WORKING DOCUMENTATION

Fire Alarm System AutroSafe

DUNG QUAT SHIPYARD H.8239

AFS project Site no.:


00000000

Autronica Fire and Security AS


N-7483 Trondheim – Norway
Phone:+ 47 73 58 25 00 Fax:+ 47 73 58 25 01
AUTRONICA
FIRE AND SECURITY AS
SYSTEM DESCRIPTION 1
WORKING
DOCUMENTATION

SYSTEM DRAWINGS 2
System:
Fire Alarm System AutroSafe

INTERNAL EQUIPMENT 3

Yard & Newbuilding:


DUNG QUAT SHIPYARD
H.8239 SMOKE & HEAT DETECOTS 4

Classification society: FLAME DETECTORS &


ABS ADDRESS UNITS 5

AFS project Site no.:


00000000
MANUAL CALL POINTS 6

DISCONNECTION UNITS 7

ZENER BARRIER &


EX-DETECTORS 8

INFORMATION PANEL
BV-320M 9

Autronica Fire and Security AS


N-7483 Trondheim, Norway.

Phone: +47 73 58 25 00
Fax: +47 73 58 25 01
CERTIFICATES 10
E-mail: info@autronicafire.no
Web: http://www.autronicafire.no
AFS Support Centre
Phone: +47 81520300
E-mail: afs.support@autronicafire. no
11
INDEX
Fire Alarm System AutroSafe

1. SYSTEM DESCRIPTION
Cable & block drawing central unt BS-320M 00000000.001
Scope of supply & Spare part list Itemlist
Spare part list SparePartList

2. SYSTEM DRAWINGS
Dimensional sketch, Central cabinet UAK-2/24 00000000.100
Arrangement drawing, Central cabinet, UAK-2/24 00000000.101
Internal ribbon cable conn. BS-320M 00000000.105
Conn. draw. LON ring 00000000.140
Conn.draw. power supply system , BS-320M 00000000.201
Conn.draw. BSD-310 modules, BS-320M 00000000.202
Conn.draw. BSB-310 module, BS-320M 00000000.203

3. INTERNAL EQUIPMENT
Datasheet BS-320 P-BS320/CE
Datasheet BSS-103A P-BSS103/CE
Datasheet BSS-310 P-BSS310/CE
Datasheet BSL-310 P-BSL310/CE
Datasheet BSD-310 P-BSD310/CE
Datasheet BSB-310 P-BSB310/CE
Datasheet BUP-310 P-BUP310/WX
Battery 18Ah Battery_18Ah

4. SMOKE & HEAT DETECTORS


Data Sheet Optical smoke detector BH-200 P-BH200/CE
Dim. and connection draw. Optical smoke detector BH-200 HB-085
Data Sheet Heat detector BD-200 P-BD200/CE
Dim. and connection draw. Heat detector BD-200 HB-084
Data Sheet BWA-100 P-BWA100/WX
Data Sheet BWP-100 P-BWP100/CE

5. FLAME DETECTORS
Data Sheet IR Flame detector 601F 601F
Data sheet, Conduit box w/interface unit for 601F P-FLAMEDETINTERF_CE

6. MANUAL CALL POINT


Data Sheet BF-300 P-BF300/CE
Dim. and connection draw. Manual call point BF-300 HB-083
Data Sheet BF-300M P-BF300M/CE
Dim. and connection draw. Manual call point BF-300M HB-087

7. DISCONNECTION UNITS
Data Sheet, Disconnection unit with pushbuttons BW-200 P-BW200/CE
Dim. & Connection drawing timer unit – BW-200 BW-200-603

8. ZENER BARRIER & EX-DETECTORS


Data Sheet Zener Barrier Unit BZ-500 P-BZ500/CE
Dim.and connection draw. Zener Barrier Unit BZ-500 HB-088
Data Sheet BH-500/Ex P-BH500Ex/CE
Dim. and connection draw. Optical smoke detector BH-500/Ex HB-085
Data sheet BF-502/Ex P-BF502Ex/CE
Dim. And connection draw. Manual call point BF-502/Ex HB-BF502
9. INFORMATION PANEL BV-320M
Datasheet BV-320M P-BV-320/CE
Dimensional sketch, Information panel BV-320M Dim_BV-320M
Internal ribbon cable conn. Information panel BV-320M Ribbon_BV-320M

10. CERTIFICATES
ABS Certificates
Ex Certificates
SYSTEM DESCRIPTION
Type of file Scope of supply / Item list Project responsible: HKK
Type of system Fire alarm system AutroSafe Order no.:
Revision: A
Yard and nb. DUNG QUAT SHIPYARD H.8239 Revision date: 2008-02-05
Autronica ref. 00000000
Description Type Qty Ref. Order code Remark

Central unit AutroSafe with BS-320M/GB200 1 Data sheet BS-320 BS-320M/GB200 BSS-103A in UAK-2/24
Detector Loop module, 100mA BSD-310 3 Data sheet BSD-310 BSD-310
Detector Loop module, 200mA BSD-311 1 Data sheet BSD-310 BSD-311
Relay output modules BSB-310 1 Data sheet BSB-310 BSB-310
Print unit BUP-310 1 BUP-310
Diode relay 24 vdc, 1 Port RSC-24DC/21 10 7624-030.0001
Diode relay 24 vdc, 2 Ports RSC-24DC/21-21 4 7624-030.0002
Diode relay 230vac RSC-230UC/21 1 7624-030.1001
ContactorCAD32P7 10AMP 7656-028.5122 1 7656-028.5122
Mounting plate + TS rail UE-474 2 UE-474
Cover plate for 19’ x 6E UW-1132/4 1 UW-1132/4
Cover plate for 19’ x 9E UW-1132/5 2 UW-1132/5
Terminal blocks, UT 2.5 7354-070.0200 40 7354-070.0200
Terminal blocks, UT 4 7354-070.0400 6 7354-070.0400
Fuse Terminal, UK5, 5x20mm 7354-075.0600 12 7354-075.0600
Cabinet (1,220 x 542 x 287mm) UAK-2/24 1 UAK-2/24
Socket for UAK-2 cabinet UE-458-1 1 UE-458-1

Batteryshelf UE-369 1 UE-369


Battery fastening strap 6570-900.1000 2 6570-900.1000
Battery set 2 x 12V/18Ah, 12 kg 4160.002 1 4160.002

Information panel/Console mounting BV-320M 2 Datasheet BV-320M BV-320M/GB500 English text

Smoke detector head, Optical type BHH-200 66 Data sheet BH-200 BHH-200
Smoke detector head, Optical type, IP44D BHH-200-44 102 Data sheet BH-200 BHH-200-44
Smoke detector head, Optical type, Exi BHH-500/Ex 9 Data sheet BH-500/Ex BHH-500/Ex

Heat detector head, IP44D BDH-200-44 1 Data sheet BD-200 BDH-200-44

Detector base BWA-100 178 Data sheet BWA-100 BWA-100


Conduit box w/M20(=PG16, 7-14mm) BWP-100/20/PG16 112 Data sheet BWP-100/20 BWP-100/20/PG16
Description Type Qty Ref. Order code Remark

IR-Flame detector head 5861-010.2011 10 Data sheet 601F-M 5861-010.2011


Socket M600 for 601F-M 5861-010.2012 10 5861-010.2012
Conduit box w/L.P Interface 601F-M 5861-010.2015 10 5861-010.2015

Manual call point accom. BF-300 13 Data sheet BF-300 BF-300 N.W.T
Manual call point eng.room IP44 BF-300M 24 Data sheet BF-300M BF-300M W.T
Manual call point, Exi BF-502/Ex 2 Data sheet BF-502/Ex BF-502/Ex
Glass for manual call point BFG-3/GB 39 BFG-3/GB English text

Zener barrier BZ-500 5 Data sheet BZ-500 BZ-500

Disconnect unit timer BW-200/GB 6 Datasheet BW-200 BW-200

WORKING SPARE PARTS


Glass for manual call point BFG-3/GB 20 BFG-3/GB English text
Detector base BWA-100 1 Data sheet BWA-100 BWA-100
Conduit box w/M20(=PG16, 7-14mm) BWP-100/20/PG16 1 Data sheet BWP-100/20 BWP-100/20/PG16
Test gas bottle WBJ-5/04 4
Type of file Spare pare list
Type of system Fire Alarm System, AutroSafe
Yard and Hull No. DUNG QUAT SHIPYARD H.8239
Autronica Site No. 00000000
Revision & Date 2008-02-05. A

Pos Spare part description Order code Q’ty Remark Outline


1 Smoke detector head BHH-200 6

2 Smoke detector head, IP44D BHH-200-44 10

3 Smoke detector head, Exi BHH-500/Ex 1

4 Heat detector head, IP44D BDH-200-44 1

5 Detector base BWA-100 2

6 Conduit box BWP-100/20/PG16 2

7 Manual Call Point, N.W.T. BF-300 1

8 Manual Call Point, W.T. BF-300M 2

9 Glass for Manual Call Point BFG-3/GB 10

10 Test gas unit, WBJ-5/01 1


SOLO 300-016
SOLO

11 Telescopic pole WBJ-5/02 1


SOLO
12 Test gas bottle WBJ-5/04 4

13 Spare fuse kit 1


5x20mm, 3.15 A slow x 10 pcs 7580-002.4931
5x20mm, 2.0 A slow x 10 pcs 7580-002.4920
5x20mm, 4.0 A slow x 10 pcs 7580-002.4940
5x20mm, 1.0 A slow x 10 pcs 7580-002.4910
5x20mm, 6.3 A slow x 10 pcs 7580-002.4963
Key for front panel x 1 pc 6745-011
SYSTEM DRAWINGS
INTERNAL EQUIPMENT
AutroSafe Fire Alarm Control Panel - BS-310 / 320

Features
• Self-Verify Function for automatic testing of detectors.
• Automatic addressing of detectors.
• Accommodates up to a maximum of 12 modules, of which
maximum 6 can be Loop Driver Modules.
• User-friendly display and operator controls.
• Backlighted operational buttons. Text display suitable for full
darkness operation.
• Capable of surface or flush mounting and for rack mounting in
standard 19’’ cabinets.
• Designed to meet EN-54 and LPCB requirements and conforms
to CE standards.
• Complies to environmental conditions of IEC-721-3-3 class 3k5.

Application / Description
BS-310 / 320 is a complete fire alarm control panel with full opera-
tion capabilities. The panel serves as a operating panel for one or
several defined operation zones. All alarm handling and system
features can be controlled and monitored from the panel.

