PLAN HISTORY

REV.
DATE DESCRIPTION BY APP. REMARKS
NO.
A 2008.10.01 SUBMITTED TO CLASS AND OWNER APPROVAL.
B 2008.11.14 RE-SUBMITTED TO OWNER FOR APPROVAL.
2008.12.02 APPROVED BY OWNER
2008.12.08 APPROVED BY CLASS WITH COMMENT
0 2009.01.16 ISSUED FOR WORKING.

Nhiem vu Ten Ky Ngay


PVT831

Nguoi KT 1
Dung quat Shipyard Nguoi KT 2
Ghi chu
Duyet
PROJECT NO.
OWNER: Petro Vietnam Transportation Company PVT831/832/833
APPROVED SUBJECT : 105,000 DWT CRUDE OIL TANKER
T.W. KIM
APPROVED

INSTRUMENT & ALARM POINT LIST


CHECKED

DRAWN.
H.S. RYU SHEET:1/34
DATE SCALE DWG. NO. REV.
2008. 10. 01 NONE PVT831-E-10-34 0
주 식 회 사 한 국 해 사 기술
KOMAC KOREA MARITIME CONSULTANTS CO., LTD.
HEAD OFFICE : (02) 549-3126,549-2117∼8 FAX : (02) 549-3127
PUSAN OFFICE : (051) 660-6603~4, 660-6651~59 FAX : (051) 660-6699
INDEX

No Description Page
1 Plan history 1
2 Index 2
3 General spec. 3
3-1 Function group 3
3-2 Main engine shut down 3
3-3 Main engine slow down (action group) 3,4
3-4 Extension alarm system 4
3-5 Alarm blocking group 4,5
3-6 Detail of head line 5,6
3-7 Output signal list for VDR 7,8
4 Alarm / Monitoring list 9-34
4-1 M/E Lub. oil system 9,10
4-2 M/E fuel oil system 11
4-3 M/E cool water system 12
4-4 M/E exhaust gas system 13
4-5 M/E Scav. Air system 14
4-6 M/E control & Safety system 15,16
4-7 Shaft & Stern tube system 17
4-8 No.1 Aux. engine system(A/E common system included) 18,19
4-9 No.2 Aux. engine system 20,21
4-10 No.3 Aux. engine system 22,23
4-11 Steam & Feed water system 24,25
4-12 Electrical system 26
4-13 Purifier system 27
4-14 Miscellaneous plants 28,29,30
4-15 F.O / D.O tanks 31
4-16 Bilge system 32
4-17 Output signal for slow/shut down signal/ECC gauges 33,34

2
General Spec. for alarm point list

1. Function group

The alarm/monitoring points are divided into following groups and listed.
The group identification is indicated for each alarm point in the table.

ML : Main engine lub oil system


MF : Main engine fuel oil system
MC : Main engine cool water system
ME : Main engine exhaust gas system
MA : Main engine scav air system
MS : Main engine control & Safety system
ST : Shaft & Stern tube system
GA : No.1 Generator engine system (Common system included)
GB : No.2 Generator engine system
GC : No.3 Generator engine system
ES : Electrical system
AB : Steam & Feed water system
PU : Purifier system
MP : Miscellaneous plants
FT : F.O / D.O tanks
BS : Bilge system

2. Main engine shut down

01 : Over speed
02 : M/E L.O inlet low pressure
03 : M/E Thrust pad bearing high temp
04 : M/E T/C L.O inlet low pressure

3. Main engine slow down

In case of following abnormal conditions, M/E speed shall be slow down.


01 : M/E L.O & P.C.O inlet low pressure
02 : M/E J.C.F.W inlet low pressure
03 : M/E Thrust pad high temperature
04 : M/E L.O & P.C.O inlet high temperature
05 : M/E P.C.O outlet high temperature
06 : M/E J.C.F.W outlet high temperature
07 : M/E Cylinder scavenging air high temperature
08 : M/E camshaft bearing high temperature
09 : M/E P.C.O Non-flow
10 : M/E Thrust radial & main bearing(cyl.) high temp
11 : M/E T/C L.O inlet low pressure

3
12 : Cyl. exh gas outlet & devaation high temperature
13: M/E T/C exh gas inlet high temperature
14 : Cylinder lubricator failure(non-flow)
15: Crankcase oil mist high
16 : Axial vibration level high

