Professional Documents
Culture Documents
Distance Setting
Distance Setting
Therefore, select:
kZ0 Res. Comp = 0.79 (Set for kZ1, kZ2, kZp, kZ4).
kZ0 Angle = –6.5° (Set for kZ1, kZ2, kZp, kZ4).
3.1.11 Resistive Reach Calculations
All distance elements must avoid the heaviest system loading. Taking the 5A CT
secondary rating as a guide to the maximum load current, the minimum load
impedance presented to the relay would be:
Vn (phase-neutral) / In = (115 / √3) / 5 = 13.3 Ω (secondary)
Typically, phase fault distance zones would avoid the minimum load impedance by a
margin of ≥40% if possible (bearing in mind that the power swing characteristic
surrounds the tripping zones), earth fault zones would use a ≥20% margin. This
allows maximum resistive reaches of 7.9Ω, and 10.6Ω, respectively.
From Table 1, taking a required primary resistive coverage of 14.5Ω for phase
faults, and assuming a typical earth fault coverage of 40Ω, the minimum secondary
reaches become:
RPh (min) = 14.5 × 0.12 = 1.74Ω (secondary);
RG (min) = 40 × 0.12 = 4.8Ω (secondary).
Resistive reaches could be chosen between the calculated values as shown in Table
10. The zone 2 elements satisfy R2Ph ≤ (R3Ph x 80%), and R2G ≤ (R3G × 80%).
Case 1:
2
Source Impedance = 230 / 5000 = 10.58Ω
Line Impedance = 48.4Ω
Fault current seen by relay = (230000 / √3) / (10.58 + 48.4)
= 2251A
Case 2:
2
Source Impedance = 230 / 3000 = 17.63Ω
Line Impedance = 48.4Ω
Fault current seen by relay = (230000 / √3) / (17.63 + 48.4)
= 2011A
The overcurrent setting must be in excess of 2251A. To provide an adequate safety
margin a setting ≥120% the minimum calculated should be chosen, say 2800A.
A further use for this feature is the ability to provide alternative settings for teed
feeders or double circuit lines with mutual coupling. Similar alternative settings could
be required to cover different operating criteria in the event of the channel failing, or
an alternative system configuration (ie. lines being switched in or out).
3.3.1 Selection of Setting Groups
Setting groups can be changed by one of two methods:
• Automatic group selection by changes in state of two opto-isolated inputs,
assigned as Setting Group Change bit 0, and Setting Group Change bit 1, as
shown in Table 11 below. The new setting group binary code must be
maintained for 2 seconds before a group change is implemented, thus rejecting
spurious induced interference.
• Or, using the relay operator interface / remote communications. Should the user
issue a menu command to change group, the relay will transfer to that settings
group, and then ignore future changes in state of the bit 0 and bit 1 opto-inputs.
Thus, the user is given greater priority than automatic setting group selection.
Binary State of SG Change bit 1 Binary State of SG Change bit 0 Setting Group
Activated
0 0 1
0 1 2
1 0 3
1 1 4
FAULT LOCATOR
kZm Mutual Comp 1 0 7 0.01
kZm Angle 0° –180° +180° 1°
4.1.1 Mutual Coupling
When applied to parallel circuits mutual flux coupling can alter the impedance seen
by the fault locator. The coupling will contain positive, negative and zero sequence
components. In practice the positive and negative sequence coupling is insignificant.
The effect on the fault locator of the zero sequence mutual coupling can be
eliminated by using the mutual compensation feature provided. This requires that
the residual current on the parallel line is measured, as shown in the Application
Diagrams: 10 P441 01; and 10 P442 01. It is extremely important that the polarity
of connection for the mutual CT input is correct, as shown.
4.1.2 Setting Guidelines
The system assumed for the distance protection worked example will be used here,
refer to section 3.1. The Green Valley – Blue River line is considered.
Line length: 100Km
CT ratio: 1 200 / 5
VT ratio: 230 000 / 115
Line impedances: Z = 0.089 + j0.476 = 0.484 / 79.4° Ω/km
1
ZM = 0.107 + j0.571 = 0.581 / 79.4° Ω/km (Mutual)
0
1200 / 5
Ratio of secondary to primary impedance = 230000 / 115 = 0.12