627081 FDC71VNP-W
3/8" (9.52) 1/2" (12.5) - 10 R32 1.30 5 60 1.60
3/8" (9.52) 5/8" (15.88) - 10 R32 1.30 5 60 1.60
1/4" (6.25) 5/8" (15.88) - 30 R32 1.70 15 20 2.00
- FDC90VNP-W 3/8" (9.52) 1/2" (12.5) - 12 R32 1.70 6 60 2.06
3/8" (9.52) 5/8" (15.88) - 12 R32 1.70 6 60 2.06
1/4" (6.25) 5/8" (15.88) - 30 R32 1.70 15 20 2.00
627105 FDC100VNP-W 3/8" (9.52) 1/2" (12.5) - 12 R32 1.70 6 60 2.06
3/8" (9.52) 5/8" (15.88) - 12 R32 1.70 6 60 2.06
3/8" (9.52) 5/8" (15.88) - 50 R32 3.30 30 54 4.38
3/8" (9.52) 3/4" (19.05) - 50 R32 3.30 30 54 4.38
628071 FDC100VNA-W
1/2" (12.5) 5/8" (15.88) - 25 R32 3.30 15 110 4.95
1/2" (12.5) 3/4" (19.05) - 25 R32 3.30 15 110 4.95
3/8" (9.52) 5/8" (15.88) - 50 R32 3.30 30 54 4.38
3/8" (9.52) 3/4" (19.05) - 50 R32 3.30 30 54 4.38
628087 FDC100VSA-W
1/2" (12.5) 5/8" (15.88) - 25 R32 3.30 15 110 4.95
1/2" (12.5) 3/4" (19.05) - 25 R32 3.30 15 110 4.95
3/8" (9.52) 5/8" (15.88) - 50 R32 3.30 30 54 4.38
3/8" (9.52) 3/4" (19.05) - 50 R32 3.30 30 54 4.38
628104 FDC125VNA-W
1/2" (12.5) 5/8" (15.88) - 25 R32 3.30 15 110 4.95
1/2" (12.5) 3/4" (19.05) - 25 R32 3.30 15 110 4.95
3/8" (9.52) 5/8" (15.88) - 50 R32 3.30 30 54 4.38
PAC MICRO INVERTER
628205 FDC100VNX 3/8" (9.52) 3/4" (19.05) 3(1) 100 R410a 4.50 30 60 8.70
1/2" (12.5) 5/8" (15.88) 3(1) 50 R410a 4.50 15 80 7.30
1/2" (12.5) 3/4" (19.05) 3(1) 50 R410a 4.50 15 80 7.30
3/8" (9.52) 5/8" (15.88) 3(1) 100 R410a 4.50 30 60 8.70
1/4" (6.25) 5/8" (15.88) 3(1) 20 R410a 4.50 10 20 4.70
628210 FDC100VSX 3/8" (9.52) 3/4" (19.05) 3(1) 100 R410a 4.50 30 60 8.70
(1)
1/2" (12.5) 5/8" (15.88) 3 50 R410a 4.50 15 80 7.30
1/2" (12.5) 3/4" (19.05) 3(1) 50 R410a 4.50 15 80 7.30
3/8" (9.52) 5/8" (15.88) 3(1) 100 R410a 4.50 30 60 8.70
(1)
1/4" (6.25) 5/8" (15.88) 3 20 R410a 4.50 10 20 4.70
628185 FDC125VNX 3/8" (9.52) 3/4" (19.05) 3(1) 100 R410a 4.50 30 60 8.70
1/2" (12.5) 5/8" (15.88) 3(1) 50 R410a 4.50 15 80 7.30
1/2" (12.5) 3/4" (19.05) 3(1) 50 R410a 4.50 15 80 7.30
(1)
3/8" (9.52) 5/8" (15.88) 3 100 R410a 4.50 30 60 8.70
(1)
1/4" (6.25) 5/8" (15.88) 3 20 R410a 4.50 10 20 4.70
628190 FDC125VSX 3/8" (9.52) 3/4" (19.05) 3(1) 100 R410a 4.50 30 60 8.70
1/2" (12.5) 5/8" (15.88) 3(1) 50 R410a 4.50 15 80 7.30
1/2" (12.5) 3/4" (19.05) 3(1) 50 R410a 4.50 15 80 7.30
3/8" (9.52) 5/8" (15.88) 3(1) 100 R410a 4.50 30 60 8.70
(1)
1/4" (6.25) 5/8" (15.88) 3 20 R410a 4.50 10 20 4.70
628195 FDC140VNX 3/8" (9.52) 3/4" (19.05) 3(1) 100 R410a 4.50 30 60 8.70
1/2" (12.5) 5/8" (15.88) 3(1) 50 R410a 4.50 15 80 7.30
(1)
1/2" (12.5) 3/4" (19.05) 3 50 R410a 4.50 15 80 7.30
3/8" (9.52) 5/8" (15.88) 3(1) 100 R410a 4.50 30 60 8.70
(1)
1/4" (6.25) 5/8" (15.88) 3 20 R410a 4.50 10 20 4.70
628200 FDC140VSX 3/8" (9.52) 3/4" (19.05) 3(1) 100 R410a 4.50 30 60 8.70
1/2" (12.5) 5/8" (15.88) 3(1) 50 R410a 4.50 15 80 7.30
1/2" (12.5) 3/4" (19.05) 3(1) 50 R410a 4.50 15 80 7.30
(1)
When the one way pipe run is less than 3m remove 1kg of refrigerant from the system.
(2)
When FDC71VNP is connected to an FDF71 the precharged length is 8m and the maximum pipe run drops to 23m
(3)
When FDC90VNP is connected to an FDF100 the precharged length is 8m and the maximum pipe run drops to 23m