Professional Documents
Culture Documents
FOR
HHI 1766
KMSS
Bekkajordet 8A
P.O Box 1009
N-3191 Horten. Norway
Table of Contents
Table of Contents
Bridge Watch Monitoring System
Yard: HHI
AO-176601-P
Table of Contents
Revisions
Document history
Rev. A
The information contained in this document is subject to change without prior notice.
Kongsberg Maritime AS shall not be liable for errors contained herein or for incidental
or consequential damages in connection with the furnishing, performance, or use of this
document.
© 2005 Kongsberg Maritime AS. All rights reserved. No part of this work covered by
the copyright hereon may be reproduced or otherwise copied without prior permission
from Kongsberg Maritime AS.
Kongsberg Maritime AS
Bekkajordet Telephone: +47 33 03 20 00
P.O.Box 1009 Telefax: +47 85 02 80 28
N-3194 Horten, www.kongsberg.com
Norway
AO-176601-P
TABLE OF CONTENS AO-176601-P
Chapter 7 - Manual
1 OF 1
CHAPTER 1
System Scope
KMK Ltd. KONGSBERG MARITIME AS
Project Department
S C O P E O F S U P P L Y
OF CHECK :
Operation Panels
Midi Operator Station
- MOS
CHAPTER 3
Functional Description
KM
Doc. No.: AD-00438B / 24-Sept-03
Design Description
DOCUMENT STATUS
1
Issue No. Date/Year Inc. by Issue No. Date/Year Inc. by
A BJW
B 24.09.2003 BjW
CHANGES IN DOCUMENT
TABLE OF CONTENTS
Section Page
1 INTRODUCTION ...............................................................................................1
4 FUNCTION ...................................................................................................4
4.1. Interval checking system ................................................................................4
4.2. Navigation warning and alarm system. ..........................................................5
1 INTRODUCTION
The purpose of the Bridge Watch Monitoring System is to detect irregularities in bridge
operation caused by operator disability, and alert another qualified navigator if the
bridge is unattended and if danger to navigation occurs.
The system meets the requirement set by IMO and classification societies for "one-man
bridge operation".
System design is based on standard modules and software, adaptable to all type of ships.
• A navigation warning and alarm system which transfers operational warnings from
the grounding and collision avoidance system as well as instrument malfunction
alarms to a central alarm panel and further to the captains quarters, public areas and
the cabin of a back-up navigator.
2 SYSTEM CONFIGURATION.
BRIDGE UNIT
MOS EXTERNAL TIMER SYST. EXTERNAL
BRIDGE / NAVIGATION EXTERNAL AUTOPILOT
BRIDGE PRE-WARNING FAIL RESET
EQUIPMENT ALARMS SOUNDOFF SWITCHED
BUZZER & RESET
MAX.25 ON
(WATCH-
DOG)
CAN
X8 RDo-16 X8
24V ch1 ch2 ch3 ch4 ch25 ch30ch31ch32
DC ALARM INPUTS
UPS K1 K2 K3 K4 K5 K6 K7 K8 K16
K9 K15 K16 MAX. 25
RDi-32
X10 X10
Cabin Buzzer
4 FUNCTION
The operation of the MOS is divided into various levels of user access;
• Commissioning
• SuperUser
• User
• Monitoring
All levels with its own password.
In BWMS the captain is defined to be “SuperUser” and the duty officers are “Users”.
It is only the “SuperUser” who has access to the “Interval check time” parameter T1
and the possibility to switch ON/OFF the interval checking system.
The system will after a predefined interval check time ( T1 = 3 – 12 minutes ) initiate a
pre-warning by use of a flashing lamp on the bridge panel. The officer on duty have to
activate a reset, otherwise a buzzer on the bridge will be activated ( pulsating sound ).
If the warning is not obeyed within 15 seconds, a buzzer will be activated in captains
quarter and the cabins of the navigators on duty.
After another timer ( T2 = 0 – 3 minutes ) has expired and the warning still not is
obeyed, buzzers are activated in public rooms and all backup cabins.
The interval checking system is reset by the switch in the pre-warning lamp, external
reset switches from external equipments or SOUND OFF button on the MOS. The
exception is, when the buzzers at public rooms and the cabins are activated, only the
SOUND OFF button on the MOS must be used.
INTERVAL EQUIPMENT
CHECKING ALARM
SYST. SYSTEM
( ICS )
INPUT
NO
BUZZER RESET
ICS Controlled manually
CHECK
ON on MOS NO
? or
NO
automatic when
INTERVAL MOS
CHECKING YES Auto-pilot ON ch32
ON ALARM
MOS ?
or EQUIPMENT
TIMER SET EXTERNAL ALARM MOS BUZZER
YES YES
3 - 12 min (T1) SOUND OFF MOS continuous sound
T1= ( ch31)
Interval check time
( parameter )
YES K7
YES BUZZER
= BRIDGE
T1 - continuous sound
30sec NO SOUND OFF NO
? PUSHED
INTERVAL K8
YES ?
CHECKING
PREWARNING YES
= K9 NO
EXTERNAL MOS
T1 - TIMER RESET ACK NO
15sec NO
PUSHED ? PUSHED
INTERVAL
? ( ch30 ) MOS ?
