You are on page 1of 31

LOGIK 9 CONTROLLER

CONTENTS
TECHNICAL FEATURES ............................................................................................. 2
DIMENSIONS AND MOUNTING ..................................................................................... 2
ELECTRICAL FEATURES ............................................................................................... 2
ELECTRICAL CONNECTIONS.......................................................................................... 2
CONTROL PANEL ....................................................................................................... 3

PROGRAMMING ..................................................................................................... 3
QUICK SETTINGS OF START AND STOP PRESSURE .............................................................. 3
PASSWORDS AND ACCESS LEVELS ................................................................................. 4
PARAMETERS ........................................................................................................... 4
PRESSURES .............................................................................................................. 4
TEMPERATURES ....................................................................................................... 5
WORKING TIMER ...................................................................................................... 6
MAINTENANCE TIMER ................................................................................................ 7
COMPRESSOR CONFIGURATION ................................................................................... 8
WORKING HOURS ................................................................................................... 10
ALARMS ............................................................................................................... 10
RESET................................................................................................................... 10

ALARMS AND WARNINGS ...................................................................................... 11


ELECTRICAL WIRING DIAGRAMS ............................................................................. 13
COMMUNICATION & CONTROL .................................................................................
REMOTE START / STOP............................................................................................. 15
SERIAL CONNECTION ............................................................................................... 16
MASTER / SLAVE OPERATION .................................................................................... 18
MULTI UNIT OPERATION ........................................................................................... 19
MODBUS COMMUNICATION AND ADDRESS LIST............................................................. 20

1
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

TECHNICAL FEATURES ELECTRICAL CONNECTIONS

DIMENSION AND MOUNTING

Terminal M1 : Power Supply and Analog Inputs

Terminals 1-2 : Power supply connection 12Vac

Terminals 3-4 : Temperature probe connection

Terminals 5-6 : Pressure Transducer connection

ELECTRICAL FEATURES (5: negative / 6: positive). Also can ben configured


as voltage free pressure switch contact.
- Directive accordance
LVD: 2014/35/UE Terminal M2 : Digital Outputs
EMC: 2014/30/UE
Terminal 1 : Common relay 24-230Vac
ROHS: 2011/65/UE
SAF-EMC: EN607130-1 Terminal 2 : Relay 1 – Line contactor
RHOS:EN 50581
UL 508 Terminal 3 : Relay 2 – Star contactor
- Degree of protection :
Ip64 for front panel and Ip20 for other Terminal 4 : Relay 3 – delta contactor
parts.
Terminal 5 : Relay 4 – Load selenoid
- Working temperature : -10..+50℃ and
%90 humidity Terminal 6 : Relay 5 – Alarm output or Fan
- Storage Temperature : -20..+70℃ contactor. Relay 5 can be configured as fan
- Power Supply : 12Vac ± %10 50-60Hz contactor as well.
- The max. Current drawing : ~ 200mA
- Opto isolated digital inputs : 12-24Vac Terminal M3 : Digital Inputs
- Relay Outputs : 1.5A 250Vac Max. for
Terminal 1 : Common (N)
each and 6A max. in total.
- Weight : 290g Terminal 2 : IN1 – Emergency stop button (L)

Logik 9 has Terminal 3 : IN2 – Or alarms (Motor thermal


overload / Fan overload etc.) (L)
- 2 analog inputs
- 4 opto isolated digital inputs Terminal 4 : IN3 – Phase control relay (L)
- 5 relay digital outputs
- 1 RS485 serial communcation interface Terminal 5 : IN4 – Remote Start/Stop (L)

2
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

Terminal M4 : Serial Connection PROGRAMMING

Terminal 1 : DGND (digital ground) QUICK SETTINGS OF START AND

Terminal 2 : D- (B) STOP PRESSURE

Terminal 3 : D+ (A) On the main menu by pressing button


simultaneously , you will enable the quick start /
CONTROL PANEL
stop pressure settings and display will show up as
below;

With the start pressure value blinking, you can set

the start pressure by using and down


Main Programming button. Then you can confirm changed setting
visualization visualization
Group 1 Working Setting Value value by pressing button. After you have
Pressure
changed the start pressure following picture will
Group 2 Press. Parameter Code
show up on the screen.
Measurement
Unit
Group 3 Screw Parameter Menu
Temperature Code
Group 4 - Parameter Sub-
menu Code

You can set the stop pressure as decribed above


and then screen wil return back to main
visualization.

