Professional Documents
Culture Documents
Manual
© Bihl+Wiedemann GmbH
Floßwörthstr. 41
D-68199 Mannheim
Manual
PROFIBUS Gateways
Table of Contents
Table of Contents
PROFIBUS Gateways
3 PROFIBUS ............................................................................................. 7
3.1 Process data channel ...................................................................................... 7
3.1.1 Digital data....................................................................................................................... 7
3.1.2 Analog data...................................................................................................................... 9
3.1.3 Flags + Fault Detector .................................................................................................. 11
3.1.4 Current limit................................................................................................................... 12
3.1.5 Fieldbus bits .................................................................................................................. 13
3.1.5.1 2 Byte Fieldbus Bits ..................................................................................................... 13
3.1.5.2 16 Byte Fieldbus Bits ................................................................................................... 14
3.1.6 Safety Control/Status.................................................................................................... 15
3.1.7 Monitor and I/O data ..................................................................................................... 17
3.1.8 Diagnostics Safe Link................................................................................................... 19
3.2 Diagnostics channel ...................................................................................... 20
3.2.1 DP diagnostics .............................................................................................................. 20
3.3 Device-specific parameters .......................................................................... 23
3.3.1 General parameters ...................................................................................................... 23
3.3.2 ASi circuit parameters .................................................................................................. 23
4 PROFIsafe ........................................................................................... 25
4.1 PROFIsafe diagnostics.................................................................................. 25
4.1.1 PROFIsafe Status indicator.......................................................................................... 25
4.1.2 PROFIsafe channel diagnostics .................................................................................. 27
4.2 System diagnostics on the PC ..................................................................... 28
4.2.1 Software for diagnostics, service and release measurements................................. 28
4.2.2 ASi Control Tools.......................................................................................................... 28
4.2.3 ASIMON360.................................................................................................................... 28
4.2.4 Online bus information................................................................................................. 28
4.2.5 Web server..................................................................................................................... 29
4.3 Diagnostics on the host controller............................................................... 29
4.3.1 On the fly diagnostics................................................................................................... 29
4.3.2 Diagnostics through process data .............................................................................. 29
4.3.2.1 Diagnosing the ASi circuits .......................................................................................... 29
4.3.2.2 Diagnosing the Safety Monitor ..................................................................................... 30
Changing the base setting .......................................................................................... 32
Issue date: 27.06.2023
4.3.3 Diagnosing the safety unit using the command interface ........................................ 32
4.4 Error indication directly on the device ........................................................ 33
4.4.1 LEDs ............................................................................................................................... 33
4.4.2 LC-Display ..................................................................................................................... 33
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
3
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
Table of Contents
5 Appendix ............................................................................................. 35
5.1 Quick Start Guides ......................................................................................... 35
4 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
Setting up the ASi Bus
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
5
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
Configuration and Start-up of the Safety Monitor
Configuration and start-up of the ASi Safety Monitor is accomplished using a PC/
notebook running the ASIMON360 configuration software.
Note!
For more detailed information please refer to the separate manual for the ASIMON360
configuration software.
Configuration should be performed only by a qualified and authorized person. All
safety-related commands are password protected.
The correct safety functioning of the unit must absolutely be verified in the system!
Note!
Quick Start Guides for commissioning and service are provided on the Bihl+Wiede-
mann website available for download.
6 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
3. PROFIBUS
3.1 Process data channel
Description of the diagnostic data which are sent via the PROFIBUS process data
channel.
These data must be integrated into the control in order to access the nodes in the
ASi circuits.
Typical GSD modules
C1:, C2: prefixed for double masters for ASi circuit selection
16 Byte Digital I/O (0 … 31) 16 byte for single-/A-nodes
16 Byte Digital I/O (0B … 31B) 16 byte for B-nodes
32 Byte Digital I/O (0 … 31B) 32 byte for single-/A- and B-nodes
Tab. 3-1.
