Panel PB1 - MAIN PANELBOARD OWNER : SATUR M.

CADENAS Rev# Date


System THREE (3) PHASE SYSTEM-400V COMPANY: PRIVATE Rev-1 8/9/2023
REVISIONS TRANSFORMER DETAILS
Fed From ANECO COMMONAL TRANSFORMER ADRESS : BRGY.10 CABADBARAN CITY AGUSAN DEL NORTE

Location BUILDING TYPE: COMMERCIAL


LIGHTING #SWITCH # C.O VOLT AMPERE LOAD
OVER CURRENT
PROTECTION
CONDUCTORS mm², Cu-B/W CONDUIT SPEC VOLTAGE DROP COMPUTATION TOTAL LOAD DF. KVA 33.5
OUTLET

DEMAND FACTOR
SPECIAL OUTLET

CKT- RUN (mtrs)


CIRCUIT
LOAD DESCRIPTION VA PRIMARY VOLTAGE L-L 415

1 GANG

2GANG

3GANG

2GANG
TOTAL
NO.

3WAY
(V) ØAB ØBC ØCA 3Ø AT AF P KAIC SIZE TYPE Ώ/305m SIZE (Φ) TYPE GRD WIRE TYPE VD %VD REMARKS

TRANSFORMER IMPEDANCE 5%
C1 BONE SAW MACHINE 1 90 2238.0 400 5.6 40 50 3 10 4w-#5.50 THHN 1.29 20mm PVC/IMC 1w-#3.50 THHN 4.26 1.85 SAFE

C2 AIR BLOWER 1 95 2163.0 400 5.4 40 50 3 10 4w-#5.50 THHN 1.29 20mm PVC/IMC 1w-#3.50 THHN 4.35 1.89 SAFE
SIZE OF TRANSFORMER 150KVA OR 3- 50 KVA
C3 ACU 1 60 4998.0 400 12.5 40 50 3 10 4w-#5.50 THHN 0.809 20mm PVC/IMC 1w-#3.50 THHN 3.98 1.73 SAFE

C4 ACU 1 60 4998.0 400 12.5 40 50 3 10 4w-#5.50 THHN 0.809 20mm PVC/IMC 1w-#3.50 THHN 3.98 1.73 SAFE

C5 MEAT GRINDER 1 75 746.0 230 3.24 40 50 1 10 2w-#5.50 THHN 1.29 20mm PVC/IMC 1w-#3.50 THHN 2.06 0.89 SAFE
TRANSFORMER CONNECTION Y-Y
C6 MEAT CHILLER 1 72 746.0 230 3.24 40 50 1 10 2w-#5.50 THHN 1.29 20mm PVC/IMC 1w-#3.50 THHN 1.98 0.86 SAFE

C7 FOOD HEATER 1 71 1342.0 230 5.83 30 50 1 10 2w-#5.50 THHN 1.29 20mm PVC/IMC 1w-#3.50 THHN 3.50 1.52 SAFE TRANSFORMER EFFECIENCY @ FULL LOAD 98.36%
C8 FOOD HEATER 1 83 1342.0 230 5.83 30 50 1 10 2w-#5.50 THHN 1.29 20mm PVC/IMC 1w-#3.50 THHN 4.10 1.78 SAFE
80%
C9 LIGHTING OUTLET 43 130 645.0 230 2.8043 20 50 1 10 2w-#3.50 THHN 2.05 20mm PVC/IMC 1w-#2.00 THHN 4.90 2.13 SAFE
TRANSFORMER EFFECIENCY @ 1/4 LOAD 97.24%
C10 LIGHTING OUTLET 42 120 630.0 230 2.7391 20 50 1 10 2w-#3.50 THHN 2.05 20mm PVC/IMC 1w-#2.00 THHN 4.42 1.92 SAFE