ICON DESCRIPTIONS

Number Descriotion
1 Fan Working
2 Compressor loading /
unloading
3 Remote Start / Stop
Enabled
4 Alarm Occur
5 Maintenance alarm
6 Temperature unit
7 Master / Slave Operation
Indicator

3
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

PASSWORD AND ACCESS LEVELS


When you press to you will able to enter
password for relevant level of password. Password
will be confirmed when you enter the last digit of
the password. In case you enter wrong password
the screen will you inform you as below.

With the password level 0 user can only access to


observe the mentioned parameters above.

PARAMETERS

Default passwords for each levels are :

- PA1 = 32 Default = 22
- PA2 = 325 Default = 333

Note : Default passwords might be changed in the


factory. To learn password information for each
level please contact with you authorized dealer /
service.
By using buttons you can navigate to
PARAMETER LIST
demanded parameter. When you press
button relevant parameter will start to blink and MENU 1 – PASS : PASSWORD CHANGE
you can set new value by using . Then by
You can change the password with service level 2
pressing button, the parameter change will password access. This process must be done by
be confirmed. authorized personel or factory.

ENTER THE PASSWORD MENU 2 – PP : PRESSURES

While the compressor is in the off position by P00 : Pressure Control

pressing to button about 2 sec password [password level – 1]


screen will show up.
[ 0 ] – Transducer (Default)

[ 1 ] – Pressure switch

Function :

Start and stop pressure can be measured by


pressure switch or transducer inputs. This
parameter depends on each compressor type.
By using buttons you can navigate to
PA1(Service) and PA2(factory) password levels.

4
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

P01 : Top Range of Transducer P05 : Slave Start Pressure

[password level – 2] [password level – 1]

Value : 15 – 60 Bar Default : 16 Bar Value : 2,8-0,2 ÷ P04-0,2 Default : 8,3 Bar

Function : Function :

If P00 is selected [ 1 ] , this parameter indicates the P05 is only enabled when CON parameter is
maximum pressure limit of the transducer. different than 0. For detailed function of this
parameter, you can read master / slave operation
P02 : High Pressure and multiunit operation.

[password level – 1] P06 : Offset

Value : P01-0,5 ÷ P03+0,5 Default : 8,5 Bar


[password level – 2]

Function : Value -2 ÷ +2 Default : 0 Bar

This is the high pressure limit of the compressor. If Function :


compressor exceeds this value, controller gives
high pressure alarm and stops This parameter is used for calibration of the
transducer.
P03 : Stop Pressure
P07 : Unit of Measurement
[password level – 0]
[password level – 0]
Value : P02-0,5 ÷ P04+0,2 Default : 7,4 Bar
[ 0 ] : Bar (Default)
Function :
[ 1 ] : Psi
When the compressor exceeds this value, first the
compressor goes in to the idle state. After idle Function :
state duration ends, the compressor stops.
Pressure unit selection that is visualized on the
P04 : Start Pressure main screen.

[password level – 0] MENU 3 – PH : TEMPERATURES

Value : P03-0,2 ÷ 3 Default : 6,5 Bar H00 : Temperature Probe Type

Function : [password level – 1]

When the compressor pressure drops under this [ 0 ] – Disabled


value, the compressor will start after safety time
[ 1 ] – KTY (Default)
duration ends.
[ 2 ] – NTC

Function :

Temperature probe type selection used in the


compressor.

5
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

H01 : High Temperature Note : H03 is visible only when if the parameter
RL5=1.
[password level – 1]
H05 : Low Temperature
Value : H02+2 ÷ 125 Default : 108 ℃
[password level – 1]
Function :
Value : -10 ÷ +15 Default : 0 ℃
If the compressor temperature reaches high
temperature parameter value, compressor stops Function :
with high temperature alarm.
If the working temperature drops below H05
H02 : High Temperature Warning parameter, compressor stops with low
temperature alarm.
[password level – 1]
H06 : Temperature Offset
Value : H03+2 ÷ H01-2 Default : 103 ℃
[password level – 2]
Function :
Value : -10 ÷ +10 Default : 0 ℃
If compressor temperature reaches to high
temperature warning setting, controller will not Function :
stop and controller gives high temperature
warning. This parameter is used for calibration of the
temperature probe.
H03 : Fan On (Relay 5)
H07 : Unit Of Temperature
[password level – 1]
[password level – 0]
Value : 30 ÷ H02-2 Default : 85 ℃
[0]–℃ (Default)
Function :
[1]– ℉
When the compressor temperature exceeds this
parameter relay 5 will be energized and cooling fan Function :
will start to run. Cooling fan stops when the
If the working temperature drops below H05
working temperature drops under the H03-H04
parameter, compressor stops with low
value.
temperature alarm.
Note : H03 is visible only when if the parameter
RL5=1. MENU 4 – Pt : WORKING TIMER

H04 : ΔT Fan Off (Relay 5) T01 : Star

[password level – 1] [password level – 2]

Value : 2 ÷ 20 Default : 5 ℃ Value : 2 ÷ 20 sec. Default : 5 sec.