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
7
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
Flags
Input data Output data
F0 ConfigError Offline
F1 APF LOS MasterBit
F2 PeripheryFault → ConfigurationMode
F3 ConfigurationActive → ProtectedMode
8 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
n byte analog
Byte Meaning
0 1. node, channel 1, high byte
1 1. node, channel 1, low byte
2 1. node, channel 2, high byte
3 1. node, channel 2, low byte
4 1. node, channel 3, high byte
5 1. node, channel 3, low byte
6 1. node, channel 4, high byte
7 1. node, channel 4, low byte
8 2. node, channel 1, high byte
9 2. node, channel 1, low byte
… …
n …
Tab. 3-4.
Note!
A-Nodes map the data on channels 1 and 2.
B-Nodes map the data on channels 3 and 4.
0
1. node, channel 1 1. node, channel 1 1. node, channel 1 1. node, channel 1
1
Tab. 3-5.
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
9
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
10 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
GSDML module:
C1:, C2: prefixed for double masters for ASi circuit selection
ASi-3 Flags + Fault Det. 2 byte input data (flags)
Note!
Using this data module it is possible to implement effective ASi diagnostics in the con-
trol with very little effort.
Issue date: 27.06.2023
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
11
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
Note!
For gateways with 1 ASi master the input data are two bytes long and for
2 ASi masters 4 bytes.
Byte 0/1 refers to ASi network 1 and byte 2/3 to ASi network 2.
Note!
Using this data module it is possible to implement effective ASi diagnostics in the con-
trol with very little effort.
Issue date: 27.06.2023
12 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
The fieldbus bits enable communication between the controller and the safety
program. The fieldbus bits can be used to pass any acknowledgment signals or
similar to the safety program and provide status information to the controller.
The states of the ASi Safety in- and outputs are sent to the controller via the input
data image (see par. <Safety diagnostics in the Input Data Image (IDI)>).
The bits of the output data bytes are ORed with the real and homonymous hard-
ware inputs of the device.
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
13
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
The bits of the output data bytes are ORed with the real and homonymous hard-
ware inputs of the device.
14 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
The module contains the diagnostics for the safety outputs in your safety monitor.
Each release circuit corresponds to a safety output.
Output data
Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
SI 4/ SI 3/ SI 2/ SI 1/
1 reserved
2.Y2 2.Y1 1.Y2 1.Y1
2 reserved
Tab. 3-14.
The bits of the output data bytes are ORed with the real and homonymous hard-
ware inputs of the device.
Input Data
Byte Meaning
0 Safety Status OSSD 1
1 Safety Status OSSD 2
... …
n Safety Status OSSD n
Tab. 3-15.
Issue date: 27.06.2023
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
15
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
The table shows the color coding as represented in the ASIMON360 software.
16 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
The module contains 6 bytes of information about the current switching states of
the local in- and outputs on the gateway as well as 1 byte of monitor information.
These are encoded as follows:
Input data
Byte Description
1 Monitor Info
2 Status SI1/SI2
3 Status SI3/SI4
4 Status SI5/SI6
5 Status SO1/SO2
6 Status SO3/SO4
7 Status SO5/SO6
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
17
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
18 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
The Safe Link process data diagnostics allows you to visualize the status of the
safe link between the various gateways in the controller.
St. Adr. data assignment out of the list 'Node overview' (bytes 1-8) and node status:
Bit-combination Meaning
11 active
01 not active
10 not taught (only in the manager, message with the highest priority)
00 not used
Note!
All Safe Link participants must be in the same subnet.
Issue date: 27.06.2023
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
19
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
3.2.1 DP diagnostics
DP diagnostics
Byte description
1 station status 1
2 station status 2
3 station status 3
4 master address
5 ident high
6 ident low
The following blocks can be attached to the DP-diagnosis optionally. According to
the PROFIBUS standard, the bytes 1 … 4 are transmitted in each block.
Only when double masters are used, the entry „circuit 2“ is available in the AS-i
flags, delta list and LPF.
ASi flags
structure 0xA0: circuit 1
structure 0xA1: circuit 2
Byte bit message
1 0 config error
1 1 slave 0 detected
1 2 automatic addressing not possible
1 3 automatic addressing possible
1 4 configuration mode
1 5 no normal operation
1 6 ASi power fail
1 7 off-line
0 0 peripheral fault
0 1 —
0 2 —
0 3 —
0 4 earth fault
0 5 overvoltage
0 6 noise
0 7 double addressing
Tab. 3-18.
