Professional Documents
Culture Documents
W-V
VACi 12 / 17.5 / 24 kV IEC Vacuum Circuit Brreakers
2 65A7355H01 December 2010 www.eaton.com
Table of contents
1 Safety ................................................................................................................................. 5
1.1 Safety precautions .................................................................................................................................. 5
1.2 Safety practices....................................................................................................................................... 5
4 Inspection .........................................................................................................................34
4.1 Inspection .............................................................................................................................................. 34
4.2 Frequency of Inspection ........................................................................................................................ 34
4.3 Inspection Process ................................................................................................................................ 34
4.4 Vacuum Interrupter Integrity Test ......................................................................................................... 34
4.5 Insulation Inspection ............................................................................................................................. 34
4.6 Main Circuit Resistance Check ............................................................................................................. 35
Mechanism Inspection Check ......................................................................................................................... 35
4.7 Torque specifications ............................................................................................................................ 35
4.8 Troubleshooting Chart .......................................................................................................................... 37
6 Operation ..........................................................................................................................43
6.1 Encapsulated Pole Units ....................................................................................................................... 43
6.2 Electrical Circuit .................................................................................................................................... 43
7 Renewal parts...................................................................................................................57
7.1 General .................................................................................................................................................. 57
7.2 Ordering Instructions ............................................................................................................................. 57
7.3 Standard accessories ........................................................................................................................... 57
7.4 Optional accessories ............................................................................................................................. 60
8 Appendix ..........................................................................................................................62
8.1 12 / 17.5 / 24 kV W–VACi Vacuum Circuit Breaker Operational Check List........................................ 62
8.2 W–VACi Vacuum Circuit Breaker Equipment Check List..................................................................... 63
Voltage (Ur) kV 12 12 12 12
1250
1600
2000
1250
1600
2000
1250
1600
2000
1250
1600
2000
630
800
630
800
630
800
Normal Current(Ir) A
Short-Time Withstand
kA 25 25 25 25 25 26.3 26.3 26.3 26.3 26.3 31.5 31.5 31.5 31.5 31.5 40 40 40
Current(Ik)
Short Circuit Breaking
kA 25 25 25 25 25 26.3 26.3 26.3 26.3 26.3 31.5 31.5 31.5 31.5 31.5 40 40 40
Current(Isc)
Frequency(fr) Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Short circuit Making 63/ 63/ 63/ 63/ 63/ 100/10 100/ 100/
kA 66/65 66/- 66/- 66/- 66/- 79/82 79/82 79/82 79/82 79/82
Current(Ima) 65 65 65 65 65 4 104 104
1