Function : Function :

When the compressor working temperature drops Indicates star working duration in seconds.
under H03-H04 the cooling fan stops.

6
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

T02 : Star / Delta Timer T06 : Master / Slave Rotation

[password level – 2] [password level – 1]

Value : 10 ÷ 50 msec. Default : 35 msec. Value : 0 ÷ 200 h Default : 100 h.

Function : Function :

Indicates Star / Delta switchover duration in milli Indicates the master / slave rotation duration. For
seconds. detailed information please read Master / Slave
Operation section.
T03 : Delta Timer
T07 : Slave Timer
[password level – 2]
[password level – 1]
Value : 1 ÷ 900 sec. Default : 2 sec.
Value : 1 ÷ 99 min. Default : 5 min.
Function :
Function :
Indicates the delta timer.
Indicates slave first start working duration in the
T04 : Unload Timer master slave operation. For detailed information
please read Master / Slave Operation section.
[password level – 1]
T08 : T04 fixed / variable
Value : 0 ÷ 10 min. Default : 1 min.
[password level – 1]
Function :
[ 0 ] : Fixed (Default)
Indicates the idle working duration of the
compressor. When the compressor reaches to set [ 1 ] : Variable
pressure value, controller waits this duration end
to stop the compressor. Function :

T05 : Safety Timer If this parameter selected as variable then the


controller will calculate the unload timer in
[password level – 2] variable mode.

Value : 10 ÷ 240 sec. Default : 30 sec. MENU 5 – P-F : MAINTENANCE TIMER

Function : CAF : Change Air Filter

Indicates the safety timer. When the compressor [password level – 1]


stops for any reason, before start the compressor
again the controller waits this duration end for Value : 100 ÷ 3000 h. Default : 3000 h.
safety reason.
Function :

Indicates air filter change remaining duration. this


parameter need to be reset after each
maintenance process that the air filter has been
replaced.

7
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

COF : Change Oil Filter bL : Lubricate Motor Bearings

[password level – 1] [password level – 1]

Value : 100 ÷ 10.000 h. Default : 3000 h. Value : 100 ÷29.999 h. Default : 29.999 h.

Function : Function :

Indicates oil filter change remaining duration. this Indicates lubrication of motor bearings remaining
parameter need to be reset after each duration..
maintenance process that the oil filter has been
replaced. MENU 6 – CnF : COMPRESSOR
CONFIGURATION
CSF : Change Seperator Filter
r-- : Restart Low Voltage
[password level – 1]
[password level – 1]
Value : 100 ÷ 10.000 h. Default : 6000 h.
[ 0 ] : Manual (Default)
Function :
[ 1 ] : Automatic
Indicates seperator filter change remaining
duration. this parameter need to be reset after Function :
each maintenance process that the seperator filter
has been replaced. If this parameter is selected [ 1 ], the compressor
will remain the last state (run / stop) before the
C-- : Change Oil power failure. If the compressor was in working
state and power failure occured, then when the
[password level – 1] power failure fixed the compressor will be in
working state again.
Value : 100 ÷ 10.000 h. Default : 3000 h.
S-h : Starts Hour
Function :
[password level – 2]
Indicates oil change remaining duration. this
parameter need to be reset after each Value : 0 ÷ 60 h. Default : 20 h.
maintenance process that the oil has been
replaced. Function :

For electric motor safety, the maximum start / stop


count indication in a hour.

C-h : Check Compressor

[password level – 1]

Value : 100 ÷ 10000 h. Default : 3000 h.

Function :

Indicates air compressor check remaining duration.

