You are on page 1of 6

Discrete SOGI Based Control of Solar Photovoltaic

Integrated Unified Power Quality Conditioner


Sachin Devassy, Student Member, IEEE Bhim Singh, Fellow, IEEE
Electrical Engineering Dept. Electrical Engineering Dept.
IIT Delhi IIT Delhi
New Delhi-110016, India New Delhi-110016, India
Email:sachindevassy@gmail.com Email:bhimsinghiitd60@gmail.com

Abstract—A discrete second order generalized integrator Custom power devices are an attractive option for the
(DSOGI) based control is presented in this work for control of mitigation of power quality issues. Custom power devices in-
solar photovoltaic integrated unified power quality conditioner clude distribution static compensator (DSTATCOM) for shunt
(SPV-UPQC). Two DSOGI based band-pass filters are used
to extract fundamental positive sequence component (FPSC) compensation, dynamic voltage restorer (DVR) for series com-
of unbalanced grid voltages. The shunt compensator of SPV- pensation and unified power quality conditioner (UPQC) for
UPQC is controlled based on philosophy of drawing balanced both shunt and series compensation [4]. Due to its shunt and
positive sequence currents (BPSC) from the point of common series compensation capability, UPQC provides a complete
coupling (PCC). The shunt compensator has the dual function of solution to power quality issues as compared to DSTATCOM
compensating for load power quality issues along with injecting
power from solar photovoltaic (SPV) array. Sensitive loads and DVR. In the recent years there has been an increased
are protected against grid voltage fluctuations such as voltage focus on integrating RES/energy storage systems with custom
sags/swells etc with the help of the series compensator of SPV- power devices [5]. A study of use of custom power devices
UPQC. A step-up DC-DC converter is used for coupling SPV for integrating wind farms to grid was reported in [6]. In
array to the DC-bus of SPV-UPQC. A Maximum power point [7], a DVR with an energy storage system with fault current
tracking (MPPT) algorithm generates appropriate duty cycle
for the dc-dc converter so that the SPV array is operated limiting functionality has been reported. Combining renewable
at its peak power. The performance of DSOGI based SPV- energy systems with custom power devices gives advantages
UPQC is simulated in Matlab-Simulink environment and tested of improving power quality, providing clean energy and also
under dynamic conditions of grid voltage disturbances, load increased fault ride through capability [8], [9].
disturbances and solar irradiation variation. A comprehensive review of various UPQC topologies and
Index Terms—Power quality, SPV-UPQC, solar mppt, FPSC,
DSOGI, series compensation, shunt compensation, step-up con- control structures have been discussed in [10]. Along with
verter, band-pass filter. issues of nonlinear currents, another major problem in dis-
tribution systems which are three-phase four-wire (3P4W)
I. I NTRODUCTION systems is that of load neutral current. Even under case of
balanced loads neutral currents are present if the loads in each

W ITH advances in power electronics and micro-


electronics technology, there is an increased prolif-
eration of power electronics based systems which are en-
phase are nonlinear. For compensation of neutral current, the
commonly topologies of shunt VSC include four-leg VSC or
three-leg VSC with split capacitor. Similarly, as most of the
ergy efficient. However, these power electronics systems are sags encountered in distribution systems are unbalanced, the
nonlinear and hence inject harmonic currents into the grid. required series compensator [11] topology is also four leg VSC
Apart from harmonics, various other load side power qualities with single capacitor or three-leg VSC with split capacitor.
in a distribution system include excessive neutral current, The control of four-leg VSC is simpler as compared three-leg
load unbalancing, excessive reactive power demand [1]. In VSC with split capacitor which involves extra control loop
many countries, the increased installation of renewable energy of balancing the split capacitors and hence four-leg based
systems (RES) has started affecting the voltage quality partic- topology is preferred for the series and shunt compensator
ularly in low voltage distribution systems [2]. The grid voltage of UPQC.
fluctuations affect sensitive industrial loads leading to frequent Digital signal processing is an important function in the con-
tripping and thus increased economic losses. Voltage sags are trol of custom power devices (CPD). Most of the methods em-
the most commonly encountered fluctuation [3] which occur ployed for control of CPD are time domain based techniques
due to faults or due to heavy loading at the point of common as it involves simpl calculations and less memory requirements
coupling. A detailed discussion on various types of voltage [1]. The commonly used methods include p-q theory [12], d-
sags and its causes are described in [3]. q theory[13] and instantaneous symmetrical component the-
c 2016 IEEE
978-1-4799-5141-3/14/$31.00 ory (ISC) [4]. In order to inject balanced positive sequence
currents into grid under conditions of asymmetrical voltages Ripple
Filter
Ripple
Filter
Rfsh, Cfsh
or harmonic distortion at PCC, the extraction fundamental vMa Ls Rs vsa
Rfs, Cfs Cr Rr