DO Resistance µΩ ≤45 ≤45 ≤45 ≤35 ≤30 ≤45 ≤45 ≤45 ≤35 ≤30 ≤35 ≤35 ≤35 ≤35 ≤30 ≤30 ≤30 ≤30
Closing Time ms 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70
Opening Time ms 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60
1 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~ 0.7~
Closing Speed m/s
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3
1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~ 1.0~
Opening Speed1 m/s
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
D.C. Component of Breaking
% 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35 29-35
Current(Idc)
Cable-Charging Breaking
A 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
Current (C2)
Single Capacitor Bank
A 400 - - - - 400 - - - - - - - - - - - -
Breaking Current (C2)
Back to Back Capacitor Bank
A 400 - - - - 400 - - - - - - - - - - -
Breaking Current (C1)
Pole to Pole Spacing (Center
mm 150 150 150 210 210 150 150 150 210 210 150 150 150 210 210 210 210 210
to Center)
Upper to Lower Terminal
mm 205 275 275 310 310 205 275 275 310 310 275 275 275 310 310 310 310 310
Spacing
Mechanical Endurance2 Cycle 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k
Electrical Endurance Cycle 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k
Rated Lighting
Impulse
kV 28 28 28 28
Withstand
Rated Voltage(Up)
Insulation
Level Rated Power
Frequency
kV 75 75 75 75
Withstand
Voltage(Ud)
Classification E2-M2-S1
1:
Testing configurations available upon request
2
: 20K operations can be achieved on the 12kV, 25 kA Breaker
1250
1600
2000
1250
1600
2000
1250
1600
2000
630
800
630
800
Normal Current(Ir) A
Short-Time Withstand
kA 25 25 25 25 25 31.5 31.5 31.5 31.5 31.5 40 40 40
Current(Ik)
Short Circuit Breaking
kA 25 25 25 25 25 31.5 31.5 31.5 31.5 31.5 40 40 40
Current(Isc)
50/6 50/6 50/6 50/6 50/6 50/6 50/6 50/6 50/6 50/6 50/6 50/6
Frequency(fr) Hz
0 0 0 0 0 0 0 0 0 0 0 0
50/60
Short circuit Making 63/ 63/ 63/ 63/ 63/ 79/8 79/8 79/8 79/8 79/8 100/10 100/ 100/
kA
Current(Ima) 65 65 65 65 65 2 2 2 2 2 4 104 104
Fixed Resistance1 µΩ ≤35 ≤35 ≤35 ≤20 ≤15 ≤20 ≤20 ≤20 ≤20 ≤15 ≤15 ≤15 ≤15
DO Resistance1 µΩ ≤45 ≤45 ≤45 ≤35 ≤30 ≤35 ≤35 ≤35 ≤35 ≤30 ≤30 ≤30 ≤30
30~7 30~7 30~7 30~7 30~7 30~7 30~7 30~7 30~7 30~7 30~7 30~7 30~7
Closing Time ms
0 0 0 0 0 0 0 0 0 0 0 0 0
40~6 40~6 40~6 40~6 40~6 40~6 40~6 40~6 40~6 40~6 40~6 40~6 40~6
Opening Time ms
0 0 0 0 0 0 0 0 0 0 0 0 0
0.7~1 0.7~1 0.7~1 0.7~1 0.7~1. 0.7~1 0.7~1 0.7~1. 0.7~1 0.7~1. 0.7~1 0.7~1 0.7~1.
Closing Speed1 m/s
.3 .3 .3 .3 3 .3 .3 3 .3 3 .3 .3 3
1.0~1 1.0~1 1.0~1 1.0~1 1.0~1. 1.0~1 1.0~1 1.0~1. 1.0~1 1.0~1. 1.0~1 1.0~1 1.0~1.
Opening Speed1 m/s
.7 .7 .7 .7 7 .7 .7 7 .7 7 .7 .7 7
D.C. Component of Breaking 29- 29- 29- 29- 29- 29- 29- 29- 29- 29- 29- 29- 29-
%
Current(Idc) 35 35 35 35 35 35 35 35 35 35 35 35 35
Cable-Charging Breaking
A 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5
Current (C2)
Single Capacitor Bank Breaking
A 400 - - - - - - - - - - - -
Current (C2)
Back to Back Capacitor Bank
A 400 - - - - - - - - - - - -
Breaking Current (C1)
Pole to Pole Spacing (Center to
mm 150 150 150 210 210 150 150 150 210 210 210 210 210
Center)
Upper to Lower Terminal
mm 205 275 275 310 310 275 275 275 310 310 310 310 310
Spacing
Mechanical Endurance Cycle 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k
Electrical Endurance Cycle 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k
Rated Power
Frequency
kV 38 38 38
Withstand
Rated Voltage(Ud)
Insulation
Level Rated Lighting
Impulse
kV 95 95 95
Withstand
Voltage(Up)
Classification E2-M2-S1
1:
Testing configurations available upon request
Voltage (Ur) kV 24 24
Short-Time Withstand
kA 20 25 25 25
Current(Ik)
Short Circuit Breaking
kA 20 25 25 25
Current(Isc)
1
Closing Speed m/s 0.7~1.3 0.7~1.3 0.7~1.3 0.7~1.3
1
Opening Speed m/s 1.0~1.7 1.0~1.7 1.0~1.7 1.0~1.7
D.C. Component of
% 30 30 30 30
Breaking Current(Idc)
Cable-Charging Breaking
A 31.5 31.5 31.5 31.5
Current (C2)
Rated Power
Frequency
kV 60 60 60 60
Withstand
Rated Voltage(Ud)
Insulation Rated
Level Lighting
Impulse kV 125 125 125 125
Withstand
Voltage(Up)
Classification E2-M2-S1
1:
Testing configurations available upon request
Altitude:
Do not exceed 1000m
For applications above 1000 m de-rating is required
Service Site:
The environment shall be free of water, flame, and/or explosive hazard.
