You are on page 1of 4

MANUAL CALL POINTS

Exed, Intrinsically Safe (Exia), Weatherproof BG Range & PB Range

Features
ᔢ Polyester enclosure – light, strong and not
subject to corrosion.
ᔢ 2 models:
Breakglass.
Pushbutton.
ᔢ 4 basic versions available:
(1) Explosion protected Exe (ATEX, Chinese
[CQST],Brazilian [Inmetro]).
(2) Explosion protected Exi (ATEX, GOST ‘R’,
GOST ‘K’, Chinese (CQST),
Brazilian [Inmetro] or CSA),
(3) Explosion protected: Class I, Div. 2,
Groups A-D.
Class II, Div. 2, Groups F & G (PB only).
Class I, Zone 2.
(4) Weatherproof & Dust-tight/UL ordinary
locations.
ᔢ In line and end of line resistors and/or zener
diodes can be fitted.
ᔢ Variety of colours available.
ᔢ Up to 9 terminals available.
ᔢ Lift flap available for extra protection against
Introduction inadvertent operation.
ᔢ Optional LED – this indicates that the unit has
These manual fire alarm call points have been designed for use in
been operated – useful for testing purposes.
hazardous locations and harsh environmental conditions. The GRP
enclosures are suitable for use offshore or onshore, where lightweight ᔢ Earth continuity option for metal glands.
combined with a high level of corrosion resistance is required. ᔢ 1 or 2 changeover switches.
ᔢ Captive cover screws.
ᔢ SIL 2 Certified.
ᔢ IECEx certified Gb, Db.

Cooper MEDC Limited, Cooper MEDC (USA)


Unit B, Sutton Parkway, 3413 North Sam Houston Parkway West
Oddicroft Lane, Sutton in Ashfield Suite 212
NG17 5FB, UK. Houston, TX 77086, USA

Sales Enq. UK: +44 (0)1623 444 445 Sales Enq. USA: +1 (713) 937- 9772 E-Mail: medc.sales@cooperindustries.com Web: www.coopermedc.com
6DS067/T
Features
Breakglass Model
ᔢ No hammer required – the glass is covered by a membrane thus
protecting the operator from glass fragments.
ᔢ A plastic ‘Break glass’ or deformable operating element is
available to replace the break glass.
Once the flexible element is pressed it bends but will not break.
The unit is reset by repositioning the element. All other functions
remain the same.
ᔢ Key operated test facility – simple but secure.
ᔢ Breakglass hammer available.

Pushbutton Model
ᔢ Stayput as standard or self reset available.
ᔢ Lift Flap as standard. (Not turn and push model).
Specification
Model: BGW & PBW *BGUL & PBUL BGE & PBE BGI & PBI
Protection: Weatherproof/ Explosion Protected Explosion Protected Explosion Protected
dust proof Class I, Div 2 Exed Exia
Class II, Div 2 (Increased Safety) (Intrinsically Safe)
Certification: Weatherproof/ UL Listed to Class I, ATEX approved Ex II 2GD ATEX approved Ex II 1GD
dust proof Div 2, Groups A-D BAS02ATEX2105X (PB only) Baseefa 03ATEX0084X
BGUL & PBUL Exia IIC T4
IP66/IP67 ATEX approved Ex II 2G
Class II, Div 2, CENELEC EN50014
BAS02ATEX2105X (BG only)
Groups F & G CENELEC EN50020
(PBUL only) Exed IICT6 (switch only) Suitable for use in Zones
Listing No. E186629 Exedm IICT4 (other versions) 0, 1 & 2
CENELEC EN50014 IECEx Exia Cert. No:
UL listed for EN50019 IECEx BAS 12.0093X
ordinary locations EN50018 IEC 60079-0
Listing No. S8117 EN50028 IEC 60079-11
*Refer to UL data Suitable for use in Zones 1 & 2 CSA Certification to C22.2 (PBI only):
sheet at rear of Nos.0-M, 0.4-M, 14-M, 25,
Chinese Certification (PBE & BGE):† 30-M, 94, 142-M1987,
catalogue for CQST – Exed IIC T6 (switch only) 157-M1987, 157-92,
complete information Exedm IIC T4 (other versions) Enclosure Type 4. T4A
GOST ‘R’ Certification (PBE & BGE): Class I Groups A, B, C & D
Exedm IIC T6 Cert. No. 79120
Exedm IIC T4 (other versions) GOST ‘R’ Certification (PBI & BGI):
Russian Fire Approved Exia IIC T4 Russian Fire Approved
GOST ‘K’ Certification (PBI only):
Brazilian (Inmetro) Certification: Exia IIC T4
Ex de mb IIC T4 Gb, Ex de IIC T6 Gb
Chinese Certification (PBI & BGI):
SIL 2 Certification to IEC 61508. CQST – Exia IIC T4
Cert. No. Sira 11013 (BGE only). Brazilian (Inmetro) Certification:
American Bureau of Shipping Type Approval Ex ia IIC T4 Ga
SIL2 Certification to IEC 61508.
BGE only
Cert. No. Sira 11013 (BGI only).
American Bureau of Shipping Type Approval
Voltage: Up to 254V Up to 240V Up to 250V Up to 28V (IS)
Certified Temp: –40°C to +55°C –25°C to +55°C (PBUL) ATEX/CENELEC –40°C to +70°C (PBI)
Weatherproof –25°C to +55°C (BGUL) –20°C to +50°C ATEX/CENELEC –40°C to +70°C (BGI)
UL Version CSA –50°C to +40°C (PBI only)
IECEx
Exia IIC T4 Ga (-40°C ≤ Ta ≤ + 70°C)
Exia IIIC T135°C Da (-40°C ≤ Ta ≤ + 70°C)
Switch Ratings: d.c. - 0-30V 5A (resistive) or 3A (inductive)
(1 or 2 changeover 30-50V 1A (resistive or inductive) NOT APPLICABLE
switches fitted) a.c. - 0-254V 5A(resistive or inductive)
Note: UL versions Max Rating 240VAC, 3A