- vsea + vla
positive sequence component (FPSC) of PCC voltage becomes isha
iLa
isa
vital. In [14], the use of two SOGI based band-pass filters have 3-Phase
vMb Ls Rs vsb vlb
been proposed for extracting FPSC. In [15], a cascaded delay - vseb +
4-wire
Linear
ishb
signal cancellation (CDSC) based technique for extraction of isb
iLb and
Nonlinear
FPSC has been proposed to be used as pre-filtering scheme in vMc Ls Rs vsc vlc
Load
- vsec +
three-phase pll. Some other FPSC detection methods include ishc iLc
isc
using adaptive notch-filter (ANF) [16], using complex vector Ls Rs iLn

filter method [17] etc. isn Lr


Lr ishn
Lf
In this paper a DSOGI based control is proposed for the Lr
Lf
Lf
control of SPV-UPQC. An implementation of DSOGI based PV-
ipv
Lr Lf
Array
band-pass filter is simple as it basically consists of two integra- L
tors, three gain blocks and two summers. Two DSOGI based
band-pass filters are used for extraction of FPSC components vpv
Cpv Cdc
vdc

of PCC voltages based on which the reference for shunt


compensator is generated. The resulting currents are balanced
and sinusoidal and UPF with the FPSC of PCC voltages. The
objective of the series compensator is to maintain the voltage Fig. 1. Configuration of SPV-UPQC
of the load terminals at desired magnitude and in-phase with
the FPSC of PCC voltages. A step-up DC-DC converter is
used for integrating the SPV array at the DC-link of SPV- A. Extraction of FPSC of PCC Voltages
UPQC. For operating the SPV array at its MPP, a MPPT
algorithm [18] is used to generate appropriate duty ratio for The extraction of FPSC components of PCC voltage is a
the step-up converter. The SPV-UPQC is tested in a 3P4W major task in control of SPV-UPQC as the reference signal
system consisting of single phase nonlinear load in each phase. generation of both shunt compensator and series compensator
The performance of SPV-UPQC is evaluated under commonly depends upon FPSC of PCC voltage. In this work, the FPSC
encountered dynamic conditions of low voltage distribution are extracted using a discrete SOGI (DSOGI) band-pass filter.
system such as load unbalancing, irradiation level variation The structure of DSOGI band-pass filter is shown in Fig.
and asymmetrical voltage sags. 2(a). As can be seen from Fig. 2(a), in the DSOGI band-
pass filter there are two discrete integrators, two summers and
II. C ONFIGURATION OF SPV-UPQC three gain blocks. The Trapezoidal version of integrator is
The configuration of SPV-UPQC for a 3P4W system is used in SOGI as it gives more accurate results as compared to
presented in Fig.1. The major parts of the system are a series forward or backward Euler discrete integration methods. The
compensator and a shunt compensator connected back to back gains ω is set at nominal grid frequency. The gain block K is
with a common DC-bus. As the shunt compensator has to adjusted based on compromise between accuracy and speed of
compensate for unbalanced loads and the neutral current in extraction of FPSC. For an input signal vs , the DSOGI band-
a 3P4W system, a four-leg shunt VSC is used for shunt pass filter gives the fundamental frequency component vs1 and
compensation. The series VSC used is a four leg VSC which fundamental quadrature shifted component qvs1 .
can compensate for unbalanced voltage sags. The step-up In order to extract FFPS components using DSOGI [14]
converter is utilized for coupling the SPV array to the DC- band-pass filter, two DSOGI band-pass filters are used as
bus of SPV-UPQC. The shunt and series compensators are shown in Fig.2(b)
interfaced to the grid through interfacing inductors Lf and Lr The PCC voltages (vsa , vsb , vsb ) are transformed into
respectively. A series injection transformer is use to inject the α − β domain using Clark’s Transform. The α component
voltages (vsea , vseb , vsec ) generated by the series compensator vα and β component vβ are filtered using DSOGI band-
to protect sensitive loads against grid voltage sags/swells. pass filter to obtain the fundamental component (vs1α , vs1β )
Ripple filters (Rr − Cr , Rf s , Rf sh ) are used to bypass the and its quadrature shifted version (qvs1α , qvs1β ). The relation
harmonics generated due to switching. between the FPSC and fundamental frequency components is
given as,
III. C ONTROL OF DSOGI BASED SPV-UPQC
The four major control blocks of SPV-UPQC are the dis-
crete SOGI based fundamental positive sequence component + 1 
vs1α = vs1α − qvs1β (1)
(FPSC) extractor for extracting FPSC of PCC voltage, MPPT 2
control block for the step-up DC-DC converter, shunt com-
pensator control block and series compensator block. These + 1 
vs1β = vs1β + qvs1α (2)
blocks are discussed in detail as follows. 2
Vpv Ppv Gating Signals
KTs ( z + 1) v s1 Ipv ´ LPF
isa
vs - ws
+ K +- 2( z - 1) isb
Vdc* Ploss isc
+- PI Hysteresis
Current
Vdc