Issue date: 27.06.2023
20 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
21
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
Each element of the manufacturer diagnostics (EC-flags and lists of nodes) can
be switched off by setting the appropriate bit in the parameter telegram.
ExtDiag will be set if at least one of the following conditions is fulfilled:
• ConfigError ≡ 1
• APF ≡ 1
• PeripheralFault ≡ 1
• EarthFault ≡ 1
• DuplicateAddr ≡ 1
Evaluation of results can be individually activated/deactivated via PROFIBUS pa-
rameter or command interface.
The configuration file includes the following presettings:
• The diagnosis transmits EC-flags, DeltaList, LPF, EarthFault and Dupli-
cateAddr.
• ExtDiag will be set if ConfigError ≡ 1 and APF ≡ 1.
ExtDiag will not be set if PeripheralFault ≡ 1, EarthFault ≡ 1 and Dupli-
cateAddr ≡ 1
22 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
Language
This parameter is used to select the display language.
Freeze diagnosis
The diagnostics data are continually updated during run time. If this is not de-
sired, this parameter can be used to turn off continual updating. An update then
only occurs if it is requested by the PROFIBUS standard.
Safety status
This parameter defines whether the status of the save nodes (red or yellow
flashing) should be displayed in the diagnostics.
Power supply
Issue date: 27.06.2023
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
23
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIBUS
The setting ASi power supply should be made if an ASi power supply or a DC
power supply ungrounded on the secondary side is used. This setting is suitable
for all Bihl+Wiedemann power supplies, provided that they are not externally
grounded on the secondary side.
The setting Grounded 24 V power supply should be made if a DC power supply
is used on which secondary-side grounding exists (e.g. because the 0V is
grounded).
Power-on off-line
This parameter defines whether the ASi master should be on-line or off-line at
power-on.
Failsafe behaviour
This parameter defines the response of the master when ASi nodes fail:
Substitution values
Setting the substitution of input data for safety ASi nodes.
24 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIsafe
4. PROFIsafe
Note!
An ASi gateway operated as PROFIsafe master does not replace the PROFIBUS
master / controller.
Thus, an additional PROFIBUS control is required in any case, regardless of whether
the gateway is operated as PROFIsafe master or PROFIsafe node.
message is generated.
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
25
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIsafe
If you are using a gateway with two ASi masters and one of the two masters is in
Projecting mode, PROFIsafe considers the entire device to be in Projecting
mode.
The display menu can also be used to query the status of PROFIsafe communi-
cation:
Main menu || SAFETY || PROFISAFE || STATUS
Status:
[1] inactive
[2] C:00 S:00 D:00
26 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
PROFIsafe
Byte Description
1 0x06 Header
2 0xAC
3 0x00 Slot
4 0x00 Spec
5 Diagnostic value
0x00 No error
0x40 Conflict at the destination address. The PROFIsafe destination
address in the parameters does not match to the destination
address configured in the device.
0x41 Invalid destination address (0 or 65535)
0x42 Invalid source address (0 or 65535)
0x43 Invalid watchdog time
0x44 SIL value too high. The SIL value in the PROFIsafe parameters
beyond the capabilities of the device.
0x45 Invalid length of the CRC2 (based on the PROFIsafe version)
0x46 Invalid PROFIsafe version. The PROFIsafe version in the
PROFIsafe parameters is not supported by the device.
0x47 CRC1 error. The CRC over the PROFIsafe parameters does not
match.
0x48 Invalid PROFIsafe parameter
0x49-0x4A Reserved
0x4B The IPAR CRC does not match to the release-code of the moni-
tor configuration.
Tab. 4-23.
Note!
The devices use PROFIsafe addressing type 1.
The F destination address (F_Dest_Add) must be unique network-wide because only
this address ensures the uniqueness of the PROFIsafe address. The F source
address (F_Source_Add) is not evaluated.
Note!
If there is an error in the F peripherals, the Device_Fault bit in the status byte is set to
"1" and then back to "0" again as soon as the error is rectified.
To prevent uncontrolled startup of the F peripherals, additional measures, e.g.
"manual reintegration", must be implemented in the safety program of the PLC.