K7
CHECKING YES ACK
WARNING BUZZER
PUSHED TIMER SET
pulsating sound BRIDGE
= YES 15 sec ( T3 )
?
T1 NO
?
YES YES
BUZZER NO
CAPT. K1 YES =
QUARTER
ACKNOWLEDGE T3
EQUIPMENT EMERGENCY ?
TIMER SET BUZZER
ALARM CALL YES
K7
T2= 0 - 3 min (T2) BRIDGE
pulsating sound
Last stage delay
( parameter ) = TIMER SET
T2 NO 15 sec ( T4 )
CALL
?
BACKUP
BUZZER 1.ST.
PUBLIC
K2
YES NAVIGATOR
BACK-UP 2.ND.
ROOM ?
ON ? BACK-UP =
1.ST.
K3
ON ? T4 NO
BACK-UP YES 3.RD.
YES ?
CABIN BACK-UP
2.ND. ON ? 4.TH.
BACK-UP
K4
YES YES
BACK-UP
CABIN
ON ?
3.RD.
K5
BACK-UP YES ICS
CABIN YES ON NO
4.TH. K6 ?
BACK-UP YES
CABIN
Keyboard
• Menu & orientation keys
• Function keys F1 – F4
• Numeric & alphanumeric keys
• Key for SOUND OFF
• Key for acknowledge of alarms
|----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------|----------|
| KONGSBERG DC C20 Date/time of files: | Ship : 8400m3 LPG Tanker | | Enable=1 Disable=0 |Relay| |Ena=1 Disable=0| Input |
| MARITIME DPU bin | P.no : P10000665 | ALARM DELAYS 100ms| INHIBIT 100ms | SYSTEM |LOG e|A| | |D I G I T A L I N - & O U T P U T S| object |
| DATABASE dat 18.04.02 12:21:17 | File : P:\ZHONGHUA\429\ROS\Con | |Anal.only| |x|h l b a a|o|a|n|v|c| a| a| Status desc.|Sign.Condit|Alarms |Eve|indx|s |c |
|---------------------------------------------------------------------------------------| al| al| al| al| | inh| inh|t|o i u i l|f|u|o|e|c| l| l| | | | | |a|a|c|o|c|o|hex |u |h |
|dpu dpu dpu tag tag func eng ty ch OCP br LOS|del1|del1|del2|del2|Inhibited by| del| del|a|r g z m o|s|t|o|n|e| g| g| open |closed|del|del| |s|b|l|p|l|p| |b |a |
|no ch typ name desc unt pe typ gr gr gr| on| off| on| off| tag | on| off|g|n t z p n|c|o|n|t|s| 1| 2| desc |desc | on|off|inv|h|r|o|n|o|n| |i |n |
|---|---|---|------------|--------------------------------|------|---|---|---|--|---|---|----|----|----|----|------------|----|----|-|-|-|-|-|-|-|-|-|-|-|--|--|------|------|---|---|---|-|-|-|-|-|-|----|--|--|
# 1 35 20 BACKUP-1 1.ST MATE BACKUP 0 3 32 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 OFF ACTIVE 0 0 0 0 0 0 0 0 0 0 0 0
# 1 36 20 BACKUP-2 2.ND MATE BACKUP 0 3 32 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 OFF ACTIVE 0 0 0 0 0 0 0 0 0 0 0 0
# 1 37 20 BACKUP-3 3.RD MATE BACKUP 0 3 32 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 OFF ACTIVE 0 0 0 0 0 0 0 0 0 0 0 0
# 1 38 20 BACKUP-4 4.TH MATE BACKUP 0 3 32 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 OFF ACTIVE 0 0 0 0 0 0 0 0 0 0 0 0
# 1 39 20 ICS-SWITCH ICS SWITCH 0 3 32 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 OFF ON 0 0 0 0 0 0 0 0 0 0 0 0
# 1 40 20 CALL-BACKUP CALL BACKUP NAVIGATOR SWITCH 0 3 32 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 OFF ON 0 0 0 0 0 0 0 0 0 0 0 0
# 1 41 20 WATCHDOG WATCH DOG SOURCE 0 3 32 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 OFF ACTIVE 0 0 0 0 0 0 0 0 0 0 0 0
|---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
|KONGSBERG DC C20 Date/time of files: | Ship : KM | | Enable=1 Disable=0 |Relay|
|MARITIME DPU bin | P.no : | ALARM DELAYS | INHIBIT | SYSTEM |LOG e|A| | | A N A L O G I N P
| DATABASE dat 03.06.2003 10:13 | File : RIO.DAT | |Anal.only| |x|h l b a a|o|a|n|v|c| a| a| Counts | Eng. Limits |d| Filters | Alarm Limits
|---------------------------------------------------------------------------------------| al| al| al| al| | inh| inh|t|o i u i l|f|u|o|e|c| l| l| | | | |e| | | ala| ala| ala|
|dpu dpu dpu tag tag func eng ty ch OCP br LOS|del1|del1|del2|del2|Inhibited by| del| del|a|r g z m o|s|t|o|n|e| g| g| cnts | cnts | eng | eng |c| dead |flt| ll| lo| hi|
|no ch typ name desc unt pe typ gr gr gr| on| off| on| off| tag | on| off|g|n t z p n|c|o|n|t|s| 1| 2| low | high | low | high |p| band |tim| lim| lim| lim|
|---|---|---|------------|--------------------------------|------|---|---|---|--|---|---|----|----|----|----|------------|----|----|-|-|-|-|-|-|-|-|-|-|-|--|--|------|------|------|------|-|------|---|------|------|------|
# 1 46 20 CLOCK SYSTEM CLOCK 0 0 254 0 0 0 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 38010 58981 0 100 1 0.5 20 0 0 0
|----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------|----------|
| KONGSBERG DC C20 Date/time of files: | Ship : | | Enable=1 Disable=0 |Relay| |Ena=1 Disable=0| Input |
| MARIITME DPU bin | P.no : P30000130 | ALARM DELAYS 100ms| INHIBIT 100ms | SYSTEM |LOG e|A| | |D I G I T A L I N - & O U T P U T S| object |
