FOUNDATION ENGINEERING
Example:
Design a square spread footing to carry a column dead load of 876.26 kN and a live load of 711.68 kN from a
400 mm square tied column containing 36mm bars as the principal column steel. The allowable soil pressure
is 215.47 kN/m2. Consider there is a 600 mm overburden weighing 16 kN/m3. Use ’c = 20.7 MPa, y = 276
MPa , and the strength method of the ACI CODE.
Given:
DL = 876.26 kN Overburden : t = 600 mm @ 16 kN / m3
LL = 711.68 kN c = 20.7 MPa
COL = 400 mm 2 y = 276 MPa
Allow. Soil Pressure = 215.47 kPa
Required : Design of square spread footing. Use strength method of the ACI Code.
Solution :
1) Estimate the footing weight and determine the plan of the footing.
= 8.29 m2
L = 8.29 2.90m
Pu = 1.4 DL + 1.7 LL
= 1.4 (876.26) + 1.7 (711.68) = 2436.62 kN
2436.62 kN
qu(net) = = 289.73 kPa
8.41 m 2
Critical Section
d/2
400 + d
2900 400
d/2
d/2 d/2
t=600 d
(Assumed) 75
289.73
b ο (400 + 500)4
= = 7.2 20 OK
d 500
1 1 1
Vc = f c bο d = 20.7 (4(400 + 500) )(500) = 2729.84kN
3 3 1000
2900
2900/2 = 1450mm
1 1 1
Vc = f ' cbw d = 20.70 (2900) (500) = 1100kN
6 6 1000
Vc = 0.85 (1100) = 935 kN V = 630.16kN
(
= 0.85 ' c Ag ) = 0.70
N
= 0.70 (0.85) 20.70 2
(400)(400)mm 2 1kN
mm 1000
= 1971 kN
= 2436.62kN NO GOOD (NG)
Thus, the column load cannot be transferred by bearing alone. A dowel shall be used to carry the excess
load.
EXCESS LOAD TO BE CARRIED BY THE DOWELS , NEGLECTING THE DISPLACED CONCRETE EFFECT:
EXCESSP
REQ’D As =
( fy − 0.85 fc)
465.62(1000)
= = 2574MM 2
0.70276 − 0.85(20.70)
2574
NO = = 4 pcs
615.75
fy
Ldb = 0.24 d b
f 'c
N
276
MM 2
= 0.24
N
20.7
MM 2
Ldb = 410 MM ( CONTROLS )
Ldb = 0.044 d b fy
= 0.044 (28)(276) = 340MM
Ld = Ldb = L2
L2 L1
DOWEL ANCHORAGE
2900
kN
M u = 289 73
2
(1.25)(2.90M ) 1 1.25M
M 2
= 656kN − M
M 656kN − M kN
REQ’D R = = = 1005 2
bd 0.90(2.90M )(0.50M )
2 2
M
1 2mRn
DET. REINF. RATIO , = 1 − 1 −
m fy
fy 276
m= = = 15.69
0.85 f ' c 0.85(20.70)
k
2(15.69)1005 2
1 M
= 1− 1−
15.69 N 1kN
276 10 6 2
M 1000 N
=
1
15.69
( )
1 − 0.885 = 0.0036
a a
M = T d − = C d −
2 2
N
C = 0.85 c ab = 0.85 20.7 (2.9 )(1000)(a )
MM 2
= 51025.50(a )
N
T = As fy = 5341MM 2 276 = 1474116N
MM 2
C =T
51025.50(a ) = 1474116
(a ) = 28.89MM
28.89 1
M n = 0.90(1474116N )505 −
2 1000 2
= 650.82kN − M 656kN − M ( NG )
5) DEVELOPMENT OF REINFORCEMENT
a) The smallest of the side cover, cover over the bar or wire ( in both cases measured to the
center of the bar or wire )
b) One-half the center-to-center spacing of bars being developed.