+
+
+
MAF Controller
qv s1 KTs ( z + 1) -1
ws
2( z - 1) vLabc
PLav
Dot +- isn
iLabc MAF +
Product isa* isb* isc* isn*=0
(a) DSOGI band-pass filter
v s+1a ´ ´ ´
v s1a 1 ()2 +
v sa
v sa + 2 v s+1a v s+1b ¸
Discrete - v s+1a () 2
+
abc SOGI-BPF qv s1a abc v s+1c
v sb v s+1b v s+1a v s+1b

v sc qv s1b
v sb
v s+1b v s+1c Fig. 3. Shunt Compensator Control Structure
Discrete
αβ αβ
SOGI-BPF v s1 b + 1
+ 2

harmonic ripple. The DC-bus of SPV-UPQC is regulated at


(b) DSOGI based FPSC Extractor its desired reference value using a digital proportional integral
Fig. 2. Structure of DSOGI and DSOGI based FPSC extraction (PI) controller. The reference for DC-bus PI controller is set
at 700V. The sensed DC-bus voltage is filtered through MAF,
the window length of which, is kept at half the grid period as
+ +
The FPSC of PCC voltage in α − β domain (vs1α , vs1β ) DC-link has even harmonics. The PI controller gives the power
are transformed back using inverse Clark transform to obtain loss component of the SPV-UPQC. The reference power to be
+ + +
FPSC of PCC voltage in stationary frame (vs1a , vs1b , vs1c ). drawn from the grid is then derived as,

