Hydraulic Calculation - Hose Reel System (V 1.2)
Hydraulic Calculation - Hose Reel System (V 1.2)
PROJECT:
Design Notes:
For 54.00 meter length 50 mm dia. The total head loss is 1.99 Meter Head
For 5.00 meter length 25 mm dia. The total head loss is 5.53 Meter Head
Total head loss through linear length of pipe 1.99 Meter Head
For 7.00 nos. bends, the equipment length of pipe is 10.22 meter
For 7.00 nos. tees, the equipment length of pipe is 20.37 meter
For 4.00 nos. valves, the equipment length of pipe is 1.52 meter
For 30 length of 25 mm diameter of NON-KINK SINGLE BRAIDED hose, the head loss is
1.52 meter head
Design Notes:
Pump location: NIL (TAPPED FROM SPRINKLER SYSTEM)
Min pumping flow rate: 2.27 L/s fixed
Min effective head required at highest nozzle 20.42 MH fixed
At 2.27 L/s flow rate, based on Hanzen William's Formula with C = 120 for Galvanized steel and
the friction head loss per hundred meters of various pipe sizes are as below:
Summary of Total head loss 4.69 MH 4.69 for static loss in negative value
10 % Safety factor 0.47 0.4689
PRV setting valve 25.58 MH 25.58