| DATABASE dat 10.06.02 18:58:00 | File : P:\Samsung\1380\ros\con | |Anal.only| |x|h l b a a|o|a|n|v|c| a| a| Status desc.|Sign.Condit|Alarms |Eve|indx|s |c |
|---------------------------------------------------------------------------------------| al| al| al| al| | inh| inh|t|o i u i l|f|u|o|e|c| l| l| | | | | |a|a|c|o|c|o|hex |u |h |
|dpu dpu dpu tag tag func eng ty ch OCP br LOS|del1|del1|del2|del2|Inhibited by| del| del|a|r g z m o|s|t|o|n|e| g| g| open |closed|del|del| |s|b|l|p|l|p| |b |a |
|no ch typ name desc unt pe typ gr gr gr| on| off| on| off| tag | on| off|g|n t z p n|c|o|n|t|s| 1| 2| desc |desc | on|off|inv|h|r|o|n|o|n| |i |n |
|---|---|---|------------|--------------------------------|------|---|---|---|--|---|---|----|----|----|----|------------|----|----|-|-|-|-|-|-|-|-|-|-|-|--|--|------|------|---|---|---|-|-|-|-|-|-|----|--|--|
# 1 47 20 AL-TEST ALARM TEST 0 3 32 0 0 15 0 0 0 0 0 0 1 1 1 1 0 1 1 0 0 0 1 0 0 NORMAL ALARM 0 0 0 0 0 1 0 0 0 0 0 0
|-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
| KONGSBERG DC C20 Date/time of files: | Ship : | | Enable=1 Disable=0 |Relay| | Enable=1 Disable=0 | Input |
| MARITIME DPU bin | P.no : P30000130 | ALARM DELAYS 100ms| INHIBIT 100ms | SYSTEM |LOG e|A| | | A N A L O G I N P U
| DATABASE dat 10.06.02 18:58:00 | File : P:\Samsung\1380\ros\con | |Anal.only| |x|h l b a a|o|a|n|v|c| a| a| Counts | Eng. Limits |d| Filters | Alarm Limits
|---------------------------------------------------------------------------------------| al| al| al| al| | inh| inh|t|o i u i l|f|u|o|e|c| l| l| | | | |e| | | ala| ala| ala|
|dpu dpu dpu tag tag func eng ty ch OCP br LOS|del1|del1|del2|del2|Inhibited by| del| del|a|r g z m o|s|t|o|n|e| g| g| cnts | cnts | eng | eng |c| dead |flt| ll| lo| hi|
|no ch typ name desc unt pe typ gr gr gr| on| off| on| off| tag | on| off|g|n t z p n|c|o|n|t|s| 1| 2| low | high | low | high |p| band |tim| lim| lim| lim|
|---|---|---|------------|--------------------------------|------|---|---|---|--|---|---|----|----|----|----|------------|----|----|-|-|-|-|-|-|-|-|-|-|-|--|--|------|------|------|------|-|------|---|------|------|------|
# 1 48 20 SYS DPU001 RDI_32 NODE 1/20 XA 0 0 255 0 0 15 2 0 2 0 0 0 1 1 1 1 0 1 1 0 0 0 1 0 0 0 0 0 100 0 0.5 20 0 0 0
40 0 0 0 0 0 0 2 0 0 0 1 2 0 0 0 0 0 0 0
##RDOi 2
|--------------------------------------------------------------------------------------------------------------------------------------|--------------------------------|-|--------------------------------|----------|
|KONGSBERG DC C20 Date/time of files: | Ship : KNC | |R | | | |C| | Input |
|MARITIME DPU bin | P.no : | LOGS |A|e |D I G I T A L O U T P U T S | |Input Tag Ref. 1 |1|Input Tag Ref. 2 | object |
| DATABASE dat 28.01.2003 13:33 | File : RIO.DAT |x|a|n|v|c|l | Status desc.|Sign.Condit|Eve| do | | | |indx|s |b |
|-----------------------------------------------------------------------------------|t|u|o|e|c|a | | | al| al| |c|o|handler|------------|------|--|--|--|---|-|------------|------|--|--|--|---|hex |u |i |
|dpu dpu dbu tag tag func eng ty ch OCP LOS|a|t|o|n|e|y | open |closed|del|del| |l|p|dpu|dpu| Input Tag chk bitbitbitf |l| Input Tag chk bitbitbitf | |b |t |
|no ch typ name desc unt pe typ gr gr|g|o|n|t|s|no| desc |desc | on|off|inv|o|n|no |ch | name 1 value m1 m2 m3 c |c| name 2 value m1 m2 m3 c | |i | |
|---|---|---|------------|--------------------------------|------|---|---|---|--|---|-|-|-|-|-|--|------|------|---|---|---|-|-|---|---|------------|------|--|--|--|---|-|------------|------|--|--|--|---|----|--|--|
# 2 1 29 K1 CAPTAINS BUZZER YC 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 2 29 K2 PUBLIC ROMM BUZZER YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 3 29 K3 1st NAVIGATOR BUZZER YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 4 29 K4 2nd NAVIGATOR BUZZER YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 5 29 K5 3rd NAVIGATOR BUZZER YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 6 29 K6 4th NAVIGATOR BUZZER YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 7 29 K7 BRIDGE BUZZER YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 8 29 K8 ICS PREWARNING LAMP YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 9 29 K9 EXTERNAL SOUNDOFF YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
# 2 15 29 K15 MOS SLAVE BUZZER YZ 0 3 132 0 0 1 0 0 0 1 0 OPEN CLOSED 0 0 0 0 0 0 0 BUZZER 1 0 0 0 3 0 0 0 0 0 0 0 0 0
##MOS 3
