Professional Documents
Culture Documents
(FACILITY 71)
OPERATIONS AND
MAINTENANCE MANUAL
August 2018
Facility 71 Wastewater Treatment Plant
Operations and Maintenance Manual
TABLE OF CONTENTS
7 SAFETY .............................................................................................................................. 73
List of Tables
Table 1 Influent Batching Process Equipment ................................................................. 6
Table 2 Influent Batching Process Equipment ................................................................. 7
Table 3 pH Adjustment Process Equipment ..................................................................... 9
Table 4 Reaction/Precipitation Process Equipment ....................................................... 14
Table 5 Flocculation Process Equipment ........................................................................ 17
Table 6 Primary Clarification Process Equipment ......................................................... 20
Table 7 Treated Effluent Management Process Equipment .......................................... 22
List of Figures
Figure DWG-1 Vicinity Map and Project Location Map
Figure DWG-2 Temporary Treatment System Process Diagram
Figure DWG-3 Temporary Treatment Plan
Figure DWG-4 Detailed Temporary Treatment Plan
Figure DWG-5 Temporary Treatment Plant Details
List of Appendices
FIGURES
Appendix A Treatment Process and Equipment ID Schedule
Appendix B System Startup Procedures/Checklist
Appendix C Shutdown Procedures/Checklist
Preface
This manual is intended to be a reference source for operation and maintenance of the
reconstructed Wastewater Treatment Plant (WWTP; Facility 71) at the Millennium Bulk
Terminals – Longview, LLC (MBT-Longview) facility in Longview, Washington. The goal of
this manual is to provide a basis for the operation and maintenance of Facility 71 in order to
maximize operational efficiency.
Facility 71 is a fully contained batch treatment system that operates seasonally as needed.
Current influent sources to the WWTP include waters from the former leachate ditch and
the former cryolite ditches. Ditch waters from the former cryolite plant area and former
leachate ditch consist of infiltrated groundwater and stormwater that have accumulated in
the ditches. These waters are accumulated seasonally (i.e., during the rainy season) and are
managed through batch treatment in the WWTP. Waters from the ditch areas are pumped
and stored in the old clarifier tanks at Facility 77 (Tanks 1, 2, and 3). The WWTP is designed
to remove fluoride, cyanide, and PAHs [including B(a)P] from wastewaters. Waters
generated during site remediation and redevelopment activities will be evaluated for fluoride
and will be treated in Facility 71 if necessary.
The plant consists of a sequenced treatment process occurring in six interconnected tanks.
Treatment is accomplished through, influent batching, pH adjustment, reaction/
precipitation, flocculation, primary clarification, treated effluent management, and sludge
management. Facility 71 discharges into the Outfall Sump/Pump Station (Facility 77)
collection sump where it is combined with site stormwater. The combined effluent
undergoes further treatment through the Retention Basin and Filter Plant (Facility 73) prior
to its discharge into the Columbia River through Outfall 002A. Additional treatment
provided by Facility 73 includes settling and multimedia filtration.
The plant was formerly used to treat the aluminum reduction plant’s wet air emission control
system bleed stream, but this influent stream ended when aluminum reduction operations
ceased in 2001. Facility 71 operating parameters were originally set to remove cyanide and
fluoride down to 2 ppm and 300 ppm, respectively. Current influent concentrations are
much lower with WAD cyanide ranging from 0.010 to 0.023 ppb and fluoride ranging from
26 to 34 ppm. When Facility 71 is operating, the average discharge is 0.08 MGD.
down. During severe storm events, the system has plenty of storage and operation could be
shut down if upset conditions are noted. During startup, the system is designed to recirculate
until it is determined the effluent is ready for discharge. The automated operations at
Facility 71 use a programmable logic controller (PLC) for process management and
monitoring. Process tank levels, pump operations, and chemical pump operations are
monitored continuously, and the control system will set off an alarm if a malfunction or
operational error occurs. The alarm system will send a text and an email notification to
MBT-Longview staff available to respond, which includes a 24-hour guard.
The PLC logs flow, pH, chemical pump operation, and process tank levels. Critical
information is transferred to a Supervisory Control and Data Acquisition (SCADA) system
for remote monitoring, trend analysis, alarm monitoring, and data processing. In addition to
the automatic logging, manual inspections and recordings of key operational parameters (e.g.,
flow rates totalizers, pH) are logged daily during regular environmental staff business hours
(Monday-Friday, 8:00 am to 5:00 pm).
The WWTP is designed to remove fluoride, cyanide, and PAHs [including B(a)P] from
wastewaters. Any small changes in influent concentrations for these parameters does not
cause upset conditions due to the fact that the system was designed to treat much higher
level concentrations.
For more detailed descriptions of the above processes please refer to the Facility 71 operating
and maintenance manual.
1 GENERAL INFORMATION
1.1 Background
The original Facility 71 was built by Reynolds Metals Company in the 1980s to treat on-site
wastewater generated by the former aluminum reduction facility. The former aluminum
reduction facility was permanently closed in 2001, and the equipment necessary for the
aluminum reduction processes was subsequently removed through decommissioning.
Consequently, the majority of the wastewater, for which the original Facility 71 was
constructed, is no longer generated. The remaining principal water sources include
stormwater from the Closed Black Mud Pond (BMP) leachate ditch and the cryolite ditches
and remediation water or water generated during construction dewatering activities.
Facility 71 was reconstructed during late 2011 and early 2012, following the destruction of
the original wastewater treatment plant by a fire that occurred in June 2011. The facility
was constructed with new parts and materials. Nothing from the original wastewater
treatment plant was included in the replacement facility.
1.2 Introduction
Facility 71 is a fully contained batch treatment plant that consists of sequenced treatment
processes occurring in six interconnected portable tanks. A high-density polyethylene
(HDPE) containment membrane underlies Facility 71 and extends vertically along the
perimeter walls of Facility 71. The treatment efficiency of the facility is intended to match
the treatment efficiency of the original Facility 71 (see Figures DWG-1 through DWG-5).
In-use bulk totes of wastewater treatment chemicals and reagents are stored within the
Facility 71 containment structure, while bulk totes of chemicals and reagent held as
inventory are stored within the original Facility 71 containment structure. The original
containment structure was not damaged by the fire and still acts as a fully functioning
containment floor. The process tanks are connected in series by force main (pumped) piping
and gravity-flow piping. Within the various process tanks are equipment controls, tank
mixers, and circulation lines necessary for monitoring and addition of chemicals and
reagents.
Facility 71 includes a main control facility that contains many of the controls and operations’
equipment. The main control facility is a container unit that is divided into the following
three subunits:
Main Control Room (MCR). A majority of the operations and controls for Facility 71
processes are located in the MCR at the control panel.
Mechanical Room. WWTP pumps (transfer pumps, sample pumps, and chemical,
reagent, and polymer feed pumps) used in Facility 71 are located in the
mechanical room.
Ancillary Storage Room. General WWTP supplies, spare parts, and electrical service
panels are located in the ancillary storage room.
The WWTP treats benzo(a)pyrene (B[a]P), total cyanide, and fluoride. The monitoring point
for Facility 71 is Outfall 002B, an internal outfall that discharges into the Outfall Sump/Pump
Station (Facility 77) collection sump where it is combined with site stormwater. The Outfall
002B discharge and site stormwater is then transferred by pumping to the Retention Basin
and Filter Plant (Facility 73). The Retention Basin provides treatment through the settling of
solids and by mechanical skimmer removal of oil and grease components that rise to the
surface. The Filter Plant provides filtration treatment by further removal of solids, associated
metals and oil and grease, as necessary, when treatment through the Retention Basin is
insufficient. Discharging water from Facility 73 is then conveyed to the Columbia River
through Outfall 002A.
Treated effluent is monitored and sampled at Outfall 002B in accordance with the NPDES
Wastewater Discharge Permit WA000008-6. Currently the permit requires monitoring and
sampling when remediation water as defined in Section S1.E of the permit is processed.
Samples collected at Outfall 002B are analyzed by in-house and contracted off-site
laboratories. Influent flow rates, water level in process tanks, pH in two process tanks, and
reagent addition rates are continually monitored and displayed at the human machine
interface (HMI).
Facility 71 is capable of automatic operation using level switches located within the various
process tanks, failsafe controls, and built-in alarms that are annunciated locally at the control
panel and a call out to operators (either text or email notification).
further treated through the on-site stormwater treatment processes and eventually pumped
into the Columbia River from Facility 73 through Outfall 002A. This train of treatment has
occurred since operation of the Retention Basin and Filter Plant began in the 1990s.
The operational objective of Facility 71 is to efficiently remove B(a)P, fluoride, and cyanide
from the influent wastewater sources for which Facility 71 is designed. Specific processes are
included in Facility 71 for the removal of each listed influent constituent. B(a)P removal is
achieved in the flocculation process and sludge handling process. Fluoride and cyanide
removal is achieved through multiple processes, such as the pH adjustment and reaction
process, precipitation process, flocculation process, and ultimately the sludge handling
process.
The treated effluent from Facility 71 at Outfall 002B undergoes further treatment through
the Retention Basin and Filter Plant (Facility 73) prior to its discharge into the Columbia
River through Outfall 002A. Additional treatment provided by Facility 73 includes settling
and multimedia filtration.
ID Assignments
Assigning unique IDs to processes and equipment follows a format described in the list
below. In general, the format is focused on individual treatment processes in ascending ID
number, which follows treatment flow sequence. For a complete list, see Appendix A.
ID Description Notes
X00 Treatment Process 100-level sequence for processes
X05 Process Influent Pump Typically a transformer pump for delivery of process water into a process tank
X19 Primary Inlet Typically an inlet to a process tank from a pump or a gravity-flow pipe
X20 Process Tank Tanks where processes occur
X21 HH Level Switch High-high-level switches (equipment control); typically installed in tanks
X22 H Level Switch High-level switches (equipment control); typically installed in tanks
X23 L Level Switch Low-level switches (equipment control); typically installed in tanks
X24 LL Level Switch Low-low-level switches (equipment control); typically installed in tanks
X25 Tank Mixer Typically for mechanical tank misers
X28 Bulk Totes/Drums1 Bulk totes and/or drums containing reagents, chemicals, or polymers
X29 Bulk Level Sensors1 Level sensors for bulk totes and/or drums to indicate product level
1
X30 Feed Pumps Feed pumps that draw product from bulk totes/drums
X40 Ancillary Pump Typically for circulation pumps
X50 Sensor/Device Typically for sensors/devices on circulation pump circuits
X52 Feed Pump Discharge Discharge point for feed pumps that draw product from bulk totes/drums
Point2
X55 Pump Discharge Point3 Discharge point for various pumps except for feed pumps; typically into a
process tank
X60 Tank Outlets X60 through X64 for tank outlets; X60 for primary tank outlet
ID Description Notes
X65 Tank Outlet Valves/ X65 through X69 for valves and other equipment attached (downstream) of
Equipment tank outlets; X65 for direct connection to outlet
X75 Process Effluent Pump Typically a transfer pump for delivery of process water into a subsequent
process tank
1 - Add five to the ID number of the primary process to generate the ID number of the additional chemical/reagent
process. For example, a primary feed pump would have the ID of X30, and the secondary feed pump would
have an ID of X35 (X30 + 5).
2 - Add one to the ID number of the primary process to generate the ID number of the additional chemical/reagent
process. For example, a primary feed pump discharge point would have the ID number of X52, and the
secondary feed pump discharge point would have an ID of X53 (X52 + 1).
3 - Add one to the ID number of the primary pump discharge point to generate the ID number of the additional
pump discharge point. For example, a primary pump discharge point would have the ID number of X55, and the
secondary pump discharge point would have an ID of X56 (X55 + 1).
