DISOMAT: ..................................................... 58 Menu table................................................................... 34, 35, 39
Connection to an INTECONT Opus: ....................................... 59
Connection to an INTECONT Tersus: ..................................... 58 N
Control panel instrument DLZ 030 E ......................................... 2
Navigating in the menu............................................................ 39
D O
Data transmission format .................................................. 44, 52
Operating state .......................................................................... 9
Dimensional drawings ............................................................. 19
Operation................................................................................... 8
Dimensions...................................................... 49, 56, 62, 67, 71
Options ...................................................................................... 1
Display console DLS ............................................................... 37
Overview of the features ........................................................... 1
Display console DLS ... ........................................................... 37
Display consoles DLZ 030 and DLZ 050 ................................... 1
Display consoles DLZ 055 and DLZ 111 ................................. 43 P
Display consoles VLZ 20151 and VLZ 20250 ......................... 31 Panel-mounting housing............................................................ 5
Disposing of electrical and electronic devices ......................... 75 Parameterization ..................................................................... 38
Does the device work correctly? ............................................. 47 Parameterization examples ..................................................... 13
Parametrization ....................................................................... 11
Password query....................................................................... 10
E
Presets .................................................................................... 13
Edit mode ................................................................................ 10
Procedure ................................................................................ 14
Error messages ....................................................................... 48
Procedure parameters............................................................. 32
Explosion Protection.................................................................. 2
DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ BV-H2015 EN, V5
20045, VAG 20200, Instruction Manual
– 81 –
Schenck Process Group
Index
Q
Quit menu ................................................................................ 39
S
Safety instructions DLZ ... E(F) ................................................. 7
Self-test during start-up ..................................................... 47, 55
Set hysteresis and switching delay ......................................... 12
Settings ................................................................................... 14
Start menu ............................................................................... 39
Switching delay ....................................................................... 13
T
Technical Data ....................... 17, 31, 38, 44, 52, 57, 65, 66, 69
Test operation ......................................................................... 47
Then ........................................................................................ 47
U
Use dimension symbol .......................................................... 2, 3
V
VLD 20100 Large Display ...................................................... 51
VLZ 20045 Type Secondary Display ....................................... 65
VLZ 20100 Large Display ........................................................ 57
BV-H2015 EN, V5 DISOMAT® Secondary and Large Displays DLZ 30/50/55/111, VLD 20100, VLZ 20100, VLZ
20045, VAG 20200, Instruction Manual
– 82 –