No chemical corrosive gases, and/or intensive vibration.
Frame Description:
Example: 12 W – 1
Frame 1
Upper to
Fixed
Continuous Interrupting Pole Lower Withdrawable Fixed
Withdrawable Breaker
Voltage (kV) current current Spacing terminal Breaker Frame Breaker
Breaker Frame Frame Page
(A) (kA) (mm) spacing Page Number Frame
Number
(mm)
Applicable Ratings
Breaking Normal
Voltage
Current Current
12kV 25kA 630A
12kV 26.3kA 630A
Applicable Ratings
Breaking
Voltage Normal Current
Current
25kA 630A 800A NA
12kV 26.3kA 630A 800A NA
31.5kA 630A 800A 1250A
Applicable Ratings
Breaking
Voltage Normal Current
Current
1 2
25kA NA 1600A 2000A
1 2
26.3kA NA 1600A 2000A
12kV
31.5kA NA 1600A1 2000A2
1 1 2
40kA 1250A 1600A 2000A
1
These ratings do not use a heat sink
2
These ratings do use a heat sink
Applicable Ratings
Breaking Normal
Voltage
Current Current
17.5kV 25kA 630A
Applicable Ratings
Breaking
Voltage Normal Current
Current
25kA 630A 800A NA
17.5kV
31.5kA 630A 800A 1250A
Applicable Ratings
Breaking
Voltage Normal Current
Current
1 2
25kA NA 1600A 2000A
1
17.5kV 31.5kA NA 1600A 2000A2
1 1
40kA 1250A 1600A 2000A2
1
These ratings do not use a heat sink
2
These ratings do use a heat sink
Applicable Ratings
Breaking Normal
Voltage
Current Current
24kV 20kA 800A
Applicable Ratings
Breaking
Voltage Normal Current
Current
24kV 25kA 1600A1 2000A2
1
These ratings do not use a heat sink
2
These ratings do use a heat sink
Applicable Ratings
Breaking Normal
Voltage
Current Current
24kV 25kA 2500A
Applicable Ratings
Breaking Normal
Voltage
Current Current
25kA 630A
12kV
26.3kA 630A
Applicable Ratings
Breaking
Voltage Normal Current
Current
25kA 630A 800A NA
12kV 26.3kA 630A 800A NA
31.5kA 630A 800A 1250A
Applicable Ratings
Breaking
Voltage Normal Current
Current
1 2
25kA NA 1600A 2000A
1 2
26.3kA NA 1600A 2000A
12kV 1
31.5kA NA 1600A 2000A2
1 1 2
40kA 1250A 1600A 2000A
1
These ratings do not use a heat sink
2
These ratings do use a heat sink
Applicable Ratings
Breaking Normal
Voltage
Current Current
17.5kV 25kA 630A
Applicable Ratings
Breaking
Voltage Normal Current
Current
25kA 630A 800A NA
17.5kV
31.5kA 630A 800A 1250A
Applicable Ratings
Breaking
Voltage Normal Current
Current
1 2
25kA NA 1600A 2000A
1
17.5kV 31.5kA NA 1600A 2000A2
1 1 2
40kA 1250A 1600A 2000A
1
These ratings do not use a heat sink
2
These ratings do use a heat sink
Applicable Ratings
Breaking Normal
Voltage
Current Current
24kV 20kA 800A
Applicable Ratings
Breaking
Voltage Normal Current
Current
24kV 25kA 1600A1 2000A2
1
These ratings do not use a heat sink
2
These ratings do use a heat sink
Applicable Ratings
Breaking Normal
Voltage
Current Current
24kV 25kA 2500A
Inspect the container for any signs of damage or rough Outdoor storage is NOT recommended. However, if
handling upon receipt. Open the container carefully to unavoidable, the outdoor location must be well drained
avoid any damage to the contents. and a temporary shelter from sun, rain, snow, corrosive
fumes, dust, dirt, falling objects and excessive moisture
Be careful that any loose items or hardware are not must be provided. Containers should be arranged to
discarded with the packing material. When opening the permit free circulation of air on all sides and temporary
container, check the content of each package against heaters should be used to minimize condensation.