Water from the leachate ditch area is pumped to Tank 3. Tank 3 is located in Facility 77 and
is one of three aboveground cylindrical tanks with an approximate volume of 600,000
gallons. Wastewater sources have, in the past, been pumped into Tanks 1 and 2 (also in
Facility 77) and then pumped from Tanks 1 and 2 into Tank 3. When possible, Tank 3 level
will be managed to avoid overflow to the surge tank by transferring water to designated
alternate storage vessels. Any incidental overflows to the Facility 77 surge tank or water
transferred to alternate storage vessels will be transferred back to Tank 3 for treatment when
capacity is available.
Water from the cryolite ditch area is pumped to Tank 1 and/or Tank 2 storage and then
pumped to Tank 3.
Table 1
Influent Batching Process Equipment
Tank 3 is equipped with a water level sensor that continuously measures the water level in
the tank. The measured level is displayed on the HMI in the MCR and on the sensor
controller near Tank 3 in Facility 77 in terms of percent full. The sensor measures the
percentage of volume capacity between the top of the tank cone and bottom of the overflow
trough near the top of the tank. If used for storage, levels in Tank 1 and Tank 2 will be
manually gauged by the system Operator. Both Tank 1 and Tank 2 have high level indicator
lights.
Table 2
Influent Batching Process Equipment
Notes:
1 = Equipment described in the previous process.
2 = Containment pump is not a process pump; it manages precipitation collected within the containment area.
3 = Valve is NORMALLY OPEN.
4 = Valve is NORMALLY CLOSED.
The batch pump is a 3-inch-diameter submersible pump located in Tank 3 (Facility 77). The
discharge line from the batch pump runs over the top of Tank 3, down along the outside wall
of Tank 3, and continues on-grade and below gratings between Tank 3 and Facility 71.
The influent air/vacuum release valve is installed on the batch pump discharge line at the top
of Tank 3 in Facility 77.
The influent batch tank is 40 feet long, 8 feet wide, 10 feet high, and it is located opposite the
main control facility. The pH tank and reaction tank are located atop the influent batch
tank. The influent batch tank volume between the batch pump normal operating cycles is
approximately 12,600 gallons. A wye-strainer and valve is attached to the influent batch
tank discharge valve; the wye-strainer valve is NORMALLY CLOSED and the wye-strainer
allows for the removal of accumulated sediment near the outlet of the influent batch tank.
The influent batch tank discharge valve is NORMALLY OPEN.
The containment pump is a common float-activated pump located near the effluent tank.
Under normal operations, the batch pump control switch at the control panel is in the
“Auto” position, and pump operations are controlled by level switches. When the water
level in the influent batch tank decreases below the influent batch tank low- (L-) level
switch, the batch pump will turn on and will continue to run until the water level in the
influent batch tank rises above the influent batch tank high- (H-) level switch, at which
point the batch pump will shut off.
A failsafe control will shut off the batch pump if the water level in the influent batch tank
rises above the influent batch tank high-high- (HH-) level switch. A second failsafe control
will shut off the batch pump if the water level in the containment area rises above the
containment level switch. The former may be engaged if the high-level switch fails, and the
latter may be engaged if any of Facility 71 process tanks are breached. Water level switches
are annunciated on the HMI with colored letter icons when an alarm condition occurs (e.g.,
HH, H, L, and LL) and a call out to operators.
When the water level within the containment area rises above the float switch on the
containment pump, the containment pump will run until water level falls below the float
switch.
Table 3
pH Adjustment Process Equipment
Notes:
1 = Equipment is described in the previous process.
2 = Valve is NORMALLY OPEN.
3 = Valve is NORMALLY CLOSED.
4 = Equipment is used in multiple processes.
5 = Included equipment is referred to as the acid feed system.
6 = Equipment monitors pH in the reaction/precipitation process.
The influent pump is a centrifugal pump located in the mechanical room of the main control
facility. The influent pump suction line is connected to the influent batch tank discharge
valve located at the bottom of the tank and runs underneath and into the mechanical room
to the influent pump. The influent batch tank discharge valve on the suction line is
NORMALLY OPEN. The influent pump discharge line runs underneath the mechanical
room and along the outside wall of the influent batch tank, over the side and into the pH
tank. Drain valves on both the influent pump suction and discharge lines are located below
the mechanical room; the drains are NORMALLY CLOSED and may be used for freeze
protection during extended periods of freezing temperatures.
The influent flow meter is a magnetic flow meter located on the influent pump discharge
line between the mechanical room and the influent batch tank. It continuously measures
the flow rate between the influent batch tank and pH tank and displays the measured flow
rate on the instrument and also on the HMI in the MCR. The flow rate is used as an
operations parameter in various processes to control reagent addition, mixing, operation of
the sample pumps, and overall process control logic. The influent flow control valve is
located upstream of the influent flow meter and is NORMALLY OPEN; it may be closed to
circulate water between the effluent tank and pH tank.
The pH tank is 18 feet long, 7 feet wide, 5 feet high, and it is located on top of the influent
batch tank. There is an approximate volume of 2,200 gallons below the outlet invert
elevation of the pH tank.
The acid feed system includes the pH Sample Pump 1, pH Sensor 1, the pH controller, and
the acid feed pump, which are located in the mechanical room. Water is circulated by pH
Sample Pump 1 from the pH tank to the mechanical room past pH Sensor 1 and back to the
pH tank. The pH of the wastewater in the pH tank is continually measured by pH Sensor 1.
The pH controller compares the measured pH against the pH set-point and modulates the
speed of the acid feed pump to maintain the pH set-point entered into the pH controller.
The acid feed pump delivers the sulfuric acid into the pH Sample Pump 1 discharge pipe
below the floor of the mechanical room. The pH Sample Pump 1 suction line drain valve,
which is NORMALLY CLOSED, is located below the mechanical room and may be used for
freeze protection during extended periods of freezing temperatures. Sulfuric acid is stored in
the acid bulk tote located outside and adjacent to the mechanical room. Containment tubing
is installed on pressure line tubing connected to the acid feed pump. The containment
tubing is larger in diameter than the pressure line tubing and drains into the acid feed pump
containment bucket located below the mechanical room.
The suction line of pH Sample Pump 1 is located on the downstream end of the pH tank, at a
NORMALLY OPEN valve on the outside wall of the pH tank. The discharge line of pH
Sample Pump 1 empties into the pH tank over the rim of the tank. Isolation valves are
located downstream of Sample Pump 1 and on either side of pH Sensor 1; the isolation valves
are NORMALLY OPEN.
The pH of the wastewater in the reaction tank is monitored by pH Sample Pump 2 and
pH Sensor 2 as part of the reaction/precipitation process, described in Section 2.4. The
measurement of pH in the reaction/precipitation process is displayed on the pH controller
and HMI; this measured pH is displayed for informational purposes and may be helpful in
fine-tuning the feed rate set-points for acid addition and the other reagents used in
Facility 71.
The pH tank mixer is a constant speed mixer that operates continuously unless shut off by
controls described subsequently.
Under normal operations, the influent pump control switch at the control panel is in the
“Auto” position, and pump operations are controlled by level switches. When the water
level in the influent batch tank rises above the influent batch tank H-level switch, the
influent pump will turn on and will continue to run until the water level remains below the
influent batch tank L-level switch for a period of 20 minutes1, at which point the influent
pump will shut off. Failsafe controls will shut off the influent pump if the water level in the
pH tank rises above the pH tank HH-level switch; similar HH-level switches in the reaction
tank, polymer addition tank, lamella clarifier, and effluent tank will also shut off the influent
pump, as will a LL-level switch in the lamella clarifier. Water level switches are annunciated
on the HMI with colored letter icons when an alarm condition occurs (e.g., HH, H, L, and
LL) and a call out to operators.
The acid feed system will operate continuously unless the pH tank mixer is off. The pH tank
mixer will shut off if the influent flow meter measures a flow rate of fewer than 5 gallons per
minute (gpm) and a delay timer elapses or if the water level within the pH tank decreases
below the pH tank LL-level switch. An adjustable delay timer enables input into the HMI
that will allow the pH tank mixer to continue to run after the influent flow meter measures a
flow of fewer than 5 gpm.
1 The 20-minute timer delay allows the batch pump to begin replenishing the water level in the influent batch
tank. The timer delay is input into the HMI and can be adjusted; a value of zero will bypass the timer delay.
calibration of the acid feed pump; and 5) periodic removal of debris and solids that may
accumulate inside the pH tank.
The pH set-point, entered into the pH controller, may be adjusted using the pH controller—
not the HMI. Refer to the pH controller user manual to adjust the pH set-point.
A level sensor on the acid bulk tote is used to annunciate a warning on the HMI that the acid
level is low and needs to be replenished. The placement of the acid bulk tote level sensor
can be adjusted to provide adequate warning based on variable acid usage rates. Replacement
of the acid bulk tote requires the use of a forklift. Refer to Section 3.6.2 for procedures to
replace empty bulk totes.
The pH Sensor 1 should be cleaned and calibrated each time pH Sensor 2 (in the reaction/
precipitation process) is cleaned and calibrated. Refer to Section 3.7.1 for procedures to clean
the pH sensors, and refer to Section 3.8.2 for procedures to calibrate the pH sensors.
The acid feed pump should be periodically calibrated, as described in Section 3.7.
Accumulated solids removal may require draining the pH tank and the use of additional
equipment (see Section 5.4.2).
Ferrous chloride (FeCl2) and calcium chloride (CaCl2) reagents (liquid solutions) are added to
the wastewater and are thoroughly mixed to promote the formation of solids (precipitates)
containing cyanide and fluoride, respectively. The solids can then settle out of the
wastewater in later processes.
Table 4
Reaction/Precipitation Process Equipment
Notes:
1 = Equipment is described in the previous process.
2 = Equipment is used in multiple processes.
3 = Included equipment is referred to as the calcium chloride and ferrous chloride feed systems.
4 = Valve is NORMALLY OPEN.
5 = Valve is NORMALLY CLOSED.
Similar to the pH tank, the reaction tank is 18 feet long, 7 feet wide, 5 feet high, and it is
located on top of the influent batch tank, downstream of the pH tank. The pH tank is
elevated about 6 inches higher than the reaction tank to provide for gravity flow from one
tank to the other. There is an approximate volume of 1,800 gallons below the outlet invert
elevation of the reaction tank.
The reagent feed system includes pH Sample Pump 2, the HMI, the calcium chloride feed
pump, and the ferrous chloride feed pump, which are located in the mechanical room. The
pH Sample Pump 2 circulates water from the reaction tank to the mechanical room past the
pH Sensor 22 and back to the reaction tank. The HMI uses the measured influent flow rate
from the influent flow meter to modulate the speed of the calcium chloride and ferrous
chloride feed pumps and maintain the calcium chloride and ferrous chloride feed rate set
points. The calcium chloride and ferrous chloride feed pumps deliver the reagents into the
discharge pipe of pH Sample Pump 2 below the floor of the mechanical room. The calcium
chloride bulk tote and ferrous chloride bulk tote are stored outside and adjacent to the
mechanical room. Containment tubing is installed on the pressure line tubing connected to
the calcium chloride and ferrous chloride feed pumps; the containment tubing are larger in
diameter than the pressure line tubing and drains into the calcium chloride and ferrous
chloride feed pump containment drums, respectively, located below the mechanical room.
The suction line of pH Sample Pump 2 is located on the upstream end of the reaction tank at
a NORMALLY OPEN valve on the outside wall of the reaction tank. The pH Sample Pump 2
suction line drain valve is located below the mechanical room and is NORMALLY CLOSED.