|----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------|---|
| KONGSBERG DC C20 Date/time of files: | Ship : KNC | | Enable=1 Disable=0 |Relay| |Ena=1 Disable=0|LOS|
| MARITIME DPU bin | P.no : | ALARM DELAYS | INHIBIT | SYSTEM |LOG e|A| | |D I G I T A L I N - & O U T P U T S| h |
| DATABASE dat 28.01.2003 13:33 | File : RIO.DAT | |Anal.only| |x|h l b a a|o|a|n|v|c| a| a| Status desc.|Sign.Condit|Alarms |Eve| a |
|---------------------------------------------------------------------------------------| al| al| al| al| | inh| inh|t|o i u i l|f|u|o|e|c| l| l| | | al| al| |a|a|c|o|c|o| n |
|dpu dpu dbu tag tag func eng ty ch OCP br LOS|del1|del1|del2|del2|Inhibited by| del| del|a|r g z m o|s|t|o|n|e| g| g| open |closed|del|del| |s|b|l|p|l|p|mod|
|no ch typ name desc unt pe typ gr gr gr| on| off| on| off| tag | on| off|g|n t z p n|c|o|n|t|s| 1| 2| desc |desc | on|off|inv|h|r|o|n|o|n| no|
|---|---|---|------------|--------------------------------|------|---|---|---|--|---|---|----|----|----|----|------------|----|----|-|-|-|-|-|-|-|-|-|-|-|--|--|------|------|---|---|---|-|-|-|-|-|-|---|
# 3 1 33 GRP 1 MOS Grp 01 0 137 137 0 0 1 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 2 33 GRP 2 MOS Grp 02 0 137 137 0 0 2 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 3 33 GRP 3 MOS Grp 03 0 137 137 0 0 3 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 4 33 GRP 4 MOS Grp 04 0 137 137 0 0 4 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 5 33 GRP 5 MOS Grp 05 0 137 137 0 0 5 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 6 33 GRP 6 MOS Grp 06 0 137 137 0 0 6 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 7 33 GRP 7 MOS Grp 07 0 137 137 0 0 7 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 8 33 GRP 8 MOS Grp 08 0 137 137 0 0 8 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 9 33 GRP 9 MOS Grp 09 0 137 137 0 0 9 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 10 33 GRP 10 MOS Grp 10 0 137 137 0 0 10 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 11 33 GRP 11 MOS Grp 11 0 137 137 0 0 11 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 12 33 GRP 12 MOS Grp 12 0 137 137 0 0 12 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 13 33 GRP 13 MOS Grp 13 0 137 137 0 0 13 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 14 33 GRP 14 MOS Grp 14 0 137 137 0 0 14 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
# 3 15 33 GRP 15 MOS Grp 15 0 137 137 0 0 15 2 0 2 0 0 0 1 0 0 0 0 0 0 0 0 0 0 1 0 ALARM NORMAL 0 0 0 0 0 0 1 0 0 0
|--------------------------------------------------------------------------------------------------------------------------------------|--------------------------------|-|--------------------------------|----------|
|KONGSBERG DC C20 Date/time of files: | Ship : KNC | |R | | | |C| | Input |
|MARITIME DPU bin | P.no : | LOGS |A|e |D I G I T A L O U T P U T S | |Input Tag Ref. 1 |1|Input Tag Ref. 2 | object |
| DATABASE dat 28.01.2003 13:33 | File : RIO.DAT |x|a|n|v|c|l | Status desc.|Sign.Condit|Eve| do | | | |indx|s |b |
|-----------------------------------------------------------------------------------|t|u|o|e|c|a | | | al| al| |c|o|handler|------------|------|--|--|--|---|-|------------|------|--|--|--|---|hex |u |i |
|dpu dpu dbu tag tag func eng ty ch OCP LOS|a|t|o|n|e|y | open |closed|del|del| |l|p|dpu|dpu| Input Tag chk bitbitbitf |l| Input Tag chk bitbitbitf | |b |t |
|no ch typ name desc unt pe typ gr gr|g|o|n|t|s|no| desc |desc | on|off|inv|o|n|no |ch | name 1 value m1 m2 m3 c |c| name 2 value m1 m2 m3 c | |i | |
|---|---|---|------------|--------------------------------|------|---|---|---|--|---|-|-|-|-|-|--|------|------|---|---|---|-|-|---|---|------------|------|--|--|--|---|-|------------|------|--|--|--|---|----|--|--|
# 3 17 33 LIGHT MOS LIGHT I 0 3 132 0 0 1 0 0 0 0 1 OPEN CLOSED 0 0 0 0 0 0 0 EXT_S_OFF 1 0 0 0 3 0 0 0 0 0 0 0 1 0
# 3 18 33 BUZZER MOS LOCAL BUZZER I 0 3 132 0 0 1 0 0 0 0 0 OPEN CLOSED 0 0 0 0 0 0 0 LIGHT 1 0 0 0 3 0 0 0 0 0 0 0 0 0
|-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
|KONGSBERG DC C20 Date/time of files: | Ship : KNC | | Enable=1 Disable=0 |Relay|
|MARITIME DPU bin | P.no : | ALARM DELAYS | INHIBIT | SYSTEM |LOG e|A| | | A N A L O G I N P