8
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

Fad : Air Flow In3 : In3 Configuration

[password level – 0] [password level – 2]

Value : 1000 ÷ 10.000 l/min. Default: 1000. [0] ÷[6] (Default : 3)

Function : Function :

The compressor’s nominal air flow rate need to be Same as the parameter In2 configuration.
entered.
In4 : In4 Configuration
S-- : Security
[password level – 2]
[password level – 2]
[0] ÷[6] (Default : 4)
[ 0 ] : Disable (Default)
Function :
[ 1 ] : Enable
Same as the parameter In2 configuration.
Function :
rL5 : Relay 5 Configuration
This parameter is related to CAF parameter. If this
[password level – 2]
parameter is enabled and CAF timer exceeded, the
compressor will give alarm A18 and stop. [ 0 ] : Alarm Relay (Default)

In2 : In2 Configuration [ 1 ] : Fan Contactor Relay

[password level – 2] Function :

[ 0 ] : Or Alarms If parameter selected as [ 0 ] , relay 5 will be alarm


relay and will trip when alarm occur. In this case
[ 1 ] : Thermal Motor (Default)
parameters H03 and H04 will not be visible.
[ 2 ] : Thermal Fan
To enable fan control relay function, this
[ 3 ] : Phase Control Relay parameter must be selected as [ 1 ] and relevant
H03 and H04 parameters will be visible.
[ 4 ] : Remote Start / Stop

[ 5 ] : Remote Load / Unload con : Connection

[ 6 ] : Disabled [password level – 1]

Function : [ 0 ] : Single (Default)

Parameter indicates the input function listed [ 1 ] : Master / Slave


above.
[ 2 ] : Multiunit Slave

Function :

If the compressor will work stand alone [ 0 ] must


be selected. For other function please read master
/ slave operation section and multiunit operation
section.

9
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

nc : Compressor Number MENU 7 – Hr5 : WORKING HOURS

[password level – 1]

Value : 0 ÷ 32 (Default : 1)

Function :

This is the compressor address number into the


communication

OFl : Working Mode

[password level – 1]

[ 0 ] : Multiunit Enable (Default)

[ 1 ] : Multiunit Disable

Function :

For detailed information please read multi unit Working Hour Modification
operation section.
It is possible to madify total and load working
drY : Dryer Delay hours with password level 2.

[password level – 0] Total working hour modification : Go to Menu 7 –


Hr5 tH parameters. Press and hold to enter button
Value : 0 ÷ 999 (Default : 0) for 3 sec. The first digit will start to blinking. Now it
is possible to edit working hour information.
Function :
Load working hour modification : Go to Menu 7 –
This parameter gives delay to dryer operation Hr5 LH parameters. Press and hold to enter button
when the compressor starts. for 3 sec. The first digit will start to blinking. Now it
is possible to edit working hour information.
E-h : Equalize Hours

[password level – 1]

[ 0 ] : Disabled (Default)

[ 1 ] : Enabled

Function :

Under Master/Slave working mode, [0] selection


will not equalize the working hours of the
compressors. Selection [1] will equalize working
hours (Align Hours Parameter)

10
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

MENU 8 – AL : ALARMS

In this menu last 20 alarms are listed.

In the picture above 13 means AL13 occured and


02 means this alarm tripped 2 times. 8 is the menü
code means we are in the alarm list.

MENU 9 – rES : RESET

This menu dedicated to reset timers and


counters in the controller as below;

When you enter this menü by pushing the enter


button, the following screen will show up.

By using up and down buttons, select the menu


that you need to reset and then press enter button
about 3 sec. and the screen will show up rES for a
while to confirm the reset procedure.

11
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

TEST FUNCTIONS Then push to start/stop button to make next test.

Enable Test Function : Power Supply Test :

Cut power of the controller. Push and hold both


enter and on/off button together then give power
back to controller unit.

Screen Test : The screen is showing power supply voltage of the


controller.

Then push to start/stop button to make next test.

Digital Input Test :

Push to Start / Stop Button then observe if all icons


and digits are shown in an order on the screen.

Then push to start / stop button to skip to second


test.
The first two digits show input number and last
Keyboard Test : character shows status (c : closed – o : open). Push
arrow buttons navigate between inputs.

Then push to start/stop button to make next test.

Digital Output Test :

P1 (up) – P2 (down) – P3 (enter) – P4 (Start / Stop)

Push to buttons in an order and screen must show


pushed button code on the screen. After last
button test, push to start / stop button to make
The first two digits show output number and last
next test.
character shows status (c : closed – o : open). Push
arrow buttons navigate between outputs. Push
Temperature Probe Test :
enter button to toggle regarding relay.

Push to start/stop button to make next test.

EEPROM Test :

The screen must show currently reading


temperature by probe. In this case the value is 105
C. Push to start/stop button to make next test.

Pressure Transducer Test : EE1 : Eeprom test is successfull

EE0 : Eeprom test is failed.