The pH Sample Pump 2 suction line drain valve may be opened for freeze protection during
extended periods of freezing temperatures. The discharge line of the pH Sample Pump 2
empties into the reaction tank over the rim of the tank. Isolation valves are located
downstream of Sample Pump 2 and on either side of pH Sensor 2; the isolation valves are
NORMALLY OPEN.
The reaction tank mixer is a constant speed mixer that operates continuously unless shut off
by controls described subsequently.
2 The pH Sensor 2 measures the pH of the wastewater in the reaction tank for process informational purposes
only. It does not affect the operation of the reaction/precipitation process.
Two level switches are located in the reaction tank—the reaction tank LL-level switch and
the reaction tank HH-level switch; each is annunciated on the HMI with colored letter icons
when an alarm condition occurs (e.g., HH and LL). If the water level in the reaction tank
decreases below the LL switch, the reagent feed systems and reaction tank mixer will shut off
after an adjustable delay timer elapses. If the water level in the reaction tank rises above the
reaction tank HH-level switch, the influent pump will shut off.
The calcium chloride and ferrous chloride feed systems operate continuously (at their input
set-points in the HMI) unless the reaction tank mixer is off. The reaction tank mixer
operates continuously, while the influent flow meter measures a flow rate of at least 5 gpm,
and the water level within the reaction tank is above the LL-level switch. An adjustable
delay timer input to the HMI allows the reaction tank mixer to continue to run after the
influent flow meter measures a flow of fewer than 5 gpm.
The calcium chloride and ferrous chloride feed rate set-points entered into the HMI may be
adjusted using the HMI. Refer to Section 3.9.2 to adjust the calcium chloride and ferrous
chloride feed rate set-points.
Level sensors on the calcium chloride bulk tote and ferrous chloride bulk tote are used to
annunciate a warning on the HMI if the reagent levels are low and need to be replenished.
The placement of the calcium chloride bulk tote level sensor and ferrous chloride bulk tote
level sensor can be adjusted to provide adequate warning based on variable reagent usage
rates. Replacement of the calcium chloride bulk tote and ferrous chloride bulk tote requires
the use of a forklift. Refer to Section 3.6.2 for procedures to replace empty bulk totes.
Cleaning of pH Sensor 2 should be conducted each time the pH Sensor 1 (in the pH
adjustment process) is cleaned and calibrated. Refer to Section 3.7.1 for procedures to clean
the pH sensors, and refer to Section 3.8.2 for procedures to calibrate the pH sensors.
The calcium chloride and ferrous chloride feed pumps should be periodically calibrated, as
described in Section 3.8.4.
Accumulated solids removal may require draining the reaction tank and the use of additional
equipment (see Section 5.4.2).
Diluted liquid polymer is added to the wastewater and gently mixed to create flocculants that
adhere to compounds present in the wastewater. The flocculants have a greater settling
potential, thereby enhancing the removal of B(a)P and the cyanide and fluoride compounds
in the primary clarification process, described in Section 2.6. Typical polymer addition to
the polymer addition tank is 1 to 2 gpd and must be determined and adjusted based on the
wastewater influent.
Table 5
Flocculation Process Equipment
Notes:
1 = Equipment is described in the previous process.
2 = Equipment is used in multiple processes.
3 = Valve is NORMALLY CLOSED.
4 = Included equipment is referred to as the diluted polymer feed system.
5 = Valve is NORMALLY OPEN.
The polymer addition tank is the head unit of the lamella clarifier and includes the polymer
addition tank mixer, which is a constant speed mixer that operates continuously unless
disabled by controls described in the following subsection. The polymer addition tank inlet
drain/valve is located at the bottom of the 6-inch-diameter steel pipe connecting the reaction
tank to the polymer addition tank; the valve is NORMALLY CLOSED and may be used to
remove solids that accumulate in the bottom of the inlet pipe.
The diluted polymer feed system is located in the mechanical room and includes the polymer
feed pump, the Mix Mate device, and the polymer bulk container. The Mix Mate device has
three liquid inputs and a single outlet. The polymer feed pump delivers diluted polymer
(through the Mix Mate device) directly into the polymer addition tank. The Mix Mate
device has two water inputs—one located upstream and the other located downstream of the
liquid polymer input; the liquid polymer is diluted with the water and thoroughly mixed
through the Mix Mate device to the desired concentration. The water input rate may be
adjusted by manipulating the valves on the water lines, and the rate of water input is
displayed on the rotameters. A sampling valve is located downstream of the Mix Mate device
where diluted polymer may be collected or for maintenance purposes as discussed later in
this manual. The speed of the polymer feed pump is modulated based on the flow rate
measured by the influent flow meter and the feed rate set-point or max speed set-point input
to the HMI for polymer addition. See Section 3.9.3 for directions to input the polymer feed
rate set-points. The polymer bulk container is located in the mechanical room, near the
polymer feed pump. Containment tubing is installed on the pressure line tubing connected
to the polymer feed pump; the containment tubing is larger in diameter than the pressure
line tubing and drains into the polymer feed pump containment drum located below the
mechanical room.
Two level switches are located in the polymer addition tank—the polymer addition tank
LL-level switch and the polymer addition tank HH-level switch; each is annunciated on the
HMI with colored letter icons when an alarm condition occurs (e.g., HH and LL) and call out
to operators.
If the water level in the polymer addition tank decreases below the polymer addition tank
LL-level switch, the polymer feed pump and polymer addition tank mixer will be disabled.
If the water level in the polymer addition tank rises above the polymer addition tank
HH-level switch, the influent pump will be disabled.
Accumulated solids removal from the polymer addition tank may require partially or fully
draining the lamella clarifier (see Section 5.4.3).
Table 6
Primary Clarification Process Equipment
Notes:
1 = Equipment is described in the previous process.
2 = Equipment is used in multiple processes.
3 = Equipment is described in the pH adjustment process.
4 = Valve is NORMALLY CLOSED.
5 = Equipment is described in the following process.
The lamella clarifier is an elevated clarifier with a conical shaped bottom and contains
inclined plates to promote settling of solids. The plates contained in the lamella clarifier
have an excess of 600 square feet of treatment surface area. Three sight tubes are installed on
the cone of the lamella clarifier; these sight tubes attach to the cone at individual ball valves.
The sight tubes may be used to determine the level of sludge accumulated in the cone. The
sludge control valve is located at the bottom of the cone and is NORMALLY CLOSED; this is
described in greater detail in the following processes.
If the water level in the lamella clarifier decreases below the lamella clarifier LL-level switch
or rises above the lamella clarifier HH-level switch, the influent pump will be disabled, as
will the filtrate pump. The filtrate pump is described in greater detail in the following
processes.
In order to clean the plates, Facility 71 needs to be shut down, and the lamella clarifier needs
to be drained into the sludge tank. The plates may be cleaned using a pressure washer.
Solids and debris accumulated on the plates will fall into the lamella clarifier cone.
After the plates have been cleaned, Facility 71 should be started up and adequate time must
be allowed to refill the lamella clarifier.
Table 7
Treated Effluent Management Process Equipment
Notes:
1 = Equipment is described in the previous process. 4 = Equipment is used in sampling processes.
2 = Equipment is used in multiple processes. 5 = Valve is NORMALLY OPEN.
3 = Equipment is described in the pH adjustment process. 6 = Valve is NORMALLY CLOSED.
The effluent tank, similar to the influent batch tank, is 40 feet long, 8 feet wide, and 10 feet
high. The effluent tank is located opposite the sludge tank. An approximate volume of
12,600 gallons is available between the pumping cycles.
An automated ISCO sampler, model 4700 (740), is configured to obtain composite samples of
the treated wastewater effluent in the effluent tank. The ISCO sampler includes the
equipment and controls necessary for the collection of composite samples; a refrigerator
keeps the samples at 4 degrees Celsius in accordance with the NPDES permit sample
collection requirements. The sampler draws water from the effluent tank from an inlet on
top of the effluent tank. (See Outfall Field Equipment SOP for ISCO operations.)
The effluent pump, a centrifugal pump, is located in the mechanical room with controls on
the control panel. In normal operations, the effluent pump switch on the control panel is in
the “Auto” position and is controlled by the level switches in the effluent tank, described in
the following subsection. The effluent pump is used to pump treated wastewater effluent
from the effluent tank into the sump in Facility 77. Drain valves on both the suction and
discharge lines connected to the effluent pump are located below the mechanical room; the
drains are NORMALLY CLOSED and may be used for freeze protection during extended
periods of freezing temperatures.
The effluent flow meter is an inline globe valve located upstream of the effluent flow meter;
the valve is NORMALLY OPEN. The effluent flow meter allows for circulation of water
from the effluent tank to the pH tank, which may be necessary to avoid damage to
equipment during freezing temperatures.
The effluent flow meter, similar to the influent flow meter, is a magnetic flow meter located
between the main control facility and the influent batch tank. The flow meter has a digital
display, and the measured flow rate is also displayed on the HMI in the MCR. The flow rate
between the effluent tank and Facility 77 is continuously measured and recorded. Flows are
totalized daily and monthly by the PLC; the flow is reset daily at 12:05 am, and the flow is
reset on the first day of each month at 12:05 am.
The effluent air/vacuum release valve is installed on the effluent pump discharge line at the
top of the containment wall.
The effluent pump will turn on when the water level in the effluent tank rises above the
effluent tank H-level switch and will continue to run until the water level decreases below
the effluent tank L-level switch, at which point the effluent pump will shut off.
Similar to the HH-level switches in the pH tank, reaction tank, polymer addition tank,
lamella clarifier, and the LL-level switch in the lamella clarifier, once the water level in the
effluent tank rises above the effluent tank HH-level switch, the influent pump will
be disabled.
Each level switch is annunciated on the HMI with colored letter icons when an alarm
condition occurs (e.g., HH, H, and L).
Operation of the ISCO sampler is handled using the on-board controller. In preparation for
sample collection, the Operator (or sampling personnel) places a clean 20-liter jar in the
sampler unit to collect the composite samples and initiates the sampling session. The sampler
is programmed to automatically take samples over a 24-hour period. Once a sample session is
completed, the Operator (or sampling personnel) will turn off the ISCO sampler and prepare
the sample jar for transport to the laboratory for analysis. The ISCO sampler should be
cleaned and maintained according to the manufacturer recommendations. Refer to MBT-
Longview’s Laboratory QA/QC manual for sampling handling and sample subcontracting.
Table 8
Sludge Management Process Equipment
Notes:
1 = Equipment is described in a previous process.
2 = Equipment is used in multiple processes.
3 = Valve is NORMALLY OPEN.
4 = Valve is NORMALLY CLOSED.
The sludge pump, a pneumatic diaphragm pump located beneath the lamella clarifier, is used
to pump accumulated sludge from the cone of the lamella clarifier to the sludge tank. The
sludge pump air valve, located on the pressurized airline connected to the sludge pump,
supplies air to operate the sludge pump; the valve is NORMALLY CLOSED. The suction line
of the sludge pump is connected to the cone of the lamella clarifier at the sludge control
valve, which is NORMALLY CLOSED.
The sludge tank is an enclosed phase separation tank measuring approximately 22 feet long,
8 feet wide, and 5 feet tall. The sludge tank has a false bottom with a filter membrane that
allows the sludge to decant; liquid phase filtrate is collected below the false bottom and solid
phase filtrate is retained above the filter membrane.