the packing list. Moisture can cause rusting of metal parts and
deterioration of high voltage insulation. A heat level of
Examine the circuit breaker for any sign of shipping approximately 400 watts for each 3 cubic meters of
damage such as broken, missing or loose hardware, volume is recommended with the heaters distributed
and damaged or deformed insulation. File claims uniformly throughout the structure near the floor.
immediately with the carrier if damage or loss is
detected and notify the appropriate Eaton Indoor storage should be in a building with sufficient
representative. heat and circulation to prevent condensation. If the
building is not heated, the same rules for outdoor
storage should be applied.
3.2 Handling
WARNING
Do not use a lifting device as a platform for
performing inspection or repair on the circuit
breaker, nor for operating the contacts or
charging the springs. The breaker may fall,
causing severe personal injury. Always use a
suitable workbench capable of supporting the
breaker.
31.5kA 123 123 124 173 173 800A 1600A 2000A 2500A
40kA N/A N/A 173 173 173 20kA 104 N/A N/A N/A
*±3kg.
Fixed
*±3kg.
4
10
5
11 6
7
12
7
1 8
2 9
3 10
4
11
5
Finge
er Cluster
Heat Sinkk
Encapsulated Pole
Unit
Racking in
Assemblyy
Wheel
Rack
king in Assembly
WARNING WARNING
• Do not work on a breaker in the "service" Applying abnormally high voltage across a pair
position. of contacts in vacuum may produce x-radiation.
The radiation may increase with the increase in
• Do not work on a breaker with secondary
voltage and/or decrease in contact spacing. X-
disconnects engaged.
radiation produced during this test with
• Do not work on a breaker with springs recommended voltage and normal contact
charged or contacts closed. spacing is extremely low and is well below
• Do not override any safety interlocks. maximum levels.
• Do not leave the charging handle in working
location after charging the closing springs. WARNING
• Do not stand less than one meter away from
After the high potential test is conducted, an
the breaker when testing for vacuum integrity.
electrical charge may be retained by the vacuum
interrupters. Failure to discharge this residual
electrostatic charge could result in an electrical
4.2 Frequency of Inspection shock. Follow safety procedures for this type of
It is recommended to inspect the breaker when it is test.
received. In cases where the breaker operates in a
clean and non-corrosive environment, the circuit
breaker should be inspected after 10 years or 10,000
operations, whichever comes first. In dusty and/or 4.5 Insulation Inspection
corrosive environment, inspection should be performed
Insulation inspection is performed to keep all insulating
at least once a year. Additionally, it is recommended to
surfaces clean. This can be done by wiping all
inspect the breaker every time it interrupts a fault
insulating surfaces with a dry lint free cloth and
current.
denatured alcohol. In case there is any tightly adhering
dirt that will not come off by wiping, it can be removed
4.3 Inspection Process with a mild solvent or distilled water. Confirm that the
surfaces are dry before placing the breaker in service.