The panel can accommodate up to a maximum of 12 modules. The


system offers a Loop Driver Module for detection loops and sev-
Optional I/O Modules
eral types of I/O modules for monitored outputs, open collector
outputs, galvanic isolated inputs and monitored inputs. There can • Loop Driver Module (BSD-310/311). For connection of detection
be a maximum of 6 Loop Driver Modules in each panel. All modules loops. 1 detection loop can be connected to each module. A
are easily plugged onto each other on a standard mounting rail maximum of 127 loop units (detectors, manual call points, I/O-
inside the unit. units and/or an electronic sounders) can be connected to each
detection loop.
The panel is menu operated on a 16 lines display with 40 charac- • Output Module (BSB-310), with 4 monitored outputs. For con-
ters per line. A built-in printer is available as an option. nection to fire alarm devices (FAD), such as sounders etc., and
fire protection equipment (FPE) such as fire doors, ventilation
With a LON Interface the Fire Alarm Control Panel can communi- controller or fire extinguishers. Also suitable for connection to
cate with other system units on the local operating network, fire alarm routing equipment (FARE), such as fire brigade
AutroLON. This interface is standard in BS-320, and not included equipment, and for connection to fault outputs.
in BS-310. The panel has a 230 VAC / 3A power module for bat-
• Output Module (BSJ-310), with 8 open collector non-monitored
tery charging and a built-in emergency battery.
outputs. For connection of external LED-indication panel.
• Input Module (BSE-310) with 4 monitored inputs.
Indicators
• Input Module (BSE-320), with 8 non-monitored inputs (galvanic
• 16 x 40 characters alphanumeric display isolated).
• Fire / Alarm, More Events, Fault, Function Disabled, Function
Delayed, Fire Brig. Signalled, Power, Testing, Fire Brigade Dis- Capacity
abled, Fire Brig. Fault, System Fault, Alarms Disabled, Alarms
Fault. • There can be a maximum of 32 panels in a LON- ring (EN-54).
• Internal buzzer. Demand for more than 32 panels needs several LON-rings.
• Each unit can be equipped with a maximum of 12 of the above
modules, of which maximum 6 can be Loop Driver Modules
Operater Controls (cabinet without internal batteries).
• More Events, Mute Panel, Silence Alarms, Reset. • A maximum of 512 detectors and manual call points can be con-
• Numeric keyboard, with scroll and alpha characters. nected to each Fire Alarm Control Panel (EN-54).
• Separate buttons for menu operation.
• Buttons and text with back light.

P-BS320/CE - Rev. D, 020605 Protecting life, environment and property...


Fire Alarm Control Panel, BS-310 / 320

Technical Specifications Dimensions


Dimensions (mm) 350x350x194
Weight (without I/O modules and batteries)
8,5 kg
Materials Steel cabinet, ABS/PC moulded front
Mounting Surface or flush mounting
Protection class IEC-529 / IP30
Ambient temperature -20 to +55 C
Power supply 230V AC
+10% / -15%
Frequency: 44-440Hz or 24V DC
Current consumption 250mA at 27V DC
(when no I/O modules are con-
nected)
Capacity - Loop Maximum 12 modules
Driver Modules and (a combination of BSD-310, BSB-
I/O Modules 310, BSE-310/320 and BSJ-310)
Capacity - Loop Maximum 6 BSD-310. The maximum
Driver Module number of detectors and manual call
points that can be connected to
these 6 modules are 512 (refer to
EN-54).
Batteries 2 x 12V = 24V not included
Detector connection By use of BSD-310/ BSD-311
Inputs By use of BSE-310 and BSE-320 or
Outputs By use of BSB-310 and BSJ-310
Communication AutroLON (BS-320 only) System Overview
AutroCom / Ethernet or Serial Port

Order Numbers
ALARM

Order number Description Fire ext.. acktivated

Fire vent. activ.

FireBrig.recvd.
Power

Prewarning
Earlywarning
MoreAlarms
Silencebuzzer

Silence sounders

Reset

1 2 3
4 5 6
Fault

Standalone system
System fault
Functiondisabled 7 8 9
T e s t C 0

BS-310/- Operator Panel ?

Self Verify

without LON Inter-


BS-320/- Operator Panel
face.
Autronica

Fire Alarm Control KNUS


TRYKK HER
GLASSET

BREAKGLASS
PRESS HERE

Autronica

Options:
BSD-310/311 Loop Driver Module I/O
BSB-310 Output Module
w/ 4 monitored outputs
BSJ-310 Control Output
Module w/ 8 open collector outputs
Non-monitored
BSE-310 Input Module Distrubuted system - AUTROLON - Ring Loop
(4 monitored inputs) with LON Interface. Controller Controller

Fire
ALARM ALARM

BSE-320 Input Module Fire Alarm


Alarm Control Panel Fireext..acktivated
Firevent.activ.
FireBrig.recvd.

Power

Prewarning
Early warning
More Alarms Silence
Silence buzzer
sounders
Reset

1 2 3
Power
Frei

Power

Prewarning
ex.t
Fire vent. activ.
Fire Brig. recvd.

Earlywarning
ackvitaetd

MoreAlarms
Silencebuzzer
Silencesounders
R e s e t

1 2 3
Power

Control
Fault 4 5 6 Fatul 4 5 6

(8 non-monitored galvanic isolated inputs)


System fault Systemfault
Functiondisabled 7
7 8 9 Fault Function disabled 7 8 9 Fault

Test C 0 Test C 0
0

2
? ?

Panel
Self Verify SelfVerify Self Verify SelfVerify

BUP-310 Printer Autronica


Operator Panel Autronica

I/O
KNUS GLASSET

K N U S G L A S S E T TRYKK
BHER
R E A P
K RG EL SAS SH SE R E

TRYKK HER GLASS


BREAK P R E S S H E R E

TRYKK
KHER PRESS
NUSGLASS E T HERE

B R E A K G L A S S

AutroCom / Ethernet or Serial Port


Autronica

Autronica

Language
TRYKK
KHER
N U S GP LR AE SS SS EH TE R E

BREAKGLASS

I/O I/O I/O


I/O

Repeater Information
Panel Panel
Power

ALARM INFORMASJONSPANEL ALARM INFORMASJONSPANEL


Fault

Fireext.aktivated Fireext.aktivated
Fire vent. activ. Silence buzzer SelfVerify Fire vent. activ. Silencebuzzer
Silencesounders Silencesounders
FireBrig.recvd. More Alarms Fire Brig. recvd. MoreAlarms
P o w e r Reset P o w e r R e s e t

Controller

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


AutroSafe Power Supply - BSS-103A/02, BSS-103A

Features
• Provides 27,4V DC / 20°C.
• Designed to meet EN-54 and LPCB requirements
and conforms to CE standards.
• Electronic current limitation at short circuiting.
• Pole reverse secure.
• Transient protection.
• Temperature compensated battery charging
voltage.

Applications
Power Supply BS-103 can be delivered as two types:
• BS-103A/02, which is an open circuit board for in-
ternal use in various fire alarm control panels
• BS-103A with a metal front cover. Used for external
mounting as an addtional unit in the fire alarm sys-
tem

Cabling
The Power Supply provides 24V DC / 3A to the Fire
Alarm Control Panel. The unit is connected to the The Power Supply BSS-103/01has the following
mains outlet 230V AC. internal connections:
For the AutroSafe Interactive Fire Alarm System it • a ribbon cable between the Power Supply BSS-
provides 24V DC / 3A to the BS-310/320 or Control- 103A/02 and the internal circuit board inside the Fire
ler BC-320. Alarm Control Panel.
• A two-wire battery connection
The Power Supply provides the following
outputs / inputs:
Refer to connection drawing on the back page.
• Output for 24V DC / 3A (27,4V DC / 20°C)
• Output for battery load test (X90-X91) Fuses
• Output for indication of mains power ON
• Mains fault output (X92-X93)
• Input for 160 -265 VAC or 180 - 375 VDC
F2
• Control input for battery test (X6)
• Plug-in connection of external termistor for tempera- F3 F1
ture control of externally mounted batteries

Fuse Size Type Protecting


Mounting
F1 1,4 A Slow Mains
The BSS-103A/02 is easily mounted inside the Fire F2 6,3 A Fast Battery
Alarm Control Panel and Controllers (AutroSafe sys- F3 1A Slow External
tem). 24V DC
The BS-103A is used for external mounting in larger
cabinets.

P-BSS103/CE-Rev. C, 010531 Protecting life, environment and property...


Power Supply, BSS-103

Technical Specifications Order numbers


Various Order number Description
Dimensions (mm) BSS-103 265 x 102 x 67
BSS-103 Power Supply, complete with metal
Dimensions (mm) BSS- 265 x 80 x 50 cover
103/01
BSS-103/01 Power Supply circuit board
Weight (g) 1100
Materials Painted metal cover
Connections
Electrical connection Internal plug connection.
Screw

10 9 8 7 6 5 4 3 2 1
- + T - + 230V Screw Terminals on
terminals for mains and bat- 8 7 6 5 4 3 2 1
Power Supply BSS-103

Connector
10 9 8 7 6 5 4 3 2 1
tery.
Mounting 4 screws

230V
Neutral
Protective Earth
External 24V Output
Test
0V
+24V DC to battery
Input
Input voltage range 160 -265 VAC, 180 - 375 VDC
Frequency 47 - 63 Hz
Current 0.92 A at Vinn = 160 VAC
Power 110 W Screw Terminal no. Description
Power efficiency ≥ 83 % at maximum load 1 Protective Earth
Protection Transient protection 2 Neutral
Safety fuse 1,4 A (slow) 3 230V AC/DC input
4 Battery +24V DC output
Output 5 Battery 0V output
Output Current 3A 6 Battery test input
Output voltage 27,4 VDC at 20°C 7 +24V DC external output
Adjustment range 22 - 30 VDC 8 0V external output
Voltage accuracy ± 50 mV
Ripple voltage across load < 25 mVRMS , < 170 mVp
Temperature compensating Uut v/5°C: 28.2 VDC
Uut v/35°C: 26.6 VDC
Protection Electronic current limitation at
short circuiting.
Pole reverse secure.
Transient protection.
Test
External 230 V AC
Output for extra load test (X90-X91) 24V output
Voltage Uut - 0.6 VDC
Live
Current 1A Neutral
Activating current - 3 mA To battery
Activated when J1,9 is put to OV. Protective Earth

Output for indication of mains power (J7-J8)


Voltage 15.0 V ± 0.7 V Chassis
Current 1,0 mA To internal
Time delay 20 s ± 5 s circuit board
+ Protective
The voltage drops to 0V when mains power is turned off. - Earth
(terminal)
Mains fault output (relay output X92-X93)
Time delay 20 s ± 5 s
Closed contact when mains power is turned on, Open contact
when mains power is turned off.
Control input for battery test (X6-X8)
Activating current Activating current
Battery voltage fault level Battery voltage fault level dur-
during test period ing test period
Activated when X6 (T) is put to OV.

