COMBINED FOOTING DESIGN

I. MAXIMUM DESIGN LOAD


Y
P1= 1114
P2= 1464
eP= 2578 KN X L1
M1x= 1.25 KNm
M1y= 1.25 KNm
M2x= 2.6 KNm
M2y= 1.43 KNm
DISTANCE B/N COLUMNS (L)= 5.36 A B
DISTANCE FROM COLUMN B
TO END OF FOOTING (L1)= 0 m b c2
c1 X
sall= 250 KN/m 2

d1 d2
Column dimensions c1= 0.60 m
d1= 0.25 m
c2= 0.40 m
d2= 0.35 m a

ema=> P1*L+M1Y+M2Y=eP*X
=>X= 3.04
a=(X+L1+d2/2)*2
=>a= 6.44 6.44 m
ea=(M1Y+M2Y)/eP
=>ea= 0.001
s= P/A(1+6xea/a)
Where s= the allowable soil pressure
s= (P/ab)(1+6xea/a)
=>b= (P/sa)(1+6xea/a)
=>b= 1.60 1.6 m
distributed contact pressure= sxb= 400.71 400.310559

The shear force & bending moment diagrams are as shown below
P1 P2

0.13 5.36 0.96

50.04 1083.86

2.66
-1063.96
-380.14

59.12737413324

57.69737413324
4.377426

3.127426

-1408.124

use concrete strength 25 Mpa


Fcd= 11.333
Fctd= 1.167
682567200.xls
rmin= 0.00200
Steel S-300
Vup= 641.67
Vud= 385.00
taking concrete cover to be = 50 mm

FOOTING DEPTH DETERMINATION

WIDE BEAM SHEAR


First column Second column
Vcd*b*d=maxshear-contactP*((d1/2)+d)
d= 0.93 d= 0.95

d= 0.95 0.95 m

PUNCHING SHEAR
First column Case 1 Case 2(if the column is at the edge)
Perimeter PR= 2.63 2.28071 0.59 0.59
V= Pcol-Psoil= 833.89 KN -132.6223670524 -0.0001109735
v=V/(PR*d)= 385.76 KN < 641.67 KN OK
Second column 0.95
Perimeter PR= 3.65 m 0.54
V= Pcol-Psoil= 1026.70 KN 0.0000382285
v=V/(PR*d)= 297.00 KN < 641.67 KN OK
Thus d= 0.95
Therefore, take:
a= 6.44 m
b= 1.60 m
d= 0.95 m
D= 1.01 1.01 m

REINFORCEMENT CALCULATION
A) LONG DIRECTION
The reinforcement is calculated for the maximum negative moment
Mdsupport= 59.13 KNm Kd=d/(Sqrt(M/b))= 19.0000 =>Ks= 3.95 safe
Mdspan= -1408.12 KNm Kd=d/(Sqrt(M/b))= 31.2720 =>Ks= 4.06 safe

As-min=rmin*b*d= 3038.37 mm2 use F14c/c130mm 20.00 16.00 14.00


As-support=Ks*M/d= 3038.371 mm2 use 165.73 106.07 81.21
As-span=Ks*M/d = 6031.827 mm 2
83.33 53.43 40.91

B) SHORT DIRECTION
Assuming that the strip A carries the whole column load of P= 1114 KN
M1= 1.25 KNm
ea=M/P= 0.001122

sas= 279.66 KN/m2 695.012378


q'= 697.93 KN/m
M'=((q'*((x1)^2))/2)+M1X 87.74 KNm/m
Kd= 19 =>Ks= 3.95 20.00 16.00 14.00
As-min= 1895.6061 mm 2
165.73 106.07 81.21
As= 1895.61 mm2 strip A 1.07 m 177.98 106.07 81.21
No of bar 6.03390155 177.978
Assuming that the strip B carries the whole column load of P= 1464 KN
M1= 2.6 KNm
ea=M/P= 0.001775956284

sas= 708.46 KN/m2 913.373538


q'= 919.45 KN/m
M'=((q'*((x1)^2))/2)+M2X 74.08 KNm/m
Kd= 19 =>Ks= 3.95 16.00 16.00 14.00
As-min= 1895.61 mm2 106.07 106.07 81.21
As= 1895.61 mm2 Strip B 1.30 m 137.65 106.07 81.21
No of bar 9.42797118 137.6545