| DATABASE dat 28.01.2003 13:33 | File : RIO.DAT | |Anal.only| |x|h l b a a|o|a|n|v|c| a| a| Counts | Eng. Limits |d| Filters | Alarm Limits
|---------------------------------------------------------------------------------------| al| al| al| al| | inh| inh|t|o i u i l|f|u|o|e|c| l| l| | | | |e| | | ala| ala| ala|
|dpu dpu dpu tag tag func eng ty ch OCP br LOS|del1|del1|del2|del2|Inhibited by| del| del|a|r g z m o|s|t|o|n|e| g| g| cnts | cnts | eng | eng |c| dead |flt| ll| lo| hi|
|no ch typ name desc unt pe typ gr gr gr| on| off| on| off| tag | on| off|g|n t z p n|c|o|n|t|s| 1| 2| low | high | low | high |p| band |tim| lim| lim| lim|
|---|---|---|------------|--------------------------------|------|---|---|---|--|---|---|----|----|----|----|------------|----|----|-|-|-|-|-|-|-|-|-|-|-|--|--|------|------|------|------|-|------|---|------|------|------|
# 3 100 33 SYS DPU003 MOS NODE 3/3 0 0 255 28 16 15 2 0 2 0 0 0 1 1 1 1 0 1 1 0 0 0 0 0 0 0 0 0 100 0 0.5 20 0 0 0
40 0 0 0 0 0 0 2 0 0 0 1 2 0 0 0 0 0 0 0
ctrl.dat:
##
##DC2000_SWNO 60052
| KONGSBERG DC C20 Date/time of files: | Ship :
| MARITIME CONTROL | P.no : P30000130
| DATABASE 24.06.02 10:44:31 | File : ctrl.dat
|-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
|
|
|Param. code | | | | | | | | | | | | | | | | |
| tag | Ext. tag | Ext. tag | Ext. tag | ext tag | ext tag | ext tag | ext tag | ext tag | Ext. tag | Ext. tag | Ext. atg | ext tag| ext tag| ext tag| ext tag| ext tag|
| name | name ref.1 | name ref.2 | name ref.3 | name ref.4 | name ref.5 | name ref.6 | name ref.7 | name ref.8 | name ref.9 | name ref.10| name ref.11| name ref.12| name ref.13| name ref.14| name ref.15| name ref.16|
|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|
#BW_MONITOR ICS_RESET EXT_S_OFF AUTO_PILOT BACKUP-1 BACKUP-2 BACKUP-3 BACKUP-4 ICS-SWITCH K15 SYS DPU003 SYS DPU002 CALL-BACKUP K1 K2 K3 K4
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
P4: | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
ext AE-PDO chk bitbitbit f |Param |Param |Param |Param |Param |Param |Param |Param |Param |Param |Param |Param |Param |Param |Param |Param |B |B |B |B |B |B |B |B |B |B |B |B |B |B |B |B |
name ref.4 value m1 m2 m3 c | no1 | no2 | no3 | no4 | no5 | no6 | no7 | no8 | no9 | no10 | no11 | no12 | no13 | no14 | no15 | no16 | 1| 2| 3| 4| 5| 6| 7| 8| 9| 10| 11| 12| 13| 14| 15| 16|
------------|------|--|--|--|---|------|------|------|------|------|------|------|------|------|------|------|------|------|------|------|------|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
0 0 0 0 0 3 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
--------------------------------|-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------|
|----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
| | SERIAL LINE | B1 = (DPU)baudrate / (dPSC)Baudrate 1X7 B4 = (dPSC)Baudrate 2X7| 0-300, 1-600, 2-1200, 3-2400, 4-4800, 5-9600, 6-19200, 7-38400, 8-57600, 9-76800 |
| SYSTEM | CONFIGURATION -> | B2 = (DPU)type / (dPSC)type 1X7 B5 = (dPSC)type 2X7| 0 - RS232 APPLICATION, 1-RS422 APPLICATION, 2-RS232 DEBUG, type>2-RS422 DEBUG |
| TAG | | B3 = (DPU)mode / (dPSC)mode 1x7 B6 = (dPSC)mode 2x7| 0-8N1, 1-8N2, 2-8E1, 3-8E2, 4-8O1, 5-8O2, 6-7E1, 7-7E2, 8-7O1, 9-7O2 |
|------------------------------------------------------------------------------------------|------------|------------|------------|------------|------------|------------|------------|------------|-
| Param.code | | | | | | | | | | | | | | |
| Tag | ext tag| ext tag| ext tag| ext tag| ext tag| ext tag| ext tag| ext tag| ext tag| ext tag| ext tag| ext tag| ext tag| ext tag|
| name | name ref.1 | name ref.2 | name ref.3 | name ref.4 | name ref.5 | name ref.6 | name ref.7 | name ref.8 | name ref.9 | name ref.10| name ref.11| name ref.12| name ref.13| name ref.14|
|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|------------|-
#SYS DPU001
#SYS DPU002
#SYS DPU003
Manual
Kongsberg Maritime
AD-0377-G / 01.11.2005
Kongsberg Maritime
Revisions
Rev Date Written by Checked by Approved by
A 02.02.2002 KGr AHo KOP
B 20.11.2002 KGr AHo KOP
C 01.02.2003 KGr BW KOP
D 07.05.2003 KGr BW KOP
E 23.10.2003 KGr BW KOP
F 29.08.2005 BW BW KOP
G 01.11.2005 EL NJF BJB
Document revisions
The original signatures are recorded in the company’s logistic database.