The filtrate pump is a centrifugal pump located in the mechanical room with controls located
on the control panel. In normal operations, the filtrate pump control switch at the control
panel is in the “Auto” position and is controlled by the filtrate level sensor in the sludge tank,
described in the following subsection. The suction line of the filtrate pump is connected to
the end of the sludge tank at the filtrate control valve, which is NORMALLY OPEN. The
discharge line of the filtrate pump runs below the mechanical room, along the pavement, and
up into the polymer addition tank. Drain valves on both the suction and discharge lines
connected to the filtrate pump are located below the mechanical room; the drains are
NORMALLY CLOSED and may be used for freeze protection during extended periods of
freezing temperatures.
The sludge pump controls are located at the pump and are “On”/“Off.”
The filtrate pump will turn on when the filtrate water level in the sludge tank rises
approximately 6 inches above the sludge tank H-level switch and will continue to run
approximately 5 minutes after the water level in the sludge tank decreases below the level
switch. The level switch is displayed on the HMI with a colored letter icon (e.g., H).
Prior to operating the sludge pump, the sludge control valve at the bottom of the lamella
clarifier cone, which is NORMALLY CLOSED, must be opened. The sludge pump is
manually operated at the pump by switching the pump on; the pump runs on compressed air
supplied by other on-site facilities. The sludge pump should be operated for a short duration
every day during treatment. Three drain tubes are installed on the side of the lamella
clarifier cone; each may be opened to determine the level of sludge accumulated in the cone.
Each drain tube is attached to a ball valve, which is NORMALLY CLOSED. To drain the
accumulation cones, turn off the sludge pump and close any valves opened during the
operation of the sludge pump. Open the site tube(s) and collect the sludge and water that
drains out into a bucket and dispose of the bucket contents into the sludge tank.
Removal of solids from the sludge tank is done by a contractor using a vactor truck. The
Operator must monitor the accumulation of solids within the sludge tank and coordinate the
solids removal by the contractor, as necessary. Occasional replacement of the sludge tank
filter membrane is necessary and should be done to maximize dewatering of sludge.
The HMI includes an interface using a single EZ Touch 8-inch display. The screen saver
mode is enabled after 15 minutes of inactivity; the screen saver mode is stopped by touching
the screen. Colors used in the EZ Touch display are summarized in Table 9.
Table 9
Color Designation on HMI EZ Touch Display
2.9.2 Alarms
The PLC is programmed to display and annunciate alarms that develop during operation of
Facility 71. Certain alarms are displayed on the HMI. Table 10 summarizes the various
alarms programmed into the PLC. Photograph 1 illustrates the Alarms Status screen on the
HMI.
Level switch-controlled alarms (triggered by water level in process tanks or by product level
in bulk totes/drum) will automatically reset after the alarm condition has cleared and
5 minutes have elapsed. The treatment system will resume operations afterwards.
Table 10
Alarms Summary
Notes:
1 = Motor failure alarms “Fail to Run” require pressing the “Alarm Reset” button on the HMI panel after the alarm
condition is clear. Turn the equipment switch on CP from “Auto” or “Hand” to “Off” when resetting the motor
failure alarms.
2 = Motor failure alarms “Fail to Run” require pressing the “Alarm Reset” button on the HMI panel after the alarm
condition is clear. Turn the equipment switch, on pH sampler/controller panel from “Auto” or “Hand” to “Off”
when resetting the motor failure alarms.
The PLC/HMI in Facility 71 receives operational signals and logs data from Facility 71 and
from other facilities onsite including Outfalls 002A, 006, and leachate ditch. Data logged by
the HMI for Outfall 002A occurs independent of the operation of Facility 71. Outfall 002A
monitoring data logged in the HMI include flow, pH, and temperature. This manual is
limited to the operation of Facility 71. Information relating to Facility 73 Operations and
Maintenance and Outfall 002A may be found in other reference documents related to those
operations.
Table 11
Summary of Data Logged by PLC/HMI
PLC Tag Description
Date mm/dd/yyyy
Time hh:mm:ss
FIT_002A_LO 002A Low Flow Rate1, 3
FIT_002A_LO_DAY 002A Low Flow Daily Totalizer
FIT_002A_LO_MON 002A Low Flow Monthly Total
FIT_002A_LO_DAY_AVG 002A Low Flow Daily Average
FIT_002A_HI 002A High Flow Rate1, 3
FIT_002A_HI_DAY 002A High Flow Daily Totalizer
FIT_002A_HI_MON 002A High Flow Monthly Total
FIT_002A_HI_DAY_AVG 002A High Flow Daily Average
AIT_003 002A pH3
TIT_004 002A Temperature Fahrenheit 2, 3
TIT_004_Celsius 002A Temperature Celsius
LIT_077 Tank 3 Level
FIT_080 71 Influent Flow
FIT_080 day 71 Influent Daily Flow Totalizer
DIT _080_mon 71 Influent Flow Monthly Totalizer
PH_SCALED 002A pH Scaled for Trend Display
FIT_980 002B Effluent Flow Rate
FIT _980_DAY 002B Effluent Flow Daily Totalizer
FIT_980_mon 002B Effluent Flow Monthly Total
FIT_006 Outfall 006 Flow
FIT_006_day Outfall 006 Daily Flow Totalizer
FIT_006_mon Outfall 006 Flow Monthly Total
Rainfall Total Daily Rainfall
Notes:
1 = Outfall 002A includes two flow meters—a High Flow meter and a Low Flow meter.
2 = Outfall 002A temperature is displayed and logged in degrees Fahrenheit.
3 = instantaneous measurement
3 NORMAL OPERATIONS
3.1 Introduction
This section expands upon Section 2, Treatment Process Descriptions, and provides guidance
to the Facility 71 Operator when making the necessary adjustments to the operational
parameters. Therefore, these two sections should be looked at jointly. Where details are not
clear, refer to the other sections, Figures DWG-2 to DWG-5, and manufacturer-supplied
equipment user manuals.
Facility 71 is a batch treatment system, and flow rate throughput is constant when the
volume of stored wastewater is not limited. It is capable of continuous operations but may
be operated intermittently to treat batches of wastewater. The ability to batch treat
wastewater improves efficiency of the facility and allows for seasonal use of the plant (i.e.,
during periods of rain). Variability in contaminant concentrations in the influent
wastewater may require adjustment of the chemical and reagent feed rates. These feed rates
must be adjusted by the Facility 71 Operator when significant changes to influent
wastewater contaminant concentrations occur in order to optimize treatment efficiency.
Flow meters
Calibration
Mix Mate device
Cleaning
Mechanical tank mixers
Valve exercising
Eye wash and shower station
ISCO sampler
3.5 Pumps
3.5.1 Pump Inventory
Not including the pump within the composite sampler or the containment sump pump, there
are 11 pumps of various types in use within Facility 71; five are used to transfer the
wastewater (and solids) between processes, two are used to circulate water for monitoring of
wastewater pH, and four are used to add chemical reagents and polymer as part of the
treatment processes. An inventory of the pumps used in Facility 71 is listed in Table 12.
Table 12
Facility 71 Pump Inventory
Notes:
1 = Table does not include Facility 71 containment sump pump or the pump within the composite sampler.
2 = By manipulating the three-valve cluster near the influent and effluent flow meters, water from the effluent
tank may be circulated into the pH tank; this is an uncommon practice that may be necessary during extended
periods of freezing temperatures to avoid freeze damage of equipment.
Facility 77. Most pumps in Facility 71 are typically available from local suppliers and can be
sourced and replaced quickly in the event of failure if they cannot be repaired.
The acid feed pump is the only pump in Facility 71 that handles the concentrated sulfuric
acid, and maintenance or repair of the acid feed pump is not recommended. A replacement
acid feed pump should be stored within the ancillary storage area of the main control facility
if pump failure occurs. See Section 3.7.4 for more information on maintenance.
The ferrous chloride, calcium chloride, and polymer feed pumps are operated based on the
feed rate set-points input into the HM (926); see Table 1 for consumption rates of ferrous
chloride and calcium chloride. The speed of the feed pumps is modulated based on the feed
rate set-point in the HMI and the flow measured by the influent flow meter. The feed
pumps will run continuously if the following conditions are met: 1) a feed rate set-point (for
that particular feed pump) is entered into the HMI; 2) the flow rate into Facility 71 is above 5
gpm (measured by the influent flow meter); and 3) other equipment interlocks are not
engaged (e.g., tank mixers are off and LL-level switches are not engaged).
Each feed pump has a single suction line and single discharge line. Each suction and
discharge line is equipped with outer containment tubing that will divert leaks that may
develop in the suction and discharge line tubing to a reagent-specific bucket located beneath
the mechanical room.
To exchange totes/drums, Operators must use the PPE required by the Safety Data Sheets
(SDS). SDSs for the chemicals currently in use within Facility 71 are located in the main
control room. Prior to exchange, the appropriate feed pump must be unplugged from the
electrical receptacle. The Operator shall then remove the suction line and L-level switch
from the empty tote/drum and reinstall on the full exchanged tote/drum.
The Operator shall then plug in the feed pump to the electrical receptacle, and return the
feed pump to the normal operating function at the HMI and inspect the system
for abnormalities.
Sulfuric acid is added to the pH Sample Pump 1 discharge pipe, which discharges into the
pH tank. The calcium chloride and ferrous chloride are added to the pH Sample Pump 2
discharge pipe, which discharges into the reaction tank. Polymer is pumped into the
Mix Mate device located in the mechanical room, where the polymer is diluted and mixed
with water. The Mix Mate discharge line discharges directly into the polymer addition tank.
The reagents are liquid concentrates that are stored in portable bulk totes, which are located
outside the mechanical room on an elevated platform. Polymer is a liquid concentrate stored
in 5-gallon drums positioned in the mechanical room next to the polymer feed pump.
Reagent and polymer is withdrawn from their respective bulk tote/drum with a dedicated
single feed pump suction line. The feed pumps are located in the mechanical room and are
automatically controlled, independently of one another, by the HMI and pH controller
respective to each unique feed set-point.
The Operator shall manage the inventory and coordinate the purchase and delivery of
reagent and polymer from the supplier. Sufficient numbers of additional totes of the
reagents and drums of polymer shall be kept in inventory at all times. Empty totes shall be
exchanged with the oldest tote in the inventory, and no tote shall be used that has an expired
“use-by” date.
Expected rates of consumption of calcium chloride and ferrous chloride are listed in
Table 13. Consumption rates shown in the table are based on observations made during
continuous operation of the plant at approximately 50 gallons per minute. The consumption
rates are not design values and changes in influent chemistry or changes to a process or plant
operation will produce different rates of consumption. In the event of an operational or
process change, design calculations should be used to estimate product consumption.
Table 13
Calculated Consumption Rates
Notes:
1 = pH ranges from 4 to 6.5 per recommendations identified in Proposed Temporary Wastewater Treatment System for Facility
71 (November 15, 2011)
CaCl2 = calcium chloride gpm = gallon per minute ppb = parts per billion
FeCl2 = ferrous chloride H2SO4 = sulfuric acid SU = standard unit
gpd = gallon per day N/A = does not apply
A forklift is necessary to exchange an empty bulk tote. The in-use bulk totes are stored in
two rows on the elevated platform within Facility 71 containment, which requires moving
the front tote in order to service the tote behind the front tote. The polymer container in
use is positioned in the mechanical room.
Totes shall not be moved or exchanged without first properly disabling the feed pump that
sources the tote/drum to be moved or exchanged. Refer to Section 3.5.6 for details required
for the feed pump operations during a tote/drum exchange.
Recovery of residual product in a polymer bulk container shall be done by manually draining
the near-empty container into a clean, 5-gallon bucket and transferring the residual polymer
into a full or partially full container.