682567200.xls
2.54

-122.3911

682567200.xls
0

682567200.xls
COMBINED FOOTING DESIGN

I. MAXIMUM DESIGN LOAD


Y
P1= 2284
P2= 2858
eP= 5142 KN X L1
M1x= 1.7 KNm
M1y= 2.52 KNm
M2x= 4.1 KNm
M2y= 6.2 KNm
DISTANCE B/N COLUMNS (L)= 3.57 A B
DISTANCE FROM COLUMN B
TO END OF FOOTING (L1)= 0.5 m b c2
c1 X
sall= 200 KN/m 2

d1 d2
Column dimensions c1= 0.40 m
d1= 0.40 m
c2= 0.40 m
d2= 0.40 m a

ema=> P1*L+M1Y+M2Y=eP*X
=>X= 1.99
a=(X+L1+d2/2)*2
=>a= 5.37 5.37 m
ea=(M1Y+M2Y)/eP
=>ea= 0.002
s= P/A(1+6xea/a)
Where s= the soil bearing pressure
s= (P/ab)(1+6xea/a)
=>b= (P/sa)(1+6xea/a)
=>b= 4.80 4.8 m
distributed contact pressure= sxb= 959.01

The shear force & bending moment diagrams are as shown below
P1 P2

0.70 3.57 1.10

671.31 1810.99

0 7.91

1.68
-1612.69
-1047.01

597.6481

591.44807432427
237.4786

234.9586

-1118.48
21.79371

use concrete strength 25 Mpa


Fcd= 11.333
Fctd= 1.167
682567200.xls
rmin= 0.00200
Steel S-300
Vup= 641.67
Vud= 385.00
taking concrete cover to be = 50 mm

FOOTING DEPTH DETERMINATION

WIDE BEAM SHEAR


First column Second column
Vcd*b*d=maxshear-contactP*((d1/2)+d)
d= 0.51 d= 0.58

d= 0.58 0.58 m

PUNCHING SHEAR
First column Case1 Case 2(if t 0.6884184
Perimeter PR= 4.45 2.625774 0.71 0.67
V= Pcol-Psoil= 2093.16 KN -0.0008831155 ###
v=V/(PR*d)= 815.15 KN < 641.67 KN NOT OK
Second column 0.71
Perimeter PR= 4.87 m 0.82
V= Pcol-Psoil= 2667.16 KN 0.0000528713
v=V/(PR*d)= 948.50 KN < 641.67 KN NOT OK
Thus d= 0.82
Therefore, take:
a= 5.37 m
b= 4.80 m
d= 0.82 m
D= 0.88 0.88 m

REINFORCEMENT CALCULATION
A) LONG DIRECTION
The reinforcement is calculated for the maximum negative moment
Mdsupport= 597.65 KNm Kd=d/(Sqrt(M/b))= 19.0000 =>Ks= 3.95 safe
Mdspan= -1118.48 KNm Kd=d/(Sqrt(M/b))= 19.0000 =>Ks= 3.95 safe

As-min=rmin*b*d= 7851.56 mm2 use F14c/c130mm 20.00 16.00 14.00


As-support=Ks*M/d= 7851.558 mm2 use 191.86 122.79 94.01
As-span=Ks*M/d = 7851.558 mm 2
192.06 122.79 94.01

B) SHORT DIRECTION
Assuming that the strip A carries the whole column load of P= 2284 KN
M1= 1.7 KNm
ea=M/P= 0.000744

sas= 234.00 KN/m2 476.32229


q'= 476.77 KN/m
M'=((q'*((x1)^2))/2)+M1X 1151.19 KNm/m
Kd= 41.44222 =>Ks= 4.1966667 20.00 16.00 14.00
As-min= 1637.4221 mm2 191.86 122.79 94.01
As= 5900.94 mm2 strip A 1.22 m 64.88 34.07 26.09
No of bar 18.7832735 64.88278
Assuming that the strip B carries the whole column load of P= 2858 KN
M1= 4.1 KNm
ea=M/P= 0.0014345696291

sas= 489.94 KN/m2 596.028504


q'= 597.10 KN/m
M'=((q'*((x1)^2))/2)+M2X 1191.26 KNm/m
Kd= 42.157223 =>Ks= 4.21 20.00 16.00 14.00
As-min= 1637.42 mm2 191.86 122.79 94.01
As= 6125.71 mm2 Strip B 1.22 m 62.50 32.82 25.13
No of bar 19.4987545 62.50199

