Professional Documents
Culture Documents
0%$3((,,(()HOORZ$3(&(QJLQHHU
$6($1&KDUWHUHG3URI(QJLQHHU
3RZHU6\VWHP0RGHOLQJDQG
)DXOW$QDO\VLV
8SGDWHG± )HEUXDU\
4
Various types
of current
6
Ground-fault current consists of any current
which flows outside the normal circuit path.
Ground-fault current flows in the equipment
grounding conductor for low-voltage systems.
In medium- and high-voltage systems,
ground-fault current may return to the
source through the earth.
Ground-fault current on low-voltage systems
may be classified as leakage, bolted, or
arcing.
Induction
Motor
Synchronous
Motor
9
10
“Symmetrical" and “Asymmetrical” are terms
used to describe the symmetry of the short-
circuit current waveform around the zero axis.
If a short-circuit occurs in an inductive reactive
circuit at the peak of the voltage waveform, the
resulting short-circuit current will be totally
symmetrical.
If a short-circuit, in the same circuit, occurs at
the zero of the voltage waveform, the resulting
short-circuit current will be totally
asymmetrical.
11
13
14
Advantages of Using Per Unit Calculations
15
16
Advantages of Using Per Unit
Calculations (cont’d):
17
18
Choose any two of the electrical parameters. In
general, the base Volt-Amperes and base Voltage
are chosen.
Note: The base MVA or kVA will also serve as base for
true/real power and reactive power. The base Z will
also be used as base for resistance and reactance.
19
20
21
22
23
4XDQWLWLHVLQSHUFHQWDUHSHUXQLW㽢
24
25
26
27
28
29
kVA/hp hp rating
30
31
32
The power system data are as follows:
Generator : 25MVA, 13.8kV, x = 0.125pu
T1 : 30MVA, 13.2kV-69kV, x = 0.105pu
Line : Z = 2 + j4 ohms
T2 : 20MVA, 34.5kV-69kV, x = 0.05pu
Load : Static load of 10+j15 MVA @ 34.5kV
33
Solution:
Generator:
Transformer T1:
35
Transmission Line:
: : ܤ
ݑ ଶ : ଶ
ܤ ܤ ܤ
ܤ
ܮ ଶ
Transformer T2:
ଶ
The Per Unit Apparent Power of the Load:
VL = 34.5/36.0682 = 0.9565 pu
, 3 SX
(J 4 MSX
SX
Draw the impedance diagram for the power system shown below. Mark all
points and all the impedances in per unit. Neglect resistance, and use a base
of 138 kV in Line 1 and 50 MVA base. The ratings of the generators, motors,
and transformers are as follow:
Generator 1: 20,000 kVA, 13.2 kV, X" = 15%
Generator 2: 20,000 kVA, 13.2 kV, X" = 15%
Synchronous motor 3: 30,000 kVA, 6.9 kV, X" = 20%
T1, T3: 20,000 kVA, 13.8Y - 138Y kV, X = 10%
T2, T4: 20,000 kVA, 13.8Y - 132Y kV, X = 10%
T5, T6: 15,000 kVA, 6.9¨-138Y kV, X = 10% =RQH
=RQH =RQH
=RQH =RQH
=RQH
38
Identifying the base values: T1: X=0.10[138/138]2[50/20]
MVAB = 50MVA =0.250 pu
kV bases: T3: X=0.10[138/138]2[50/20]
Zone 1: kVB=138kV =0.250 pu
Zone 2: kVB=138[13.8/138]=13.8kV T2: X=0.10[13.8/13.8]2[50/20]
Zone 3: kVB=138[13.8/138]=13.8kV =0.250 pu
Zone 4: kVB=13.8[132/13.8]=132kV T4: X=0.10[132/132]2[50/20]
Zone 5: kVB=13.8[132/13.8]=132kV =0.250 pu
Zone 6: kVB=132[6.9/138]=6.6kV T5: X=0.10[138/132]2[50/15]
=0.3643 pu
Computing for the new PU impedances: T6: X=0.10[138/132]2[50/15]
G1: X”=0.15[13.2/13.8]2[50/20] =0.3643 pu
=0.3431 pu SM3: X”=0.20[6.9/6.6]2[50/30]
