You are on page 1of 5

DC Fail-Over Option for

AIRSYS HVAC Systems


Interconnect Guidelines

ASPCB.2 DC Fail-Over Option


For AIRSYS HVAC Systems
from the global leader in ICT cooling
AIRSYS Refrigeration Engineering

AIRSYS Model #
ASPCB.2
DC Fail-Over
Option

AIRSYS Model #
ASLLC.2
Lead/Lag Controller

DC Fail-Over Option for AIRSYS HVAC Systems


❖ Provides DC powered cooling/ventilation during Prime Power Outage
❖ DC plant load ≤ 1 kW
❖ Virtually no loss of efficiency during normal operation
❖ Works in conjunction with ASLLC.2 controller to run supply fans only
❖ Great for sites without back-up AC
❖ Great insurance for sites that experience generator failure
DC Fail-Over Option for
AIRSYS HVAC Systems
Interconnect Guidelines

24 or 48 VDC
Input
230 VAC
Single Phase
Input (x2)

ASPCB.2

230 VAC
Output (x3)

AIRSYS Model #
ASPCB.2
DC Fail-Over
Option

TECHNICAL SPECIFICATIONS
Model Inverter Box Model (1) ASPCB.2.24 (1) ASPCB.2.48
Capacity Product No. 2040305060 2040306840
DC Voltage Input V 24Vdc 48Vdc
Normal DC Max. Power Input W 0 0
Operation AC Voltage Input V 230Vac±10% 230Vac±10%
AC Max. Current Input A 60A 60A
DC voltage Input V 24Vdc 48Vdc
DC Fail-Over DC Max. Power Input W 1,000 1,000
Operation AC Voltage Output V 230Vac±10% 230Vac±10%
AC Max. Power Output W 900 900
Width in 18.50 18.50
Depth in 5.90 5.90
Dimensions & Weight
Height in 24.90 24.90
Weight lbs 55 55
Note:
Note: Compatiblewith
(1) Compatible to HVAC
HVACmodel
model#:Numbers:
3E1C1, 5E1C1, 7E1C2,
8E1C2, 9E1C2(8E1C2),
13E1C3 & 10E1D3. 13E1C3 & 10E1D3.
DC Fail-Over Option for
AIRSYS HVAC Systems
Interconnect Guidelines

HVAC #2 from HVAC #1 from prime


prime power panel power panel
L2’ L1’ L2 L1

+24V supply/ +24V return/


- 48V return - 48V supply

Please verify L1 is the


same phase as L1’, and L2
is the same phase as L2’:
1. Voltage between L1’ and
L1 should be ~0Vac
2. Voltage between L1’ and
L2 should be ~230Vac

To HVAC #2 To HVAC #1
input power input power
DC Fail-Over Option for
AIRSYS HVAC Systems
Interconnect Guidelines

ASPCB.2 Interconnect List


Signal Name FROM TO Comments

INPUTS
Positive QF1 + 40 Amps Max for 24
DC Input DC Power Plant Terminal VDC
Power Breaker Negative QF1 - 20 Amps Max for 48
Terminal VDC
Prime Power Panel L1 ASPCB.2 Dc
HVAC1 Input 40 Amps 230
Dual Pole breaker (40 Fail-Over QF3
Power L2 VAC/1p/60Hz
Amp)
HVAC2 Input Prime Power Panel L1
40 Amps 230
Power Dual Pole breaker (40 L2 QF2
VAC/1p/60Hz
Amp)
OUTPUTS
Term block Term
Form C Contact
Prime Power #60 block #60
Default = Normally
Lost Signal Term Block Term
Open
#5 ASLLC.2 Block #5
Term Block Controller L1
ASLLC.2 Input L7 (L1) 0.5 Amp
Power Term Block L2 230 VAC/1p/60Hz
N7 (L2)
ASPCB.2 DC Fail-Over
Term Block L1
HVAC 1 Input 4L1 32 Amps
HVAC 1
Power Term Block L2 230 VAC/1p/60Hz
4L2
Term Block L1’
HVAC 2 Input 4L1’ 32 Amps
HVAC 2
Power Term Block L2’ 230 VAC/1p/60Hz
4L2’
DC Fail-Over Option for
AIRSYS HVAC Systems
Interconnect Guidelines

1 4
1
2 5

Main
Components 9
of ASPCB.2

Item Name Description


Auxiliary
1 Control signal transit
Relay(KA4,KA5,KA6)
2 DC Breaker (QF1) Used for control the DC power input, Maximum current ampere 50A
3 Inverter For inverter 24/48 Vdc to 220Vac;
4 Auxiliary Relay (KA1,KA2) Control signal transit
5 Time relay (KT1&KT2) Used for control the inverter work when prime power goes off. (default: 30s delay)
6 AC Breaker (QF2&QF3) Used for control the prime power input, Maximum current ampere 32A
7 AC contactor (KM1&KM2) Maximum current ampere 32A
8 AC contactor (KM3) Maximum current ampere 9A
9 Terminal Block Used for connecting to HVAC1, HVAC2 and ASLLC.2