Sprinkler System Alarm Testers

Each separate sprinkler system must be equipped with a separate waterflow alarm. In a high rise building, the system for each floor
must be separately alarmed. Where pressure reducing valves are used, a dual alarm and drain piping arrangement is required. The
alarm testers listed below combine test and drain valves, a waterflow sight glass, and a calibrated flow orifice in a single assembly to
simplify the piping required for such arrangements.

Model TD-2

Product Specification

Nominal Pipe Size Rated Working Pressure


Model No K-Factor Remarks
in (mm) psi (kPa)
TD-2 1 1/4 (32) 2.8 300 (2070) a, b
TD-2 2 (50) 4.2 300 (2070) a, b

Remarks:
a. Devices supplied with male NPT threaded inlet and female NPT threaded outlet end connections.
b. Devices contain integral pressure relief valve which is field adjustable from 100 to 310 psi.

Company Name: Tyco Fire & Building Products


Company Address: 1467 Elmwood Ave, Cranston, Rhode Island 02910, USA
Company Website: http://tyco-fire.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved
Class of Work: 1625-Branch Line Testers