The information contained in this document is subject to change without prior notice.
Kongsberg Maritime AS shall not be liable for errors contained herein or for incidental
or consequential damages in connection with the furnishing, performance, or use of this
document.
© 2005 Kongsberg Maritime AS. All rights reserved. No part of this work covered by
the copyright hereon may be reproduced or otherwise copied without prior permission
from Kongsberg Maritime AS.
Kongsberg Maritime AS
P.O.Box 1009 Telephone: +47 815 73 700
3194 HORTEN Telefax: +47 850 28 028
Norway www.kongsberg.com
AD-0377-G / 01.11.2005 2
Kongsberg Maritime
Table of contents
7 MAINTENANCE ...................................................................................................38
7.1 Introduction ..........................................................................................................38
7.2 Overview ..............................................................................................................38
7.3 Unit replacement ..................................................................................................39
7.4 Preventive maintenance........................................................................................40
7.5 How to install the MOS ........................................................................................44
7.6 Troubleshooting the MOS ....................................................................................47
AD-0377-G / 01.11.2005 3
Kongsberg Maritime
8 APPENDIX .............................................................................................................50
8.1 Introduction ..........................................................................................................50
8.2 Abbreviations........................................................................................................50
Table of Figures
AD-0377-G / 01.11.2005 4
Kongsberg Maritime
AD-0377-G / 01.11.2005 5
Kongsberg Maritime
AD-0377-G / 01.11.2005 6
Kongsberg Maritime
When cleaning the inside of this system, do not inhale the dust.
The dust is a temporary health hazard, depending on individual
allergies.
Kongsberg Maritime AS disclaims any responsibility for
damage or injury caused by improper installation, use or
maintenance of the equipment.
Caution Electrostatic sensitive device
AD-0377-G / 01.11.2005
Kongsberg Maritime
2.1 Purpose
2.1.1 The reader
This instruction manual describes how to use the DataChief® C20 Alarm and
monitoring system with process control and power management controls and display
facilities. It is intended for system operators. He/she should be experienced in the
operation of Alarm and monitoring system with process control and power management
and have basic knowledge of personal computers or should have attended a Kongsberg
Maritime training course.
2.1.2 Note
Due to the flexible nature of DataChief® C20 not all systems described in this manual
are relevant for all deliveries. DataChief® C20 Alarm and monitoring system with
process control and power management is a registered trademark of Kongsberg
Maritime Ship Systems. Windows NT and Windows are either registered trademarks or
trademarks of Microsoft Corporation in the United States and/or other countries.
AD-0377-G / 01.11.2005 8
Kongsberg Maritime
AD-0377-G / 01.11.2005 9
Kongsberg Maritime
4 GETTING STARTED
4.1 Introduction
This chapter teaches you how to use the control functions and
displays of different DataChief® C20 operator stations. It is
intended for personnel just starting to use the system.
In this manual, only subject is converted:
• Using the MOS.
AD-0377-G / 01.11.2005 10
Kongsberg Maritime
Alarms acknowledge.
AD-0377-G / 01.11.2005 11
Kongsberg Maritime
AD-0377-G / 01.11.2005 12
Kongsberg Maritime
AD-0377-G / 01.11.2005 13
Kongsberg Maritime
Main Menu
1 Alarm Menu
2 Tag Selection Menu
3 User Access
4 Configuration Menu
5 Keyboard/Screen
Alarm Menu
1 Alarm History
2 Alarm Summary
3 Alarm Group Display
AD-0377-G / 01.11.2005 14
Kongsberg Maritime
Configuration Menu
1 Self check
2 Palette Display
2 Clock
3 Favourite Mimics
4 LOS Emulator
AD-0377-G / 01.11.2005 15
Kongsberg Maritime
AD-0377-G / 01.11.2005 16
Kongsberg Maritime
AD-0377-G / 01.11.2005 17
Kongsberg Maritime
4 Use the Page down and Page up buttons to step through all
alarms a page at a time.