682567200.xls
COMBINED FOOTING DESIGN

I. MAXIMUM DESIGN LOAD


Y
P1= 2518
P2= 2834
eP= 5352 KN X L1
M1x= 2.5 KNm
M1y= 3.5 KNm
M2x= 0.04 KNm
M2y= 1.6 KNm
DISTANCE B/N COLUMNS (L)= 3.59 A B
DISTANCE FROM COLUMN B
TO END OF FOOTING (L1)= 0.5 m b c2
c1 X
sall= 200 KN/m 2

d1 d2
Column dimensions c1= 0.40 m
d1= 0.40 m
c2= 0.40 m
d2= 0.40 m a

ema=> P1*L+M1Y+M2Y=eP*X
=>X= 1.90
a=(X+L1+d2/2)*2
=>a= 5.20 5.2 m
ea=(M1Y+M2Y)/eP
=>ea= 0.001
s= P/A(1+6xea/a)
Where s= the soil bearing pressure
s= (P/ab)(1+6xea/a)
=>b= (P/sa)(1+6xea/a)
=>b= 5.15 5.15 m 199.850635
distributed contact pressure= sxb= 1029.60 1029.23077

The shear force & bending moment diagrams are as shown below
P1 P2

0.70 3.59 0.91

720.72 1898.96

1.75
-1797.28
-935.04

439.86504464121

438.26504464
255.7508

252.2508

-1312.938

use concrete strength 25 Mpa


Fcd= 11.333
Fctd= 1.167
682567200.xls
rmin= 0.00200
Steel S-300
Vup= 641.67
Vud= 385.00
taking concrete cover to be = 50 mm

FOOTING DEPTH DETERMINATION

WIDE BEAM SHEAR


First column Second column
Vcd*b*d=maxshear-contactP*((d1/2)+d)
d= 0.53 d= 0.56

d= 0.56 0.56 m

PUNCHING SHEAR
First column Case 1 Case 2(if the column is at the edge)
Perimeter PR= 4.63 2.71484 0.76 1.33
V= Pcol-Psoil= 2332.90 KN ### -390.2266285882
v=V/(PR*d)= 896.56 KN < 641.67 KN NOT OK
Second column 0.76
Perimeter PR= 4.86 m 0.81
V= Pcol-Psoil= 2648.90 KN ###
v=V/(PR*d)= 970.16 KN < 641.67 KN NOT OK
Thus d= 0.81
Therefore, take:
a= 5.20 m
b= 5.15 m
d= 0.81 m 0.48
D= 0.87 0.87 m

REINFORCEMENT CALCULATION
A) LONG DIRECTION
The reinforcement is calculated for the maximum negative moment
Mdsupport= 439.87 KNm Kd=d/(Sqrt(M/b))= 19.0000 =>Ks= 3.95 safe
Mdspan= -1312.94 KNm Kd=d/(Sqrt(M/b))= 19.6031 =>Ks= 3.95 safe

As-min=rmin*b*d= 8386.10 mm2 use F14c/c130mm 20.00 16.00 14.00


As-support=Ks*M/d= 8386.097 mm2 use 192.85 123.43 94.50
As-span=Ks*M/d = 8386.097 mm 2
192.93 123.43 94.50

B) SHORT DIRECTION
Assuming that the strip A carries the whole column load of P= 2518 KN
M1= 2.5 KNm
ea=M/P= 0.000993

sas= 241.34 KN/m2 489.124345


q'= 489.69 KN/m
M'=((q'*((x1)^2))/2)+M1X 1379.90 KNm/m
Kd= 45.606925 =>Ks= 4.285 20.00 16.00 14.00
As-min= 1629.0088 mm 2
192.85 123.43 94.50
As= 7259.49 mm2 strip A 1.21 m 52.56 27.70 21.21
No of bar 23.1076599 52.55852
Assuming that the strip B carries the whole column load of P= 2834 KN
M1= 0.04 KNm
ea=M/P= 1.411433E-05

sas= 453.29 KN/m2 550.507702


q'= 550.52 KN/m
M'=((q'*((x1)^2))/2)+M2X 1300.93 KNm/m
Kd= 44.282681 =>Ks= 4.26 20.00 16.00 14.00
As-min= 1629.01 mm2 192.85 123.43 94.50
As= 6804.10 mm2 Strip B 1.21 m 56.08 29.55 22.62
No of bar 21.6581308 56.07614