C11 LIGHTING OUTLET 10 120 400.0 230 1.74 20 50 1 10 2w-#3.50 THHN 2.05 20mm PVC/IMC 1w-#2.00 THHN 2.81 1.22 SAFE
PRIMARY AND
C12 POWER OUTLET 6 45 2160.0 230 9.3913 30 50 1 10 2w-#3.50 THHN 2.05 20mm PVC/IMC 1w-#2.00 THHN 5.68 2.47 SAFE PROVIDE PROTECTION ON TRANSFORMER
C13 POWER OUTLET 6 43 2160.0 230 9.4 30 50 1 10 2w-#3.50 THHN 2.05 20mm PVC/IMC 1w-#2.00 THHN 5.43 2.36 SAFE
SECONDARY SIDE
C14 ICE CREAM FREEZER 1 25 746.0 230 3.2 30 50 1 10 2w-#3.50 THHN 2.05 20mm PVC/IMC 1w-#2.00 THHN 1.09 0.47 SAFE
TYPE OF PROTECTION ON ON PRIMARY AND CIRCUIT
C15 ICE CREAM FREEZER 1 23 746.0 230 3.2 30 50 1 10 2w-#3.50 THHN 2.05 20mm PVC/IMC 1w-#2.00 THHN 1.00 0.44 SAFE FUSE
C16 ICE CREAM FREEZER 1 21 746.0 230 3.2 30 50 1 10 2w-#3.50 THHN 2.05 20mm PVC/IMC 1w-#2.00 THHN 0.92 0.40 SAFE
SECONDARY SIDE BREAKER
TOTAL 95 12 30 0.8 26,806 230 19.9 14.9 19.1 36.0 250 250 3 10 4W -#80.00 THHN 0.0797 65mm PVC/IMC 1x5.50 THHN 1.41 0.61 SAFE
RESULTS
Item # Computations PEC -Gen. Reference provisions Main : 250AT/250AF/3POLE3-PHASE ACB
Feeder Size Computations: PEC2017, Part#1, Art. 2.15, Section 2.15.1.2 (a) p50 Connected Load: 26,806.0
Wire Line Ampacity Size = [(1.732x36)+(19)x(0.80DF)+12.5] Demand Load Factor - 80% Demand Factor : 80%
1
Wire Ampacity= 90.05A Diversity Factor - 1
230V
TRANSFORMER VOLTAGE/ CURRENT
Load Growth Factor - 20% in 15 years Volts :
Therefore as per ampacity above use: 4W-80MM2 THHN Cu. STRANDED PEC2017,Part#1, Table B-3.10.2.6 (B)(16) p.174
2
PEC2017 Table 10.1.1.8 Conductor Properties p.941 Main Kaic : 10KAIC PRIMARY LINE VOLTAGE (L-L) 415 VOLT
3 25mm dia. RSC Conduit Pipe PEC2017,Part#1, Appendix C- Table C1p976/C9p1023/C10 p1031

4
Voltage Drop Sample Computation for Service Entrance
Voltage Drop = (200% x 30 /305) x (0.0797) x 90.05
PEC2017 Table 10.1.1.8 Conductor Properties p.941 Branch KAIC : 10kAIC PRIMARY PHASE VOLTAGE (L-P) 240 VOLT
Voltage Drop Volts : 1.41V Amperes : 75.76A

