CONDUIT WIRING IN ELECTRICAL CONSTRUCTION


CONTRACT WORKS
 

Scope of Work of this this sample specification covers the supply, installation,
testing and commissioning of all wiring materials for power and lighting in
concealed and/or surface conduits.

1. APPLICABLE STANDARDS
The conduits shall conform to IS 9537 I & II  or equivalent standards. Switches,
Plug Sockets shall conform to IS 3854 and IS 4615, however, contractor shall
comply with the latest or superseded versions of IS/BIS to be used for the
complete work.
 

2. WIRING SYSTEM DETAILS


1. All wiring to lights, fans, convenience outlets, call bells, etc. will be
considered on 'point rate' basis and shall include the required length of
wires from sub-distribution board outlet to the ceiling roses, switches,
convenience outlet sockets, bell pushes, call bells, connectors, etc. The
wiring shall be carried out separately for 'lighting' and power as indicated
in the drawings.
2. All conduits shall be run as far as possible along the walls and ceiling and
above false ceilings so as to be easily accessible for inspection if need be.
While the Architects drawings indicate the distribution for light and power
points, it shall be the contractors' responsibility as well, to balance the load
on all the three phases for an even distribution. Before commencement of
work, the contractor shall seek the approval of the Consultants on the
distribution of balancing of loads and circuits. The wiring shall be done by
the process of looping the live conductors and the neutral wires. 
3. Bare or twist joints shall be carried out with due care and preferably
through proper junction boxes.
4. Before commencement of work, the contractor shall seek the approval of
the Architects/Consultants on the layout of the conduit runs. Separate
conduits shall be run for lighting and power circuits and also for telephone
cables. To avoid any cross talk and extraneous interference in the
telephone circuits, all telephone wiring conduits shall be run with a
sufficient clearance from the power and lighting conduits.
5. All separate circuits from DB's shall have separate neutral to the points.
Common neutral between separate circuits are not permissible.
6. As far as possible wiring shall be run in conduits. Any open wiring to be
done shall first be approved by the Architects/Owners.  All conduit wiring
shall be complete with continuous earth as per I.E.R.
7. The wiring shall be carried out as specified.  'Power' and 'heating' wiring
shall be kept separate and distinct from 'Lighting' wiring. The wiring shall
be done on the distribution system with main and branch distribution
boards at convenient physical and electrical centers and consideration shall
be given for neatness and good appearance.
8. The wiring shall be done in the 'Looping System. 'Phase' or 'live'
conductors shall be looped at the switch box and neutral conductor can be
looped from the light fan or socket outlets. 1.5 sq. mm PVC wires in green
colour are to be run continuously in conduits for continuous earthing. The
earth wire should be connected to GI Switch boxes and DB boxes by tapped
screws.
9. No bare or twist joints shall be made at intermediate points in the through
run of cables.
10.If any joint becomes unavoidable such joints shall be made through proper
cutouts or through proper junction boxes open to easy inspections.

Electrical Lighting Layout Conduit Installation


3. CABLES, WIRES & FLEXIBLE CORDS
1. All conductors shall be of electrolytic copper. The wires and cords shall
have adequate cross-section and current carrying capacities for the
intended loads. The minimum size of conductor used shall have a nominal
cross section area 1.5 sq. mm copper for lighting and 2.5 sq. mm copper for
power. In case of aluminium wires, 2.5 sq. mm wires for lighting and 4 sq.
mm wires for power and 2.5 sq. mm wires for earthing shall be used.
2. The cables, wires and cords shall be PVC insulated type. Cables which are
to be run in areas where there  is likelihood  of damage to the PVC
insulation, all such cables shall be of the armored type. Cables and wires
run through walls shall be run in conduits only.
3. The rates for laying of low tension cables shall include all hardwares like
trays, racks, cleats, etc.  Separate rates for such items shall not be
considered.

4. CONDUITS & ACCESSORIES - MS/FLO COATED


CONDUITS
1. Steel conduiting shall be conforming to relevant IS specifications (IS 9537).
All steel conduits shall be of heavy gauge, welded and threaded type. 
Conduit accessories such as boxes, bends, inspection bends, boxes, elbows,
reducers, etc. shall conform to relevant standards.  As far as possible, boxes
shall have internally tapped spouts to receive the conduits.
2. All conduits and accessories shall be cleaned and painted with two coats of
bituminous paint before  installation.  Where conduits are installed in
straight run, draw boxes shall be provided at intervals not exceeding 30
feet(9 meters). Between two consecutive draw boxes, the right angle bends
shall not exceed two in number. Conduits shall be properly threaded and
screwed in to the accessories.
3. The minimum size of conduits used shall be 20 mm. The minimum
thickness of the conduits shall be 16 SWG.
4. Wherever steel conduits terminate into points control boxes, distribution
boards, etc. conduits shall be rigidly connected to the boxes, boards, etc.
with check nuts on either side of the entry to ensure electrical continuity
and with PVC or bakelite bushes. Turning joints in conduits wherever
necessary shall be rigidly held in aligned position by check nut tightened on
the running side. After conduits, junction boxes, outlets, etc. are fixed in
position, their outlets shall be properly plugged with PVC stop cover or
with any other suitable material so that water, mortar, vermin or any other
foreign material do not enter into the conduit system.
5. All steel conduit runs shall have 3/22 PVC green copper earth continuity
wire throughout the lengths inside the conduits.