After this test, cut controller power and give back


to make it in normal operation.
The screen is showing currently reading pressure
value by pressure transmitter.

12
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

ALARMS AND WARNINGS A10 : High Pressure

Alarms which stops the compressor immediately. The workig pressure exceeded the parameter P02.

A11 : Pressure Transducer Failure

The Pressure transducers failed and need to be


replaced with new one.

A12 : Emergency Stop Button

Emergency stop button is opened (IN1)

A13 : Thermal Motor

Thermal motor alarm related input is opened.

A14 : Thermal Fan

Coolin fan thermal overload related input is


opened.

A15 : Or Alarms

A01 : Reversed Phase The input which is used for or alarms is opened.

Phase control relay related input has been opened A18 : Security
( IN3).
The parameter S-- is [ 1 ] . and CAF timer is ended.
A02 : High Temperature This alarm can be removed by resetting the CAF
timer.
The working temperature sensed from the probe
exceeded the parameter H01. A19 : Fieldbus Error

A04 : Low Temperature There is no communication between modbus


master device.
The temperature deteced from probe is lower than
the parameter H05. POF : Power Off

A05 : Temperature Probe Failure The compressor power is cutted off for any reason.

The temperature probe failed and need to be


replaced with new one.

A07 : Low Voltage

Controller power supply is lower thant 9Vac.

A09 : Security Pressure Switch Open

All the inputs will be opened.

13
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

WARNINGS A18 : Without the temperature probe

Warning messages does not stop the compressor The parameter H00 is [ 0 ].
and it is possible to reset while the compressor is
in runnig state. MAINTENANCE CODES

F-A : Change air filter


A00 : Set Data Lost
The timer CAF is over.
EEPROM failure or the firmware is upgraded. All
the parameters are lost and backs to the default F-O : Change oil filter
values.
The timer COF is over.
A03 : Reversed Phase
F-S : Change separator filter
This is high temperature warning and the working
The timer CSF is over.
temperature is exceeded the parameter H02. This
warning resets automatically when the working
OIL : Change oil
temperature drops below the parameter H02.
The timer C-- is over.
A06 : Without the temperature probe
C-h : Check compressor
If the parameter H00 is set to [ 0 ] in the main
screen the temperature indication side will The timer C-h is over.
visualized as “---“ .
bL : Lubrication Bearings
A08 : Max. Starts/Hour
The timer bL is over.
The compressor start count is exceeded the value
in the parameter S-h.

A16 : Multinuit Failure

The master unit in the multiunit is failed or there is


no communication between master and slave unit.

A17 : Master / Slave Failure

There is a serial communication error between the


compressors in the master / slave modbus
network.

14
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

TIY 3-5 SERIES

15
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

TIDY 7-30 SERIES

16
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

REMOTE START STOP

ELECTRICAL REVISIONS

Standard Connection

As default connection all the logik9 Controller’s Remote Start / Stop input is short circuited to the terminal
M1-1. To use the remote Start / Stop function, some electrical revisions are needed to make on the control
panel connections. After electrical revisions has been made, also some parameters must be checked as well.

Electical Revisions

1. Remove the cable bridge between the terminals M3-5 & M1-1.
2. Use electrical selector switch between the terminals connection M3-5 and M1-1

Parameter Setup

On the controller the Input 4 can be configured for remote Start / Stop function signal usage.You need to set
In4 parameter as [ 4 ] – Remote Start / Stop

Note : Start / Stop button on the logik controller and remote start / stop input works in serial manner. To use
remote start / stop function , the compressor must be left in the working state.
17
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

SERIAL CONNECTION

The serial communication type is RS485 and uses modbus RTU protocol.

Electrical Connection Multiunit

Electrical Connection Master / Slave

18
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

Each logik 9 has 1 serial communcation port on the termial M4

Master / Slave operation only two compressor must be connected


via serial communication.In case of communication between two
units, no need to use 120 Ω resistor for each end.

Serial Connection Notes

1. Use shielded flexible twisted cable


2. Connect D+ and D- terminals throug each compressor controller and connect shield part to terminal
“M4-1 : 0” digital ground for each side as well.
3. Do not connect the cables shield to the ground
4. The cable lenght must not be longer than 400 meters
5. The units on the serial net must be connected without any reversal connection and connections must
be like :

D+ -> D+ / D- -> D- / 0 -> 0

MASTER / SLAVE OPERATION & PRINCIPLE

Parameter for Master / Slave Operation

1. Parameter nc – the compressor number . Each compressor must have different


compressor number (for compressor 1 nc=[1] and compressor 2 nc=[2] )
2. Parameter con must be selected as [ 1 ] master / slave operation for each controller.
3. Under the Pt timer menu t06 is the master to slave change timer.
4. Parameter t07 timer to slave start duration that master compressor does not reach
to stop pressure at the start Up

19
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

PRINCIPLE

- Pushing the start / stop button of controller from the one of the two compressor will
start or stop the compressors both.