Issue date: 27.06.2023
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
27
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
5.2.3 ASIMON360
The ASIMON360 software is used to configure the safety unit. Already configured
systems can be diagnosed live using the software. The status of all in- and out-
puts is graphically represented as are the results of the preparatory processing.
When projecting the user has the ability to assign unique identifiers to the individ-
ual devices. These also appear in the device displays in connection with error
messages. To prevent errors in the projecting stage the ASIMON360 software
provides advance warning at the relevant points.
28 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
29
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
Bits 2 and 3 are used to send the status of the safety input (the device color of the
ASIMON360):
30 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
The diagnostic informations are transfered via the Input Data Image, coded to the
input bits of the diagnostic address (diagnostic node) of an ASi safety module.
The diagnostics information for the safety output is encoded to the input data of
the diagnostics node of the respective safety output.
Device colors
The colors refer to the diagnostics in the ASIMON360.
LED
Value Color Description state change "OUT" (1)
0 green output on – on
green
1 – – –
flashing
2 yellow restart inhibit auxiliary signal 2 1 Hz
yellow
3 – – –
flashing
4 red output off – off
waiting for reset of error
5 red flashing auxiliary signal 1 8 Hz
condition
connection or only via Power On all LEDs
6 gray
internal error on device flashing
output released, switched on by setting
7 green/yellow off
but not switched on the output bit1
Tab. 5-27. Device colors
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
31
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
Important!
The following points must be noted for processing:
• The color information of the device is only available if the safe input is also
used within the Safety Monitor.
• The information for switching state and error status are not processed time-
synchronous.
• When there is a configuration error all bits having value 0 are sent; this must
be noted when processing the data.
• When the Monitor is stopped the device color is "gray".
• When regularly switching, the status "yellow flashing" can be recognized as a
transition status. This depends on the component model set. This status can-
not be understood as a testing request until it is stably reported (see Monitor
Info and Safety Control/Status Byte). This is not the case until bit ’6’ is set in
the Monitor Info and Safety Control/Status Byte ("At least one module in Test
status"). This means the diagnostics information in the input data image does
not serve as a trigger for the testing request, but rather only as detailed infor-
mation after the Monitor Info and Safety Control/Status byte have indicated
that at least one component has reported a testing request.
32 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
5.4.1 LEDs
The LEDs located on the device allow you to quickly see the status of the main
function parameters, such as power, communication with the host controller, com-
munication on the ASi circuit and state of the safety in- and outputs.
5.4.2 LC-Display
In the display of the Gateways plain text messages are shown spontaneously for
any detected errors (e.g. missing nodes, earth fault, duplicate address…).
Configuration error
The actual configuration found on ASi does not match the projected configura-
tion, or the ASi master performs startup operations.
Node 0 detected
There is an ASi node with zero address.
Configuration mode
The ASi master is in configuration mode.
No normal operation
ASi master is performing startup operations
Off-line
ASi master doesn't send telegrams on ASi
Issue date: 27.06.2023
Peripheral fault
At least one ASi node reports a peripheral fault, or the ASi master performs start-
up operations.
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
33
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
24V AUX
External 24 V voltage is present.
Power-Fail 24V
External 24 V voltage is not present.
Earth fault
The earth fault monitor checks the symmetry of the ASi voltage. If the voltage is
no longer sufficiently symmetrical, the noise immunity of data transmission is
compromised.
Overvoltage
Normally UASi+ and UASi- are in symmetry with system ground. If this potential
rises significantly, the overvoltage detector reports this anomaly.
Noise voltage
Noise voltages on the ASi cable can cause telegram errors. The noise voltage
detector monitors the ASi circuit for AC voltages which have been generated by
neither the ASi Master nor the nodes.
Duplicate address
The Master detects when two nodes having the same address are present in the
ASi circuit.
34 Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Manual
PROFIBUS Gateways
Appendix
6. Appendix
6.1 Quick Start Guides
Quick Start Guides for commissioning and service are provided on the Bihl+Wie-
demann website available for download.
Issue date: 27.06.2023
Subject to technical modifications; no responsibility is accepted for the accuracy of this information © Bihl+Wiedemann GmbH
35
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399