See Table 4-4 and follow the steps to inspect the If a solvent is required to remove the dirt, once the
breaker. switchgear has been isolated, use benzene or white
spirit. Secondary control wiring requires inspection for
tightness of all connections and damage to insulation.
4.4 Vacuum Interrupter Integrity
Test
Vacuum interrupters used in all W-VACi circuit
breakers are highly reliable interrupting elements.
Satisfactory performance of these devices is
dependent upon the integrity of the vacuum in the
interrupter and the internal dielectric strength. Both of
these parameters can be readily checked by a one
minute AC high potential test. During this test, the
following warning must be observed:
4.7 To
orque spec
cifications
T
Table 4-3: Torqu
ue Specification
ns
Nominal size
e and
Newton Mete
ers (Nm)
pitch
M5 x 0.80 6
M6 x 1.00 10
M7 x 1.00 18
M8 x 1.25 25
M10 x 1.50 50
M12 x 1.75 88
M14 x 2.00 141
Table 4-4: Inspection Process Chart
Section Inspection Item Criteria Inspection Method Corrective Action
Drive insulator, Clean with lint-free
No dirt and no
Insulation barriers, and stand- Visual inspection cloth or replace
cracking
off insulators cracked piece
Main circuit to AC High Potential Clean and retest or
Withstand
ground Test replace
Between main circuit AC High Potential Clean and retest or
Insulation Integrity Withstand
terminals Test replace
Control circuit to AC High Potential Clean and retest or
Withstand
ground Test replace
Fail to Close
● No control power
(fuse blown or switch off)
● Motor failure
Undesirable Close
Fail to Trip
Undesirable Trip
W
WARNING
Before plac cing the circuit breaker in service,
s
follow the installation prrocedure given below
carefully. Not
N following thet procedure e can lead
Fig. 5-1: Pu
ull the round handle down
to a failure
e to uncover damage that maym have
resulted in faulty breakeer operation.
CAUTION
C
Any wiring instructions
i pre
esented in this document
must be folllowed preciselyy. Failure to do
o so could
cause permmanent equipme ent damage.
Fig. 5-3: Tu
urn the handle clockwise
c
5.2 Ma
anual Operration Che
eck
Withdraw the charging handle as shown in Fig. 5-1 &
Fig. 5-2. Charrge the closing spring by turning the
handle clockwwise, as shown in Fig. 5-3. Wh hen the
closing spring is charged, the e indicator of th
he spring
charged state (Fig. 3-4) turnss to “charged”.
Return the haandle to its orig
ginal resting pla
ace and
press the “closse button” (Fig. 5-4). The clos sing spring
becomes disccharged and the e breaker close es. Note the
indicator now reads “CLOSE E”. Now press the “open”
Fig. 5-4:
5 Close manu
ually
button (Fig. 5--5). The breakeer is now open and the
indicator readss “OPEN”.
Fig. 5
5-5: Open manu
ually
5.3 ameplate
Na CAUTION
N
Compare the circuit breaker nameplate info ormation Exammine the insidee of the cell beffore inserting or
with technical data in the tecchnical parameters sections mounting the breakker for excessivve dirt or anyth hing
2.3, 2.4 or 2.5
5. Also compare e the breaker with
w the that might interfere with the breakker travel or
breaker outline drawings and d switchgear drawings for insta
allation.
conformance and compatibility. In case of potential
p
discrepancy, contact
c your Eaaton representa
ative before
WARNING
installing the circuit
c breaker.
Extreme caution must
m be exerc
cised to ensure
that primary circu
uits are not energized while
checcks are perforrmed in the bre
eaker
com
mpartment. Failure to do so may
m result in
pers
sonal injury orr death.