4. Extension alarm system

When the engine room is in unattended condition, the alarms from the machinery
alarm/monitoring system shall be classified into seven(7) groups and extended to
extension alarm panels in the wheelhouse and accommodation as

1) Alarm groups : (AL. GRP)

01 : Main engine shut down/slow down


02 : Vital alarm
03 : Non vital alarm
04 : Personal alarm
05 : Fire alarm
06 : Bilge high level
07 : System abnormal

2) Location of the extension alarm panel & Buzzer

1 – Bridge control console


1 – Chief Engineer’s day room with buzzer in bed room
1 – 2nd Engineer’s day room with buzzer in bed room
1 – 3rd Engineer’s room
1 – electrician room
1 – Officer's mess room
1 – Officer's recreation room
1 – Cargo control console
1 – Duty mess room
3(only buzzer)-Ship's office, Conference room, Gymnasium

The duty engineer shall be selected between engineers(C/E, 2nd, 3rd, Electrician ) by the duty
engineer select switch on the engine control console.
Engineer call alarm shall be activated, if an alarm is not acknowledged from the engine control
room within the predetermined time according to the rule.

5. Alarm blocking group : (BL.GRP)

To avoid unnecessary alarms in case of machinery stop conditions, alarm blocking function is
applied with following conditions.

4
01 : Finished with engine
02 : M/E stop
03 : M/E D.O use
04 : A/E D.O use
05 : No.1 A/E stop
06 : No.2 A/E stop
07 : No.3 A/E stop
08 :No.1 Aux. Boiler stop
09 :No.2 Aux. Boiler stop

6. Detail of head line

1) CH. NO : Series Nos. of point for function group

2) Description : Name of each point

3) Code

* Example : TIAH : Temperature indication and alarm high

1st letter 2nd letter Last letter


T : Temperature I : Indication L : Low
P : Pressure A : Alarm H : High
L : Level LL : Low Low
F : Flow, Frequency HH : High High
NF : Non Flow Etc.
DP : Differential pressure BL: Blocking
S : Speed revolution, Salinity SHD: Shut down
D : Density, Deviation SLD: Slow down
X : General Failure , Run C : Control

4) Signal type

4-20mA : - Pressure transmitter


- Level transmitter
- Salinity transmitter

PT100 : - Temperature transmitter

B/I(NC) : Binery input (Normal close) contact


- Level switch
- Pressure switch -    Salinity switch
- Diff. Pressure switch -    Etc.
- Temperature switch
- Limit switch/Micro switch
- Oil detector
- Flow switch
5
B/I(NO) : Binery input (Normal open) contact
- Machinery run signal

B/O(NO) : Binery output (Normal open) contact


-Pump, fan start/stop, each valve open/close order signal

5) Range : Display limitation

6) Unit

-
Pressure : Kg/cm2
-
Temperature : Deg. C
-
Level : meter (M)
-
Salinity : PPM
-
Revolution : RPM
7) Alarm(setting value) : alarm on limitation
8) AL GRP : Extension Alarm Group No.
9) BL GRP : Alarm Blocking Group no.
10) AC GRP : Action Group No.
11) Time delay : Delayed Time of alarm(adjustable)
12) Test method : Method of alarm test
-RV: Actual test
-PA: Pressure test(analog)
-PR: Pressure test(on-off)
-TA: Temperature test(analog)
-TR: Temperature test(on-off)
-LP: Pressure type level transmitter test
-LR: Level test(on-off)

13) DPU No. : A.M.S local control unit number


14) Supplier

- AMS : Alarm monitoring system maker


- PMS : Powe management system maker
- M/E : Main engine maker
- BMS : M/E remote control system maker
- A/E : Aux. engine maker
- D/G : Alternator maker
- BLR : Boiler maker
- : Press sensor maker
- : Temp sensor maker
- : Level switch maker
- MKR : Related system’s maker

6
7. Output signal list for VDR

M/E shut down

M/E over speed TRIP

M/E slow down

M/E L.O inlet low pressure

M/E P.C.O inlet low pressure

M/E T/C L.O inlet low pressure

M/E T/C exh. gas inlet high temperature

M/E L.O inlet high temperature

M/E P.C.O inlet high temperature

M/E thrust pad high temperature

M/E thrust radial bearing high temperature

M/E camshaft bearing high temperature

M/E P.C.O. outlet high temperature

M/E P.C.O. non flow

M/E crank case oil mist high

M/E cyl. Lubricator failure(L.O non flow)

