MEGATIKER M3 125-160/250
Trip Unit
05/04/2023 – rev. 2
Factory settings:
Ir = In
Protection Seals:
It’s possible to seal the adjustements Before the adjustment, the
at minimum and maxiumum value. breaker must be in trip
Not allowed in intermediate values. position
Factory settings:
Ir = In
Protection Seals:
It’s possible to seal the adjustements Before the adjustment, the
at minimum and maxiumum value. breaker must be in trip
Not allowed in intermediate values. position
Settings:
Factory settings:
Protection Seals: Ir =1xIn
It’s possible to seal the Ii = 10xIn / 13xIn
adjustements at minimum
and maxiumum value. Before the adjustment, the
Not allowed in intermediate breaker must be in trip position
values.
Settings:
Factory settings:
Ii = 14In
Protection Seals:
It’s possible to seal the
adjustements at minimum and Before the adjustment, the
maxiumum value. breaker must be in trip
Not allowed in intermediate position
values.
Protection Seals:
the window in front of ajusters
can be sealed
➢ Activation/deactivation REMARK
➢ Fine prot. adjustments • It’s not possible to deactivate RCD and Isf protections.
➢ Advanced settings • Dinamic selectivity adjustment (HIGH/LOW) no longer present.
Electrical Infrastructures SBU
250 (ELE S10) – ELECTRONIC PROTECTION S10
COMING
SOON ! 13
Settings for breakers from FRONTAL BUTTONS:
Factory settings:
IΔn = 0.03A;
tΔ = 0s
Class of use:
Type A
Factory settings:
IΔn = 0.03A;
tΔ = 0s
Class of use:
Type A
Factory settings:
IΔn = 0.03A;
tΔ = 0s
Class of use:
Type A
Navigation buttons
Class of use:
Type A Factory settings:
IΔn = 0.03A;
REMARK: tΔ = 0s
The USB socket is always accessible
even with display cover sealed, for
diagnostics purpose. The RCD protection can’t
So, the mechanical seal cannot be deactivated by means
prevent the protection adjustments of dongle or PCS
via software (PIN needed).
AC DC
AC DC
AC DC
COMING
SOON !
S1 S10
S1 S10
REMIND: Dinamic
selectivity settings
(HIGH/LOW) are no
longer available,
but the S10 trip
characteristics
over Isf is
equivalent to old
S2/Sg set in HIGH
S1 S10
COMING
SOON !
Ig/tg setting
NOT AVAILABLE
S1 S10
(6)
POWER METERING
DEVICE
(PMD)
Ea 2
ErA, ErV 2
f 0,1
I 1
U 0,5
LEGENDA PFV 0,5
QA: Total reactive power arithmetic
THDU (3P), THDV (4P) 5
QV: Total reactive power vector
ErA: Total reactive energy arithmetic THDI 5
ErV: Total reactive energy vector
U: Voltage (Line-Line or Line-Neutral)
PFV: Power Factor vector
THDU , THDV: Voltage THD (Line-Line, Line-Neutral)
THDI : Current THD
Green and red LED alternatively blink Alarm overtemperature ➔ T > 90°C 1 The trip occurs at
95°C
Red LED blinks Alarm ➔ IΔ>60%IΔN 2
Batteries are useful in order to navigate and adjust the protection in absence of current on plant (or
voltage, in case the breaker is with RCD integrated) or auxiliary supply.
In absence of batteries or with battery low, the ETU continue to work correctly and the protection
settings and fault hystory log will not get lost.
REMIND
Battery supply is not used for keep the protection state LED lighted in case of tripping.
(1)
Current higher than
35%In
(2)
External auxiliary Without current on plant
supply activated (by and auxiliary module, the
external module or backlight is not activated,
communication even if batteries are
interface). present and charged
(3) Note: The display backlight gets activated also by miniUSB port (connected to the dongle or a PC)
Protections and
advanced functions
NB: NOT
needed for
protection
REMIND
In order to guarantee the
correct working of
advanced features, the
NB: with external auxiliary supply
specific
interface
must be assured
➢ System modality:
▪ Stand alone;
Address: 1…9
▪ Supervision /
Remote monitoring
Address: 1…9 x9
1…247
REMIND:
➢ Max n°3 supplier x EMS system
➢ Max 3m bus x EMS system
➢ Max 32 devices x EMS/RS485
interface
➢ Max 247 devices x RS485 system
ATTENTION:
The operating mode of logical selectivity present
on new MCCBs S10 (but also for new ACBs) is
different than the old one in order to make it more
effective in the different work conditions.
Anyway two different logics (OLD and NEW) can work
togheter on the same installation (see retrofit
solutions for more details).
The DINAMIC
DOWNSTREAM SELECTIVITY («HI/LOW»)
LEVEL does not need to be
adjusted and it is NO
LONGER AVAILABLE on
new devices
CASE 1
CASE 2
In order to perform the dielectric test for RCD breakers, it’s necessary disconnect the electronic
card by means of DIELECTRIC TEST SELECTOR
1. Open the 2. Rotate the 3. Carry out the 4. Rotate the selector
dielectric selector in dielectric test in «NORMAL USE»
test slider: the «DIELECTRIC TEST position and close the
breaker trips POSITION» dielectric test slider
Electrical Infrastructures SBU
125-160/250 (TM/ELE +RCD) – RCD PROTECTION TRIP TEST 59
The earth leakage device must be
periodically checked performing the
diagnostic trip test.
➢ In case of electronic S1 protection unit, the trip test can be performed only by Technical Assistance, by means
of specific PC/breaker interface (internal reference code);
➢ In case of electronic S10 protection unit, the trip test can be performed by customer too.
REMIND
The protection trip
curve cannot be
verified,
Power Test Equipment
(PTE), Power Control
Station (PCS) and
Enerup+Project are not
able to verify the
protection charactestics
(overcurrent trip curve) S1 S10
❑ General device and installation state (presence of conductive dust, burning signs,
insulation losses, breakings...);
❑ If the device has an integrated RCD, verify the tripping indicator: if yellow, the
device has protected an earth leakeage fault.
The entity of fault can be checked only on ELE+RCD devices by means of USB port
or display, if present).
❑ If the device has an electronic release S10, verify the protection unit display in
order to quickly confirm if the device has protected an overcurrent fault (last
trip menu page). For more details, it’s always possible to connect the device to a PC
or mobile device by mini USB port, in order to check the full hystory log with details on
phases/protections involved.
For S1 devices, the last trip indication and the trip log can be checked only by
means of SERVICE port (S1) by Technical Assistance and Service team.