AD-0377-G / 01.11.2005 18
Kongsberg Maritime
4 Use the Page down and Page up buttons to step through all
alarms a page at a time.
5 Push ENTER.
6 Use the right and left side of the navigator key to display
all available information for each tag group.
AD-0377-G / 01.11.2005 19
Kongsberg Maritime
3 Use the top and bottom of the Navigator key to select the
item you want to change.
Colour Palette
4 Push ENTER.
5 Use the top and bottom of the Navigator key to select Day,
Night or Dawn.
6 Push ENTER.
Keyboard click
7 Push ENTER.
9 Push ENTER.
Keyboard Light
10 Use the Page down and Page up buttons to increase or
decrease the value.
11 Push ENTER.
AD-0377-G / 01.11.2005 20
Kongsberg Maritime
Screen Brightness
12 Use the Page down and Page up buttons to increase or
decrease the value.
13 Push ENTER.
AD-0377-G / 01.11.2005 21
Kongsberg Maritime
3 Use the Page down and Page up buttons to step through all
DPU’s a page at a time.
4 Use the top and bottom of the navigator key to step through
each DPU one at a time.
6 Use the right and left side of the navigator key to display
all available information for each tag.
AD-0377-G / 01.11.2005 22
Kongsberg Maritime
Tag menu
When the tags for a DPU is displayed:
8 Push MENU
12 Push 3 to display the Alarm status for this tag (if any).
AD-0377-G / 01.11.2005 23
Kongsberg Maritime
5 Push ENTER.
6 Use the top and bottom of the navigator key to select the
tag you want to change parameters for.
7 Push ENTER to display the parameters for the selected tag.
8 Use the top and bottom of the navigator key to select the
parameter you want to change.
Colours are used to indicate if the current access level allows a
parameter to be changed:
• Grey parameter text: Can not be changed at current access
level setting.
• White parameter text: Parameter can be changed.
Note If you try to make changes without having inserted the right
password the system will automatically request it.
AD-0377-G / 01.11.2005 24
Kongsberg Maritime
9 Push ENTER.
A parameter entry window is displayed
12 Push ENTER.
The new value is inserted. The display picture is updated and the
new value is transferred to the Distributed Processing Unit and
other Remote- and MOSs in the system.
AD-0377-G / 01.11.2005 25
Kongsberg Maritime
AD-0377-G / 01.11.2005 26
Kongsberg Maritime
AD-0377-G / 01.11.2005 27
Kongsberg Maritime
AD-0377-G / 01.11.2005 28
Kongsberg Maritime
6.2 Functions
The Bridge Watch Monitoring System serves the following
purposes:
- Central bridge alarm panel provides visual and audible
alarms and warnings. These are initiated by systems and
individual navigation equipment serving primary bridge
functions.
- Bridge watch monitoring feature for detection of
unattended bridge or operator disability based on interval
checking.
- Alarm transfer to specific locations outside the bridge to
alert and call the master and back-up navigator(s),
automatically initiated in case the bridge alarms are not
attended to or an operator disability is detected.
- Call back-up navigator for purpose of manual and instant
initiation of alarm transfer from bridge for alert and call of
master and back-up navigator(s).
AD-0377-G / 01.11.2005 29
Kongsberg Maritime
Pre-warning:
• Pre-warnings are only given on the bridge.
• 30 seconds before the alarm timer expires a pre-warning lamp
starts flashing.
• 15 seconds before the alarm timer expires a pre-warning
buzzer starts sounding.
Alarm:
The alarm is configurable to sound between 3 and 12 minutes
after the last alarm-timer reset. To reset the alarm timer push:
• Any external sound off button
• Any key on the Bridge Watch Monitoring panel.
AD-0377-G / 01.11.2005 30
Kongsberg Maritime
AD-0377-G / 01.11.2005 31
Kongsberg Maritime
AD-0377-G / 01.11.2005 32
Kongsberg Maritime
AD-0377-G / 01.11.2005 33
Kongsberg Maritime
2 Push ENTER.
The Tag Details View for the Bridge Watch Monitoring
System is shown.
3 Use the navigator key to select Internal Check Time.
This is the time from the last push of any external sound
off or Bridge Watch Monitoring panel key, until the alarm
is given.
4 Push ENTER.
AD-0377-G / 01.11.2005 34
Kongsberg Maritime
3 Use the top and bottom of the Navigator key to select the
item you want to change.
Color Palette
4 Push ENTER.
5 Use the top and bottom of the Navigator key to select Day,
Night or Dawn.
6 Push ENTER.
AD-0377-G / 01.11.2005 35
Kongsberg Maritime
Keyboard click
7 Push ENTER.
9 Push ENTER.
Keyboard Light
10 Use the Page down and Page up buttons to increase or
decrease the value.