Recovery of residual sulfuric acid, calcium chloride, or ferrous chloride shall be done by:
1) donning appropriate PPE; and 2) taking necessary safety measures and draining residual
product from the near-empty reagent bulk totes into a full reagent bulk tote. To drain a
near-empty reagent bulk tote, personnel may need to use a forklift to tip the near-empty
reagent bulk tote and use the bottom drain on the bulk tote to transfer residual product into
another bulk tote. To minimize exposure of residual product, tubing should be used between
the drain of the near-empty bulk tote and the top inlet of the full bulk tote.
With many of the system components in Facility 71 operated by the PLC, there is little day-
to-day interaction between the Operator and the equipment in Facility 71. For this reason,
frequent visual inspections are necessary to monitor the condition of the equipment.
Table 14
Equipment Maintenance Schedule
Maintenance
Equipment System No. Purpose Frequency
Necessary
Maintain
Clean sensors in a Monthly or more frequently as
pH Sensors1 350, 450 accuracy of pH
soap solution needed
measurements
Disassembly of
Maintain Annually or more frequently as
Mix Mate Device 550 device and cleaning
proper function needed
components
Replace pump with Once per 5 years or more
Acid Feed Pump2 330 Replacement
a new unit frequently as needed
Calcium Chloride
Calcium Chloride,
(430) Replace
Ferrous Chloride, Replacement of Once every 2 years or more
Ferrous Chloride combination valve
and Polymer Feed wearing parts frequently as needed
(435) seat-seal ring
Pumps Polymer (530)
Replace suction and
Replace
Feed Pump discharge line Annually or more frequently as
--- degraded
Tubing tubing and needed
material
containment tubing
Process Transfer
Pumps (not 175, 275, 775, Maintain See manufacturer
Lubrication
including Sludge 875 proper function recommendation
Pump)
pH Sampling Maintain See manufacturer
340, 440 Lubrication
Pumps proper function recommendation
Replace flexible
Maintain piping (suction and Inspect piping monthly; replace
Sludge Pump 805
proper function discharge piping, as conditions warrant
plant air supply line)
Replace as Inspect for proper Inspect monthly; replace upon
Tank Mixers 325, 425, 525
necessary function failure
Maintain
Process Valves Numerous Exercise valves Annually
proper function
Emergency Operate eyewash
Maintain Monthly or more frequently as
Eyewash and 950 and shower to flush
proper function needed
Shower water
Maintenance
Equipment System No. Purpose Frequency
Necessary
Lift float to check
Containment Maintain Once per week during
240 that pump is
Pump proper function precipitation events
functioning properly
Cleaning and
Maintain Four times per year or more
ISCO Sampler 740 replacement of
proper function frequently as needed
wearing parts
Evacuate tanks;
Evacuate and
220, 320, 420, remove Annually during period of low
inspect tanks;
Process Tanks 520, 620, accumulated solids precipitation
clean as
720, 820 and debris; inspect (see Section 5.4)
necessary
tank interior
Draw down the
Inspect clarifier Lamella Clarifier and Weekly inspections; clean as
Lamella Clarifier 620 holes and weirs clean as needed; needed
on top of unit cleaning requires (Section 0)
pressure washer
Close outlet valve,
Prevent
clean wye-strainer3, Weekly or more frequently as
Wye-Strainers 266, 766, 866 clogging of tank
reassemble, and needed
outlets
open outlet valve
Remove
Polymer Addition Open the valve and Monthly or more frequently as
accumulated
Tank Inlet 518 drain solids into a needed; may include in
solids from
Drain/Valve container3 cleanout of Lamella Clarifier
inlet pipe
Test fire system
components
950, 955, 956,
Maintain including
Fire System 957, 960, Monthly
proper function extinguishers;
965, 970
replace batteries in
fire detector
Notes:
1 = Equipment calibration to follow maintenance activity.
2 = Maintenance shall not be done on the acid feed pump without supervisory approval. The acid feed pump will
be replaced at a regular interval.
3 = Drain contents into a bucket or other portable container and dispose of collected contents into the Sludge Tank.
Cleaning of the pH sensors is required to remove accumulated biofilm and debris from the
sensor, which may interrupt and affect the accuracy and response of the pH measurement.
Cleaning the sensors usually takes less than 10 minutes. Cleaning of the pH sensors shall be
done prior to calibration of the pH sensors. The sensors are removed from their respective
sample pump line to facilitate sensor cleaning.
15. Open the respective isolation hand valves on either side of the respective pH sensor.
16. Plug in the feed pumps to the electrical receptacles.
17. Return the control manually shut off in Step 3 to normal automatic operations.
18. Monitor the feed pumps to determine that the reagent feed is normal. If needed, the
feed pumps may be operated in the “Jog” mode to prime the pumps.
Clogging of the Mix Mate device can usually be observed in the tubing or sight tube
downstream of the second dilution line. Additionally, if clogging is occurring, the polymer
feed pump may be working harder than normal; the pump may sound labored.
Maintenance on the calcium chloride (430), ferrous chloride (435), and polymer (530) feed
pumps includes replacing the combination valve seat and seal ring, which is a wearable part
in the pumps. Replacement parts shall be manufactured for use in the feed pumps, and
replacement of the pump parts shall follow the manufacturer recommendations.
Prior to servicing feed pumps, Facility 71 should be shut down, and the feed pumps should
be unplugged from their electrical receptacles. Personnel performing maintenance on the
feed pumps should be equipped with PPE in accordance with the SDS for the appropriate
chemical exposure and in accordance with the required site safety practices. Follow the
procedures outlined in Sections 2.4.6 and 2.5.2.
Other maintenance may include replacement of the feed pump tubing, as necessary, to allow
for visual observation of product flow through the tubing.
Table 15
Equipment Calibration Schedule
Equipment
Purpose Calibration Necessary Frequency
(System No.)
Influent Flow Meter Certified testing by
Check signal of meter At least once per year
(310) manufacturer or vendor
Effluent Flow Meter Certified testing by
Check signal of meter At least once per year
(785) manufacturer or vendor
Following sensor
pH Sensor 1 (350) and Calibrate sensors to
2-point calibration method cleaning; at least once
pH Sensor 2 (450) maintain accuracy
per month
The NPDES permit requires that the influent and effluent flow meters be calibrated
according to the manufacturer recommendations or at a minimum frequency of once per
year.
The two flow meters are calibrated by a certified and authorized technician. The calibrations
are documented and retained in accordance with the NPDES permit. The calibration
documentation shall include, at a minimum, the name of the technician that conducts the
calibration and the date and time of calibration.
1. The flow to the sensors must be turned off as described in Section 3.7.1
2. Check that there is sufficient quantity of standard buffer solution of pH 7; expired
solutions shall not be used.
3. Prior to calibration of the sensors, the sensors shall be thoroughly cleaned; refer to
Section 3.7.1.
4. Put the sensor(s) in the reference solution. Check that the sensor portion of the probe
is fully immersed in the liquid.
5. Wait for the sensor and solution temperature to equalize. This can take 30 minutes or
more if the temperature difference between the process water and reference solution
is significant.
6. On the pH controller, push the “Menu” key and select Sensor Setup, [Select Sensor],
Calibrate.
7. Select the type of calibration: 1-Point Buffer or 1-Point Sample.
8. If the passcode is enabled in the security menu for the controller, enter the passcode.
9. Select the option for the output signal during calibration: “Active”.
10. With the sensor in the first reference solution, push <ENTER>. The measured value
is shown.
11. Wait for the value to stabilize and push <ENTER>.
12. Review the calibration result
a. Passed – the sensor is calibrated and ready for use. The slope and/or offset
values are shown.
b. Failed – the calibration slope or offset is outside of accepted limits. Repeat the
calibration with fresh reference solutions. Refer to the manufacturer
documentation for further detail.
13. If the calibration passed, push <ENTER> to continue.
14. On the New Sensor screen, select whether the sensor is new:
a. Select no, unless the sensor is new.
b. Select yes if the sensor is new and is replacing the old during this calibration.
15. Return the sensor(s) to the sample pump lines and push <ENTER>. The output signal
returns to the active state and the measured sample value is shown on the
measure screen.
16. . Calibrate the second probe as described above.
Operational parameters for Facility 71 are values that the PLC uses to control the processes
and related process equipment. Sludge management is manually controlled.
Normal operations include replenishing the sulfuric acid bulk tote. The acid feed pump has a
“Hand” function that allows for testing of the feed pump and is also used to purge and prime
the feed pump suction line. This “Hand” function will be used for the following:
pH Set-point
The acid feed rate in the pH tank is controlled by an adjustable pH value entered into the
pH controller. The value displayed in the pH controller as “pH SET-POINT” is entered as a
value between 0.0 and 14.0. The target treatment pH value ranges between 4.0 and 6.5.
The value for pH set-point may require adjustment if it is determined that the removal
efficiency of fluoride or cyanide can be improved to the benefit of adding less calcium
chloride or ferrous chloride, respectively.
Should the value require adjusting, the Operator shall refer to the pH controller user manual,
Vendor Installation, Operations and Maintenance Manuals for details; modification of the
pH set-point is not normally required.
The pH tank equipment off delay timer is an adjustable value entered into the HMI to
control the operation of the pH tank mixer, pH Sample Pump 1, and the acid feed pump.
The value displayed in the HMI as “pH TANK EQUIPMENT OFF DELAY,” has an entry
range between 0 and 9,999 minutes. A value of 0 entered into the HMI will disable the
delay timer.
The delay timer extends the operation of the pH tank mixer, pH Sample Pump 1, and the
acid feed pump to the entered timer value when the influent flow meter measures a flow rate
less than 5 gpm. The purpose of the delay timer is to avoid equipment shutdown caused by
short pump cycle times.
Note that if the water level in the pH tank decreases below the LL-level switch in the pH
tank, the equipment will also be disabled.
Normal operations include replenishing the calcium chloride and ferrous chloride bulk totes.
The calcium chloride and ferrous chloride feed pumps have a “Jog” function that allows for
testing of the feed pumps and is also used to purge and prime the feed pump suction lines.
This “Jog” function will be used for the following:
When troubleshooting interruptions in the feed stream
To purge the feed pump suction line before exchanging a bulk tote
To prime the feed pump suction line, as necessary, after exchanging a bulk tote
Additional reaction tank reagent feed system parameters described in this subsection include
the following:
Calcium Chloride Jog Speed: Entered into the HMI
Ferrous Chloride Jog Speed: Entered into the HMI
It is important to note that the removal efficiency of fluoride in the wastewater when adding
calcium chloride is pH-sensitive; therefore, a change in the pH set-point should be
considered when adjusting the feed rate of calcium chloride.
To adjust the calcium chloride ratio, use the touch-screen navigation on the HMI to enter
the Set-points screen. Select the button “CALCIUM CHLORIDE RATIO” and enter the lab
reported value. Return the HMI to the Home screen.
It is important to note that the removal efficiency of cyanide in the wastewater when adding
ferrous chloride is pH-sensitive; therefore, a change in the pH set-point should be considered
when adjusting the feed rate of ferrous chloride.
To adjust the ferrous chloride ratio, use the touch-screen navigation on the HMI to enter the
Set-points screen. Select the button “FERROUS CHLORIDE RATIO” and enter the lab
reported value. Return the HMI to the Home screen.
The delay timer extends the operation of the reaction tank mixer, pH Sample Pump 2, and
the calcium chloride and ferrous chloride feed pumps to the entered timer value after the
influent flow meter measures a flow rate less than 5 gpm. The purpose of the delay timer is
to avoid a shutdown of these equipment caused by short pump cycle times.
Note that if the water level in the reaction tank decreases below the LL-level switch in the
reaction tank, the equipment will also be disabled.