Atr f yt
k tr =
260sn
Thus,
20
a) Bottom and side cover = 40 (i.e., clear ) + ( i.e., bar radius )
2
= 50 MM
145 2
= 72.50
b) 2
C = 50MM
Ld 15 fy
= db
d b 16 f 'c db
15 (276) (20) (1)(1)(0.8)(1) (20)
Ld = = 56.87
16 20.7 2.5 2 .5
= 364MM
6) DESIGN SKETCH
19-Ø19mm
each way
2.90
2.90
19-Ø19mm 75mm
each way clear cover
410 450
75mm
clear cover 600
2900
DESIGN DATA: Service DL = 1000.80 kN, Service LL = 778.40 kN, Allow. Soil Pressure = 240 kPa;
f’c for the Col = 27.58 MPa; f’c for footing = 20.70 MPa, f y = 413.70 MPa, Longitudinal Col. Steel
consists of 25 MM bars. Weight of Earth = 16kN/M3
SOL’N.:
P (1000.80 + 778.40)
REQ ' D A = = = 8.24 2
S 216
L = W = 8.24 = 2.87 M
(
Say 2.90M . A = 2.90 2 = 8.41M 2 )
2) FACTORED SOIL PRESSURE
d = 600 − 75 − 65 = 500
FOR TWO-ACTION
d
B = 450 + (2) = 450 + d = 450 + 500 = 950
2
The Total Factored Shear acting on the Critical Section is;
V = q (W 2 − B 2 )
= 323.95
kN
M2
2.9 2 − 0.95 2 = 2432kN
The Shear Strength of the Concrete is;
V V
kN
V = q (2.9)(0.725) = 323.95 (2.9)(0.725) = 681.10kN
M2
The Shear Strength of the Concrete is ;
1
Vc = f ' c bw d
6
1
= 20.70 (2900)(500)(1 / 1000) = 1099.52kN
6
V = Vc = 0.85(1099.52) = 934.59kN
V = 681.10kN
NO SHEAR REINFORCED IS NEEDED.
V V
Therefore, the 600MM Assumed Thickness is satisfactory.
M = q (2.9)(1.225)(1.225 / 2 )
= 323.95
kN
2
(2.9M )(1.225M ) 1.225 M = 704.88kN − M
M 2
M
Re q' d R N = R N = COEF. OF RESISTANCE
bd 2
704.88kN (1000) MM − N
2
N
Re q' d R N = = 1.08 = 1.08MPa
0.90(2900)MM (500) MM
2 2
MM 2
0.0522 = w − 0.59 w 2
w 2 − 1.69w + 0.088 = 0
− (− 1.69) (− 1.69)2 − 4(1)(0.088) 1.69 1.58
w= =
2(1) 2
w(+ ) = 1.635 w(− ) = 0.055
CHOOSE SMALLER VALUE
wf ' c 0.055(20.70)
= = = 0.00275
fy 413.70
1.4 1. 4
Check with MIN = = = 0.00338 0.00275
fy 413.70
Use = MIN = 0.00338
As = bd = 0.00338(2900)(500) = 4906.94MM 2
(
U sin g 25MM A25 = 490.87 MM 2 )
4906.94
No. = = 9.99 say 10 pcs − 25 bars
490.87
CHECK DEV ' T LENGTH ,
LARGER OF : Ab = 490.87
0.02 Ab fy 0.02(490.87 )(413.70)
Ld = = = 892.68MM
f 'c 20.70
Ld = 0.06 d b fy = 0.06(25)(413.70) = 620.55
Ld = 300MM
AVAILABLE Ld = 1225 − 75 = 1150 892.68 OK
ADDENDUM
SUBSTITUTE VALUES
N V
1.52 =
MM 2
0.85(4 )(0.45 + d ) d m 2 ( )
(
But V = q w 2 − B 2 )
= 323.95
kN
M 2
2.9 − (0.45 + a )
2 2
( )
= 323.95 8.41 − 0.2025 − 0.90d − d 2
= 323.95(8.2075 − 0.90d − d )kN 2
Therefore, the foregoing solution illustrates that the assumed 600 mm thick footing is satisfactory for Shear and
chosen economically.
Design a rectangular spread footing to carry 1045.28 kN Dead Load and 511.52kN Live Load from a 450 MM
Square Tied Column that contains 28 MM bars. One dimension of the footing is limited to a maximum of 2.15
M. The Allowable Soil Pressure is263.36 kPa. Neglect the effect of overburden. Use f’c = 20.7 MPa, fy = 276
MPa and the Strength Method of ACI Code.