- At the first start master compressor (the compressor which has lower level
compressor number) will start. If master unit can not reach to stop pressure value
after the duration that is indicated under the parameter t07 – slave start delay at the
start up, slave compressor / unit will start to reach stop pressure. This process only
occur while the first start up of the compressors.

- If the working hour difference between the compressors are higher than the
indicated value in the parameter t06 – master slave change period, the compressor
which has less working hours than another will keep working untill reaches to other
compressor’s working hours + t06 value. Then master slave switches.

- During the master slave operation some parameter are shared and copied from the
master to the slave. These parameters are :
PO2,PO3,PO4,PO5,r—and timers t06,t07

The slave compressor works only;


- At the first start up and if the master unit does not reach to stop pressure within the
time set in the parameter t07.
- If the pressure drops down than set of P05
The master unit switches with slave;
- When the timer set t06 is over
- In case of shut off alarm of the master unit

Note : In case of communication failure between the compressors, both


compressors will start to work under stand alone mode.

20
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

MULTI UNIT OPERATION

Multiunit function allows max. 5 units (one of the unit will be master) allows to coorporative
operations of the compressors management.

Note : In the multiunit system at least one of the controller must be Logik33S (will be
master unit) or Logik200 multiunit management controller must be used as master unit in
the system.

All the controllers must be connected via RS485 serial line decribed in the Master / Slave
communication section. In this case 5 unit can be connected by using serial connection. Each
controller must have different compressor number since each compressor number is the
modbus address. You can set the modbus compressor number by changing nc within the
range 1÷32 parameter. You can give compressor number by starting with 1 (master unit)
through 5 for each compressor. It is strictly recommended to give compressor number “1” to
the master controller in the multiunit system.

Multiunit system is working under 3 modes described below ;

- SMART MODE (INTELLIGENT) :


Operating principle is to obtain the best performance by optimizing the power
consumption. Master controller calculates the air consumption and arranges the
compressor according to their rated flow rates and aims to supply needed amount of
pressurized air under low electric consumption.
- EQUIL MODE (BALANCE HOURS) :
Under this mode multunit system aims to balance the all the compressor’s working
hours to be same. In this mode its important to make this senario between same
type and sized compressors. Each compressors will start to work first in first put FIFO
principle according to their working hours informations and the timer indicated in the
rotation timer parameter.
- PRIOR MODE :
User can select the priority of the compressors in this mode according to compressor
numbers assingned by the user. Lower number assingned compressor will have more
priority in the system.

Note : Since Logik9 does not have ability to be master unit in the multiunit system. For
more detailed information and parameter adjustments refer to Logik33S or Logik200
manual.

21
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

MODBUS COMMUNICATION

The serial connection has described in Serial Connection Section.

Logik9 has 1 RS485 Serial interface. This serial interface suppots modbus RTU protocol and
allow to read compressor data’s under the conditions :

- Compressors must be working stand alone. If two compressors are working under
master / slave mode, its not possible to use same serial line to external
communication.
- If compressors are working under the multiunit operation, then Logika ethernet serial
converter interface is needed to make possible to read data from the compressors
externally modbus tcp protocol. (Serial ethernet interface also have capability to
convert modbus rtu into the modbus tcp.)
Note: Its not possible to use standard serial ethernet converter to convert the
modbus rtu protocol into the modbus tcp, since the logik ethernet serial interface
has special function to prevent master message interruption. Standard converters
do not have such capability.

Modbus communication parameters :

Baud Rate : 9600

Data Bits : 8

Stop Bits : 1

Parity : None

These modbus connection parameters are constant and they are not able to change.

Each compressor number is also modbus address of the relevant compressor. All the
compressor must have different compressor number under the compressor number
parameter setting nc.

22
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

MODBUS ADDRESS LIST FOR LOGIK 9

23
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

24
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

25
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

26
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

27
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

28
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

29
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

30
HZ-L9M.V1.23 10/2019
LOGIK 9 CONTROLLER

31
HZ-L9M.V1.23 10/2019

You might also like