B. Control of Step-Up Converter P ∗ = PLavg + Ploss − Ppv (4)


A step-up converter is used for integrating the SPV array where Ppv is the SPV array power. The balanced positive
to the DC-link of SPV-UPQC. The SPV array is operated at sequence reference grid currents are obtained as,
its MPP by controlling the step-up converter using a MPPT +
algorithm. In this work, perturb & observe (P&O) algorithm is vs1,abc
i+
s1,abc = +2 +2 P∗ (5)
implemented for tracking MPP. The MPPT algorithm directly vs1α + vs1β
generates the duty ratio for the next switching period of the
where P ∗ is average power drawn from grid.
step-up converter. The duty ratio updating rule is given as,
The reference neutral current (i∗s ) is set as zero. The
reference currents (i∗sa , i∗sb , i∗sc , i∗sn ) are compared with the
dn+1 = dn + δd.sgn(δPpv ) (3) sensed currents (isa , isb , isc , isn ) in a hysteresis controller to
where dn+1 is duty cycle for next switching cycle, dn is duty generate gating pulses corresponding to shunt VSC.
cycle ratio of current switching period, δd is perturbation size D. Control of Series Compensator of SPV-UPQC
of duty ratio, δPpv is difference in power calculated between
two cycles of MPPT algorithm. The purpose of the series compensator is the protection of
sensitive load against disturbances in PCC voltages. The series
C. Control of Shunt Compensator of SPV-UPQC compensator injects voltage in-phase with the FPSC of the
PCC voltages. The series compensator control block diagram
The two major functions of the shunt compensator is to
is presented in Fig. 4.
mitigate the load side power quality problems and supply real
The amplitude of FPSC of PCC voltages is calculated as,
power obtained from the SPV array. The control methodology q
for the shunt compensator control is such that, the currents Vs+ = vs1α +2 +2
+ vs1β (6)
drawn from PCC are balanced positive sequence currents,
both under unbalanced sags of PCC voltages or unbalanced The unit templates of FPSC of PCC voltages are obtained
condition of nonlinear loads. The shunt compensator control as,
structure is shown in Fig.3. +
vs1,abc
The average load real power (PLavg ) is extracted by filtering u+
s1,abc = (7)
the dot product of load voltages and currents. The filter used Vs+
is a moving average filter (MAF), the window length of The load reference voltages (vLabc

) are obtained by multiply-
which, is fixed at half the grid fundamental period as during ing the peak reference voltage (VL∗ ) with the unit templates
unbalanced condition the instantaneous load power has double (u+
s1,abc ). The reference for the fourth leg of series VSC (vLu )

VL* Gating Signals 500

v s(V)
v *La v La 0
v s+1a
´
v s+1b
¸u +
s1a
v *Lb
v Lb
v Lc
-500
Voltage 500
¸u ´

v L (V)
+ Hysteresis
v s+1c s1b v *Lc 0
Control

+
+
+
v s+1a
¸u +
s1c
´
-1
-500
800

V dc(V)
v s+1b Amplitude
v *Lu = 0 v Lu 700
Calculation
600
100
Fig. 4. Series Compensator Control Structure

i s(A)
0
-100

is set as zero. The reference voltages (vLa



, vLb

, vLc

, vLu

) 10

i sn (A)
are compared with the sensed voltages (vLa , vLb , vLc , vLu ) 0
in a voltage hysteresis controller, which generates the series -10
compensator gating pulses. 200

i L (A)
0
IV. P ERFORMANCE E VALUATION -200
The DSOGI based SPV-UPQC is simulated in Mat- 200

i Ln(A)
lab/Simulink software using SimPowerSystems blockset. The 0
dynamic performance is evaluated at different scenarios such -200
as unbalanced sag of PCC voltages, irradiation variation and 200
load disturbances. The load used consists three single phase i SH(A) 0
current-fed nonlinear loads each connected between a phase -200
and neutral of the system. The detailed design values of the 200
i SHn(A)

SPV-UPQC are given the Appendix. 0


-200
A. SPV-UPQC performance during Load Disturbances
30
P pv(kW)

