You are on page 1of 1

Power Xpert® UX with W-

VACi

• IEC 60265: High-voltage switches – Part 1:


1.3 Safety instructions
Switches for rated voltages above
Read this user manual carefully before commissioning the 1 kV and less than 52 kV
switchgear. Make sure that you have read and understood • IEC 60282-1: High-voltage fuses – Part 1:
all safety warnings and instructions. Current-limiting fuses
1.3.1 General instructions • IEC 62271-105: High-voltage alternating current switch-
fuse combinations
Eaton has done its utmost to inform user as accurately and
• IEC 60470: High-voltage alternating current
as fully as possible concerning any dangers involved in
contactors and contactor-based
using the system. Users are responsible for supervising
motor-starters.
implementation of the instructions contained in this manual.
Eaton Power Xpert® switchgear can be used in areas under
Personnel normal conditions as described in IEC 62271-1, Chapter
The user must make sure that personnel are qualified to 2.1.
carry out the task.
1.3.2 Safety of the Switchroom
Safety of bystanders The installation and the switchroom must comply with all
Access to the equipment is to be limited to those directly applicable local safety regulations. The switchroom is the
involved in operating or maintaining it. room in which the switchgear has been set up and must
meet at least the following requirements:
Other persons must not remain in the vicinity of the
equipment. - Clear space
Front Access:
During switching operations, no personnel must be behind If the switchgear is arranged for front cable access then no
or above the installation. rear or side clear space is required. However Eaton
recommends at least 1mtr at one end of the switchgear is
Safety plan left to allow for ease of installation.
It may be necessary to draw up a safety plan.
Comprehensive advice on this should be obtained from the Rear Access:
relevant authorities (fire brigade, local authorities, If the switchgear is arranged for Rear cable access then a
occupational health & safety, company safety department, clear space of 0.5m is required to the wall of the switch-
first aid service etc.). room and 0.5m space at either end of the switchboard to
Safety standards allow for adequate escape routes.
Power Xpert® UX switchgear complies with the following
standards: All installations:
At the front of the switchgear Eaton recommends a
• IEC 62271-200: AC metal-enclosed switchgear and dimension of at least 1.5mtr at the front of the switchgear to
control gear for rated voltages allow for ease of operation, removal of vacuum circuit
above 1 kV and up to and including breaker from the panel and adequate escape route.
52 kV;
• IEC 60529: Degrees of protection provided by Facing installations:
enclosures (IP code); At the front of the switchgear Eaton recommends a
• IEC 62271-1: General conditions for high voltage dimension of at least 2m.
switchgear and control gear
standards

The components used comply with standards:

• IEC 62271-100: High-voltage alternating current circuit-


breakers
• IEC 62271-102: Alternating current disconnectors and
earthing switches
• IEC 60044-1: Instrument transformers – part 1:
Current transformers
• IEC 60044-2: Instrument transformers – part 2:
Voltage transformers

8 535.0001.067.00 A