ALESSANDRO RESIDENTIAL BUILDING STRUCTURAL DESIGN ANLYASIS


ISOLATED FOOTING DESIGN ( F1 )

I. MAXIMUM DESIGN LOAD


Y
Ps= 355.54
Soil Wt. & own Wt. Of footing 108.80
Pmax= 464.34 KN
Mx= 4.94 KNm
My= 58.31 KNm
a c X
sall= 280 KN/m2
d
Column dimensions c= 0.40 m
d= 0.20 m

b
s= P/A(1+6xea/a+6eb/b)
Where s= the allowable soil pressure
A= axb ASSUME a/b= 1.00
a= length of footing 1.60 1.60
b= width of footing 1.60 1.60
P= load sustained by the footing

ea= 0.011
eb= 0.126
DMT: Use the "tools-Goal seek" command
s1= 274.03 and feed the allowable soil pressure to obtain
this result. The value in "E19" should be used
s2= 103.20 as a variable to change in order to achieve
s3= 259.56 this result.

s4= 88.73
savg= 181.38
Structural design
use concrete strength 25 Mpa
use steel strength 300 Mpa
Fcd= 11.333
Fctd= 1.167
Fyd= 260.870
rmin= 0.00200
Steel S-300
Vup= 641.67
Vud= 385.00
A) Punching Sheer
b= 1m
d= 0.356 m
taking concrete cover to be = 50 mm
D= 405.898 mm
~D= 406.000 mm
hence d= 356.000 mm
B) Wide beam shear
da= 249.49 mm
db= 249.49 mm

d= 356.000 mm

Use,D= 406.000 mm

C) Bending moment
Ma-a= 32.65
Mb-b= 44.44
D) Reinforcement 14
Asmin= 712
3.97 12 113
rS= 0.0009996 As(cal)= 355.7502 Asa-a= 712 mm2 ,F14c/c 159 mm
rS= 0.0013664 As(cal)= 486.292297 Asb-b= 712 mm2 ,F14c/c 159 mm

STRUCTURAL DESIGN BY LAL CONSULTING ARCHITECTS AND ENGINEERS