The dynamic behavior of SPV-UPQC under load distur- 20


bance is presented Fig.5. The irradiation(G) of SPV array is 10
0
kept at 1000W/m2. The signals shown are PCC voltages(vs ), 700
V pv(V)

load voltages (vL ), DC-bus voltage (Vdc ), grid currents (is ), 600
grid neutral current (isn ), load current (iL ), load neutral 500
current (iLn ) shunt compensator current (iSH ), shunt com- 0.55 0.6 0.65 0.7 0.75 0.8
pensator neutral current (iSHn ),SPV array power (Ppv ), SPV Time(s)
array voltage (Vpv ). It is to be noted that the PCC and load
Fig. 5. Performance of SPV-UPQC under Load Disturbances
voltages shown are phase to neutral voltage.
As observed from Fig.5, the shunt compensator keeps the
PCC neutral current (isn ) at nearly zero by compensating neutral current(iSHn), SPV array Power (Ppv ), SPV voltage
for load neutral current. It can also be observed that the (Vpv ), and irradiation (G(W/m2 )). As the load is symmetrical,
though the load is nonlinear, the grid current is sinusoidal at the shunt compensator currents are symmetrical and hence
unity power factor. From t=0.6s to t=0.7s phase ’a’ is opened only phase ’a’ current is shown in case of load currents
through circuit breaker. It is observed that the grid currents and shunt compensator currents. From 0.6s to 0.65s, the
are still sinusoidal and balanced. The DC-bus voltage settles solar irradiation(G) is uniformly varied from 1000W/m2 to
within 4% reference value of 700V within 0.06s after a slight 200W/m2 . As observed from Fig.6, as the power from the
overshoot/undershoot during opening and closing of circuit SPV array reduces, the real power demand of the load side is
breaker. supplied by the PCC. The DC-link is regulated at its desired
B. SPV-UPQC performance during Irradiation change value.
The dynamic performance of DSOGI based SPV-UPQC is
C. SPV-UPQC during Asymmetrical Sag in PCC Voltages
evaluated by giving a ramp decrease in solar irradiation. The
relevant signals are shown in Fig.6. The signals shown are Fig.7 presents the SPV-UPQC performance under asymmet-
three-phase PCC voltages (vs ), load voltages (vL ), DC-bus rical sag in PCC voltages. The SPV array is at STC conditions
voltage (Vdc ), grid currents (is ), grid neutral current (isn ), load of 1000W/m2 and 25◦C. Signals shown are grid voltages
current of phase ’a’ (iL ), load neutral current (iLn ), shunt (vs ), load voltages (vL ), series compensator voltages (vSE ),
compensator current of phase ’a’ (iSH ), shunt compensator DC-bus voltage (Vdc ), grid currents (is ), grid neutral currents
500 500

v s(V)
v s(V)
0 0
-500 -500
500 500

v L (V)
v L (V)

0 0
-500 -500
750 200
V dc(V)

v se(V)
700 0
-200
650
800

V dc(V)
100
i s(A)

0 700
-100 600
10 100
i sn (A)

i s(A)
0 0
-100
-10
100 200

i sn (A)
i L (A)

0 0
-100 -200
100 200

i L (A)
i Ln(A)

0 0
-100 -200
100 200

i Ln(A)
i SH(A)

0 0
-200
-100
100 i SH(A) 100
P pv(kW) i SHn(A)

0 0
-100 -100
100
V pv(V) P (kW) I (A)

30
20 0
SHn

10 -100
0
700 30
G(w/m2) V pv(V)

20
600
pv

10
500 0
700
1000 600
500 500
0
0.55 0.6 0.65 0.7 0.75
0.55 0.6 0.65 0.7 0.75
Time(s)
Time(s)

Fig. 6. SPV-UPQC performance under varying irradiation condition Fig. 7. SPV-UPQC performance during asymmetrical sags in PCC voltage