G2: X”=0.15[13.2/13.8]2[50/20] =0.3463 pu
=0.3431 pu
39
Line 1: ZL1=(6+j40)[50]/[138]2
=0.0158+j0.1050 pu
Line 2: ZL2=(3+j20)[50]/[132]2
=0.0861+j0.574 pu
Line 3: ZL3=(3+j20)[50]/[132]2
=0.0861+j0.574 pu
Impedance diagram:
40
41
42
In dealing with normal or near normal operation of
power systems, the slight unbalances are ignored
and therefore, balanced operation is assumed, i.e.,
balanced loads, balanced generator outputs, and
balanced line/transformer parameters
43
Phasor Rotation
Counter clockwise
direction by
international
convention
Phase Sequence
The order in which
phasors pass a fixed
point
44
=V
=V
=V
45
46
=
=)
=
%DODQFHG %DODQFHG
6RXUFH /RDG
47
48
Alternative solution methods
Symmetrical components
Alpha, beta, zero components (popularized by
Edith Clarke of General Electric)
Positive-plus-negative, positive-minus-negative,
zero components
Only the method of symmetrical components will be
discussed in this material
49
50
Positive-sequence components consisting of
three phasors equal in magnitude displaced
from each other by 120° in phase and having
the same sequence as the original phasors
Negative-sequence components consisting of
three phasors equal in magnitude, displaced
from each other by 120° in phase and having
a phase sequence opposite that of the
original phasors
51
52
3RVLWLYH6HTXHQFH 1HJDWLYH6HTXHQFH
=HUR6HTXHQFH 8QEDODQFHG3KDVRUV
53
Definition:
The operator a is a phasor with a magnitude
equal to unity with an angle of 120°, i.e.,
a=1/120°
Function:
Any phasor that is
multiplied by the
operator a is rotated
counterclockwise by
120㼻. This is shown
by the phasor diagram
on the right:
54
Equalities of Operator a
55
56
(T䇻QD
(T䇻QD
(T䇻QD
57
0DNLQJWKHFRHIILFLHQWVRIVa1
DQGVa2 LQ(TXDWLRQVDDQG
DHTXDOWRWRVROYHIRUVa1
DQGVa2UHVSHFWLYHO\LQWHUPV
RIVaVbDQGVc ZLOO\LHOG
7KXV
58
7KHV\PPHWULFDOFRPSRQHQWVRIWKHFXUUHQWVLQWHUPVRIWKH
XQEDODQFHGFXUUHQWV
59
In summary:
60
In summary (matrix form):
61
62
Sequence Impedances
63
Definition:
Positive-sequence
impedance (Z1)
Negative-sequence
impedance (Z2)
Zero-sequence
impedance (Z0)
Sequence impedances of most power system components, i.e.,
rotating machines, transformers, etc., except transmission/
distribution lines, are generally expressed in percent or per unit
based on equipment ratings
64
65
66
67
68
69
70
71
72
73
¾Positive-sequence impedance
Xd = direct-axis synchronous reactance
X͛d = direct-axis transient reactance
X͟d = direct-axis subtransient reactance
ΎŶĂůLJƐŝƐŽĨ&ĂƵůƚĞĚWŽǁĞƌ^LJƐƚĞŵ 75
Ͳ W͘D͘ŶĚĞƌƐŽŶ
Subtransient X” (pu)
76
77
78
dŚĞnjĞƌŽͲƐĞƋƵĞŶĐĞƌĞƚƵƌŶĞĚĨůƵdžŝŶĂĨŝǀĞͲůĞŐŐĞĚĐŽƌĞͲ ĂŶĚƐŚĞůůͲƚLJƉĞƚƌĂŶƐĨŽƌŵĞƌŝƐϭ͘ϱ
ƚŝŵĞƐƚŚĞĨůƵdžĨůŽǁŝŶŐĂƚĞĂĐŚůĞŐƚŚĞǁŝŶĚŝŶŐŝƐǁŽƵŶĚĂƌŽƵŶĚ͘ƐĂƌĞƐƵůƚ͕ĂƐƐƵŵŝŶŐ
ƚŚĂƚƚŚĞƌĞƚƵƌŶƉĂƚŚŽĨƚŚĞnjĞƌŽͲƐĞƋƵĞŶĐĞĨůƵdžŝŶƚŚĞƚƌĂŶƐĨŽƌŵĞƌŵĂŐŶĞƚŝĐĐŽƌĞƌĞŵĂŝŶƐ
ŝŶƚŚĞůŝŶĞĂƌĂƌĞĂĂŶĚĚŽĞƐŶŽƚƐĂƚƵƌĂƚĞ͕ŝƚŝƐĞdžƉĞĐƚĞĚƚŚĂƚƚŚĞŵĂŐŶĞƚŝĐŝŵƉĞĚĂŶĐĞ
ĂƉƉƌŽdžŝŵĂƚĞůLJĞƋƵĂůƐƚŚĞƉŽƐŝƚŝǀĞŽƌŶĞŐĂƚŝǀĞƐĞƋƵĞŶĐĞŵĂŐŶĞƚŝĐŝŵƉĞĚĂŶĐĞ͘
¾ Thus, for three-phase shell type transformers, the zero-sequence
reactance is equal to the positive-sequence reactance. The same is
true for and single-phase transformers.