5. CONDUITS & ACCESSORIES - PVC CONDUITS


1. PVC conduits shall be ISI grade and it shall be rigid type.  Where conduits
are laid in straight run, draw boxes shall be provided at intervals not
exceeding 10 meters.  Between two consecutive draw boxes the right angle
bends shall not exceed two in number.
2. PVC conduits shall have continuous run of PVC insulated wires inside the
conduit for earthing. Terminations of PVC conduits into switch boxes, DBs,
etc. shall be with adapters.  PVC conduits shall be fixed to accessories such
as coupler, circular boxes, etc. with vinyl cement.

6. LAYING OF CONDUITS
1. Conduits which are to be taken in the ceiling slab shall be laid on the
prepared shuttering work of the ceiling slab before concrete is poured. The
conduits, boxes, accessories, joints, etc. shall be laid along with the
conduits.
2. Conduits recessed in walls be fixed rigidly with staples at maximum 1 M
intervals. All chases shall be properly filled and concreted and finished.
The conduit boxes, accessories, joints, etc. shall be laid along with the
conduits. The chases shall be sufficiently deep and properly filled with
cement mortar.
3. All chases, grooves shall be neatly made to proper dimensions to
accommodate the required number and size of conduits and staples. The
outlet boxes, point control boxes, inspection and draw boxes shall be fixed
as an when conduit is being laid. The recessing of conduits in walls shall be
so arranged as to allow atleast  12 mm plaster over the same. 
4. All grooves, chases, etc. shall be refilled with cement mortar and finished
upto the wall surface before plastering of walls is taken up by the General
Contractor.  Where conduits pass through expansion joints in the building,
adequate expansion fittings or other approved services shall be used to take
care of any relative movement. As far as possible, chasing of wall to embed
the conduits to be avoided. Conduits with switch boxes to be fixed and
supported before brick work has commenced.
5. Wherever surface conduit system is specified, only steel conduits shall be
used and conduits shall be fixed by means of GI saddles. Conduits shall be
run in square and symmetrical line with proper drawing.
6. Concealed conduits in slabs shall be brought out as vertical drops in beams,
wherever such drops are required.  All vertical conduits in beams shall be
left protruding from the bottom of the beam, atleast 150 mm in length. All
such ends of conduits protruding from bottom of beams shall be provided
with couplings  to receive extension. The open ends should be protected
during concreting.
7. Vertical conduits in wall shall be laid and terminated in switch boxes,
before the brick walls are erected.  Chiseling of brick walls for laying such
conduits will not be allowed. The terminations of conduits shall be in GI
PVC boxes and the size of the boxes shall be suitable to accommodate all
control switches required for that particular location.
8. The switch boxes shall be of GI/PVC and shall be fixed to the conduits with
adapters. The switch box shall be flush with the plaster and it shall be
contractors' responsibility to cut open the brick work and plaster wherever
necessary to make good the surface for achieving flush finish. The height of
the switch boxes shall be as indicated in the drawings. The switch boxes
should be sufficient depth to give minimum 20 mm  plaster cover to
conduits embedded.