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.
Visit Autronica Fire and Security's Web site: www.autronicafire.com
AutroSafe Power Module - BSS-310

Features
Provides 24V DC and 5V DC regulated voltage to all
panel mounted I/O modules.
Easily plugged onto a standard mounting rail.
Designed to meet EN-54 and LPCB requirements
and conforms to CE standards.

Applications
The Power Module BSS-310 converts unregulated
battery voltage to 24V DC and 5V DC regulated volt-
age to all I/O modules mounted in the Fire Alarm
Control Panel (BS-310/320) or the Controller (BC-
320).

Connecting several modules in parallel can increase


the power.

Connections / Indicators
Mounting
Front view when mounted on rail
The Power Module is always delivered with the Fire
Alarm Control Panel (BS-310/320) or the Controller
(BC-320).
The module is easily plugged onto a mounting rail -
as the first module placed at the bottom of the rail - Screw
inside the Fire Alarm Control Panel (BS-310/320) or terminal 10
the Controller
(BC-320). Screw
terminal 1
Green Green
Cabling indicator indicator
H2 (5V) H1 (24V)
Two wires are used for the internal connection be-
tween the connection block on the Power Module
BSS-310 and the terminals on the Connection Mod- The module has two green indicators;
ule BSF-310A. • Right green indicator (H1) - the presence of 24V
Refer to connection drawing / schematics on the DC
other side of this data sheet. • Left green indicator (H2) - the presence of 5V DC
The I/O module has the following connections:

Screw Terminal no. Signal


1 +24 V Input
2 +24 V Input
3 0 V Input
4 0 V Input
5 Chassis
6 Chassis
7 Not in use
8 Not in use
9 Not in use
10 Not in use

P-BSS310/CE-Rev. B, 010531 Protecting life, environment, and property...


Power Module, BSS-310

Technical Specifications Installation Overview


Dimensions (mm) 95x89x32
Weight (g) 81
BSF-310A
Materials Top and bottom: Zytel + BSS-310
FR7200 5 1
+ 2
Snap-on mounting device:
Zytel 7335S -
4 3 I/O Modules
Electrical connection Internal system: plug-in - 4
connection
Removable screw terminals
5
(maximum cable dimension
6
2,5mm2)
Mounting Onto a standard 35 mm
mounting rail inside the Fire
Chassis
Alarm Control Panel or
Controller.
Current Consumption (idle) 40mA
Maximum output power, 24V 840mA
regulated
Maximum output power, 100mA Schematics
5V
Input voltage 18-32 V DC
24V DC input Internal
24V Output 24V +/- 5% 1 + 24V reg
5V Output 5V +/- 5%
Dimensions (mm) 95x89x32 0V BSS-310 Internal
3 + 5V reg
Weight (g) 81
Materials Top and bottom: Zytel
FR7200 Chassis Internal
0V
5
Snap-on mounting device:
Zytel 7335S
Electrical connection Internal system: plug-in
connection
Removable screw terminals
(maximum cable dimension
2,5mm2)

Order Numbers
Order number Description
BSS-310 Power Module

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.
Visit Autronica Fire and Security's Web site: www.autronicafire.com
AutroSafe Communication Module - BSL-310

Features
• Interface for internal communication between all I/O
modules
• Easily plugged onto each other or onto other I/O mod-
ules on a standard mounting rail
• Automatic addressing of the I/O module
• Designed to meet EN-54 and LPCB requirements and
conforms to CE standards

Application / Description
The Communication Module BSL-310 serves as an inter-
face for the common internal communication line between
all the different I/O modules.

The module provides the following:


• RS-232 interface with hand-shake, all lines
galvanically isolated to allow floating reference
• Built-in battery monitoring with control outputs for acti-
vation of charger/battery Connections
• Monitoring of earthing faults
Front view when mounted on rail
Mounting Cable 2
To Power Supply
The Communication Module is easily plugged onto a BSS-103A/02
mounting rail inside the Fire Alarm Control Panel (BS-
310/320) or the Controller (BC-320).
The Communication Module - as well as the Power Mod-
ule (BSS-310) - is always delivered with the Fire Alarm
Control Panel (BS-310/320) or the Controller (BC-320).

Since the Communication Module provides the common Cable 1


external interface for all modules, the module must al- To Connection
ways be mounted on the rail directly on top of the Power Module BSF-310B
Module BSS-310, which is the first module placed at the
bottom of the rail.
Connector on ribbon Cable 1 Signal
The I/O module will automatically detect its own address, To Connection Module BSF-310B
no Dip-switch or jumper settings are required. 1 INT
Cabling 2 RS_GND
3 TX
Two small ribbon cables are used for the internal connec- 4 RS_GND
tions inside the cabinet (BS-310/320 or BC-320). One
5 RS_GND
cable is used to interconnect the Communication Module
and the Connection Module BSF-310A (indicated as ca- 6 RS_GND
ble 1). The other cable is used to interconnect the Com- 7 RX
munication Module and the Power Supply BSS-103 (indi- 8 RS_GND
cated as cable 2). 9 CTS
10 RS_GND
Refer to connection drawing/schematics on the other side Connector on ribbon Cable 2 Signal
of this data sheet.
To Power Module BSS-103A/02
1 TEST
2 N.C.
3 N.C.
4 MAINS_OK
5 N.C.

P-BSL310/CE-Rev. B, 031117 Protecting life, environment and property...


Communication Module, BSL-310

Technical specifications Order Numbers


Dimensions (mm) 95x89x32 Order numbers Description
Weight (g) 81 BSL-310 Communication Module
Materials Top and bottom: Zytel
FR7200
Snap-on mounting device:
Zytel 7335S
Electrical connection Internal system: plug-in Installation Overview
connection
and ribbon cables.
Mounting Onto a standard mounting rail
inside the Fire Alarm Control
Panel or Controller.
BSF-310B
Internal current 24VREG: 15 mA
consumption Connection
Cable 1 Module
Current consumption, idle 13mA
24V REG
BSL-310
Current consumption, idle 2mA
5V REG
Current consumption, idle 18,5mA
24V BAT BSS-103A/02
Current consumption, 21,5mA Power Supply
24V REG Cable 2
Current consumption, 2,7mA
5V REG
RS-232 output Minimum 3K load resistance
at +/-5V
RS-232 input Minimum load resistance 3K
RS-232 Baud Rate 9600 Baud, 1 stop bit,
no parity
Battery Voltage failure Ubatt <22,6V +/-0,2V

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


AutroSafe Loop Driver Module – BSD-310/ BSD-311

Features
• Each Loop Driver Module allows connection of 127 loop
units
• Monitoring function for break or short-circuiting on the de-
tection loop
• Fail_Safe function ensures continuous communication on
the detection loop
• Easily plugged onto each other or onto other I/O modules
on a standard mounting rail
• Automatic addressing of the I/O module
• Designed to meet EN-54 and LPCB requirements and con-
forms to CE standards

Applications
The Loop Driver Module functions as a modem for data ex-
change between the control system and the detection loop.
The Loop Driver Module is easily plugged onto a mounting
rail inside the Fire Alarm Control Panel (BS-310/320) or the
Controller (BC-320). Indicators / Connections
1 detection loop for connection of 127 loop units can be con-
Front view when mounted on rail
nected to each Loop Driver Module. A loop unit is defined as
either a point (i.e. a detector or a manual call-point), I/O-unit
or an electronic sounder.
In addition to its main function, the I/O module provides two
important monitoring and security features. The loop resis-
tance on the detection loop is continuously monitored to reg- Screw
ister a possible break or short-circuit on the detection loop. terminal 10

If a communication failure occurs, a Fail_Safe function is


automatically activated. A low-frequency modulation on the Screw
loop will be detected, and a separate control output (F/S) will terminal 1
then be activated.
Green Red
The I/O module will automatically detect its own address, no indicator indicator
Dip-switch or jumper settings are required. H5 H1

Versions • Green indicator, H5. Communication indicator that gives a


pulsing green light during traffic.
The Loop Driver Module normally comes in two versions,
BSD-310 and BSD-311. The BSD-311 is a high-power ver- • Red indicator, H1. Fail_Safe indicator that gives a steady
sion (refer to technical specifications). red light if a communication failure occurs, i.e. the system
does not respond to an alarm.
Optionally there is a BSD-310/N version for use when there
are zone 2 detectors of type EXn on the loop. This is for
type /N detectors only. The I/O module has the following connections:

Capacity / Limitations Screw Terminal no. Signal


There can be a maximum of 6 Loop Driver Modules in each 1 OUT + (+24V)
Fire Alarm Control Panel or Controller. 2 OUT - OV
3 Shield
The maximum number of detectors and manual call-points
that can be connected to these 6 modules are 512 (refer to 4 IN +
EN-54). 5 IN -
Due to maximum loading, the maximum number of detectors 6 Shield
and manual call-points connected to each Loop Driver Mod- 7 F/S +
ule BSD-310 is 100. The remaining 27 loop units on each 8 F/S -
Loop Driver Module can be used for I/O signals. Reducing 9 Chassis
the number of detectors will allow the use of more I/O signals.
10 Chassis

P-BSD310/CE - Rev. F, 2005-09-26 Protecting life, environment and property...


Loop Driver Module, BSD-310

Technical Specifications Schematics - Detection Loop


Dimensions (mm) 95x89x32
Weight (g) 81
Materials Top and bottom: Zytel BSD-310 Detector
FR7200
1
Snap-on mounting device: +
3 3
Zytel 7335S 24V DC Out
Mounting Onto a standard mounting 1 2 1 2
2
rail inside the Fire Alarm -
3
Control Panel or Controller.
Electrical connection Internal system: plug-in +
4 3
connection In
Detection Loop: screw 2 1
5
terminals (maximum cable -
2
dimension 2,5mm )
6
Loop output voltage 24V DC
Maximum current output to 100 mA (BSD-310)
loop (24VREG) 200 mA (BSD-311)
Internal current consumption 24VREG, idle: 10 mA
24VREG, 12,5% Schematics - F/S Output Signal
communication
capacity: 26 mA
Output resistance (Ohm) +/-15% From previous Loop Driver Module
measuring accuracy on the
loop
Loop resistance measuring 0-300 Ohm
7
range +
Loop
Maximum capacitance on loop BSD-310 and BSD-311: Driver F/S Signal
cable 500 nF Module -
Maximum resistance on the BSD-310: 8
total cable length (+ and - 50 Ohm (each wire
conductors) maximum 25 Ohm) To next Loop Driver Module
BDS-311:
20 Ohm (each wire
maximum 10 Ohm)
Fail safe (F/S) output signal 10 ms OFF, 20 ms ON
Certificate for BSD-310/N NEMKO 03ATEX217X

Order Numbers
Order numbers Description
BSD-310 Loop Driver Module
BSD-311 Loop Driver Module H.P.
BSD-310/N Loop Driver Module
Certified to drive EXn
detectors inside zone 2

Installation Overview
I/O Unit Manual Call Point
Detector BN- 320
BRANNALARM

Tilpasningsenhet
K N US G LA S SE T
FIRE ALARM TR YK K HER PRE SS H ER E
Interface unit B R EA K G LA SS

Nr.