79
dŚĞŵĂŐŶĞƚŝĐƌĞůƵĐƚĂŶĐĞĨŽƌnjĞƌŽͲƐĞƋƵĞŶĐĞĨůƵdžŝƐƌĞůĂƚŝǀĞůLJŚŝŐŚĂŶĚĚĞƉĞŶĚĞŶƚŽŶƚŚĞ
ƚƌĂŶƐĨŽƌŵĞƌΖƐƉŚLJƐŝĐĂůƐƚƌƵĐƚƵƌĞĂŶĚƚŚĞƚLJƉĞƌĂƚŚĞƌƚŚĂŶŽŶƚŚĞƚLJƉĞĂŶĚƐƚƌƵĐƚƵƌĞŽĨ
ƚŚĞŵĂŐŶĞƚŝĐĐŽƌĞ͘dŚĞƌĞĨŽƌĞ͕ƚŚĞŵĂŐŶĞƚŝĐŝŵƉĞĚĂŶĐĞ͕ǁŚŝĐŚŝƐŝŶǀĞƌƐĞůLJƉƌŽƉŽƌƚŝŽŶĂů
ƚŽƚŚĞŵĂŐŶĞƚŝĐƌĞůƵĐƚĂŶĐĞ͕ŝƐǀĞƌLJůŽǁ͘
¾ Hence, the zero-sequence reactance of the three-phase core-type
transformers is smaller than the positive-sequence reactance due to
the leakage of zero-sequence flux to the transformer tank during
ground faults.
80
81
Ύ:͘W͘dƌĂŶƐĨŽƌŵĞƌ,ĂŶĚŬ
82
83
84
Where:
ra = A-C resistance of the conductor at
specified frequency
GMR = Geometric Mean Radius of the conductor
GMD = equivalent symmetrical spacing
= (DABDBCDCA)1/3
85
d Bundle of Four
d d
య
ܾܴܯܩൌ ܴܯܩൈ ݀ d ܾܴܯܩൌ ܴܯܩൈ ݀ʹ
ర
ܾܴܯܩൌ ͳǤͲͻ ܴܯܩൈ ݀͵
ܽ
ܽ ܾ
87
a c' a a'
b b' b b'
c a' c c'
Low-reactance Super-bundle
Configuration Configuration
88
¾ The zero-sequence impedance of
transmission lines is of higher value than
the positive-sequence impedance due to
the fact that the zero-sequence current
must return through the earth, or via the
earth and ground wires, if there are any.
89
90
Where:
ܽ :
݀ ݁ݍ :
݁ ݁ :
య
݁ݍ ܾܽ ܾܿ ܿܽ
݁
91
93
where:
94
One Ground Wire (with earth return)
95
Transmission Lines
96
Transmission Lines
97
98
Electro-dynamic forces due to abnormally large
currents resulting in
deformation of the bus-bars
disconnection of cables
excessive temperature with the risk of damage to
insulation
Electromagnetic interference with conductors in the
vicinity (disturbance to communication lines,
personal danger)
Mechanical and thermal stress, resulting in damage
of equipment
¾ Equipment containing insulating oil may explode during short circuits
and may cause fire resulting in serious hazard to personnel and to
other equipment
99
100
1. The determination of the required
mechanical strength of electrical
equipment to withstand the stresses
brought about by the flow of high short
circuit currents
2. The selection of circuit breakers and
switch ratings
3. The selection of protective relay and fuse
ratings
101
102
8. The sizing of series reactors to limit the
short circuit current to a desired value
9. To determine the short circuit capability of
series capacitors used in series
compensation of long transmission lines
10. To determine the size of grounding
transformers, resistances, or reactors
103
104
¾Factors Affecting Fault
Circuit configuration
Grounding system design/methods
Voltage class
Relative insulation levels to ground and
between phases
System characteristics
105
106
Single line-to-ground faults
Double line-to-ground faults
Line-to-line faults
Three-phase faults
107
108
Single line-to-ground and one-line open
Double line-to-ground and one-line open
faults
Line-to-line and one-line open faults
Three-phase and one-line open faults
109
111
Sequence Networks
112
The fault point of a system is that point
to which the unbalanced connection is
attached to an otherwise balanced
system.
