APPROVED DOCUMENT
Technical Data Sheet
HCI634K
SPECIFICATIONS & OPTIONS
Stamford industrial generators meet the requirements All generator rotors are dynamically balanced to better
of BS EN 60034 and the relevant section of other than BS6861:Part 1 Grade 2.5 for minimum vibration in
international standards such as BS5000, VDE 0530, operation. Two bearing generators are balanced with a
NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. half key.
Other standards and certifications can be considered
on request.
INSULATION/IMPREGNATION
2
HCI634K
WINDING 13
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321
PROTECTION IP23
WINDING LEADS 6
MAIN STATOR RESISTANCE 0.001 Ohms PER PHASE AT 22°C STAR CONNECTED
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
1 BEARING 2 BEARING
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.185s
T''d SUB-TRANSTIME CONST. 0.025s
T'do O.C. FIELD TIME CONST. 3.4s
Ta ARMATURE TIME CONST. 0.049s
SHORT CIRCUIT RATIO 1/Xd
3
HCI634K
Winding 13
APPROVED DOCUMENT
4
HCI634K
Winding 13
Locked Rotor Motor Starting Curve
380V 400V 416V
30
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
APPROVED DOCUMENT
5
0
0 500 1000 1500 2000 2500 3000 3500 4000
LOCKED ROTOR kVA
SYMMETRICAL
ASYMMETRICAL
CURRENT (Amps)
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
Note 1 Note 2
The following multiplication factors should The following multiplication factor should be used to convert the values
be used to adjust the values from curve calculated in accordance with NOTE 1 to those applicable to the various
between time 0.001 seconds and the types of short circuit :
minimum current point in respect of nominal
operating voltage :
3-phase 2-phase L-L 1-phase L-N
Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380 X 1.00 Minimum x 1.00 x 1.80 x 3.20
400 X 1.05 Sustained x 1.00 x 1.50 x 2.50
416 X 1.09 Max. sustained duration 10 sec. 5 sec. 2 sec.
All other times are unchanged
The sustained current value is constant
irrespective of voltage level 5
HCI634K
Winding 13 / 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Star (V) 380 400 416 380 400 416 380 400 416 380 400 416
60Hz
Delta (V) 220 230 240 220 230 240 220 230 240 220 230 240
kVA 1260 1260 1260 1375 1375 1375 1455 1455 1455 1500 1500 1500
kW 1008 1008 1008 1100 1100 1100 1164 1164 1164 1200 1200 1200
Efficiency (%) 95.6 95.7 95.7 95.4 95.6 95.6 95.3 95.5 95.5 95.2 95.4 95.5
kW Input 1054 1053 1053 1152 1151 1150 1221 1219 1218 1260 1258 1257
APPROVED DOCUMENT
DIMENSIONS
SAE 14 18 21 24
AN 25.4 15.87 0 0
6
APPROVED DOCUMENT
www.cumminsgeneratortechnologies.com
HCI6K-13-TD-EN-SG-A