Loop
No.

Driver
Module BN- 320
BRANNALARM

Tilpasningsenhet

FIRE ALARM
Interface uni t

Nr.

No.

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


AutroSafe Output Module, Monitored - BSB-310

Features
• Provides 4 monitored output circuits.
• Monitoring function for break or short-circuiting.
• Easily plugged onto each other or onto other I/O
modules on a standard mounting rail.
• Automatic addressing of the I/O module.
• Designed to meet EN-54 and LPCB requirements
and conforms to CE standards.

Applications
The Output Module BSB-310 provides 4 monitored
output circuits for alarm sounders, fire alarm de-
vices, fire alarm routing equipment, fire protection
devices and other fault outputs.

The I/O module is easily plugged onto a mounting Connections


rail inside the Fire Alarm Control Panel (BS-310/320)
or the Controller (BC-320).
Front view when mounted on rail
Each alarm circuit has its own freely programmable
address and signal frequencies. The standard fre-
quency is 2 Hz.

Each output is fused with a 1A self-resetting fuse. Screw


The outputs are continously monitored to detect a terminal 10
possible break or short-circuit.
Screw
24V is supplied to the relay contacts via the internal terminal 1
bus, or in parallell via the screw terminals.
The I/O module has the following connections:
The I/O module will automatically detect its own ad-
dress, no Dip-switch or jumper settings are required. Screw Terminal no. Signal
1 Output AK1 - OV
2 Output AK1 + (+24V)
3 Output AK2 - (OV)
4 Output AK2 + (+24V)
5 Output AK3 - OV
6 Output AK3 + (+24V)
7 Output AK4 - OV
8 Output AK4 + (+24V)
9 Input 24 VBAT
10 Input 0 VBAT

The output AK4 may be configured to be used as a


monitored Fault Warning Routing Equipment
(FWRE) output (an output which routes a fault warn-
ing signal to a fault warning signal receiving station).

P-BSB310/CE - Rev. C, 000315 Protecting environment, life and property...


Output Module, Monitored - BSB-310

Technical Specifications Installation Overview


Dimensions (mm) 95x89x32
Weight (g) 81
Materials Top and bottom: Zytel
FR7200
Output
Snap-on mounting device: Module A utronica A utronica Autronica
End of line resistor
Zytel 7335S
Electrical connection Internal system: plug-in
connection
Outputs: screw terminals
(maximum cable dimension
2,5mm2)
Mounting Onto a standard mounting Schematics - Monitored Output
rail inside the Fire Alarm
Control Panel or Controller.
Control outputs: 4 pcs Voltage: 24V DC
monitored Maximum load: Terminal point 2, 4, 6, 8
1A each output +
24V_BAT
3A total
Sense
Electronic fuse: -
Terminal point 1, 3, 5, 7
Trip current: 2,2
A per output
at 25°C
Monitoring
End of line resitor 2000 Ohm
Internal current consumption 24VREG, idle: 10 mA

24VREG, 12,5% communi-


cation capacity: 26 mA Schematics - Fault Warning Routing Equipment
Output resistance accuracy on +/-25% (FWRE) Output, output 4 only
the loop
Output monitoring - short cir- < 200 Ohm
Ext FW Routing Eq
cuit
Output monitoring - normal 1000 - 3000 Ohm 8
(Not connected)
Output monitoring - break > 3000 Ohm 24V_BAT
Sense FWRE

7
Order Number
0V_BAT
Order Description Ship Weight
number metric/imperial
BSB-310 Output Module, Monitored

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.
Visit Autronica Fire and Security's Web site: www.autronicafire.com
MOUNTING INSTRUCTION
PRINTER and PAPER METAL BRACKET MOUNTING, WHEN POWER IS OFF
See drw. 1 and 2.

Make sure that the mains power is OFF!


• Remove from the front panel the transparent front cover (1) and the text foil behind it.
Use a thin screwdriver on the left side of the front cover to carefully lift it.
Use the same screwdriver to remove the cover from the printer-mounting place (2).
• To open the front panel door, unscrew 2 screws ”A” and ”B”.
• Place the metal bracket UD-598 (3), without a paper roll and a hole cut to the right, in a position shown on the drw.2.
• Fasten the metal bracket to the Front Panel with 2 screws M3x8 (”C”) from the front side.

Make sure that the end of the paper roll has a clean 90°° cut.
• Move the end of the paper upwards and insert it under the rounded ending of the metal bracket and printer board up to the front side.
• Pull out 20 cm of paper. Place the paper roll onto the bracket cylinder and fasten the washer and split pin.

Make sure that the paper roll is not touching the printer board.

• Remove the typewriter ribbon (4) from the printer unit so that the paper feed roller ”D” on the right side of the printer is easily accessible.
• Move the printer into the Front Panel.
• Insert the end of the paper in the printer paper slot and draw it through with the roller ”D” to the printer front.
• Fasten the printer with 3 screws M2.5x5. (the lower right pin hole is not to be used).
• Install the typewriter (4) so that the type ribbon is over the paper.
• Plug in the printer.
• Feed the paper through the printer cover paper slot (2) and mount the cover.
• Replace the text foil and transparent front cover (1).

PRINTER INTERFACE BA-180 and BSS-320 MOUNTING:


See drw. 2.
• Mount the pin-terminal (5) (2x15) on the backside of the BSS-320 - board.
• Plug the BSS-320 in the BSZ-310 board (on the front panel door back).
• Fasten its left side with 2-plate screws no.6x6.5 and 2 screws M3x5 on the right side.
• Note! Use a fibre-seating washer (6) under the M3x5 screws to evade the printer-boards contact.
• Plug the BA-180 printer interface on the BSS-320 board and fasten it with a 4 screws M3x5.

INSERTING OF THE PAPER-ROLL, WHEN POWER IS ON.


• Enter the Main Menu. Go to (4) SYSTEM. Select (4) PRINTER. Start (3) PAPER FEED.
Make sure that the end of the paper has a clean 90°° cut and the roll is in a position shown on the drw.2.
• Insert the end of the paper in the paper slot under the printer. Align the paper edges and slightly move the paper upwards.
The printer will feed the paper on the panel front side.
• Press PAPER FEED (3) again to stop the paper feeding.
• Place the paper roll onto the bracket cylinder and fasten the washer and split pin.
• Close the front panel. Fig.2
• To return to the Main Menu, press ? three times.

Fig.1

"A" "C"

4 BSZ-310

"D"

2 3
1

"C" Printer
For metal bracket / for papirholder interface
BA-180
"B"
BSS-320 6

P-BUP310/WX, 020429 Autronica Fire and Security AS


TECHNICAL DATA SHEET OF
F G 2 1 8 0 3
Performance Specification for battery type FG 21803 Battery dimensions (mm)

Nominal Voltage 12 Volts


Nominal Capacity
at 20 hour rate 18 Ah
at 10 hour rate (1,60 A) 15,5 Ah
at 5 hour rate (2,08 A) 14,0 Ah
at 1 hour rate (18 A) 9 Ah
Dimension (mm) Length=181, Width=76, Height=167
Approximate weight 6,2 kg
Energy Density 91Wh/l
Specific Energy 33,9Wh/kg
Internal Resisiteance (Fully charged battery) 10,5 mΩ 167
Maximum discharge current in 1 minute discharge 108 A
Maximum discharge current in 5 seconds discharge 270 A
Recommended charging tension (temperature=20°C)
floating use:13,5-13,8 V cyclic use:14,4-15,0 V 181
Thermal compensation factor
76
floating use: -18mV/°C cyclic use: -30mV/°C
Maximum charging current 4,5 A
Terminals Bolt and Nut M5
Vibration Test (2000 cycles/minute, 2,55 mm excursion, 2 hours)
No loss in capacity or performance
Shelf life - % of nominal capacity at 20°C
1 month 97% Terminal type
3 months 91%
6 months 83%
Storage temperature -20°C to 40°C 12
2
Operative temperature Range
Charge 0°C to 40°C
Discharge -20°C to 50°C

12
Case material Acrylonitrile-Butadiene-Styrene
Standard Version: According to UL-94 HB
Also available: According to UL-94 V0
Life expectancy (Stand-by) 3 to 5 years according Eurobat standards Nut M5

Constant Power Discharge Table (Watt)


Time 5' 10' 15' 20' 30' 45' 1h 2h 3h 5h 10h 20h
1,8V/Cell 540,3 388,6 310,2 261,0 201,1 152,1 123,6 72,7 52,4 34,3 18,9 10,3
1,75V/Cell 583,0 408,3 322,3 269,4 206,1 155,1 125,7 73,6 53,1 34,7 19,1 10,4
1,7V/Cell 628,9 429,0 334,8 278,1 211,2 158,2 127,8 74,6 53,7 35,1 19,3 10,5
1,65V/Cell 654,4 437,2 338,6 280,0 212,0 158,4 128,0 74,8 53,9 35,3 19,4 10,5
1,6V/Cell 680,8 445,5 342,3 282,0 212,7 158,7 128,2 75,0 54,1 35,4 19,5 10,5

Constant Current Discharge Table (Ampere)


Time 5' 10' 15' 20' 30' 45' 1h 2h 3h 5h 10h 20h
1,8V/Cell 54 37 29 24 18,0 13,5 10,9 6,3 4,5 2,9 1,59 0,90
1,75V/Cell 58 38 29 24 18,3 13,6 11,0 6,3 4,5 2,9 1,60 0,90
1,7V/Cell 62 40 30 25 18,6 13,8 11,0 6,4 4,6 3,0 1,62 0,92
1,65V/Cell 64 40 31 25 18,6 13,7 11,0 6,4 4,6 3,0 1,63 0,93
1,6V/Cell 67 41 31 25 18,6 13,7 11,0 6,4 4,6 3,0 1,65 0,93

Discharge time vs. discharge current Discharge time vs. discharge current
13,0 6,5 13,0 6,5

12,0 6,0 12,0 6,0


Terminal voltage (V)

Terminal voltage (V)

11,0 5,5 11,0 5,5

1.8A 0.9A
10,0 5,0 3.6A 10,0 5,0
9A
9,0 4,5 9,0 4,5
18A

8,0 4,0 8,0 4,0


36A
6 3 Temperature: 25°C (77°F) 6 3 Temperature: 25°C (77°F)
cells cells cells cells
0 2 4 6 8 10 12 14 16 18 20 22 0 10 20 30 40 50 60 70 80