113
114
For determining the
maximum short circuit
current:
115
116
Note: The leakage impedances must first be converted into per unit
using the appropriate base values of voltage and kVA/MVA
117
118
119
Where:
121
122
123
Solidly-Grounded Neutral
124
Impedance-Grounded Neutral
125
126
Transformer Zero-Sequence
Connection Circuit Equivalent
127
Transformer Zero-Sequence
Connection Circuit Equivalent
128
Transformer Zero-Sequence
Connection Circuit Equivalent
129
(Credits to Engr. Antonio C. Coronel, Retired VP, Meralco and former Member, Board of Electrical Engineering)
P Q
*URXQGHGZ\H± *URXQGHGZ\H
S1 = 1
S2 = 1
S3 = 0
S4 = 0
P Q
131
(Credits to Engr. Antonio C. Coronel, Retired VP, Meralco and former Member, Board of Electrical Engineering)
*URXQGHGZ\H± 8QJURXQGHGZ\H
S1 = 1
S2 = 0
S3 = 0
S4 = 0
P Q
132
(Credits to Engr. Antonio C. Coronel, Retired VP, Meralco and former Member, Board of Electrical Engineering)
*URXQGHGZ\H± 'HOWD
S1 = 1
S2 = 0
S3 = 0
S4 = 1
P Q
133
(Credits to Engr. Antonio C. Coronel, Retired VP, Meralco and former Member, Board of Electrical Engineering)
'HOWD± 'HOWD
S1 = 0
S2 = 0
S3 = 1
S4 = 1
P Q
134
The zero-sequence network model for a
transmission line is the same as that of the
positive- and negative-sequence networks.
The sequence impedance of the model is of
course the zero-sequence impedance of the
line. This is normally higher than the
positive- and negative-sequence impedances
because of the influence of the earth͛s
resistivity and the ground wire/s.
135
136
137
Boundary conditions:
(T䇻Q
(T䇻Q
138
139
140
Where:
= fault impedance
= Thevenin䇻s equivalent positive-sequence
impedance as seen from the fault point
= Thevenin䇻s equivalent pre-fault voltage as
seen from the fault point
141
142
143
144
Derivation of Sequence Network
Interconnections
Boundary conditions:
145
146
Where:
7KHYHQLQ䇻VHTXLYDOHQWSUH
IDXOWYROWDJHDVVHHQIURPWKH
IDXOWSRLQW
7KHYHQLQ䇻VHTXLYDOHQW]HUR
VHTXHQFHLPSHGDQFHVHHQIURP
WKHIDXOWSRLQW
7KHYHQLQ䇻VHTXLYDOHQW
SRVLWLYHVHTXHQFHLPSHGDQFH
VHHQIURPWKHIDXOWSRLQW
7KHYHQLQ䇻VHTXLYDOHQW
QHJDWLYHVHTXHQFHLPSHGDQFH
VHHQIURPWKHIDXOWSRLQW
IDXOWLPSHGDQFHLQPRVWFDVHV
LVSXUHO\UHVLVWLYHLIQRW]HUR
147
148
149
Boundary conditions:
150
(T䇻Q
(T䇻Q
(T䇻Q
(T䇻Q
151
(T䇻Q
152
153
154
155
Boundary conditions:
(T䇻Q%&
(T䇻Q%&
(T䇻Q%&
156
157
158
159
160
Negative-sequence Component:
Zero-sequence Component:
161
162
163
164
165
166
Single-to-line Ground Faults
167
168
169
170
171
172
Line-to-line fault:
173
174
175
178
Outline Procedures for Short Circuit
Calculations
1) Setup the network impedances expressed
in per unit on a common MVA base in the
form of a single-line diagram.
¾ In the impedance diagrams, only the
rotating machines in the positive sequence
network will have voltage sources
2) Determine the single equivalent
(Thevenin䇻s) impedance of each sequence
network as seen from the fault point.