total harmonic distortion (THD) of the nonlinear load current


(isn ), phase ’a’ load current (iL ), load neutral current (iLn ),
is 36.44%, the THD of the grid current is 2.17% and is thus
phase ’a’ shunt compensator current (iSH ), shunt compensator
within limits prescribed in IEEE-519 standard [19].
neutral current (iSHn ), SPV array power (Ppv ), SPV array
voltage (Vpv ). As the load is symmetrical but nonlinear, the V. C ONCLUSION
shunt compensator signals are also symmetrical and nonlinear; A DSOGI based SPV-UPQC and its dynamic performance
hence, only phase ’a’ current is shown in case of load and has been presented in this work. Two DSOGI band-pass
shunt compensator signals for good clarity in representation. filters have been used to extract FPSC of PCC voltages. The
As can be seen from Fig. 7, from t=0.6s to t=0.7s there is an extracted FPSC has been used for reference signal generation
unsymmetrical sag of 0.3pu in phase ’b’ and ’c’ along with a in case of shunt and series compensator. The SPV-UPQC
phase jump. It can be noted that the load voltage is sinusoidal performs satisfactorily under conditions of load unbalance,
and at its reference value despite the distortions in the grid asymmetrical sags and solar irradiation variation. The grid
voltage. Under nominal conditions the series compensator does currents are balanced and sinusoidal even under conditions of
not inject voltage. The grid current rises during sag to maintain nonlinear and unbalanced load. The load voltages are also bal-
real power balance. anced and sinusoidal under conditions of asymmetrical sags.
The harmonic spectra of grid currents and load currents are The integration of SPV array with SPV-UPQC enhances the
given in Fig.8. The DSOGI based SPV-UPQC compensates for functionality of the UPQC. SPV-UPQC integrates the concept
the harmonics of load current. It can be noted that though the of clean energy along with power quality improvement.
100 Series Compensator: 4mH; Injection Transformer: 12kVA,
415V/138V; VA Rating of Shunt Compensator=38kVA, Rat-
ing of Series Compensator=12kVA; Gains of DC-bus PI
i s (A)

0 contoller: Kp =500,Ki=3000; MAF Parameters for DC bus


filtering:N =100,Tw=0.01,Ts=1e-4; MAF Parameters for Load
Power Calculation:N =100,Tw=0.01,Ts=1e-4; DSOGI Par-
-100 maters: Ts =5e-5,K=0.8; DC Inductor: L=0.5mH; Input Capac-
0.76 0.77 0.78 0.79 0.8 itor of Step-Up Converter:100µF; SPV array data: P =13.8kW,
Time(s) Voc =703V, Isc 25.8=A, Vmpp =568V, Impp =24.12A.
100
(% of Fundamental)

R EFERENCES
Fundamental (50Hz) = 55.93A [1] B. Singh, A. Chandra, K. A. Haddad, Power Quality: Problems and
Mag.

THD = 2.17% Mitigation Techniques. London: Wiley, 2015.


50 [2] H. Hafezi, G. D’Antona, R. Faranda, D. D. Giustina, A. Dede, and
G. Massa, “Power quality conditioning in lv distribution networks:
Results by field demonstration,” IEEE Transactions on Smart Grid,
vol. PP, no. 99, pp. 1–1, 2016.
0 [3] M. Bollen, Understanding Power Quality problems: Voltage Sags and
0 200 400 600 800 1000 interruptions. New York: IEEE Press, 2000.
Frequency(Hz) [4] A.Ghosh and G. Ledwich, Power Quality Enhancement using Custom
Power devices. London: Kluwer Academic Publishers, 2002.
(a) Harmonic Spectra of Grid Current [5] C. Jain and B. Singh, “A single-phase two-stage grid interfaced spv
system with adjustable dc link voltage for vsc under non ideal grid
100 conditions,” in IEEE International Conference on Power Electronics,
Drives and Energy Systems (PEDES), Dec 2014, pp. 1–6.
[6] M. F. Farias, M. G. Cendoya, and P. E. Battaiotto, “Wind farms in
i L (A)

weak grids enhancement of ride-through capability using custom power


0 systems,” in IEEE/PES Transmission and Distribution Conference and
Exposition, Aug 2008, pp. 1–5.
[7] S. S. Choi, T. X. Wang, and D. M. Vilathgamuwa, “A series compensator
with fault current limiting function,” IEEE Trans. Power Del., vol. 20,
-100 no. 3, pp. 2248–2256, July 2005.
0.76 0.77 0.78 0.79 0.8 [8] S. Devassy and B. Singh, “Dynamic performance of solar PV integrated
Time(s) UPQC-P for critical loads,” in Annual IEEE India Conference (INDI-
100 CON), Dec 2015, pp. 1–6.
(% of Fundamental)

[9] S. Devassy and B. Singh, “Enhancement of power quality using solar


Fundamental (50Hz) = 85.62A pv integrated upqc,” in 39th National Systems Conference (NSC), Dec
2015, pp. 1–6.
Mag.