Material: Anti static U.V. resistant glass reinforced polyester. SW1


Basic single changeover
Finish: Red painted finish as standard or to customer specification. switch wiring diagram.
Weight: 1.2 kg. (Varies with model & entries). Note: additional
Ingress Protection: IP66 & IP67. terminal as standard
for ATEX/CENELEC
Entries: Up to 4 entries, M16 or M20 top and bottom (1/2" NPT available on UL version).
1 2 3 4 5 6
units.
Terminals: 6 x 2.5mm2 – standard (BGUL only).
7 x 2.5mm2 – standard.
9 x 2.5mm2 optional – up to 60V only.
SW1 SW2
Resistors & Diodes: Various configurations available on versions up to 24V and all "IS" versions. Basic double changeover
(Minimum Resistor value 100ΩPBE/BGE, 470ΩPBI/BGI). switch wiring diagram.
Earth Continuity: Internal & external earth continuity is provided via an optional earth plate. Note: additional
terminal as standard
LED Indication: A high intensity red LED can be fitted as an optional extra to indicate operation
for ATEX/CENELEC
on versions up to 24V and all "IS" versions.
units.
1 2 3 4 5 6
Labels: BG Glass label - reads either (1) Fire Break glass – press here.
(2) Break glass – press here.
(3) Worded to customer requirements. For versions containing inline and end of line
PB & BG Duty label - worded to customer requirements. Riveted on. resistors or diodes, please specify your requirements.
PB & BG Tag label - worded to customer requirements. Screwed on.
ALL DIMENSIONS IN MILLIMETERS ALL DIMENSIONS IN MILLIMETERS

Ordering Requirements
The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each
component into the appropriate box. Standard products available ex-stock. Please visit www.coopermedc.com for further details.

Model Certification Entries Labels Voltage Switches Options Terminals Finish

BG Certification Code Entries Code Voltage Code Options Code Finish Code
PB ATEX/CENELEC – Ex ed EB M16 *A a.c. A None N Red (Standard) R
ATEX/CENELEC – Exi IB M20 *B d.c. D LED A Natural Black N
CSA – Exi (PBI only) IC 1/2" NPT *C Lift Flap (BG only) B Blue B
IECEx Exia IJ Resistor Series C* Yellow Y
UL – Listed UL *Prefix entry size (see diagram Resistor EOL D* Grey G
above) with entry position
UL - Ordinary locations UW code e.g. 1A, 2A, 4B, 6B. Diode E† Yellow/Black X
GOST ‘R’ – Exi IG* Earth Continuity F** Stripes
UL & CSA versions only
GOST ‘R’ – Ex ed EG* available with 1/2" NPT Turn & Push (PB only) T† Special S*
GOST ‘K’ – Exi (PBI only) IK entries. Self reset (PB only) M
* Please specify.
CQST – Ex ed EQ† Resistor Series & EOL S*‡
CQST – Exi IQ† Plastic element replaces
Inmetro – Ex ed EM Labels Code Break glass P
Inmetro – Exi IM None 0
Uncertified WN Glass label (1) reqd. 1 * Specify values.
Glass label (2) reqd. 2 † Not available for UL/CSA versions.
‡ Choose for BGE or PBE only – on
* Russian Fire Approved as standard. Glass label (3) reqd. 3*
BGI/W or PBI/W choose C & D.
† Not suitable for use in China on fire Duty label reqd. 4* ** Must be selected when selecting CSA
alarm systems
Tag label reqd. 5* certification.

* Specify wording on 3, 4 or 5 as required.

Switches Code Terminals Code


Single changeover S 6 x 2.5mm2 (standard) 6*
Double changeover D 7 x 2.5mm2 (standard) 7
9 x 2.5mm2 (optional) 9
* BGUL only availablewith six terminals.

All the above specifications, dimensions, weights and tolerances are nominal (typical) and Cooper MEDC reserve the right to vary all data without prior notice. No liability is accepted for any consequence of use.

01/13