3) Determine the distribution factor giving
the current in the individual branches for
unit total sequence current.
179
180
Outline Procedures for Short Circuit
Calculations
7) Determine the sequence voltages
throughout the different sequence
network from the sequence current
distribution and branch impedances.
8) Synthesize the phase voltages from the
sequence voltage components.
9) Convert the per unit currents and voltages
to actual physical units.
181
182
In the power system shown below, determine the
single line-to-ground and three phase fault levels for a
bolted fault (ZF = 0) at bus T. What is the ohmic value
of the neutral reactor to be connected at the neutral of
the 50 MVA power transformer to limit the single line-
to-ground fault to the three phase fault level. Compare
the voltage at Phase B-to-neutral for the bolted SLG
fault of the two conditions.
183
184
ͷͲͳ͵Ǥͺ
ͳǣ
ଶ
ͳ͵Ǥͺ ͷͲ
ͳݔൌ ʹݔൌ ͳʹΨ ൌ ͳͷǤͲΨ
ͳ͵Ǥͺ ͶͲ
ଶ
ͳ͵Ǥͺ ͷͲ
Ͳݔൌ Ψ ൌ ͺǤͷΨ
ͳ͵Ǥͺ ͶͲ
ͷͲǣ
ଶ
ͳ͵Ǥͺ ͷͲ
ݔൌ ͳͲΨ ൌ ͳͲΨ
ͳ͵Ǥͺ ͷͲ
ͳͲͲǣሾሿ ൌͳ͵ʹǣ
ଶ
ͷͲ ͳ͵ʹ
ܳܲݔൌ ͳͷΨ ൌ ǤͺʹͲΨ
ͳͲͲ ͳ͵ͺ
ଶ
ͷͲ ʹ͵Ͳ
ܴܳݔൌ ͳͲΨ ൌ ͻǤͳͶͻ͵Ψ
ͷͲ ʹͶͲǤͶͷͶͷ
ଶ
ͷͲ ͳ͵ʹ
ܴܲݔൌ ʹͲΨ ൌ ͳͺǤʹͻͺΨ
ͷͲ ͳ͵ͺ
ͳ
ܲݔൌ ሺǤͺʹͲ ͳͺǤʹͻͺ െ ͻǤͳͶͻ͵ሻ ൌ ͺǤͲͲͷΨ
ʹ
ͳ
ܳݔൌ ǤͺʹͲ െ ͳͺǤʹͻͺ ͻǤͳͶͻ͵ ൌ െͳǤͳͶ͵Ψ
ʹ
ͳ
ܴݔൌ ሺെǤͺʹͲ ͳͺǤʹͻͺ ͻǤͳͶͻ͵ሻ ൌ ͳͲǤʹͻ͵ͲΨ
ʹ
186
ʹ͵Ͳǣ
ܨܣܸܯ ͳʹͲͲ
ܨܫ ͵ ൌ ൌ ൌ ʹͶǤͲݑ
ܤܣܸܯ ͷͲ
ͳͷͲͲ
ܩܮܵ ܨܫൌ ൌ ͵ͲǤͲݑ
ͷͲ
Ǧ
ǣ
ͳͲͲΨ
ͳݔൌ ൌ ͶǤͳΨ
ʹͶ
Ǧ
ǣ
͵ͲͲΨ
Ͳݔൌ െ ʹ ͳݔΨ
ܩܮܵ ܨܫሺݑሻ
͵ͲͲΨ
Ͳݔൌ െ ʹ ൈ ͶǤͳΨ ൌ ͳǤΨ
͵Ͳ
187
ʹ͵Ͳ
ܸ݇ܤሺ݊݁ ݓሻ ൌ ͳ͵ͺ ൌ ʹͶͲǤͶͷͶͷܸ݇
ͳ͵ʹ
ʹͶͲǤͶͷͶͷǣ
ଶ
ʹ͵Ͳ
ͳݔൌ ͶǤͳΨ ൌ ͵Ǥͺͳʹ͵Ψ
ʹͶͲǤͶͷͶͷ
ଶ
ʹ͵Ͳ
Ͳݔൌ ͳǤΨ ൌ ͳǤͷʹͶͻΨ
ʹͶͲǤͶͷͶͷ
188
Positive sequence network:
1
189
193
Let’s determine the appropriate kV base values
choosing 230kV for the equivalent system:
kVB=230(132/230) kVB=230 kV
kVB=132(13.8/138) = 132 kV
=13.2 kV kVB=230(13.8/230)=13.8 kV
Next step is to convert all p.u. impedances to new
base values:
ͳͲͲʹ͵Ͳ̷ʹ͵Ͳǣ
ͳǣ
ଶ
ͳ͵Ǥͺ ͳͲͲ
ͳݔൌ ʹݔൌ ͳʹΨ ൌ ͵ʹǤͺͻ͵Ψ
ͳ͵Ǥʹ ͶͲ
ଶ
ͳ͵Ǥͺ ͳͲͲ
Ͳݔൌ Ψ ൌ ͳͻǤͳʹͳΨ
ͳ͵Ǥʹ ͶͲ
ͷͲǣ
ଶ
ͳ͵Ǥͺ ͳͲͲ
ݔൌ ͳͲΨ ൌ ʹͳǤͺͷͻͷΨ
ͳ͵Ǥʹ ͷͲ
ʹ͵Ͳǣ
ܨܣܸܯ ͳʹͲͲ
ܨܫ ͵ ൌ ൌ ൌ ͳʹǤͲݑ
ܤܣܸܯ ͳͲͲ
ͳͷͲͲ
ܩܮܵ ܨܫൌ ൌ ͳͷǤͲݑ
ͳͲͲ
Ǧ
ǣ
ͳͲͲΨ ͳͲͲΨ
ͳݔൌ ൌ ൌ ͺǤ͵͵͵͵Ψ
͵ ܨܫሺݑሻ ͳʹ
Ǧ
ǣ
͵ͲͲΨ
Ͳݔൌ െ ʹ ͳݔΨ
ܩܮܵ ܨܫሺݑሻ
͵ͲͲΨ
Ͳݔൌ െ ʹ ൈ ͺǤ͵͵͵͵Ψ ൌ ͵Ǥ͵͵͵͵Ψ
ͳͷ
Positive sequence network:
202
203
204
Two 11-kV, 20 MVA, three-phase, three-phase, wye-connected