To manually operate the calcium chloride or ferrous chloride feed pumps in the “Jog” mode,
navigate the HMI to the Calcium Pump Calibration screen and select “CALCIUM
CHLORIDE JOG” or “FERROUS CHLORIDE JOG” to toggle the operation of the feed pump
to “Jog.” Next, select “CALCIUM CHLORIDE JOG SPEED” or “FERROUS CHLORIDE JOG
SPEED” and enter a value between 0 and 100 percent.
To return the calcium chloride or ferrous chloride feed pumps to normal operations, select
“CALCIUM CHLORIDE JOG” or “FERROUS CHLORIDE JOG” to toggle the operation out of
the “Jog” operation.
The feed rate must be determined and used to calculate the polymer pump ratio value to be
entered into the HMI; the value is the ratio of the calculated feed rate to the influent flow
rate. The rate is based on a combination of factors, such as determination of performance
and the polymer manufacturer’s recommendations.
To adjust the feed rate set-point, use the touch-screen navigation on the HMI to enter the
Set-points screen. Select the button “POLYMER PUMP RATIO” and enter the calculated
value; range of entry is between 0.000000 and 1.000000. Return the HMI to the
“Home” screen.
The delay timer extends the operation of the polymer addition tank mixer and polymer feed
pump to the entered timer value after the influent flow meter measures a flow rate less than
5 gpm. The purpose of the delay timer is to avoid a shutdown of these equipment caused by
short pump cycle times.
Note that if the water level in the polymer addition tank decreases below the LL-level switch
in the reaction tank, the equipment will also be disabled.
To return the polymer feed pump to normal operations, select “POLYMER PUMP JOG” to
toggle the operation out of the “Jog” operation.
The polymer feed system includes pumping the liquid polymer from the polymer bulk drum
to the Mix Mate device, located in the mechanical room, which dilutes the liquid polymer
prior to its addition to the polymer addition tank.
Provided that the feed rates of calcium chloride and ferrous chloride are sufficient to produce
the desired fluoride and cyanide compounds, respectively, the effectiveness of polymer
addition can be determined by comparing the sampling analyses of the influent and effluent,
with respect to fluoride and cyanide concentrations.
To determine the appropriate amount of polymer to add, follow the polymer manufacturer
recommendations; jar testing may be necessary to determine the appropriate polymer dosage.
Optimization of the polymer feed rate is often necessary depending on process variables such
as influent wastewater characterization, solids generation, and fouling of equipment.
4 STARTUP PROCEDURES
Startup is not an immediate and instantaneous task. Startup of Facility 71 requires planning,
requisition of supplies, inspection of equipment and supplies, laboratory analyses, and
process optimization before discharging treated wastewater effluent through Outfall 002B.
During a normal (planned) shutdown, the water levels in the influent batch tank and
effluent tank may be manually drawn down to minimize the amount of water remaining in
Facility 71 during the shutdown period. For this reason, discharge from Facility 71, upon a
startup, may not occur for quite some time, depending on the volume of raw influent
wastewater collected in Tank 3 of Facility 77.
The general procedures for starting Facility 71 are summarized in the following subsections.
A startup event should be thoroughly documented to include operational parameters,
procedures taken, observations made, and modification of equipment and systems.
Documentation will provide valuable information to aid in troubleshooting problems that
may arise during startup.
The results of the characterization should be considered before starting up Facility 71, and
adjustments to the processes shall be made, as necessary, usually through determination of
the operational parameters.
There is a three-valve cluster near the influent and effluent flow meters. Manually close the
effluent flow control valve (782), located upstream of the effluent flow meter (785) and
manually open the effluent bypass flow control valve (781). The influent flow control valve
(309) should remain open. This modification will circulate water from the effluent tank into
the pH tank, while allowing water from the influent batch tank to pump water into the
pH tank.
Check that there is the proper type and quantity of PPE for use in Facility 71. Consult with
the Site Safety Officer and refer to the SDS and equipment manufacturer recommendations
for the proper types of PPE. Determine if the proper equipment is available prior to start up
and select the proper equipment for use prior to startup.
Check that there are the proper types, sufficient quantities, and non-expired solutions
necessary for calibration of the pH sensors.
The pH sample pumps (340 and 440) are controlled at the pH sampler/controller control
panel; the two pumps should be in the “Auto” position.
The reagent and polymer feed pumps should be plugged in to electrical receptacles and their
suction lines should be properly located in the bottom of their respective reagent bulk tote
and polymer drum; check suction lines to avoid cross-connections between the feed pumps
and the bulk totes/drum. Each tote/drum should have a properly located low-level switch on
the exterior of the tote/drum; check that the correct L-level switch is placed on the
appropriate tote/drum.
The containment pump (240) should be plugged in to the electrical receptacle and properly
connected to its discharge line to the influent batch tank.
In startups following brief shutdowns (less than 24 hours) or where the wastewater influent
characterization has not changed, changes to the operating parameters may not be necessary.
In all other circumstances, the operational parameters should be evaluated and reviewed for
approval by supervisory personnel prior to inputting the parameters into the HMI and
pH controller.
controller in the mechanical room. Check that the acid feed equipment and operational
parameters are correctly positioned and entered, respectively, as follows:
Visually inspect the sulfuric acid product level in the acid bulk tote (328) and check
that the L-level switch is in its proper position on the tote exterior.
Caution—do not attempt to open the tote and look inside
without taking the necessary precautions. Precautions include
following applicable plant safety protocols and regulations,
including plant protocols specific to work with or around
chemicals.
Check that the acid feed pump suction line is in the bottom of the acid bulk tote.
Plug in the acid feed pump (330) to the electrical receptacle.
At the HMI, run the acid feed pump in “Jog” to check that that the pump is primed
and working correctly.
Visually inspect the clear tubing lines to check that the pump is primed and
drawing product.
Plug in the calcium chloride (430) and ferrous chloride (435) feed pumps to the
electrical receptacles.
At the HMI (926), run the feed pumps in “Jog” to check that the pumps are primed
and working correctly.
Visually inspect the clear tubing lines to check that the pumps are primed and
drawing product.
If polymer addition is not necessary for an extended period (about 1 year), carefully remove
the polymer feed pump suction line from the polymer bulk drum and purge the suction line
by running the polymer feed pump in the “Jog” function, controlled by the HMI. Turn off
the dilution water lines with their respective valves located upstream of the Mix Mate
device, and check that the polymer feed pump is unplugged from the electrical receptacle.
Prior to obtaining influent and effluent samples, the ISCO samplers should be plugged in to
the designated electrical receptacle, should be kept at a constant temperature, and a clean
glass jar should be placed in each sampler refrigerator.
Prior to startup, review the treatment process descriptions as a final check that the systems
are in order.
Report any observed leaks, equipment failures, or other system upsets and take action, as
necessary, to correct issues.
Depending on the purpose of the planned shutdown, it may be necessary to evacuate the
process tanks. For an extended period, it may be prudent to evacuate the process tanks to
avoid fouling of the equipment.
In general, the procedure for shutdown of Facility 71 is the reverse order as described in
startup; and modified as described subsequently. For a complete list of tasks in checklist
format relating to an extended shutdown, refer to the Facility 71 Extended Shutdown
Procedures Checklist in Appendix C.
5.1 Documentation
Documentation can provide the Operator valuable information if problems occur during
startup after the planned shutdown. In general, and at a minimum, documentation should
include a list of sequential events provided with a date, time, and initials of the personnel
involved in the shutdown. Other critical information includes documenting observations
made during the shutdown; observations should include date, time, and initials of those
making the observations.
At the control panel (925), manually switch the batch pump control from “Auto” to “Off.”
This will cease the inflow of wastewater from Tank 3 into the influent batch tank (220). The
influent batch tank L-level switch (223) will shut off the influent pump once the water level
in the influent batch tank decreases below the L-level switch and 20 minutes’ elapse.
Note that the effluent pump (775) may continue to pump depending on the level switches in
the effluent tank (720); discharge from the effluent tank may continue even if the effluent
pump is not operating. To stop gravity flow of effluent from the effluent tank, manually
close the effluent flow control valve (782) located upstream of the effluent flow meter (785).
Alarms will be triggered as equipment turns off; the alarms will be displayed on the HMI.
Tanks in the WWTP area are confined spaces and should be considered inherently
dangerous. A confined space entry permit is required to enter any tank in the WWTP.
Operators and personnel are required to abide by company safety policies and procedures
and relevant state safety regulations in order to work in a confined space.
CONSULT THE SITE SAFETY OFFICER BEFORE ENTRY OR WORK IN A CONFINED SPACE.
If evacuation of the process tanks is not needed, continue to Section 5.5. It should be noted
that the system is designed such that evacuation water is routed back to Facility 71, Tanks 1
and 2.
To evacuate the pH and reaction tank, open the ball valves at the end of the tanks and turn
off the batch pump (175) and leave Facility 71 running in normal operations. The influent
batch tank (220) will draw down to its L-level switch (223) and will shut off the influent
pump after 20 minutes’ elapse, which will in turn shut down all other equipment except for
the effluent pump (775). Once piping configurations are completed on the outlets of the pH
tank or reaction tank, open the necessary outlet valve and drain the water remaining in the
pH tank or reaction tank into the influent batch tank. Close the outlet valves once the tanks
are evacuated.
Note, once the water level in the polymer addition tank decreases below its LL-level switch
(524) or the influent flow meter (310) measures a flow fewer than 5 gpm and a delay timer
has elapsed, the polymer addition tank mixer (525) will shut off.
External equipment and piping re-configurations may be used to fully evacuate the effluent
tank. One solution is to pump water from the effluent tank back to the influent batch tank
or other on-site tanks. This would include reconfiguration of the piping connected to the
outlet of the effluent tank. A pump of sufficient lift would be necessary to pump water from
the effluent tank into other tanks on site.
The calcium chloride, ferrous chloride, and polymer feed pumps (430, 435, and 530,
respectively) have a “Jog” operation that can be enabled to purge the feed lines.
Through the HMI (925), select “CALCIUM CHLORIDE PUMP JOG,” “FERROUS
CHLORIDE PUMP JOG,” or “POLYMER PUMP JOG,” and enter speed for the selected
parameter; entry range is between 0.0 and 100.0 percent.
Once the lines are purged, repeat the process above and enter a speed of 0.0 percent for
each parameter.
Note that the pumps in the leachate ditches (105 and 110) should remain in operation during
a planned shutdown; these pumps may need to be manually operated to continue to pump
stormwater wastewaters to Tank 3 in Facility 77.
Drain or pump down, clean, and rinse process tanks (except for sludge tank). Note:
Solid materials from the process tanks are transferred into the sludge tank (820).
Waters are sent back to Facility 71, Tanks 1 and 2.
pH and reaction tanks (320 and 420, respectively)
Influent batch tank (220)
Polymer addition tank (520)
Lamella clarifier (620): Run sludge pump to empty clarifier
Effluent tank (720)
Fill process tanks and components with clean well water.
Use well water supply from the water services connection in Facility 71.
Set valves for recirculation within the treatment system.
Close the effluent flow control valve (782)
Close the influent flow control valve (309)
Open the effluent bypass flow control valve (781)
Pump down and clean sludge dewatering box in the sludge tank (820).
Replace filter fabric if damaged or clogged
Stabilize and dispose of residual solids in accordance with Solid Waste Control Plan
The Operator should manually turn off all equipment switches on the control panel (925),
starting with the batch pump and working down the line (1-7). If it is necessary to cease
discharge from Facility 71, manually close the effluent flow control valve (782)3, located
upstream of the effluent flow meter (785) between the main control facility and the influent
batch tank (see Photograph 3). The main control power switch should always be on so the
HMI/PLC can continue to collect continuous monitoring field data.
