EN81-01
SLF.01
jarak 333mm. 300mm.
- Guarantees a safety space of ≥ 500x600x1000 mm if car is on fully compressed buffers.
- Gives safe access to the elevator parts for maintenance work.
- Make sure that no part of the elevator collides with the platform when car/cwt is on fully compressed buffers.
SLF.01 EARTHING SYSTEM REQUIREMENT:
- The building main switch shall be RCD 300mA Type B with over current protection for TT earthing network.
- The building main switch shall be MCB for TN-S / TN-C earthing network.
SHAFT STRUCTURE
Shaft structure are strongly recommended to be concrete. If brick situation, adding structure beam to the position of
brackets locates should be taken into account.
STRUCTURE OPENING
C When front wall of shaft is brick, a lintel used to fasten brackets should be added above the hole of landing door, with
C height not less than 350mm.
GROUTING
Grouting of door frames to be filled up after door frames are installed.
EMERGENCY DOORS
When the distance between consecutive landing door sills exceeds 11 m, one of the following conditions shall be
fulfilled; there shall be:
a) Intermediate emergency doors, or
b) Adjacent cars each fitted with an emergency door. Note:
NOTE "Consecutive" is understood as meaning two adjacent floors, with landing doors, regardless of open through or
open adjacent configurations. - Mohon koordinasi dengan main/civil
6.) VENTILATION OF THE WELL
contractor untuk superimpose shopdrawing
The well, machinery spaces and pulley rooms shall not be used to provide ventilation of rooms other than those
belonging to the lift. Ventilation shall be such that the motors and equipment, as well as electric cables, etc., are
protected from dust, harmful fumes and humidity.
The well shall be suitably ventilated. It shall not be used to provide ventilation of rooms other than those belonging to the
lift.In the absence of relevant regulations or standards, it is recommended that ventilation openings at the top of the well,
with a minimum area of 1 % of the horizontal section of the well, are provided.
1 1
BUILDING TOLERANCE
Shaft and axis dimensions may not exceed perpendicular tolerance of: +/-25mm.
SLF.01
REVIEW STATUS APPROVED (TICK ONE)
811230929-SLF.01-LB-01
1. AGAR DIBUATKAN PANEL TERSENDIRI (LCP-LIFT), UNTUK
SUPPLY LISTRIK :
A. CAR LIFT
B. LAMPU & STOP KONTAK SERTA AC (JIKA ADA) DI CAR LIFT
C. LAMPU & STOP KONTAK DI PIT & OVERHEAD
D. EARTH QUAKE SENSOR
E. ARD, DLL
2. AGAR DIBUATKAN GROUNDING UNTUK LIFT TERSEBUT,
YANG SESUAI SNI 2011
C C
C
Note:
- Mohon koordinasi dengan main/civil
contractor untuk superimpose shopdrawing
SLF.01
SLF.01
811230929-SLF.01-LB-02
Note:
- Mohon koordinasi dengan main/civil
contractor untuk superimpose shopdrawing
A. APPROVE
B. REVISE & RESUBMIT
C.NOT ACCEPTABLE
SIGNATURES & DATES FOR APPROVAL
811230929-SLF.01-LB-03
di gambar struktur, separator
Tidak sesuai dengan beam WF200x100
denah di LB-01 --> harus
ada detail tambahan
untuk koneksi bracket ke Note:
separator beam karena - Mohon koordinasi dengan main/civil
ada jarak SF=333mm contractor untuk superimpose shopdrawing
(lihat di denah).
811230929-SLF.01-LB-03