When testing
t a withdrrawable breake er electrically, it
should be done in the e TEST position n. To achieve the
5.4 Va
acuum Inte
errupter Inttegrity TEST position,
p the cirrcuit breaker must
m first be placed
in the cell
c structure with the shoot bo olt engaged an nd
Ch
heck the seccondary contaccts engaged. To o complete thiss
Clean all the insulating surfaaces of the polee units with a testing procedure, the e operator shou uld first be familiar
dry, lint free clloth and denatuured alcohol. Refer
R to with insserting and remmoving the circu uit breaker intoo and
section 4.4 aftter this action is
s completed. out of the cell structurre. When the circuit breaker
needs to t be racked innto switchgear, insert the rackking
handle onto the rackin ng coupling levver and rotate it
clockwiise for insertion n and countercclockwise for
5.5 Ins
sulation withdraawal. When the e circuit breaker has reached
“CONN NECTED” position during the racking processs, a
The primary in
nsulation for the
e vacuum interrrupters distincttive sound will bbe heard. Excessive force
need to be checked. Refer to o the procedure e in Table appliedd to the rackingg handle when the t circuit brea aker
4-1. This can be done by cloosing the circuitt breaker has reaached “CONNE ECTED” positio on could cause
and performinng a power freqquency voltage test. mechan nism damage.
5.7 Ele
ectrical Op
perations Check
C
After going thrrough the previous steps, the e breaker is
ready to be op cally. It is preferred that this
perated electric
check be mad de with a withdrrawable breake er in a “Test”
position or dis
sconnected possition. A fixed breaker
b can
not be in the cell
c during this test.
5. Withdrawable type breakers cann
not perform
5.8 Ra
acking han
ndle “CLOSE” and “OPEN” operations be etween the TES
ST
The racking handle is used to t move withdra awable and SEERVICE positio
ons.
circuit breakerrs from the testt position to the
e service
position. 6. For withdrawable
w b
breakers with optional electriccal
magnettic interlock, the breaker cannnot finish the
“CLOSE” operation, unless
u the seco
ondary disconn nect
is conn
nected and the breaker is either at TEST or
SERVIC CE position.
7. As to
o other optionaal parts, such ass, Under Voltag ge
Release (UVR) trip de evice or an oveer current trip, you
y
must coonfirm their fun
nction based on n their system
Fig. 5-7: Rac
cking Handle design needs. Please e refer to your own
o specificatioons
when you
y ordered the e breaker.
Fig.
F 5-8: Inserted
d racking Handlle
W
WARNING
Never disaable any interlo
ocks. They aree intended
for proper and
a safe operattion. Failure to
o comply
vere personal injury
could result in death, sev
and/or property damage e due to the hazzardous
esent.
voltage pre
1
2
4
Fig. 5-9: Pull the round handle down
WARNING 1
Keep hands and fingers away from the breaker's 5
internal parts while the breaker contacts are 2
closed or the closing springs are charged. The
breaker contacts may open or the closing
6
springs may discharge causing a serious injury.
3
Discharge the springs and open the breaker 7
before performing any breaker inspection or
repair.
4 8
The operating mechanism uses stored energy from the
closing spring (Fig. 6-2). The closing unit has one 9
shunt closing release and the opening unit is
composed of one or more shunt opening release Fig. 6-2: Universal Mechanism Assembly (UMA)
coil(s). Both have auxiliary switches and indicating
devices which are all installed in the circuit breaker 1. Closing Spring 6. Close Button
frame. Closing and opening buttons, the manual 2. Charge Indicator 7. Charging Handle
charging handle, spring charging state indicator, and 3. Operations Counter 8. Optional Shunt Opening Release Location
closed/open indicators are all front accessible. 4. Auxiliary Switches 9. Open Button
5. Motor
1
Gearrs
2
3 Closing Spring
Signaling
4 Contacts
6.4 Ch
harging
The energy reequired for a cirrcuit breaker closing is
provided by chharging a closing spring using g a charging
motor or manu w the charging handle.
ually charging with
When electrically charging, the
t output shafft of the
motor actuates a gear drive system. When n manually
charging, the gear
g driving syystem is actuateed through a
pinion gear that is attached to
t the charging g handle.