Discharge time (hours) Discharge time (minutes)

Viale Europa, 63 - 36075 Montecchio Maggiore - VICENZA - ITALY - Phone +39 444 709350 - Fax +39 444 709360
SMOKE & HEAT DETECTORS
AutroSafe Optical smoke detector - BH-200

Features
• Interactive.
• Different sensitivity settings possible.
• Comprises the DYFI+ adaptive and self learning
functions.
• Selective to misleading environmental phenomena
that in a traditional system would lead to an un-
wanted fire alarm.
• Monitoring of optical path and electric circuit.
• Built-in thermistor for reading of temperature at the
detector point.
• Short circuit isolator in each detector.
• Comprises a built-in alarm indicator (LED).
• Conforms to EMC directive.
• Automatic addressing.
• Proven technology.
• Immune to electromagnetic disturbance. Versions
• Designed to meet the requirement of the major • BH-200 Smoke detector without SelfVerify.
maritime classification societies. • BH-300* Smoke detector with SelfVerify.
Applications • BH-500* Smoke detector with SelfVerify,
environment protected.
BH-200 is a point smoke detector for detection of
combustion gases mainly consisting of visible parti- • BH-500/S* Smoke detector with SelfVerify,
environment protected, with extra
cles. The detector has a built in thermistor and is
high sensitivity
designed for use with Autronica’s interactive fire
• BH-500/Ex* Smoke detector with SelfVerify,
alarm system, which can provide temperature infor-
EExia-version for use in all zones.
mation from the detector point.
• BH-500/S/Ex Smoke detector with SelfVerify,
EExia-version for use in all zones,
BH-200 is suitable for use in most applications with extra high sensivity
where visible smoke can be expected during a fire,
• BH-500/N Smoke detector with SelfVerify,
such as:
Eexn-version for use in zone 2 only
• Bedrooms • Corridors • BH-500/S/N Smoke detector with SelfVerify,
and extra high sensivity, Eexn
• Restaurants • Electrical rooms version for use in zone 2 only
• Offices • Production areas, etc. * See separate data sheet.

Principle Technical Specifications


Photoelectric, operating on the light scatter principle. Weight 150 g
Materials Polycarbonate Macrolon
Colour Light grey
Sensitivity Acc. to EN-54/9
Voltage 10 - 27V DC
Current consumption
Stand by: < 0,3mA
External alarm indicator 6mA
Environm. requirement EN-54/7
Degree of protection IP 44D
Working temperature - 20 - + 70°C
Humidity (non condensing) Max. 95% RH
Maintenance None
Service Replace if faulty
Approvals See separate documentation

P-BH200/CE - Rev. B, 000315 Protecting life, environment and property...


Optical smoke detector - BH-200

Connections

Order number Description


BWA-100 Socket (Base)
BHH-200 Detector head
BWP-100/20 Optional
Conduit box
for M20 GLANDS
BWP-100/25 Optional
Conduit box
for M25 GLANDS

1. - in
2. - out
3. common (+ in, + out)
4. external LED

Dimensions

Use of LED output:


When LED or other equipment is connected to the
LED output, a varistor - Siemens SIOVS07K25
(39V)-Autronica art. no. 8464-003.5039, is required
between terminals 1 and 4 in base.
The LED is connected between terminals 3 and 4,
terminal 3 being the positive terminal.

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.
Visit Autronica Fire and Security's Web site: www.autronicafire.com
AutroSafe Heat detector - BD-200

Features
• Interactive
• Heat detector intended for use in dry areas
• Plug-in detector head
• Short circuit isolator in each detector
• Comprises a built-in alarm indicator (LED)
• Automatic addressing
• Conforms to EMC directive
• Proven technology
• Configurable to class A1, A1R, A2S, B, C
• Immune to electromagnetic disturbance
• Not influenced by dust, humidity, exhaust gases,
electromagnetic fields such as radio transmitters,
cellular telephones, etc.
• Designed to meet LPCB requirements
• EN 54 pt. 5
• Designed to meet the requirement of the major Versions
maritime classification societies
• BD-200 Heat detector without SelfVerify
• BD-300* Heat detector with SelfVerify
Applications • BD-500* Heat detector with SelfVerify,
environment protected
BD-200 is a point heat detector for detection of rise • BD-500/Ex* Heat detector with SelfVerify,
in environment temperature caused by a fire. The EExia-version for use in all zones
detector is designed for use with Autronica’s interac-
tive fire alarm system, AutroSafe.
* See separate data sheet
BD-200 is often used in areas where the environ-
ment is likely to produce false/unwanted alarms from
smoke detectors such as: Technical Specifications
Weight 140 g
• Kitchens Materials PC/ABS
• Galleys Colour Light grey
• Bathrooms Sensitivity Acc. to EN-54/5
Voltage 10 - 27V DC
• Boiler rooms
Current consumption
• Workshops, etc. Stand by: < 0,3mA
External alarm indicator: 6mA
Environm. requirement EN-54/5
Degree of protection IP 44D
Principle
Working temperature -20 - +80°C
Temperature measurement by means of a thermis- Max. application Ref. table 1
tor for registration and reading of temperature at the Humidity (non condensing) Max. 95%
detector point. Alarms at temperature according to Maintenance None
configured class (Ref. table 1). Service Replace if faulty
Approvals See separate documentation
Weight 140 g

116-P-BD200/CE - Rev. C, 2005-07-20 Protecting life, environment and property...


Heat detector, BD-200

Dimensions

Table 1
Detector Typical application Maximum application Minimum static Maximum static
class temperature temperature response temperature response temperature
°C °C °C °C
A1 25 50 54 65
A1R* 5 50 54 65
A2S* 25 50 54 70
B 40 65 69 85
C 55 80 84 100
* R= Rate of rise.
* S= (Slow) Does not respond below the minimum static response temperature.

Note: The detector may give prewarning on a temperature below the max. application temperature.

Connections Use of LED output:

When LED or other equipment is connected to the


LED output, a varistor - Siemens SIOVS07K25
(39V) - Autronica art. no. 8464-003.5039, is required
between terminals 1 and 4 in base. The LED is con-
nected between terminals 3 and 4, terminal 3 being
the positive terminal.

Order number Description


BWA-100 Socket (Base)
1. - in BDH-200 Detector head
2. - out BWP-100/20 Optional Conduit box
3. common (+ in, + out) for M20 GLANDS
4. external LED BWP-100/25 Optional Conduit box
for M25 GLANDS

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


Connections in detector base BWA-100

CONNECTIONS IN DETECTOR BASE (SOCKET) BWA-100


TILKOBLING I DETEKTORSOKKEL BWA-100

AutroSafe system Conventional system


AutroSafe system Konvensjonelt system

1 = - NEGATIVE IN 1 = - NEGATIVE COMMON


MINUS INN FELLES MINUS

2 = - NEGATIVE OUT 2 = + POSITIVE IN


MINUS UT PLUSS INN

3 = + POSITIVE COMMON 3= POSITIVE OUT


FELLES PLUSS PLUSS UT

4= OUTPUT EXT.LED 4= OUTPUT EXT.IND. (T)


UTGANG EXST. LED UTGANG EKST. IND.(T)

3 3

LED
LED
R ≈ 2kΩ

4
4

NB! Figure shows connections to AutroSafe System.

NOTE!

Tamper- and vibration-proof installation.


On Maritime, Offshore and other installations
where vibration can be expected, the detector
head should be locked in place in order to
secure proper electrical connection and to
prevent damage. This is obtained by removing
the locking nub in the detector base with a pair
of cutting nippers or similar.

Inngreps- og vibrasjonssikker installasjon.


Ved maritime, offshore og andre installasjoner
hvor vibrasjoner forventes, må detektorhodet
låses for å sikre korrekt elektrisk forbindelse og
for å forhindre skade. Dette oppnås ved å fjerne
fjærstopperen i detektorbasen med avbiter eller
lignende.

Locking nub / Fjærstopper

AUTRONICA FIRE AND SECURITY AS


Fire and Security, Trondheim, Norway Phone: +47 73 58 25 00, Fax: 73 58 25 01
Oil and Gas, Stavanger, Norway Phone: +47 51 84 09 00, Fax: +47 51 84 09 99
Maritime division, Spikkestad, Norway Phone: +47 31 29 55 00, Fax: +47 31 29 55 01

Visit Autronica Fire and Security AS’ website: www.autronicafire.com

116-P-BWA100/WX, Rev. A, 2006-04-24


AutroSafe Conduit box BWP-100

Features
• Designed to protect the wiring to the detectors in
humid environments.
• Easy to mount.

Applications
BWP-100 is a conduit box for installation of detec-
tors in environments that may be humid/ wet. The
conduit box is designed for use with Autronica’s in-
teractive fire alarm system, AutroSafe, to make the
detector terminals drip-proof.

BWP-100 is suitable for use in environments such


as engine rooms, workshops, storerooms etc.
Terminals for screens are available in the box.
Standard detector base BWA-100 is used for con-
nection and mounting to the detector head. Technical Specifications
Dimensions Ø 112 x 63 mm
Weight 182g
Versions Material Self extinguishing
polycarbonate, light grey
• BWP-100/20 Standard version, 4 knock outs for Degree of protection IP44 (IEC 529)
mounting of M20 skintop glands. with detector
Two glands with back nuts are Maintenance None
enclosed.
• BWP-100/25 Offshore version, 4 holes ø25 for
mounting of glands or blanks
(not enclosed).

P-BWP100/CE, 010531 Protecting life, environment and property...