5
Short Circuit Analysis and Computations (Ohmic Method -NEC)
Short Circuit Current at Main ACB= 10 KAIC
Service Entrance 4w-#80.00mmsq THHN Copper + 14.00mmsq THHN Grounding PRIMARY LINE CURRENT 211 AMP
Breaker Ampacity Size: PEC2017, Part#1, Table 4.30.4.2 p174 Mounting : Wall Mounted
6 16-BRANCH, SIDE-MAIN
Breaker Ampacity Size= I (Wire )+125% Largest Load Current= 90.05A +(125%) 12.5A =105.65A
Breaker Ampacity Used= 250 AT/250AF
Enclosure :
PLUG-IN/BOLT-ON W/ GRD STRIP, NEMA-1 PRIMARY PHASE CURRENT 211 AMP
Genset Computation : USE GENSET: 150KVA/120KW, THREE PHASE ,400V, 60HZ
Pkw= ((90.05*400*1.732)/1000))*0.80DF USE MAIN= 2-14MM2 THHN & 1- 5.50 THHN (GW) IN A 25MMΦ RSC PIPE
7 Pkw= 49.90KW MAIN= 250AT/250AF, 400V,3P,10KAIC SECONDARY LINE VOLTAGE 230 VOLT
Pkva= 41.98KW/0.80DF
Pkva= 62.38KVA
SECONDARY PHASE VOLTAGE 133 VOLT
LOAD CONDUCTOR AMPACITY ANALYSIS
PROTECTION WIRE AMPACITY LOAD CURRENT SECONDARY PHASE CURRENT 376 AMP
SECTION CONDUCTOR USE MM2 REMARKS
RATING (A) (A) SECONDARY LINE CURRENT 376 AMP
C1 40 4-5.50MM² (10AWG) THHN WIRE 40 5.6 SAFE
SIZE OF CIRCUIT BREAKER AS PER (NEC 450.3 )
C2 40 4-5.50MM² (10AWG) THHN WIRE 40 5.4 SAFE
SIZE OF CIRCUIT BREAKER ON PRIMARY SIDE 500 AMP
C3 40 4-5.50MM² (10AWG) THHN WIRE 40 12.5 SAFE
C4 40 4-5.50MM² (10AWG) THHN WIRE 40 12.5 SAFE SIZE OF FUSE ON PRIMARY SIDE 500 AMP

C5 30 2-5.50MM² (10AWG) THHN WIRE 40 3.24 SAFE SIZE OF CIRCUIT BREAKER ON SECONDARY SIDE 450 AMP
C6 30 2-5.50MM² (10AWG) THHN WIRE 40 3.24 SAFE SIZE OF FUSE ON SECONDARY SIDE 450 AMP
C7 20 2-5.50MM² (10AWG) THHN WIRE 40 5.83 SAFE
TRANSFORMER LOSSES
C8 20 2-5.50MM² (10AWG) THHN WIRE 40 5.83 SAFE
TOTAL LOSSES AT FULL LOAD 1420 WATT
C9 20 2-3.50MM² (12AWG) THHN WIRE 40 2.80 SAFE
C10 20 2-3.50MM² (12AWG) THHN WIRE SAFE TOTAL LOSSES AT 1/4 FULL LOAD 590 WATT
40 2.74
C11 30 2-3.50MM² (12AWG) THHN WIRE 30 1.74 SAFE FULL LOAD COPPER LOSS 833 WATT
C12 30 2-3.50MM² (12AWG) THHN WIRE 30 9.39 SAFE CORE LOSS 522 WATT
C13 30 2-3.50MM² (12AWG) THHN WIRE 30 9.4 SAFE
C14 30 2-3.50MM² (12AWG) THHN WIRE 30 3.2 SAFE
C15 30 2-3.50MM² (12AWG) THHN WIRE 30 3.2 SAFE
C16 30 2-3.50MM² (12AWG) THHN WIRE 30 3.2 SAFE
MAIN 250 4-80.00MM² (3/0AWG) THHN WIRE 285 89.8 SAFE

FROM THE OFFICE OF: NO. SEAL PROJECT TITLE APPROVED PER PLAN AND SPECIFICATIONS CAD BY: SHEET CONTENT: SHEET NO
PRC REG. SCHEDULE OF LOADS
CONNECTED LOAD AMPACITY
VALIDITY TRANSFORMER DETAILS

PTR
NO. AS BUILT PLAN FOR VROSS CORPORATION SATUR M. CADENAS E
PROFESSIONAL ELECTRICAL ENGINEER DATE
OWNER 36
PLACE
TN
NO. LOCATION:BRGY.10,CABADBARAN CITY AGUSAN DEL NORTE ADDRESS: BRGY.10,CABADBARAN CITY AGUSAN DEL NORTE