7. BRANCH SWITCHES, CONVENIENCE OUTLETS


AND CEILING ROSE
1. All branch switches shall be installed in the phase circuit in the
distribution. All switches shall be of rocker pattern type incorporating solid
silver contacts suitably enclosed.  Where conduits are  concealed, switches
will be of the flush type with single or multiple gang plates. Where conduits
are on surface, the switches shall be mounted on surface type GI boxes
after obtaining approval of the Architects/Owner.  All switches shall be of
adequate current carrying capacities for specified load application.
2. The convenience outlets shall be of 5A/15A/20A rating as specified. All
sockets shall be of 3 pin type and 5 pin as required and shall conform to the
Indian Standards. The socket outlets shall be mounted  on heights specified
on drawings and in consultation with the Architects/Owners. All wiring
shall be on looping system of wiring.
3. All ceiling rose shall be suitable for use on 250V. Ceiling rose shall not be
used for voltage level higher than 250 volts. Only one flexible cord shall be
attached to ceiling rose.
4. All light points on ceiling shall be terminated in bakelite lamp holders of
fluorescent as per drawings. All points shall be left connected to PVC
terminals. Terminations to light fixtures shall be through 3 way terminals.
All light points on wall shall be terminated on angular lamp holders fixed
directly on PVC round box.
5. The lamp holders shall be white in colour.  Samples shall be submitted for
Architect's approval PVC Boxes in the ceiling are to be covered with round
cover flush with the ceiling and screwed to the box properly. The flexible
wire extension is to be connected by means of suitable connectors inside
the box.  Wooden round blocks are not to be used any where in the ceiling
or wall. All point opening shall be properly finished in plaster.
6. The single pole circuits switches, decorative type 5 Amps and 15 Amps with
or without plug sockets shall be approved by Architects before installation.
7. The following Indian Standard Specifications are applicable for decorative
switches.
1. IS 3854 1966: Switches for domestic and similar purpose.
2. IS 1293 1967: Three pin plug and socket outlets.
3. IS 4614 1968: Switch Socket outlet (non-interlocking type)
4. IS 6538 1971: Three pin plugs made of resistant materials.

 

ELECTRICAL INSTALLATION

CONSTRUCTION SPECIFICATION

CONDUIT INSTALLATION

ELECTRICAL CONDUIT

WIRING METHOD

 Log in or register to post comments

BOOK TRAVERSAL LINKS FOR CONDUIT WIRING


IN ELECTRICAL CONSTRUCTION CONTRACT
WORKS
 ‹ Conditions Of Sub-Contract Agreement In Construction
 

 Up

 Connecting Methods of Electrical Earthing or Grounding ›

RELATED POSTS

INSTALLATION OF STRUCTURED CABLING FOR VOICE / DATA SYSTEM IN


BUILDING CONSTRUCTION
EMERGENCY POWER DIESEL GENERATING SET IN ELECTRICAL
CONSTRUCTION

ELECTRICAL ENGINEERING

AUTOMATIC TRANSFER SWITCH (ATS) OR AUTOMATIC MAINS FAILURE


(AMF) PANEL
Search
Username
Password
 Create new account
 Reset your password
MAIN NAVIGATION
 Home
 Log in
TOOLS
 Cookie settings
 Recent content
 Sources
 Aggregator
 List Of Madhya Pradesh Scheduled Castes (SC) And Scheduled Tribes (ST)
 List Of Socially And Educationally Backward Classes (SEBC) in Andhra Pradesh
 List of Andhra Pradesh Scheduled Castes (SC) and Scheduled Tribes (ST)
 LPG Connection Transfer Due To Change Of Address - Same City / Distributor
(BharatGas, HPGas, And IndaneGas)
 LPG Connection Transfer Due To Change Of Address - Same City / Distributor
(BharatGas, HPGas, And IndaneGas)
 Janaushadhi Medical Store or Jan Aushadhi Kendra or Jan Aushadhi Generic Drug Store
 Janaushadhi Medical Store or Jan Aushadhi Kendra or Jan Aushadhi Generic Drug Store
 LPG Connection Transfer Procedures
 List Of Socially And Educationally Backward Classes (SEBC) in Karnataka
 LPG Connection Transfer Procedures
 List Of Socially And Educationally Backward Classes (SEBC) in Karnataka
 List Of Denotified Communities In Tamil Nadu
 List of Tamil Nadu Backward Classes (BC), Muslims and Most Backward Classes
 List Of Denotified Communities In Tamil Nadu
 List of Tamil Nadu Backward Classes (BC), Muslims and Most Backward Classes
 The Impact of PM MUDRA Yojana Or PM MUDRA Scheme In Indian Financial Sector
 The Impact of PM MUDRA Yojana Or PM MUDRA Scheme In Indian Financial Sector
 Procedure of Youth Club Formation and Registration in India
 Income, Income Certificate and Application Form For Income Certificate
 Union Bank Of India (UBI) Pradhan Mantri Mudra Yojana (PMMY) Scheme for
Collateral Free Bank Loan
More
 Maverick Windows
 Atmosphere Air Care
 Star Gate & Fence
 A to Z Quality Fencing & Structures
 Tyrone Garage Door Masters
 24 Hour Pinecrest Locksmith
 Pro-Tech Locksmith
 J&R Construction Services, Inc.
 Law Offices of Marc S. Albert Injury and Accident Attorneys
 First Impression Graphics
 Peabody Optimal Door
 Lilburn Garage Door Repair
 Green California Dental Group
 AnandaCare | Rehabilitation Center in Delhi
 Webster Secure Locksmith
 State to State Move
 Canyon Lake Hospice Care
 Serenity Hospice Care Provider
 Good Heart Hospice and Palliative Care
 mydoc urgent care
More
© 2020. Electricveda.com. All Rights Reserved.

You might also like