Conduit box BWP-100

Order Numbers
Order numbers Description
BWP-100/20 Conduit box
(Standard version)
BWP-100/25 Conduit box
(Offshore version)

Dimensions

125mm Ø=5,4mm

70mm

112mm

63mm

108mm

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


FLAME DETECTORS &
INTERFACE UNIT
Fire Detection Detector Flame IR 601F 253040

Clearance for

20
Detector head
Removal
Detector base
Deckhead
mounting

87
Conduit knockout
to suit ø20 mm or
ø 25 mm gland.
4 Positions
Front View

163

ø 144

2 x ø 5 mm
R
L2

L
L1

Top View
Voltage: 18 - 28 VDC
Quiescent current: 150 - 350 µA at 18 - 28VDC
Stabiliation time: 30 sec.
Reset time: 2 sec.
Alarm current: 36 - 70,5 mA 18 - 31 V
Operating temp: - 20 to + 70 dg.C
Relative Humidity: 90% continious (non-condensating) INSTALLATION DATA
Weight detector head/base: 0,08 Kg See data sheet no. 253040-MDS--A-001/002
Weight deckhead mounting box: 0,30 Kg
Cable entry: 4 x ø 20 / ø 25 mm Knockout Part no:
Degree of protection: IP 54 with deckhead mounting box 601F IR Detector head: 253040
Field of view: 100 dg. Detector base: 253044
Detection range: 0,1 m2 n-heptane / 20 meter Deckhead mounting box: 253036
Material: Heien-Larssen
Fire Suppression Systems
FR1 10'BAYBLEND' IR Flame Detector Autronica Fire and Security AS
Data Sheet No. 601 F Division Maritime
Industriveien 7, 3430 Spikkestad, Norway
Phone: + 47 31 29 55 00,
253040 - PDS - B To copy or use this document without owners permission is prohibited
Fax: + 47 31 29 55 01
e-post: info@autronicafire.no A UTC Fire & Security Company
Fire Detection Detector Flame IR 601F 253040

Detector head
1. Install the Deckhead Mounting Box
2 Off M4 Pan to the deck.
Head Screw 2. Install the detector base to the
Deckhead Mounting Box using the
Detector base two M4 Panhead screws.
3. Connect the wires from the control
Deckhead panel to the terminals in accordance
mounting with the interconnection diagramas.
Conduit knockout 4. Snap the detector head into correct
to suit ø20 mm or position.
ø 25 mm gland.
4 Positions

Exploded View
163

ø 144

2 x ø 5 mm
R
L2

L
L1

Top View with


detector head removed
- Next detector
Loop out or
End Of Line
L(-) L2 (+)
Loop in
L1 (+) R
Optional
Remote
+ Indicator

Detector Base Wiring

Material: Heien-Larssen
IR Flame Detector Fire Suppression Systems
FR1 10'BAYBLEND'
601 F Autronica Fire and Security AS
Division Maritime
Data Sheet No.
Installation data Industriveien 7, 3430 Spikkestad, Norway
Phone: + 47 31 29 55 00,
253040-MDS-B-001 To copy or use this document without owners permission is prohibited
Fax: + 47 31 29 55 01
e-post: info@autronicafire.no A UTC Fire & Security Company
Fire Detection Detector Flame IR 601F 253040

50O 50O

4m
0,05 m2

ø 9,50 m

8m
0,1 m2

ø 19,00 m
12m

0,3 m2

ø 28,50 m
16m

0,4 m2 Height above the fire

ø 38,00 m
Approx. flame area
Fig. 1 Field of view

Nore 1:
If necessary the detector can be mounted securely using a suitably
fabricated bracket at an angle or on a vertical surface to view the risk.

Note 2:
The above diagram is not to scale.

Material: Heien-Larssen
IR Flame Detector Fire Suppression Systems
FR1 10'BAYBLEND'
601 F Autronica Fire and Security AS
Division Maritime
Data Sheet No.
Installation data Industriveien 7, 3430 Spikkestad, Norway
Phone: + 47 31 29 55 00,
253040-MDS-B-002 To copy or use this document without owners permission is prohibited
Fax: + 47 31 29 55 01
e-post: info@autronicafire.no A UTC Fire & Security Company
AutroSafe Flame Detector Interface 116-5861-010.2015

Features
• Interface for 601F Flame Detector
• Loop-powered interface
• Low cost
• Proven technology
• Easy installation
• High degree of protection

Applications/Description
The addressable Flame Detector Interface is a loop-
powered unit for interfacing the 601F IR Flame
detector to the AutroSafe Interactive Fire Detection
System. The interface is connected directly to the
detection loop and requires no external power source.
The unit can be used for interfacing of one flame
detector only and is mounted in a deckhead mounting
box.

The surface chosen for the mounting should be flat


over the area of the underside of the housing to
ensure a stable fixing and strong enough to take the ESD Warning Label
weight of the mounting, detector base and sensor. The product is marked with the ESD symbol.
Attention: Observe precautions for handling
The unit is intended for indoor applications only. electrostatic sensitive devices”.

Compatibility Note: When opening the package, take the


The Flame Detector Interface is compatible with necessary precautions to avoid electrical
AutroSafe version 3.7 and later versions. discharges caused by static electricity.
The interface is not compatible with AutroMaster 5000
Presentation System, AutroOS Control & Monitoring
System or Autroprime Interactive Fire Detection
System.

Degree of Protection
The interface, with the detector mounted, has IP 54
degree of protection. Ex-versions are not available.

Mounting Interface with detector mounted


Note:
D
Do not disassemble the interface unit or disconnect
the wires. Any other way of handling the unit than
what is described may jeopardize the warranty.

The interface unit is mounted in a deckhead mounting


box. See illustration on the back of this datasheet .

116-P-FLAMEDETINTERF/CE 2007-02-21 Protecting life, environment and property...


AutroSafe, Flame Detector Interface, 116-5861-010.2015

Cable Connections
Mounting / Dimensions

L1: red

L: black

Technical Specifications
Dimensions 40x163x132 mm
(HxWxD)
Weight 300 g
Material 20% Glass filled PBT
Cable entry 4 x ø 20 / ø 25 mm Knockout
Degree of IP 54 with detector mounted
protection
Operating 0 to + 70 ºC
temperature

Part number Description


AutroSafe Flame Detector
116-5861-010.2015
Interface

116-5861-010.2012 Detector Base for 601 series


116-5861-010.2011 IR-Flame Detector Head 601F
Accessories
116-6571-011.1920 Gland M20
116-6531-006.1920 Back-nut M20

AUTRONICA FIRE AND SECURITY AS


Fire and Security, Trondheim, Norway Phone: +47 73 58 25 00, Fax: 73 58 25 01, e-mail: info@autronicafire.no
Oil and Gas, Stavanger, Norway Phone: +47 51 84 09 00, Fax: +47 51 84 09 99
Maritime division, Spikkestad, Norway Phone: +47 31 29 55 00, Fax: +47 31 29 55 01

Visit Autronica Fire and Security AS’ website: www.autronicafire.com


MANUAL CALL POINTS
AutroSafe Manual call-point with SelfVerify® - BF-300

Features
• Addressable
• Max. 3-second response time
• The call-point comprises a built-in indicator (LED)
• Can be tested by means of a special test-key
• With the SelfVerify®-functions
• Short-circuit isolator in each call-point
• Automatic addressing
• Proven technology
• Intended for connection to Autronica’s interactive
alarm system, AutroSafe
• Designed to meet the requirement of the major
maritime classification societies
Applications
BF-300 is a manual call-point for indoor use.
The call-point is designed for use with Autronica’s
interactive fire alarm system, AutroSafe, and com-
prises the SelfVerify® function. This function en-
sures the highest grade of reliability and the lowest
degree of manual testing because all units compris- Versions
ing this function are automatically self-tested once
• BF-300 Manual call-point with SelfVerify®
every 24 hours.
• BF-300M* Manual call-point with SelfVerify®,
with metal mounting box and cable
Optionally there is a BF-300M version, which is de-
glands
livered with a metal box fitted with two cable glands.
• BF-500/EX* Manual call-point with SelfVerify®.
This version is made for applications where a higher
EExia-version for use in all zones
degree of weather protection is required.
• BF-300M/N* Manual call-point with SelfVerify®.
Eexn-version for use in zone 2 only
There are also manual call-points for use in hazard-
ous area zone 2. The BF-300M/N has a metal • BF-500/N Manual call-point with SelfVerify®.
Eexn-version for use in zone 2 only
mounting box with two cable glands.
The BF-500/N has a standard plastic mounting box. * See separate data sheet
They must be connected to the BSD-310/N loop
driver, but do not require an isolator/barrier unit. Technical Specifications
Weight 108 g
The call-point must be installed according to local
Material Thermo plastic
regulations, which normally means along escape
Colour Red
routes, landings and exits.
Voltage 10 - 27V DC
Principle Current consumption
Stand by: 0,3mA
Break glass operation, releasing alarm switch.
Alarm (LED): 6mA
Reset when a new glass is mounted.
Environm. requirement EN-54
Degree of protection IP 24
“SelfVerify®”, the call-point’s ability to initiate Working temperature - 30 to + 50°C
alarms is regularly checked.
Storage temperature - 55 to + 70°C
Humidity (non-condensing) Max. 95% RH
Maintenance Replace broken glass
Service Replace if faulty
Approvals See separate documentation
2
Cable wire Maximum 2,5 mm
Certificate for BF-500/N NEMKO 03ATEX217X

116-P-BF300/CE - Rev. G, 2006-09-07 Protecting life, environment and property...


Manual call-point with SelfVerify® - BF-300

Order Numbers Connections


Order number Description
BF-300 Call-point
BF-300/GB BF-300 with labels 1 2 3 4 5 6
according to BS5839 part 2
BF-500/N Call-point certified for use in
zone 2. BNB-300
BF-300/GB1 BF-300/GB without
mounting box
BF-300/Y1 Manual Call-point, yellow
BF-300/S BF-300, Swedish label

1. Pos (+) in
2. Pos (+) out
3. Neg (-) in
4. Neg (-) out
5. Internal connection
6. Internal connection
Dimensions

Dimensions: HxWxD = 87x87x39mm

20 Open mounting Flush mounting


19

Fig. 1 Fig. 1

Cable knock-outs
60
Ø10mm

Fig. 2
Fig. 3

Standard mounting box BFW-1


Flush mounting box

Fig. 1: Manual call-point


Fig. 2: Standard mounting box BFW-1
Fig. 3: Box for flush mounting

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


AutroSafe Manual call-point with SelfVerify® - BF-300M

Features
• Addressable
• Max. 3-second response time
• The call-point comprises a built-in indicator (LED)
• Can be tested by means of a special test-key
• With the SelfVerify®-functions
• Short-circuit isolator in each call-point
• Automatic addressing
• Proven technology
• Intended for connection to Autronica’s interactive
alarm system, AutroSafe
• Designed to meet the requirement of the major
maritime classification societies

Versions
Applications
• BF-300* Manual call-point with SelfVerify®
BF-300M is a manual call-point designed for use • BF-300M Manual call-point with SelfVerify®,
with Autronica’s interactive fire alarm system, with metal mounting box and cable
AutroSafe, and comprises the SelfVerify® function. glands
This function ensures the highest grade of reliability • BF-500/EX* Manual call-point with SelfVerify®.
and the lowest degree of manual testing because all EExia-version for use in all zones
units comprising this function are automatically self- • BF-300M/N Manual call-point with SelfVerify®.
tested once every 24 hours. Eexn-version for use in zone 2
only
BF-300M is delivered with a metal box fitted with • BF-500/N* Manual call-point with SelfVerify®.
two cable glands. This version is made for applica- Eexn-version for use in zone 2
tions where a higher degree of weather protection is
* See separate data sheet
required.