682567200.xls
1.89

14.42308

682567200.xls
COMBINED FOOTING DESIGN

I. MAXIMUM DESIGN LOAD


Y
P1= 930
P2= 1348
eP= 2278 KN X L1
M1x= 0.411 KNm
M1y= 5.65 KNm
M2x= 5.8 KNm
M2y= 2 KNm
DISTANCE B/N COLUMNS (L)= 1.79 A B
DISTANCE FROM COLUMN B
TO END OF FOOTING (L1)= 0.5 m b c2
c1 X
sall= 200 KN/m 2

d1 d2
Column dimensions c1= 0.40 m
d1= 0.40 m
c2= 0.80 m
d2= 0.40 m a

ema=> P1*L+M1Y+M2Y=eP*X
=>X= 1.06
a=(X+L1+d2/2)*2
=>a= 3.53 3.53 m
ea=(M1Y+M2Y)/eP
=>ea= 0.003
s= P/A(1+6xea/a)
Where s= the soil bearing pressure
s= (P/ab)(1+6xea/a)
=>b= (P/sa)(1+6xea/a)
=>b= 3.25 3.25 m
distributed contact pressure= sxb= 649.90 645.325779

The shear force & bending moment diagrams are as shown below
P1 P2

0.68 1.79 1.06

438.82 672.15

0.76
-491.18
-675.85

318.82

316.8175521173
154.8493

149.1993

-30.76003

use concrete strength 25 Mpa


Fcd= 11.333
Fctd= 1.167
682567200.xls
rmin= 0.00200
Steel S-300
Vup= 641.67
Vud= 385.00
taking concrete cover to be = 50 mm

FOOTING DEPTH DETERMINATION

WIDE BEAM SHEAR


First column Second column
Vcd*b*d=maxshear-contactP*((d1/2)+d)
d= 0.19 d= 0.29

d= 0.29 0.29 m
0.00
PUNCHING SHEAR
First column case1 Case 2(if the column is at the edge)
Perimeter PR= 3.18 1.988575 0.39 0.67
V= Pcol-Psoil= 835.57 KN -0.0007926052 ###
v=V/(PR*d)= 915.95 KN < 641.67 KN NOT OK
Second column 0.39 0.67
Perimeter PR= 4.13 m 0.43
V= Pcol-Psoil= 1198.60 KN -0.0000003254
v=V/(PR*d)= 1011.56 KN < 641.67 KN NOT OK
Thus d= 0.43
Therefore, take:
a= 3.53 m
b= 3.25 m
d= 0.43 m 0.48
D= 0.49 0.49 m

REINFORCEMENT CALCULATION
A) LONG DIRECTION
The reinforcement is calculated for the maximum negative moment
Mdsupport= 318.82 KNm Kd=d/(Sqrt(M/b))= 22.9450 =>Ks= 3.97 safe
Mdspan= -30.76 KNm Kd=d/(Sqrt(M/b))= 19.0000 =>Ks= 3.95 safe

As-min=rmin*b*d= 2805.58 mm2 use F14c/c130mm 20.00 16.00 14.00


As-support=Ks*M/d= 2931.968 mm2 use 348.18 222.84 170.61
As-span=Ks*M/d = 2805.577 mm2 363.92 232.88 178.30

B) SHORT DIRECTION
Assuming that the strip A carries the whole column load of P= 930 KN
M1= 0.411 KNm
ea=M/P= 0.000442

sas= 226.72 KN/m2 286.196393


q'= 286.43 KN/m
M'=((q'*((x1)^2))/2)+M1X 290.72 KNm/m
Kd= 39.496804 =>Ks= 4.17 20.00 16.00 14.00
As-min= 863.38295 mm 2
363.87 232.88 178.30
As= 2808.24 mm2 strip A 0.83 m 93.04 59.55 54.82
No of bar 8.93888964 93.04192
Assuming that the strip B carries the whole column load of P= 1348 KN
M1= 5.8 KNm
ea=M/P= 0.004302670623

sas= 502.74 KN/m2 414.8309


q'= 418.13 KN/m
M'=((q'*((x1)^2))/2)+M2X 313.60 KNm/m
Kd= 41.021906 =>Ks= 4.1966667 20.00 16.00 14.00
As-min= 863.38 mm2 363.87 232.88 178.30
As= 3048.66 mm2 Strip B 0.83 m 85.70 65.95 50.49
No of bar 9.70420033 85.70428

682567200.xls
13.05

-39.38371

682567200.xls