Once charged d, the indicator will display “CHHARGED”
and the motorr cutting switch will break the power
supply of the charging
c motorr. The circuit breaker
b is
now ready for closing.
6.5 Closing
The closing op peration is acco
omplished by either
e
manually presssing the “CLOS SE” button or byb remote
operation to actuate the shunt opening rele ease coil.
Once closed, the indicator will
w read “CLOSED” and the
circuit for the power
p supply to the motor is returned. At
the same time e the counter is
s actuated to pe erform the
counting functtion and the driiving linkage acctuates the
main auxiliaryy switch to transsfer states of th
he other
switches and sensors
s betweeen on and off. The 4 states
of the mechan nism can be se een in Figures 6-6
6 through
Figure6-9 on thet following pa age.
Fig. 6-5: M
Manual Charging
g Process
1 1
3
3
4 4
5 5
11 6 11 6
2 2
7 8 7 8
9 9
10
10
Fig. 6-6: Breaker Open and Closing Spring Fig. 6-7: Breaker Closed and Closing Spring
Discharged Discharged
1 1
3 3
2 2
5 5
11 6 6
8 11 8
4 7 4
9 7 9
10 10
Fig. 6-8: Breaker Open and Closing Spring Charged Fig. 6-9: Breaker Closed and Closing Spring Charged
1
Rated Parameters of UMA Motor
Item Value
Rated
Ua (DC) 24-48-60-110-125-220-250 V
Voltage
Rated
Ua (AC) 110-120-220-230 V
Voltage
Voltage
85%-110% rated voltage
Range
Time for
≤15
Charging (S)
Rated Parameters of Releases1
Item Value
Rated
Ua (DC) 24-48-60-110-125-220-250 V
Voltage
Rated
Ua (AC) 110-120-220-230 V
Voltage
Rated
≤3 ≤2 ≤5 ≤5 ≤10
Current(A)
Attributes
Ua (DC) 24-48-60-110-125-220-250 V
Ua (AC) 110-120-220-230 V
70…110% Ua (DC)
Operating Limits
85…110% Ua (AC)
Insulating voltage 2000 V 50/60 Hz (for 1 min.)
Attributes
Ua (DC) 24-48-60-110-125-220-250 V
Ua (AC) 110-120-220-230 V
70…110% Ua (DC)
Operating Limits
85…110% Ua (AC)
Insulating voltage 2000 V 50/60 Hz (for 1 min.)
Ua (DC) 24-48-60-110-125-220-250 V
Ua (AC) 110-120-220-230 V
48 VDC
V / 6.0A
60 VDC
V / 5.0A
110-12
25 VDC / 2.9A 65A7009G02
220-25
50 VDC / 1.7A
220-23
30 VAC / 9.5A
Attributes
A IEC Contact Class 1,, Rated Continuouss Current 10A, Brea
aking Capacity 440
0W
Insula
ating voltage 2000 V 50/60 Hz (for 1 min.)
48 VDC
V / 2.5A
60 VDC
V / 2.0A
110-12
25 VDC / 0.9A 65A7014G01
220-25
50 VDC / 0.4A
110-12
20 VAC / 9.5A
220-23
30 VAC / 5.0A
Attributes
A
Insula
ating voltage 2000 V 50/60 Hz (for 1 min.)
48 VDC
V / 7.0A
60 VDC
V / 6.0A
110-12
25 VDC / 3.7A 65A7012G01
220-25
50 VDC / 0.9A
110-12
20 VAC / 5.0A
220-23
30 VAC / 2.5A
A
Attributes IEC Contact Class 1,, Rated Continuous
s Current 10A, Brea
aking Capacity 440
0W
Insulating voltage 2000 V 50/60 Hz (for 1 min.)