There is also a BF-300M/N version for use in haz- Technical specifications


ardous area zone 2. It must be connected to the
Weight 989 g
BSD-310/N loop driver, but does not require an iso-
Material Thermo plastic
lator/barrier unit.
Material, M-version box Silumin
Colour Red
The call-point must be installed according to local
Voltage 10 - 27V DC
regulations, which normally means along escape
Current consumption
routes, landings and exits.
Stand by: 0,3mA
Alarm (LED): 6mA
Environm. requirement EN-54
Principle Degree of protection, IP 44
inner housing
Break glass operation, releasing alarm switch. Working temperature - 30 - + 50°C
Reset when a new glass is mounted. Humidity (non-condensing) Max. 95% RH
Maintenance Replace broken glass
“SelfVerify®”, the call-point’s ability to initiate Service Replace if faulty
alarms is regularly checked. Approvals See separate documentation
2
Cable wire Maximum 2,5 mm
Certificate for BF-300M/N NEMKO 03ATEX217X

116-P-BF300M/CE, Rev. E, 2007-08-10 Protecting life, environment and property...


Manual call-point with SelfVerify® - BF-300M

Order Number Description


116-BF-300M BF-300 with metal mounting
box, including two FG16
1 2 3 4 5 6
cable glands
116-BF-300M/GB BF-300M with labels
according to B5839 part 2 BNB-300
116-BF-300M/N BF-300M certified for use in
zone 2

1. Pos (+) in
2. Pos (+) out
3. Neg (-) in
4. Neg (-) out
5. Internal connection
6. Internal connection

Dimensions

Slot for test key

Inlet = PG 16

Alarm test key

AUTRONICA FIRE AND SECURITY AS


Fire and Security, Trondheim, Norway Phone: +47 73 58 25 00, Fax: 73 58 25 01, e-mail: info@autronicafire.no
Oil and Gas, Stavanger, Norway Phone: +47 51 84 09 00, Fax: +47 51 84 09 99
Maritime division, Spikkestad, Norway Phone: +47 31 29 55 00, Fax: +47 31 29 55 01

Visit Autronica Fire and Security AS’ website: www.autronicafire.com


DISCONNECTION UNITS
AutroSafe Disable Input Unit with Pushbuttons- BW-200

Features
• Disables detection zone(s).
• Configurable disablement time.
• 2 buttons for disablement / enablement.
• 1 Output: 24V for indication.
• LED- indicator.
• Built in short circuit isolator
• Adressable unit.
• Loop powered

Applications
BW-200 is a disable unit connected to the detection
loop, to disable one or a number of detection zones
The disablement time is configurable from the
Technical Spesifications
system configuration (AutroSafe configuration Tool).
Weight 250 g
A “Disablement” button activates disablement of Material Polycarbonate
zones, and a steady light in the LED indicates the Colour Light grey
disablement. The light starts flashing 5 minutes Input function Buttons
before the disablement time expires. To enable Output 24V for external indication
zones during disablement, i.e. before the Voltage ALcom (detector loop) 24V DC
disablement time automatically expires, the Current consumption:
“Restore” button is used. Stand by 0,3 mA
Environm. requirement EN-54/5,7
BW-200 has one (1) output for parallel indication / Degree of protection:
control. The output requies separate 24V supply. PG-inlets (PG-13,5) IP 66
Working temperature - 20 - + 70°C
The unit har a built-in short-circuit isolator. In the Humidity (non condensing) Max. 95% RH
event of a short cut, the short circuit location will be Maintenance None
isolated. Service Replace if faulty
Approvals See separate documentation
BW-200 is designet for use with Autronica’s
interactive fire alarm system, AutroSafe.

P-BW200/CE – 010531 Protecting life, environment and property...


Disable Input Unit with Pushbuttons- BW-200

Order Number
Order number Description
BW-200 Disable Input Unit w/ Pushbuttons

DISABLED FUNCTION / AREA

Innstallation Overview
DISABLE RESTORE

BN- 320
B RANNALARM

Tilpasn ingsenhet
K N U S GLA S SE T
FIRE ALARM TRYKK HER PRESS H ERE
I nterface unit BRE AK G LA S S

Loop
Nr.

No.

Driver DISABLE INPUT DEVICE BW-200 FIRE & SECURITY

Module BW-200

Connections

24V Output

24V

LED
Steady light when disabled
Flashing the last 5 min. of disablement

Disable detection zones


+
+
- Restore detection zones
Al_Com Loop
-

1 or 2 units on each loop: Connect detector loop + 24V to Ø1, and detector loop -24 to Ø3
More than 2 units on each loop: Use external 24V supply

Separate 24V DC must always be used when control outputs are connected to the loop

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.
Visit Autronica Fire and Security's Web site: www.autronicafire.com
ZENER BARRIER &
EX-DETECTORS
AutroSafe Barrier Unit BZ-500

Declaration of conformity and instructions

Features
• Covers Ex zones 0, 1, 2.
• EEx ia IIC approval.
• Galvanic isolator.
• NO PE-conductor required.
• Up to 20 detectors.
• Full interactive communication.
• Detectors, call-points and I/O-units available.

Applications
BZ-500 is a barrier unit designed for intrinsically
safe installation of AutroSafe detectors in hazard-
ous area zone 0, 1 or 2.

The barrier is a galvanic isolator, hence the in- Notified Body NEMKO-Oslo-Norway
stallation requires no PE-conductor. ID no. 0470
EC type examination certificate NEMKO 03ATEX230
BZ-500 must be installed in safe area and is con- Directive and standards 94/9/EC (ATEX)
nected to the Al_Com detector loop. EN 50014
EN 50020
Also a separate 24V supply is required. The loop 89/336/EEC (EMC)
branch-off into the hazardous area accepts 1-20 Emission: EN 500814:1992
detectors, call-points etc. depending on gas group Immunity: EN 50130-4: 1995
and loop unit type. All must be approved Ex- EN 61000-6-2: 1999
types. Ex parameters
II 1 G
[EEX ia] Iic
Co gas group IIC * 0,48mF
Technical Specifications Co gas group IIB * 2,88mF
Weight 1000 g Co gas group IIA * 11,6mF
Dimensions 220 x 170 x 152 mm Uo 15,75V
Io 63,5 mA
Material Polycarbonate
Po 443 mW
Colour Light grey
Lo 1,26 mH
Degree of protection IP55
Maintenance None
Temperature -20 - +60°C
Service Replace if faulty
Humidity (non condensing) Max. 95%
Supply voltage 23 - 27V DC * The total capacitance (cable included) in the branch-off must not
Current consumption 50mA exceed Co.
Environmental requirement EN50020
Barrier Certificate BASEFA No.
BAS00ATEX7087
Barrier Pepperl+Fuchs
KFD0-CS-Ex1.54

P-BZ500/CE-Rev. C, 030819 Protecting life, environment and property...


Zener Barrier - BZ-500

Order Numbers Connections


Order number Description
BZ-500 Complete unit SAFE AREA HAZARDOUS AREA
BZB-500 Spare part, interface unit
8481-500.0001 Spare part barrier KFDO-CS-Ex1.54
-
+ Al_Com / Ex
Branch-off
3
Compatibility Matrix
BARRIE 6
KFDO-CS-Ex1.54 KFDO-CS-Ex1.54 BZB-500
PN.71997 PN.107496 P&F 1.54

BZB-500 rev. 0 x
BZB-500 rev. 1 x x

24V + in/ou
24V - in/out
Al_Com + in/ou
Al_Com - in/out

24V + in/ou

Dimensions

152
170
26

152

BARRIER UNIT
+ +
Type BZ-500
Ø4.3

220
Fixing holes
204

26 + +

Glands = PG-16

Managing director Mr Frode Lund

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


Optical smoke detector
AutroSafe with SelfVerify® - BH-500/EX

Declaration of conformity and instructions


Features
• Interactive.
• Comprises the DYFI+ adaptive and self learning
functions.
• Selective to misleading environmental phenomena
that in a traditional system would lead to an un-
wanted fire alarm.
• Detection of visible smoke.
• Built-in thermistor for reading of temperature at the
detector point.
• Short circuit isolator in each detector.
• Automatic addressing.
• Proven technology.
• Immune to electromagnetic disturbance.
• Additional coating of PCB.
• Designed to meet the requirement of the major
maritime classification societies.
Technical Specifications
Application Weight 150 g
BH-500/EX is a point smoke detector for use in Material Polycarbonate / ABS
hazardous area zone 0, 1 or 2. It must be connected Colour Light grey
to the approved AutroSafe barrier BZ.500. The de- Sensitivity (BH-500/EX) Acc. to EN-54/7
tector has a built in thermistor and is designed for Voltage 10 - 27V DC
use with Autronica’s interactive fire alarm system, Current consumption
AutroSafe, which can provide temperature informa- Stand by: < 0,3mA
tion from the detector point. The SelvVerify® func- Environm. requirement EN-54/7
tion ensures the highest grade of reliability because Degree of protection IP 44D
all units comprising this function are automatically Working temperature - 20 - + 70°C
tested with a calibrated test once every 24 hours. Storage temperature - 55 - + 70°C
Humidity (non condensing) Max. 95% RH
Additional coating of PCB combined with the adap- Maintenance None
tivity of BH-500/EX, is making this detector suitable Service Replace if faulty
for industrial, maritime, off-shore and other «rough Notified body Nemko-Oslo-Norway
area» applications. ID No. 0470
EC type examination NEMKO 03ATEX218X
Principle certificate
Photoelectric, operating on the light scatter princi- Directives and Standards 94/9/EC (ATEX)
ple. EN 50014
EN 50020
«SelfVerify®», the detectors ability to initiate alarm 89/336/EEC (EMC)
at correct amount of smoke is regularly checked. Emission: EN 90081-1: 1992
Immunity: EN 50130-4: 1995
EN 61000-6-2:
1999
Ex parameters
II 1 G
EEx ia IIc T5
Ui = 15,75V
Ii = 63,5mA
Ci = 21,6nF
Li = 0
Pi = 443mW

116-P-BH500EX/CE, Rev. D, 2005-12-15 Protecting life, environment and property...


Optical smoke detector with SelfVerify® - BH-500/EX

Order Numbers Connections


Order number Description
116-BWA-100 Socket (Base)
116-BHH-500/EX Detector head
116-BHH-500/S/EX High sensitivity version
116-BWP-100/20 Optional
Conduit box
for M20 GLANDS
116-BWP-100/25 Optional
Conduit box
for M25 GLANDS

1. - in
2. - out
3. common (+ in, + out)

Dimensions

Managing director Mr Frode Lund

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


AutroSafe Manual call-point with SelfVerify - BF-502/EX

Declaration of conformity and instructions

Features
• Break glass unit for use in harsh environmental
conditions.
• Weather proof.
• Corrosion resistant GRP.
• Protection degree IP-66 and 67.
• Short circuit isolator in each unit.
• Automatic addressing.
• Proven technology.
• Designed to meet the requirement of the major
maritime classification societies.