generators operate in parallel as shown; Z1=j0.18 pu, Z2=j0.15 pu,
Z0=j0.10 pu. The neutral point of one the generators is isolated
and that of the other is grounded through a 2.0-ohm resistor. A
solid single line-to-ground fault occurs at the terminal of one of
the generators. Calculate:
a) Fault current
b) Current in the grounding resistor
c) Voltage across the grounding resistor
205
Solution:
206
Solution:
Positive sequence network: Negative sequence network:
207
Solution:
208
Solution:
Alternatively:
209
211
Solution:
Convert all impedances to a common MVA base
and appropriate kV base:
212
Solution (cont’d):
213
Solution (cont’d):
Positive-sequence Network
Negative-sequence Network
214
Solution (cont’d):
Zero-sequence Network
215
Solution (cont’d):
For a fault at the high-tension bus of
transformer T2:
Positive-sequence Network
Zero-sequence Network
216
Solution (cont’d):
For a fault at the high-tension bus of transformer
T2:
217
Solution (cont’d):
Sequence Network
Interconnection:
218
Solution (cont’d):
Symmetrical Components
of Current:
Fault Current:
219
Solution (cont’d):
Ia1
Ia1G1 Ia1G2
ܽͳܩ
ܽʹܩ
220
Solution (cont’d):
For a single line-to-ground fault at the high-
tension bus of transformer T2,
221
Solution (cont’d):
Symmetrical Components of Current:
Fault Current:
222
Solution (cont’d):
Generator fault current contributions:
223
Solution (cont’d):
Zero-sequence Network
224
Solution (cont’d):
225
Solution (cont’d):
Fault Current:
226
Solution (cont’d):
Generator fault current contributions:
227
Solution (cont’d):
Generator phase current contributions:
228
Solution (cont’d):
229
Solution (cont’d):
Fault Current:
230
Solution (cont’d):
Symmetrical components of current:
231
Solution (cont’d):
Symmetrical components of current:
232
Solution (cont’d):
Symmetrical components of current:
233
Solution (cont’d):
Zero-sequence Network
234
Solution (cont’d):
Zero-sequence Network
235
236
A portion of a power system is shown below, which
also shows the ratings of the generators and the
transformer and their respective percent reactance. A
symmetrical short circuit appears on a feeder at F.
Find the value of the reactance X (in percent) such
that the short-circuit MVA does not exceed 300 MVA.
237
238
Assuming X = 0:
239
240