GIVEN:
REQ’D. : DESIGN
SOLN.
1. DET. PLAN OF FOOTING
REQ' D A =
DL + LL
=
(1045.28 + 511.52)
NET SOIL PRESSURE 248.96
= 6.25M 2
DUE TO SPACE LIMITATION ,
6.25M 2
LENGTH = = 3.0M
2.15M
(
TRY 2.15m 3.0m A = 6.45M 2 )
2. DET. DEPTH REQ’D FOR SHEAR STRENGTH
2333kN
qu (net ) = = 361.71kPa
6.45M 2
1 1
Vc = f ' c bw d = 0.85 20.7 ( 2.15 )(1000 )( d ) = 1386d
6 6
V = qu (net ) ( AREASHADE FOR ONE − WAY ACTION )
kN
= 36.71 ( 2.15 )(1.275 − d ) = 777.68 (1.275 − d )
Critical M2
section for
shear
450
900 2150
d 1275 - d
450 1275
3000
b = COL.DIM . + d
= 450 + 450 = 900
kN
V = 361.71 2.15(3.0 − 0.90(0.90 )) M 2
M
= 2040 kN
3
c = = 1.39 2.0
2.15
b = 4(900 ) = 3600 MM
3600
b = = 8 20
450
1 1 1
Vc = f ' c b d = 20.70 (3600 )(450 ) = 2456.85 kN
3 3 1000
Vc = 0.85(2456.85) = 2088kN V = 2040 kN OK
ADOPT: 550 mm thickness
0.24 fy d b
MIN L1 = Ldb =
f 'c
0.24(276)(20)
= = 290mm
20.70
AVAILABLE L1 = 50 − 75 − 2(20) − 20 = 415MM 290 OK
Check:
C = 0.85f’cba = 0.85(20.70)(2150)(a) = 37829.25a
T = Asfy = 5699(276) = 1,572,924 kN
1572924
a = = 41.60 mm
37829.25
Reinforcement in bandwidth 2 2
= = = 0.84
Total reinforcement +1 3 +1
2.15
= is the ratio of the long side to the short side of the footing
Number of bars in the 2.15 meter band:
= 8(0.84) = 6.72 say 7 pcs
plus: 2 bars on each side of 2.15 meter band = 2(2) = 4
Total: 7 + 4 = 11 bars
USE 11 – Ø25 bars (As = 3926.96 mm2) along short direction This will be adopted for the
reinforcements along the short direction.
e) DEV’T OF REINF.
Ld 15 fy
=
d b 16 f c c + K tr
db
For long direction,
3000 − 75(2)
Spacing of bars = = 259
11
f) DESIGN SKETCH
MASONRY FOOTING
Design a Reinforced Concrete Footing for a 300MM masonry wall carrying a146kN/M Dead Load including the
wall weight and 73kN/M Live Load. Use f’c = 20.70MPa. fy = 276MPa, Allowable Soil Pressure of 191.53kN/M2
and the Strength Method of the ACI Code.
GIVEN :
SOLN. :
W + W LL
(146 + 73) kN
FOOTING WIDTH = DL = M = 1.18M 1.2 M
PNET kN
185.53
M
b) DET. DEPTH
kN
W = 1.4WDL + 1.7WLL = 1.4(146) + 1.7(73) = 328.50
M
kN
W 328.50
q ( NET ) = = M = 273.75 kN
D 1.20M M
c) Reinforcement for Moment Strength the Critical Section for bending moment under masonry walls occurs
halfway between the middle and the edge of the wall.
1 2(15.69)2334.72 fy 276
= 1 − 1 − m= = = 15.69
m 276(1000) 0.85 f ' c 0.85(20.70)
2(15.69)(2334.72)
=
1
1 − 1 −
15.69 276(1000)
=
1
( )
1 − 1 − 0.265 = 0.009
15.69
Required As = bd = 0.009(1000)(134) = 1206 mm2
Check strength
406.44
Therefore, a = = 0.023m = 23 mm
14595
ØMn = 0.90T(d – a/2) = 0.90(406.44 kN)(0.134 – 0.023/2)
= 44.81 kN-m > [Mu = 37.73 kN-m] OK
d) Development of reinforcement
e) Temperature bars
f) Design Details