1 General
Note: The recommended feed and boiler water characteristics are only valid
for boilers with a working pressure below 20 barg.
There is a number of ways to produce good quality feed water for boiler plants.
Methods such as e.g. reverse osmosis plants or ion exchange plants produce good
quality distillate. Also evaporators generally produce good distillate. The important
thing is that the distillate used should be clean and without foreign salt
contamination.
In practice most distillates used contain minor parts of various salt combinations
which can and must be chemically treated away. Furthermore, the distillate may
contain dissolved gases like for example oxygen (O 2) and carbon dioxide (CO2)
which may lead to corrosion in the boiler, steam, and condensate system.
Important: Boiler and feed water must be chemically treated in order to avoid
corrosion and scaling in the boiler.
Table 1
If hydrazine (N2H4) is not used, sodium sulphate (Na2SO3) can be used instead, and
the excess should be 30 - 60 ppm.
In cases where other kinds of oxygen binding agents are used, it is recommended
that an excess of oxygen binding agents can be measured and indicates that no
oxygen has been dissolved in the boiler water.
If it is requested to measure the content of dissolved oxygen directly, it is
recommended to keep the value 0.02 ppm.
In addition to the above values, the various water treatment companies will add
further demands, depending on the method used for treatment of feed and boiler
water.
However, the most important point is that the above values or their equivalents are
observed and that a regular (daily) test of feed and boiler water is carried out.
Concentrations are usually expressed in "ppm" i.e. parts solute per million.
Concentrations for parts solution by weight are the same as "mg/litre".
3.1.1 Specific gravity
As guidance the following conversion can be used:
1 Be = 10.000 mg/l total dissolved solids (TDS)
1 mg/l total dissolved solids = 2 S/cm
1 S/cm = 1 mho
4.1.2 Weekly
Step A: Skimming (surface blow down) according to analyses, but at least once per
week (2 minutes with fully open valve).
Step B: Blow down (bottom blow down) according to analyses, but at least once per
week (each blow down valve 1 minute in low load condition).
4.1.3 Monthly
Step A: Check the functions for salinity and oil detection systems.
Step A: The boiler water side (interior) must be carefully inspected at least twice a
year.
4.1.5 Yearly
Step A: Check of the water side of the boiler and hotwell/deaerator for corrosion
and scaling.
Step B: Use the name of the manufacturer and type of chemicals to select which
tables that can be used.
Step C: Check the flow diagrams (Figure 1, Figure 2, or Figure 3) to find a diagram
that matches the actual boiler plant.
Step D: Find in the selected tables the table which includes the matching diagram.
Step E: If more than one table is found to match the actual boiler plant in question it
is recommended to use the method/table which includes note No. 1.
Table No. 2
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 3
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 4
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 5
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 7
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 8
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 9
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 10
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 12
Manufacturer / supplier: Ashland Chemical / Drew Marine Division
Table No. 13
Manufacturer / supplier: Marichem
Table No. 14
Manufacturer / supplier: Marichem
Table No. 15
Manufacturer / supplier: Marichem
Table No. 17
Manufacturer / supplier: Marichem
Table No. 18
Manufacturer / supplier: Marichem
Table No. 19
Manufacturer / supplier: Unitor Chemicals
Table No. 20
Manufacturer / supplier: Unitor Chemicals
Table No. 22
Manufacturer / supplier: Unitor Chemicals
Table No. 23
Manufacturer / supplier: Unitor Chemicals
Table No. 24
Manufacturer / supplier: Unitor Chemicals
Table No. 25
Manufacturer / supplier: Unitor Chemicals
Table No. 27
Manufacturer / supplier: Uniservice Group
Table No. 28
Manufacturer / supplier: Uniservice Group
Table No. 29
Manufacturer / supplier: Uniservice Group
Table No. 30
Manufacturer / supplier: Uniservice Group
Table No. 32
Manufacturer / supplier: Uniservice Group
Table No. 33
Manufacturer / supplier: Uniservice Group
Steam
dum p
valve
Cooling
Condenser
water
Condensate
M ake-up
B o ile r
Overflow
Hot well
Drain
2
PI PI
PS
Feed water
pum ps
Single boiler operation with or w ithout PI PI
forced circulation exhaust gas boiler
Figure 1 flowdiag_1.cdr
Steam
dum p
valve
C ooling
Condenser
w ater
C ondensate
M ake-up
B oile r B o ile r
O verflow
Hot w ell
D rain
1
2a
PI PI
PS
Feed water
2b PI PI PI PI
pum ps
PS
Feed w ater
pum ps
Double boiler operation with separate feed w ater pum ps PI PI
Steam
dum p
valve
C ooling
Condenser
w ater
C ondensate
M ake-up
B oile r B o ile r
O verflow
Hot w ell
D rain
1
2a
PS P I PI
Feed w ater
pum ps
2b PS P I PI
PS P I PI