THD = 36.44%
50 [10] V. Khadkikar, “Enhancing electric power quality using UPQC: A com-
prehensive overview,” IEEE Trans. Power Electron., vol. 27, no. 5, pp.
2284–2297, May 2012.
[11] K. M. Praveen, K. M. Mahesh, and J. Sandeep, “Switching minimization
0 of three-phase four-leg dynamic voltage restorer,” in Annual IEEE India
0 200 400 600 800 1000 Conference, Dec 2009, pp. 1–5.
[12] H. Akagi, E. Watanabe, M. Aredes, Instantaneous Power Theory and
Frequency(Hz) Applications to Power Conditioning. New Jersey: Wiley, 2007.
(b) Harmonic Spectra of Load Current [13] P. Kanjiya, B. Singh, A. Chandra, and K. Al-Haddad, “’SRF Theory
Revisited’ to control self-supported dynamic voltage restorer (dvr) for
Fig. 8. Harmonic Spectra of Grid and Load currents unbalanced and nonlinear loads,” IEEE Trans. Ind. Appl., vol. 49, no. 5,
pp. 2330–2340, Sept 2013.
[14] P. Rodriguez, R. Teodorescu, I. Candela, A. V. Timbus, M. Liserre,
and F. Blaabjerg, “New positive-sequence voltage detector for grid
ACKNOWLEDGMENT synchronization of power converters under faulty grid conditions,” in
Power Electronics Specialists Conference, 2006. PESC ’06. 37th IEEE,
This work is sponsored by Department of Science and June 2006, pp. 1–7.
Technology, Govt. of India, under Grant Number: RP02583. [15] Y. F. Wang and Y. W. Li, “Three-phase cascaded delayed signal
cancellation pll for fast selective harmonic detection,” IEEE Trans. Ind.
A PPENDIX Electron., vol. 60, no. 4, pp. 1452–1463, April 2013.
[16] M. Mojiri, M. Karimi-Ghartemani, and A. Bakhshai, “Processing of
Detailed Design Values: Per phase grid voltage: 239.6V, harmonics and interharmonics using an adaptive notch filter,” IEEE
Trans. Power Del., vol. 25, no. 2, pp. 534–542, April 2010.
50Hz; Grid Impedance:0.1mH, 0.02Ω; Reference DC-bus [17] W. Li, X. Ruan, C. Bao, D. Pan, and X. Wang, “Grid synchronization
Voltage: 700V; DC-bus Capacitor: 10mF; Nonlinear Load systems of three-phase grid-connected power converters: A complex-
in each phase: Bridge Rectifier with R-L: 3Ω, 100mH; vector-filter perspective,” IEEE Trans. Ind. Electron., vol. 61, no. 4, pp.
1855–1870, April 2014.
Shunt Compensator Interfacing Inductor:1mH; Shunt com- [18] B. Subudhi and R. Pradhan, “A comparative study on maximum power
pensator neutral leg Inductor:0.8mH; Average switching fre- point tracking techniques for photovoltaic power systems,” IEEE Trans-
quency of shunt and series VSC: 10kHz; Ripple Filter of actions on Sustainable Energy, vol. 4, no. 1, pp. 89–98, Jan 2013.
[19] “IEEE recommended practices and requirements for harmonic control in
Shunt VSC:10µF, 10Ω; Ripple Filter Series VSC:25µF,5Ω; electrical power systems,” IEEE Std 519-1992, pp. 1–112, April 1992.
Ripple Filter at PCC:10µF, 10Ω; Interfacing Inductor of

You might also like