3 The effluent pump is a centrifugal pump that allows for gravity flow even when not in operation (powered
on). The effluent pump will allow gravity flow as long as the water level in the effluent tank is above the
effluent pump, located in the MCR.
Photograph 2. Control Power Switch on Control Panel - Turn Off in emergency shutdown
1 2 3 4
5 6 7
Effluent Flow
Control Valve (782)
(Normally Open)
Note: The effluent flow control valve is NORMALLY OPEN and, if closed, the valve should
have a tag-out or lock-out according to site safety procedures.
The Operator shall document the time of the emergency shutdown, the reason for the
shutdown (if known), and the time when startup occurs following resolution of the
emergency shutdown.
Following resolution of the emergency shutdown, the Operator shall follow the normal
startup procedures.
7 SAFETY
Facility 71 contains and uses materials that are potentially dangerous. Additionally,
mechanical equipment used in the treatment process can be dangerous. The MBT-Longview
standard safety protocol regarding PPE apply to Facility 71, and additional special protective
clothing and gear should be worn when there is potential for contact with the influent and
various chemical additives. Special attention is drawn to the following conditions:
Sulfuric acid may cause severe burns on contact with skin.
Sulfuric acid is potentially explosive. Never add water to sulfuric acid. There must be
adequate ventilation when sulfuric acid fumes may be generated.
The wastewater influent, when in contact with skin, may cause irritation.
Many pieces of equipment will start automatically without warning. Always keep
clear of moving equipment and follow the lock-out/tag-out procedure when working
on any piece of equipment. Moving equipment, in general, poses a potential safety
hazard.
Gases and fumes produced in process tanks are potentially dangerous. While
Facility 71 is open to atmospheric conditions, equipment and enclosed spaces should
be regularly checked for correct ventilation and operation. Take necessary precaution
before opening closed tanks and totes.
Dust masks shall be worn when handling dry materials that may become airborne
when disturbed or handled.
The open top process tanks constitute fall hazards and tanks shall be considered
confined spaces; precautions related to these hazards shall be taken when working in
or near the process tanks.
Operations of Facility 71 may require heavy lifting to replenish and stockpile supplies.
Personnel should seek help in lifting heavy items and/or use dollies or carts to move
heavy items. Heavy items shall not be stockpiled in a manner that poses a
falling hazard.
Walkway gratings have been installed within Facility 71 and should be used unless it
is necessary to inspect or operate elements of Facility 71 that are inaccessible from
the walkways.
Walkways and platforms shall be free of trip hazards and storage of items that impede
easy ingress or egress from Facility 71.
Feed pump line containment tubing is installed on the suction and discharge lines for
each feed pump. This larger diameter tubing will contain leaks that may develop in
the suction and discharge line tubing. The containment tubing on each feed pump is
Chemical product data and SDSs can be found in the main control room. Other related
safety information may be covered in the subsequent Section 8 – Emergency Plans and
Procedures.
There are several features of Facility 71 that aid in responding to emergencies. These are
listed in the following subsections:
Toxic and hazardous solutions used in Facility 71 include sulfuric acid, ferrous chloride, and
calcium chloride. Personnel that observe the spill should take extra precautions before
attempting to respond to the spill; precautions should always follow site safety procedures.
Spills may need to be cleaned up by hand, depending on the volume of the spill, whether or
not rainfall has collected within Facility 71, and the spill location. Spills originating from
influent and reagents used within Facility 71 may be routed into Facility 71 for treatment;
these spills should be characterized and evaluated for proper processing through Facility 71
to avoid system upsets. Spills originating from sources other than those present in Facility 71
process shall be properly handled and disposed of in accordance with applicable SDS and the
Solid Waste Control Plan.
Small releases that can be readily contained and do not involve fire, explosion, injuries or
storm drains and cannot escape containment, may be cleaned by area employees.
A release of hazardous materials that cannot be readily contained and/or involve fire,
explosion, injury, storm drains, could escape offsite, and threaten human health or the
environment, trigger the guard to implement emergency response.
8.4 Communications
There are no phones located in Facility 71. The Operator and personnel involved with the
operations or maintenance will be equipped with radios and/or mobile telephones in
accordance with MBT-Longview policies.
8.5 Alarms
There are many operational conditions that will cause an alarm condition, as described in
Section 2.9.2.
Sampling shall be done by the Operator or other personnel trained for sample collection.
The influent sampling schedule is included in Table 16.
8. Refer to the Lab Quality Assurance Manual for NPDES Wastewater Analysis for
complete instruction of sampling protocols.
Specialty Analytical
9011 SE Jannsen Road
Clackamas, OR 97015 (503) 607-1331
info@specialtyanalytical.com
In the event that the primary contract laboratory cannot perform the analyses, the secondary
contract laboratory is as follows:
Table 16
Monitored Analytes
E
ENU
AV
TH
WEST LONGVIEW
38
SEATTLE
WASHINGTON
IN
DU
ST
LONGVIEW RI
AL
W
AY
CO
LU
M MILLENNIUM BULK
BI
A TERMINALS - LONGVIEW
RI
DWG-1
V ER
FACILITY 71, INDUSTRIAL
LONGVIEW
L:\Projects\Millennium_Bulk_Terminals-Longview_LLC\Matters_Subject_To_Holdback_Agreement_(110730-01.05)\WWTP Redesign\CAD\RECORD DRAWINGS\11073001-PL-002.dwg
LORD ISLAND
MILLENNIUM BULK TERMINALS - LONGVIEW, LLC TREVOR SIMMONS DAVID RICE, P.E.
4029 INDUSTRIAL WAY (PARCELS 61953 & 6195302) MILLENNIUM BULK TERMINALS - LONGVIEW, LLC ANCHOR QEA, LLC
LONGVIEW, WA 98632 LONGVIEW, WA 98632 720 OLIVE WAY, SUITE 1900 DRAWING INDEX: 0 200 400
36 & 38 SECTION T8N/R3W (360) 636-8340 SEATTLE, WA 98101 SHEET NUMBER DRAWING NUMBER DESCRIPTION
ONE INCH
2 DWG-2 TEMPORARY TREATMENT SYSTEM PROCESS DIAGRAM
MILLENNIUM BULK TERMINALS - LONGVIEW, LLC DENNIS CAUDELL 3 DWG-3 TEMPORARY TREATMENT PLAN
TERRA HYDR INC.
P.O. BOX 3616 4 DWG-4 DETAILED TEMPORARY TREATMENT PLAN
PORTLAND, OREGON 97208 5 DWG-5 TEMPORARY TREATMENT PLANT DETAILS
(503) 710-1227
REVISIONS
MILLENNIUM BULK TERMINALS - LONGVIEW, LLC
REV DATE BY APP'D DESCRIPTION DESIGNED BY: D. RICE
WASTEWATER TREATMENT PLANT DWG-1
Aug 01, 2012 12:30pm drice
ACID FEED PUMP CACL2 FEED PUMP FECL2 FEED PUMP POLYMER FEED PUMP
(330) (430) (435) (530)
OVERFLOW
LEVEL SWITCHES, LEVEL SWITCHES, LEVEL SWITCHES, VALVE (782) AND EFFLUENT FLOW
HIGH-HIGH (321) HIGH-HIGH (421) (520) HIGH-HIGH (521) ISCO AUTO SAMPLER (740), METER (785)
DWG-2
LOW-LOW (324) LOW-LOW (424) POLYMER LOW-LOW (524) OUTFALL 002B POINT OF
(320) (420) COMPLIANCE
ADDITION TANK
LEVEL SWITCHES, (720)
L:\Projects\Millennium_Bulk_Terminals-Longview_LLC\Matters_Subject_To_Holdback_Agreement_(110730-01.05)\WWTP Redesign\CAD\RECORD DRAWINGS\11073001-PL-002.dwg
FILTRATE
INFLUENT PUMP
(275)
INFLUENT
LEVEL SWITCHES,
LEVEL SENSOR/SWITCHES,
HIGH-HIGH (221)
HIGH (122)
HIGH (222)
LOW (123)
LOW (223)
LEVEL SWITCHES,
RAW INFLUENT HIGH (822)
STREAM
SOLIDS DISPOSAL
(120) BATCH PUMP (220)
(175)
THICKENER TANK 3, FACILITY 77 INFLUENT BATCH TANK FILTRATE PUMP (820)
(875)
SYSTEM NO. SYSTEM
SLUDGE TANK
100 WASTEWATER SOURCE MANAGEMENT
200 INFLUENT BATCHING PROCESS
300 pH ADJUSTMENT PROCESS CONTAINMENT
PUMP
400 REACTION/PRECIPITATION PROCESS
ONE INCH
600 PRIMARY CLARIFICATION PROCESS
700 TREATMENT EFFLUENT MANAGEMENT PROCESS
800 SLUDGE MANAGEMENT PROCESS
900 OPERATIONS AND PLC
REVISIONS
MILLENNIUM BULK TERMINALS - LONGVIEW, LLC
REV DATE BY APP'D DESCRIPTION DESIGNED BY: D. RICE
WASTEWATER TREATMENT PLANT DWG-2
Aug 01, 2012 12:31pm drice
ONE INCH
0 8 16
M FLOW METER
SCALE IN FEET
P PUMP
FLOW DIRECTION
REVISIONS
MILLENNIUM BULK TERMINALS - LONGVIEW, LLC
REV DATE BY APP'D DESCRIPTION DESIGNED BY: D. RICE
WASTEWATER TREATMENT PLANT DWG-3
Aug 01, 2012 12:31pm drice
AND EQUIPMENT.
