Scope of Work of this this sample specification covers the supply, installation,
testing and commissioning of all wiring materials for power and lighting in
concealed and/or surface conduits.
1. APPLICABLE STANDARDS
The conduits shall conform to IS 9537 I & II or equivalent standards. Switches,
Plug Sockets shall conform to IS 3854 and IS 4615, however, contractor shall
comply with the latest or superseded versions of IS/BIS to be used for the
complete work.
6. LAYING OF CONDUITS
1. Conduits which are to be taken in the ceiling slab shall be laid on the
prepared shuttering work of the ceiling slab before concrete is poured. The
conduits, boxes, accessories, joints, etc. shall be laid along with the
conduits.
2. Conduits recessed in walls be fixed rigidly with staples at maximum 1 M
intervals. All chases shall be properly filled and concreted and finished.
The conduit boxes, accessories, joints, etc. shall be laid along with the
conduits. The chases shall be sufficiently deep and properly filled with
cement mortar.
3. All chases, grooves shall be neatly made to proper dimensions to
accommodate the required number and size of conduits and staples. The
outlet boxes, point control boxes, inspection and draw boxes shall be fixed
as an when conduit is being laid. The recessing of conduits in walls shall be
so arranged as to allow atleast 12 mm plaster over the same.
4. All grooves, chases, etc. shall be refilled with cement mortar and finished
upto the wall surface before plastering of walls is taken up by the General
Contractor. Where conduits pass through expansion joints in the building,
adequate expansion fittings or other approved services shall be used to take
care of any relative movement. As far as possible, chasing of wall to embed
the conduits to be avoided. Conduits with switch boxes to be fixed and
supported before brick work has commenced.
5. Wherever surface conduit system is specified, only steel conduits shall be
used and conduits shall be fixed by means of GI saddles. Conduits shall be
run in square and symmetrical line with proper drawing.
6. Concealed conduits in slabs shall be brought out as vertical drops in beams,
wherever such drops are required. All vertical conduits in beams shall be
left protruding from the bottom of the beam, atleast 150 mm in length. All
such ends of conduits protruding from bottom of beams shall be provided
with couplings to receive extension. The open ends should be protected
during concreting.
7. Vertical conduits in wall shall be laid and terminated in switch boxes,
before the brick walls are erected. Chiseling of brick walls for laying such
conduits will not be allowed. The terminations of conduits shall be in GI
PVC boxes and the size of the boxes shall be suitable to accommodate all
control switches required for that particular location.
8. The switch boxes shall be of GI/PVC and shall be fixed to the conduits with
adapters. The switch box shall be flush with the plaster and it shall be
contractors' responsibility to cut open the brick work and plaster wherever
necessary to make good the surface for achieving flush finish. The height of
the switch boxes shall be as indicated in the drawings. The switch boxes
should be sufficient depth to give minimum 20 mm plaster cover to
conduits embedded.