11 Push ENTER.
Screen Brightness
12 Use the Page down and Page up buttons to increase or
decrease the value.
13 Push ENTER.
AD-0377-G / 01.11.2005 36
Kongsberg Maritime
AD-0377-G / 01.11.2005 37
Kongsberg Maritime
7 MAINTENANCE
7.1 Introduction
This chapter explains how to keep the system in good working
order and what to do if the system fails.
The following subjects are covered:
• Overview
• Unit replacement
• Preventive maintenance
• Troubleshooting Remote Operator Stations
• Troubleshooting MOSs
• Troubleshooting Local Operator Stations
• Troubleshooting the Watch Calling System
• Troubleshooting Distributed Processing Units
7.2 Overview
This maintenance chapter is intended for trained maintenance
technicians or engineers with experience of electronic and
digital circuits, computers and electro mechanical design. The
level of information is based on Kongsberg Maritime’s
maintenance philosophy:
The onboard technical personnel shall, with the help of the
documentation and the system’s built-in test functions, be able
to identify malfunctions, locate the fault, and replace major
parts, modules and components on a “Line Replaceable Unit”
(LRU) level.
He/she will however not attempt to repair the LRUs.
Note Cleaning with abrasive material or strong chemical cleaning
solutions is not recommended as these may damage the system.
AD-0377-G / 01.11.2005 38
Kongsberg Maritime
Note DataChief® C20 AMS units are not field repairable. Any attempt
will void the warranty.
Package faulty units using the box from the replacement unit
and send it to Kongsberg Maritime for repair.
→ Refer to no tag for information on how to get in touch with
us.
7.3.1 Recommended tools
• Drawings of the installation.
• Digital multimeter.
• Sensor simulator.
• Screwdriver for wire terminals: Flat 3 x 0.7 mm.
• Screwdriver for screen termination board: Flat 7 x 1.0 mm.
• Screwdriver Pozidriv: POZI #1.
• Cable ties.
AD-0377-G / 01.11.2005 39
Kongsberg Maritime
AD-0377-G / 01.11.2005 40
Kongsberg Maritime
AD-0377-G / 01.11.2005 41
Kongsberg Maritime
AD-0377-G / 01.11.2005 42
Kongsberg Maritime
AD-0377-G / 01.11.2005 43
Kongsberg Maritime
7.5.1 Placement
AD-0377-G / 01.11.2005 44
Kongsberg Maritime
7.5.2 Cut-out
For flush mount installations use the following cut-out.
AD-0377-G / 01.11.2005 45
Kongsberg Maritime
Fuse
Note A 4.0 Amp slow fuse should always be installed to protect the
unit.
AD-0377-G / 01.11.2005 46
Kongsberg Maritime
AD-0377-G / 01.11.2005 47
Kongsberg Maritime
AD-0377-G / 01.11.2005 48
Kongsberg Maritime
AD-0377-G / 01.11.2005 49
Kongsberg Maritime
8 APPENDIX
8.1 Introduction
This appendix contains definitions, abbreviations and references
used in this document.
The following subjects are covered:
• Abbreviations
• References
8.2 Abbreviations
8.2.1 General
AC Alternating Current
BIST Built In System Test
CAN Control Area Network
CE Communite Europeen
CD Compact Disc
CCR Cargo Control Room
dPSC Dual Process Segment Controller
DC DataChief
DPU Distributed Processing Unit
ECR Engine Control Room
EMC Electro Magnetic Compatibility
EMD European union Maritime Directorate
GUI Graphic User Interface
IACS International Assocciation of Class Societies
IMO International Maritime Organisation
I/O Input/Output
IFH Instrument Failure High alarm
IFL Instrument Failure Low alarm
IP Ingress Protection
KMSS Kongsberg Maritime Ship Systems
LAN Local area Network
AD-0377-G / 01.11.2005 50
Kongsberg Maritime
AD-0377-G / 01.11.2005 51
Kongsberg Maritime
Analogue sensors
OffSc Offscan alarm. Indicates that the input signal is
not checked for alarm situations and is not
measured any more.
Grad Gradient alarm. The input signal is changing
rapidly.
Low Low alarm. When the input signal is lower than a
set limit.
Lo-Lo Low-Low alarm, when the input signal is lower
than a set limit.
High High alarm. When the input signal is higher than
a set limit
Hi-Hi High High alarm When the input signal is higher
than a set limit
IFL Instrument failure low alarm. Used for example
when a 4 to 20 mA current loop is giving less than
4 mA.
IFH Instrument failure high alarm. Used for example
when a 4 to 20 mA current loop is giving more
than 20 mA.
Inhib Inhibit. The input signal has been inhibited to
avoid unnecessary alarms such as when the main
engine is stopped.
AD-0377-G / 01.11.2005 52
Kongsberg Maritime
Digital sensors
OffSc Offscan alarm. Indicates that the input signal is
not checked for alarm situations
Open The switch is open, such as ”valve open”
Closed The switch is closed, such as ”valve closed”
Short The wiring to the sensor has a short-circuit
Broken The wiring to the sensor has a open-circuit
Inhib Inhibit. The input signal has been inhibited to
avoid unnecessary alarms such as when the main
engine is stopped
AD-0377-G / 01.11.2005 53