Racking Ha andle
This device is used to man nually rack the circuit breakerr into the switch
hgear. One unit of this device
e can
be used for all of the circu
uit breakers on a particular site
e.
Attributes
Ua (DC) 24-48-60-110-125-220-250 V
Ua (AC) 110-120-220-230 V
70…110% Ua (DC)
Operating Limits
85…110% Ua (AC)
Insulating voltage 2000 V 50/60 Hz (for 1 min.)
Attributes
Ua (DC) 24-48-60-110-125-220-250 V
Ua (AC) 110-120-220-230 V
Attributes
Ua (DC) 24-48-60-110-125-220-250 V
Ua (AC) 110-120-220-230 V
35-0% Ua: UVR operates, circuit breaker opens
Operating Limits
70-110% Ua: UVR does not operate
Insulating voltage 2000 V 50/60 Hz (for 1 min.)
65A7020G01
12 / 17.5 kV all frames
24 kV 210 Pole Spacing
Fixed Circuit Breaker Interlock
65A7020G02
24 kV 275 Pole Spacing Only
Use the following charts to verify that the circuit breaker is in the correct operational status and that the received circuit
breaker has the exact same equipment as ordered.
Reference
List Explanation Result
Section
Short Circuit
Breaking Current □20 □25 □26.3 □31.5 □40
(kA)
Pole To Pole (mm)*
□150 □210 □275
Distance
Technical Parameters of UMA Mechanism
Shunt Opening □24VD □48VD □60VD □110V □125V □220V □250V □110V □120V □220V □230V
Release (Ua) C C C DC DC DC DC AC AC AC AC
Shunt Opening □24VD □48VD □60VD □110V □125V □220V □250V □110V □120V □220V □230V
Release #2 (Ua) C C C DC DC DC DC AC AC AC AC
Shunt Closing □24VD □48VD □60VD □110V □125V □220V □250V □110V □120V □220V □230V
Release (Ua) C C C DC DC DC DC AC AC AC AC
□24VD □48VD □60VD □110V □125V □220V □250V □110V □120V □220V □230V
Charging Motor(Ua)
C C C DC DC DC DC AC AC AC AC
Additional Equipment
Under-Voltage □24VD □48VD □60VD □110V □125V □220V □250V □110V □120V □220V □230V
Release C C C DC DC DC DC AC AC AC AC
Mechanism
□24VD □48VD □60VD □110V □125V □220V □250V □110V □120V □220V □230V
Electromagnet
Interlock C C C DC DC DC DC AC AC AC AC
Eu
urope, Middle East annd Africa Asiia Pacific
Ea
aton Electric B.V. Eatton Electrical Sector Asia
A Pacific
P.O
O. Box 23 Heaadquarters
7550 AA Hengelo No..3 Lane 280 Linhong Road
R
The Netherlands Chaangning District
el.: +31 74 246 4012
Te Shaanghai 200335, P.R.C China
Fa
ax: +31 74 246 4601 Tel.: +86 21 5200 0099
Se
ecretariaatCSsystems@@eaton.com Faxx: +86 21 5200 0200
ww
ww.eatonelectrical.com
m ww
ww.eatonelectrical.com m.cn
So
outh America Norrth America
Ea
aton Ltda. Eatton Corporation
Av
v. Pierre Simon de Lapplace, 751 Ele
ectrical Sector
Co
ond. Techno Park – Via 00 Cherrington Parkwa
100 ay
An
nhanguera, Moon Township, PA 151008
Km
m 104,5 Uniited States
Ca
ampinas - SP - 13069--320 - Brasil 877
7-ETN-CARE (877-386 6-2273)
Te
el.: +55 19 2117 0000 ww
ww.eaton.com
eatonelectricalbrasil@ea
aton.com
ww.eaton.com.br
ww