Applications
BF-502/EX is a manual call point for use in haz-
ardous area zone 0, 1 or 2. It must be connected
to the approved AutroSafe barrier BZ-500. The Technical Specifications
call point has been designed for use with
Autronica’s interactive fire alarm system, Autro- Weight 0,5 kg
Safe, and comprises the SelfVerify function. This Material Glass reinforced polyester
function ensures the highest grade of reliability Colour Red
and the lowest degree of manual testing, because Voltage 10 - 27V DC
all units comprising this function are automatically Current consumption
self-tested once every 24 hours. Stand by: 0,3mA
Environm. requirement EN-54
The high IP degree and mechanical strength of Degree of protection IP 66
the enclosure makes the call point suitable for
Working temperature - 20 - + 70°C
outdoor applications in industrial, maritime and off-
Storage temperature - 55 - + 70° C
shore installations.
Cable inlets 2 x M20
The call point must be installed according to local Maintenance Replace broken glass
regulations which normally means along escape Service Replace if faulty
routes, landings and exits. Notified body Nemko-Oslo-Norway
ID No. 0470
Principle EC type examination certificate NEMKO 03ATEX218X
Break glass operation, releasing alarm switch. Directives and standards 94/9/EC (ATEX)
Reset when a new glass is mounted. EN 50014
EN 50020
“SelfVerify”, the call-points ability to initiate 89/336/EEC (EMC)
alarms is regularly checked. Emission: EN 50081-1: 1992
Immunity: EN 50130-4: 1995
EN: 61000-6-2: 1999
Ex parameters
II 1 G
EEx ia IIc T5
Ui = 15,75V
Ii = 63mA
Ci = 21,6nF
Li = 0
Pi = 443mW

P-BF502EX/CE - Rev A, 030819 Protecting life, environment and property...


Manual call-point with SelfVerify - BF-502/EX

Connections

Order number Description


BF-502/EX Manual Call-point certified for
use in zone 0, 1, 2
1 2 3 4 5 6

BNB-300/22/EX

1.Pos (+) in
2. Pos (+) out
3. Neg (-) in
4. Neg (-) out
5. Internal connection
6. Internal connection

Dimensions

Dimensions: HxWxD = 126x120x75mm

Managing director Mr Frode Lund

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.

Visit Autronica Fire and Security's Web site: www.autronicafire.com


INFORMATION PANEL, BV-320
AutroSafe Information Panel, BV-320

Features
• User-friendly display and operator controls.
• Scroll function for more alarms.
• Possible to change to different event windows.
• Backlighted operational buttons. Text display suitable
for full darkness operation.
• 16 lines display with 40 characters per line.
• Capable of surface or flush mounting and for rack
mounting in standard 19’’ cabinets.
• Designed to meet local regulations and conforms to CE
standards.
• Complies to environmental conditions of IEC-721-3-3
class 3k5.

Applications
The Information Panel BV-320 serves as an indication
device only. It provides information related to the defined
operation zone(s).
The panel offers a More Events button for scrolling
through several alarms within the same event window.
The Next Window button allows you to step to a new
event window, for example from Fire to Fault Warning
window.
The Lamp Test button activates all indicators to be lit for
5 seconds.
The panel communicates with other system units on the
local operating network, AUTROLON. There can be a
maximum of 32 panels in a LON- ring (EN-54). Demand
for more than 32 panels needs several LON-rings
External 24V DC power is required.

Text Display
• 16 x 40 characters alphanumeric display

Indicators
• Fire / Alarm, Function Disabled, Function Delayed,
Test, Power.
• Internal buzzer.

Operator Controls
• More Events button (black)
• Mute Panel button (black)
• Next Window button (red)
• Lamp Test button (green)

P-BV320/CE - Rev. D, 010531 Protecting life, environment and property...


Information Panel, BV-320

Technical Specifications Dimensions


Dimensions (mm) 350x195x84
Cut Out Dimensions 320 x 170 x 30 mm
Weight 2,3 kg
Materials Steel cabinet, ABS/PC
moulded front
Protection class IEC-529 / IP30
Power supply 24V DC
Two individual 24V sources
may be connected for redu-
dancy.
Current Consumption 180mA
Communication AUTROLON

Order Numbers

Order number Description


BV-320/N Information Panel, Norwegian
BV-320/D Information Panel, Danish
BV-320/GB Information Panel, English
BV-320/NL Information Panel, Dutch
BV-320/S Information Panel, Swedish

System Overview
AUTROLON - Ring Loop

Controller Controller

Fire
AA LL AA RRM
M AA LL AA RRM
M

Alarm Fire ext.. acktivated

Fire vent. activ.

Fire Brig. recvd. More Alarms


Silence buzzer

Silence sounders
Fire ext.. acktivated

Fire ve nt. activ.

Fire Brig. recvd. More Alarms


Silence buzzer

Silence sounders

Control
Power Rese t Power Reset

Prewarning Prewarning
1 2 3 Power 1 2 3 Power
Early warning Early warning
Fault 4 5 6 Fault 4 5 6

Panel
System fault System fault
7 8 9 Fault 7 8 9 Fault
Function disabled Function disa bled
Test C 0 Test C 0

Self Verify Self Verify


?

Self Verify Self Verify 2

Operator Panel
Autronica
Autronica

I/O
K NU S G L A SSE T
K NU S G L A SSET TR YK K H ER PRE SS H ER E
TR YK K H ER P RE SS H ER E BR EA K G L ASS
B R EA K G LA SS
KN U S G L AS SET
Autronica TR YK K H ER P RES S H ER E
B R EA K G LA SS

Autronica

I/O
K N US G LA S SE T
TRYK K HER PRE SS H ER E
I/O I/O
I/O
B REA K G L A SS

Repeater
Information
Panel Panel
AA LL AA RR M
M INFORMASJONSPANEL Power AA LL AA RR M
M INFORMASJONSPANEL

Fault

Fire ext. aktivated Fire ext. aktivated


Silence buzzer Sile nce buzzer
Fire vent. activ. Fire vent. activ.
More Alarms Silence sounders More Alarms Silence sounders
Fire Brig. recvd. Self Verify Fire Brig. recvd.

Power Rese t Power Reset

Controller

Autronica Fire and Security AS


Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01.
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99.
Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.
Visit Autronica Fire and Security's Web site: www.autronicafire.com
CERTIFICATES
Thorn Security Ltd.
SecurityHouse,the Summit ManufacturingPlant:
HanworthRoad
Sunbury-on-Thames Tyco Electronic ProductGroup
Middlesex TW16 5 DB 160,Billet Road
United Kingdom Walthamstow
Telephone:+44 (0) 1932743268 LondonE17 5DR
Fax: +44 (0) 1932743292 United Kingdom

MA Certificate No. 04-LD484746-XI

Product: Fixed Fire DetectionUnits


Model: Series600
Intended Service:
ConventionalFire detectorunits for machineryand accommodation
spaceson board of ACC and ACCU vesselsand
offshorestructures
Description:
The series 600 detection units comprise conventional and high performance optical smoke detectors, rate of rise,
'fixed temperature heat and flame detectors. The Series 600 range is coded with the following serial designations:

1601P-M -Optical smoke detector;


!601 PH-M -High performance optical smoke detector;
1601H-R-M -60 degree Crate of rise heat detector;
1601H-F-M -Fixed temperature 60 degree C heat detector;
1601F-M -Flame detector;
5B 5 ins. and Minerva Universal detector bases

Ratings:
Power supply: 18-28 V DC; 70 rnA Max
IOperating temperatures: -20 degree C to 70 degree C

Service Restrictions:
Unit certification is not required for these products. Not suitable for hazardous area applications.

IComments:
iTests and approval are for hardware only. Each configuration and external connection is to be specifically approved.

Term of Validity:
!This product/model is covered under Product Design Assessment(PDA) Certificate # 04-LD413626-1-PDA, dated
12/Aug/2004. This PDA Certificate expires Aug of 2009. It will remain valid for the 5 years from date of issue or
iuntil the Rules or specifications used in the assessmentare revised (whichever occurs first).

iSTANDARDS
ADS Rules:
2004 SteelVesselRules 1-1-4/3.7and4-7-3/11.5

54 (parts 5 and 7)
International:
IMO FSSCode Chapter9

As of 17/Aug/2004 List of Type Approved Equipment Page1 of 1

'National:IEN
Thorn SecurityLtd.
SecurityHouse,the Summit ManufacturingPlant:
HanworthRoad
Sunbury-on- Thames Tyco Electronic Product Gr
1 up

Middlesex TW16 5 DB 160, Billet Road


Walthamstow "
United Kingdom
i'
Il l;

Telephone:+44 (0) 1932743268 London E17 5DR 'iCc'j

Fax: +44 (0) 1932743292 United Kingdom I

MA Certificate No. 04-LD484746-XI

Product: Fire Detection System(Intrinscially Safe)


Model: M600 Ex Range
Intended Service: 1
Fire detectorunits for machineryand accommodation
spaceson boardof ACC andAClfU vessels

Description:
Intrinsically safe conventionalsmoke(opticalandionisation),heat,carbonmonoxide,flame and combinedcarbon
monoxideheatdetectorheadsthat aremountedinto a commonbaseunit for supplyand signalling.The M600 Ex
rangecomprisesthe following serialdesignations:

MR 601T Ex Optical smokedetector;


MF 601 Ex Ionisationsmokedetector;
MD 601 Ex, MD 611 Ex, Heatdetectors;
MU 601 Ex and MDU 601 Ex Carbonmonoxideand heatdetectors;
601 FEx-M Flamedetector;
M600 Ex baseUniversalmountingbaseunit for the M600 Ex detectors

Ratings:
Powersupply: 18-28V DC; 93 mA Max; Operatingtemperatures:0 °C to 40 °C
Safetyprotection:EEx ia llC T5
ServiceRestrictions:
Unit Certificationis not requiredfor theseproduct.
Comments:
Testsand approvalare for hardwareonly. Eachconfigurationand externalconnectionis to be specificallyapproved.

Term of Validity:
This product/modelis coveredunderProductDesignAssessment(PDA) Certificate # 02-LD312960-l-PDA, dated
12/Aug/2004.This PDA CertificateexpiresAug of 2009. It will remainvalid for the 5 yearsfrom date of issueor
until the Rules or specificationsusedin the assessment
arerevised(whicheveroccursfirst).

STANDARDS
ADS Rules:
2004 SteelVesselRules 1-1-4/3.7and4-7-3/11.5
National:
EN 50014:1997+ Amendments1 & 2, EN 50020:1994and EN 50284:1999;EC Directive 94/9/EC

International:
FSSCode Chapter9 Section2.3

As of 17/Aug/2004 List of Type Approved Equipment Page1 of 1