3" HDPE
EFFLUENT FLOW CONTROL VALVE (782)
3" HDPE
(NORMALLY OPEN)
3" HDPE
3'-0"
EFFLUENT FLOW METER (785)
3" HDPE
3" HDPE
ONE INCH
COMPRESSED AIR System Drain Valve (307) FERROUS CHLORIDE FEED PUMP (435) CONTAINMENT PUMP (240)
FILTRATE PUMP (875) LINER UNDER EQUIPMENT AND
(FROM FACILITY 77) ACID FEED PUMP (330) ALONG INTERIOR OF PRE-CAST
(Upside Down Valve) POLYMER BULK DRUM (528)
PROCESS WATER CONCRETE BARRIER WALL PLACED 0 5 10
(FROM FACILITY 77) AROUND PERIMETER
DETAILED PLAN SCALE IN FEET
REVISIONS
MILLENNIUM BULK TERMINALS - LONGVIEW, LLC
REV DATE BY APP'D DESCRIPTION DESIGNED BY: D. RICE
WASTEWATER TREATMENT PLANT DWG-4
Aug 01, 2012 12:32pm drice
PIPING, CONDUIT, AND APPURTENANCES EFFLUENT PUMP (775) SEE PLAN VIEW FOR PIPING BELOW FLOOR
ARE SHOWN. INFLUENT PUMP (275)
L:\Projects\Millennium_Bulk_Terminals-Longview_LLC\Matters_Subject_To_Holdback_Agreement_(110730-01.05)\WWTP Redesign\CAD\RECORD DRAWINGS\11073001-PL-002.dwg
(NORMALLY OPEN)
BOTTOM OF TANK/ INFLUENT PUMP pH SAMPLE PUMP 2 FILTRATE LINE WYE (866)
TOP OF FOUNDATION DISCHARGE LINE 3" HDPE SLUDGE PUMP (805) FILTRATE PUMP
SUCTION LINE 3" HDPE
INFLUENT PUMP CONTAINMENT PUMP SLUDGE PUMP SUCTION SUCTION LINE 3" HDPE
FILTRATE PUMP
SUCTION LINE, 3" HDPE DISCHARGE LINE 1" HDPE DISCHARGE LINE 3" HDPE LINE 4" HOSE PRE-CAST CONCRETE
pH SAMPLE PUMP 2 SUPPORT AND TIMBER
INFLUENT BATCH TANK INFLUENT BATCH TANK DISCHARGE FILTRATE PUMP CRIBBING (TYP)
DISCHARGE LINE 3" HDPE SLUDGE CONTROL VALVE (665)
VALVE (265), 3" BALL VALVE
ONE INCH
FACILITY 77, THICKENER TANK 3 INFLUENT BATCH TANK LAMELLA CLARIFIER SLUDGE TANK
REVISIONS
MILLENNIUM BULK TERMINALS - LONGVIEW, LLC
REV DATE BY APP'D DESCRIPTION DESIGNED BY: D. RICE
WASTEWATER TREATMENT PLANT DWG-5
Aug 01, 2012 12:32pm drice
453 FeCl2 Feed Pump Discharge Point 700 Treated Effluent Management Process 900 Operations and PLC
455 pH Sample Pump 2 Discharge Point 719 Effluent Tank Inlet from Lamella Clarifier 901 Main Control Facility
460 Reaction Tank Outlet to Polymer Addition Tank 720 Effluent Tank 910 Ancillary Storage Room
461 Reaction Tank Outlet/Valve (Inactive 1) 721 Effluent Tank HH Level Switch 920 Main Control Room
462 Reaction Tank Outlet/Valve (Inactive 2) 722 Effluent Tank H Level Switch 925 Main Control Panel (MCP)
465 Reaction Tank Discharge Pipe Drain/Valve 723 Effluent Tank L Level Switch 926 Human-Machine-Interface (HMI)
739 Electrical Receptacle 927 Sensaphone
500 Flocculation Process 740 ISCO Auto Sampler 930 Equipment Room
518 Polymer Addition Tank Inlet Drain/Valve 741 ISCO Sample Inlet 935 pH Controller
519 Polymer Addition Tank Inlet from Reaction Tank 760 Effluent Tank Outlet to Facility 77 950 Emergency Eyewash/Shower Station
520 Polymer Addition Tank 765 Effluent Tank Discharge Valve 955 Fire Extinguisher 1
521 Polymer Addition Tank HH Level Switch 766 Effluent Tank Discharge Wye-Strainer w/ Valve 956 Fire Extinguisher 2
524 Polymer Addition Tank LL Level Switch 774 Effluent Pump Suction Line Drain Valve 957 Fire Extinguisher 3
525 Polymer Addition Tank Mixer 775 Effluent Pump 960 Smoke Detector 1
526 Polymer Addition Tank Mixer Motor Relay 776 Effluent Pump Motor Relay 965 Fire Hydrant & Hose House
528 Polymer Bulk Drum 777 Effluent Pump Discharge Line Drain Valve 970 Plant Water Control Valve
529 Polymer Bulk Drum Level Sensor 781 Effluent Bypass Flow Control Valve 975 Plant Air Control Valve
530 Polymer Feed Pump 782 Effluent Flow Control Valve 980 Electrical Panels
531 Polymer Feed Pump Containment Drum 785 Effluent Flow Meter
544 Water Input Rotameter/Control Valve, Upstream 786 Effluent Flow Transmitter
545 Polymer Feed Pump Discharge Point 790 Effluent Air/Vac Release Valve
546 Water Input Rotameter/Control Valve, Downstream
550 MixMate Device 800 Sludge Management Process
551 Diluted Polymer Sampling Valve 805 Sludge Pump
555 Filtrate Pump Discharge Point 810 Sludge Pump Air Valve
556 Diluted Polymer Discharge Point 819 Sludge Pump Discharge Point
560 Polymer Addition Tank Outlet to Lamella Clarifier 820 Sludge Tank
822 Sludge Tank H Level Switch
600 Primary Clarification Process 860 Sludge Tank Outlet to Filtrate Pump
620 Lamella Clarifier 861 Sludge Tank Hatch for Solids Removal
621 Lamella Clarifier HH Level Switch 865 Sludge Tank Discharge Valve
624 Lamella Clarifier LL Level Switch 866 Filtrate Line Wye/Control Valve
650 Lamella Clarifier Cone Sight Tubes 874 Filtrate Pump Suction Line Drain Valve
660 Lamella Clarifier Outlet to Effluent Tank 875 Filtrate Pump
661 Lamella Clarifier Outlet to Sludge Tank 876 Filtrate Pump Motor Relay
665 Sludge Control Valve 877 Filtrate Pump Discharge Line Drain Valve
Page 2 of 2
APPENDIX B
SYSTEM STARTUP
PROCEDURES/CHECKLIST
Millennium Bulk Terminals – Longview, LLC
Updated: May 2018 Page 1 of 1
Wear personal protective equipment when working in Facility 71. Confer with Site Safety Officer and review SDS if you have
questions about appropriate personal protective equipment.
Supplies Inventory: Check current supplies and order additional supplies as necessary.
Chemicals/Reagents Qty. On-hand Reorder Qty. Personal Protective Equipment Reorder Qty.
o Sulfuric Acid o Face Shield
o Calcium Chloride o Chemical Resistant Suit
o Ferrous Chloride o Chemical Resistant Gloves
o Liquid Polymer
o pH 7, Standard Solution
– Properly dispose of expired solutions or solutions that are not properly labeled; see SDS for more information
Initial Inspection of System: Inspect all equipment; begin at wastewater sources and end at Facility 77.
See the Operations and Maintenance Manual for further details regarding a System Startup
Startup Procedure of Facility 71
1. Check all chemical totes and suction lines to pumps from chemical totes. Be sure
there is enough chemicals onsite for startup—at least 4 totes of calcium and 2
totes of sulfuric.
2. Turn “upside down valve” in front of Conex box off and disconnect the black hose
going to #2 tank at Facility 77.
3. Turn on batch pump to “auto” and start filling up the influent tank. Be sure there
is enough process water in #3, #2, and #1 for startup.
4. Close ball valves on the ends of pH and reaction tanks (two grey tanks).
5. Be sure blue valve is open and recirculation valve is closed. Check to make sure the
influent valve is open and the wye strainer has been cleaned.
6. Turn on the influent pump on the control panel inside the Conex box. Fill up pH
tank and reaction tank. Gravity flow starts to fill up reaction tank, polymer tank,
and clarifier then goes to effluent tank. Fill up effluent tank about half-full
according to arrow on end of tank.
7. Turn all switches on control panel to “auto” (except effluent pump).
8. Calibrate pH probes. Replace pH probes in holders. Open red ball valve under
Conex box for acid.
9. Plug in all chemical pumps (except polymer pump). Turn on switch in electrical
panel labeled “chemical pumps”. Turn pH and reaction pumps in auto (located by
pH probes).
10. Start recirculation process for a couple hours.
11. Fill polymer container with polymer. Hook up tubing to bottom of container.
Open container and let polymer gravity flow to pump head. Disconnect the tubing
at the pump head to allow the polymer to gravity fill the tubing in order to prime
the pump. Put in prime mode and leave discharge side off until polymer is to the
mix chamber. Screw tubing on. Turn on poly feed water valves to #1 and #2.
12. After system has been recirculating for a couple hours, open effluent control valve
by the readout meter and close effluent sample line ball valve.
Recirculation Process:
Influent valve off
Open up recirculation valve
Turn on effluent
Extended/Seasonal Shutdown
6 o Begin extended shutdown when water levels in Tank 3 (System 120), clarifiers 1 & 2 and ditch levels are low.
7 o Perform steps 1-5 of temporary shutdown.
8 o Drain and/or pump down, clean, and rinse process tanks, except for sludge tank (System 820).
– Process tank contents transferred into sludge tank; filtrate and effluent pumps in "Auto" position at MCP/HMI
a o pH tank (System 320) and reaction tank (System 420)
b o Influent batch tank (System 220);
c o Polymer addition tank (System 520)
d o Lamella clarifier (System 620); run sludge pump (System 805) to empty clarifier
e o Effluent tank (System 720);
9 o Clean wye-strainers at pump connections to tanks.
10 o Pump down and clean sludge dewatering box in sludge tank (System 820).
a o Replace filter fabric if damaged or clogged; As needed
Inspect level of solids in sludge tank. Stabilize and dispose of residual solids in accordance with Solid Waste Control Plan.
b o As needed.
11 o Set valving for recirculation within the treatment system.
a o Close the effluent flow control valve (System 782) located behind Conex box near flow meter.
b o Close the influent flow control valve (System 309). Blue valve near influent flow meter
Open the effluent bypass flow control valve (System 781). After effluent tank is drained, open effluent sample line ball
c o valve located againt the back barrier under effluent line leading to Fac 77. This valve can be left open till start-up.
See the Operations and Maintenance Manual for further details regarding a System Shutdown
Note: The reagent bulk totes and polymer bulk drums may remain in-place. If it is desirable to remove the bulk totes and
drums from the plant, refer to the Operations and Maintenance Manual for information on how to purge the feed
pumps. Storage of bulk totes and drums shall have adequate containment measures.
Temporary Shutdown Procedure of Facility 71
(Maximum Two Weeks)
1. In Facility 71’s back storage room, turn off the chemical pumps at the
electrical panel located on the wall by flipping the circuit breaker labeled
Chemical Pumps. In the pump room, unplug each chemical pump at their
wall outlets.
2. On the back side of the Conex box, along the walkway halfway down
underneath the box, close the red ball valve to stop the flow of acid.
3. On the PLC in the main control room, turn the following equipment switches
from “auto” to “off”:
Batch pump
pH tank
Reaction tank
Polymer tank
Effluent pump
Influent pump
Filtrate pump
4. In the pump room, turn pumps from auto to off (labeled pH Loop and
Reaction Loop). Turn the red-handled vertical ball valves (labeled pH Loop
and Reaction Loop) to the off position. Remove pH probes, rinse and clean
with DI water, and then place in pH buffer (potassium chloride).
5. In the pump room, turn water off to the polymer mixing chamber by using
the two red ball valves labeled with green tags (Poly Feed Water 1 Isolation
and Poly Feed Water 2 Isolation).
2. After the effluent tank is drained (check the level indicator at the end of the
tank), open the effluent sample line ball valve which is located against the
back barrier under the effluent line to Facility 77. This valve can be left open
until startup.
3. Close the effluent control valve located back of the Conex box, next to the
readout meter, labeled Effluent Flow Valve.
4. Close the blue valve on the influent flow meter. Open the recirculation
valve. Hook up the black hose to Clarifier Tank 2 at Facility 77.
5. In the front of the Conex building, left of the front door, open the blue valve
(upside-down) going into Clarifier Tank 2 through the black hose.
6. Check to make sure the influent valve is open at the end of the influent Baker
tank. Inside the Conex box, turn the influent pump to auto at the control
panel. Do not let the influent tank go empty—a few feet of water can be
left in the tank.
7. Open the ball valves on both the pH tank and reaction tank (two gray tanks
on top of the influent tank). This will allow them to drain into the influent
tank.
8. Check the flow from the black hose on the top of Clarifier Tank 2.
9. After the pH and reaction tanks have been drained, use a garden hose to
wash the inside of the tanks.
10. Using the butterfly valve on the bottom of the filtrate tank, drain the water
until it has dropped at least 1 foot. Use a garden hose to wash the louvers
inside the tank.
11. After a few hours (or at the end of the day) turn the filtrate pump and
influent pump to the off position.