M/E Cyl. Scavenge air outlet high temperature

M/E Jacket C.F.W inlet low pressure

M/E Jacket C.F.W outlet high temperature

M/E cyl. Exh. Gas outlet temperature

M/E cyl. Exh. Gas Dev. temperature

M/E Axial vabration level high


Main bearing high temperature(cylinder)

M/E manual em'cy stop

M/E wrong way

M/E control system abnormal

M/E safety system abnormal

M/E critical speed

M/E telegraph power failure

M/E telegraph system abnormal

M/E bridge control inperfact

M/E bridge control power failure

M/E governor system abnormal

7
No 1 A/E common trip

No 2 A/E common trip

No 3 A/E common trip

Em’cy generator common abnormal

AMS UPS1 power failure

AMS UPS2 power failure

MSBD common abnormal

Battery charger common abnormal

Aux. bioler common trip

Personnal alarm

Auto pilot power failure

Auto pilot no.1,2 control motor failure(hyd. Lock)

Public addressor main unit Power fail


Public addressor main unit system fail
E/R Co2 release

Pump room Co2 release

Local fire fighting system(LFFS) release

Signal light column power failure

E/R FWD port bilge high level

E/R FWD stbd bilge high level

E/R AFT bilge high level

Hull part bilge high level(common)

E/R Co2 alarm reley box power failure

8
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
ML01 M/E Main L.O inlet press PIAL 4-20mA 0 4 Kg/cm2 1.4 1 1 1 2 PA M/E 4 SLD:1.2 W /IND ON ECC

ML02 M/E P.C.O inlet press PIAL 4-20mA 0 4 Kg/cm2 1.4 1 1 1 2 PA M/E 4 SLD:1.2 W /IND ON ECC

ML03 M/E Main L.O inlet temp TIAH PT100 0 200 Deg.C 55 1 2 2 TA M/E 4 Slowdown:60
ML04 M/E P.C.O inlet temp TIAH PT100 0 200 Deg.C 55 1 2 2 TA M/E 4 Slowdown:60
ML05 M/E T/C L.O. inlet pressure PIAL 4-20mA 0 4 Kg/cm2 0.9 1 1 11 2 PA M/E 4 Slowdown:0.8
ML06 M/E camshaft bearing(fore side) temperature TIAH PT100 0 200 Deg.C 70 1 8 2 TA M/E 4 Slowdown:75
ML07 M/E thrust pad temp TIAH PT100 0 200 Deg.C 75 1 3 2 TA M/E 4 Slowdown:80
ML08 M/E thrust radial bear. temp TIAH PT100 0 200 Deg.C 65 1 10 2 TA M/E 4 Slowdown:70
ML09 M/E No.1 cyl. Main bearing(fore side) temperature TIAH PT100 0 200 Deg.C 65 1 10 2 TA M/E 4 Slowdown:70
ML10 M/E No.1 cyl. Main bearing temperature TIAH PT100 0 200 Deg.C 65 1 10 2 TA M/E 4 Slowdown:70
ML11 M/E No.2 cyl. Main bearing temperature TIAH PT100 0 200 Deg.C 65 1 10 2 TA M/E 4 Slowdown:70
ML12 M/E No.3 cyl. Main bearing temperature TIAH PT100 0 200 Deg.C 65 1 10 2 TA M/E 4 Slowdown:70
ML13 M/E No.4 cyl. Main bearing temperature TIAH PT100 0 200 Deg.C 65 1 10 2 TA M/E 4 Slowdown:70
ML14 M/E No.5 cyl. Main bearing temperature TIAH PT100 0 200 Deg.C 65 1 10 2 TA M/E 4 Slowdown:70
ML15 M/E No.6 cyl. Main bearing temperature TIAH PT100 0 200 Deg.C 65 1 10 2 TA M/E 4 Slowdown:70
ML16 M/E P.C.O. 1 outlet temp TIAH PT100 0 200 Deg.C 70 1 5 2 TA M/E 4 Slowdown:75
ML17 M/E P.C.O. 2 outlet temp TIAH PT100 0 200 Deg.C 70 1 5 2 TA M/E 4 Slowdown:75
ML18 M/E P.C.O. 3 outlet temp TIAH PT100 0 200 Deg.C 70 1 5 2 TA M/E 4 Slowdown:75
ML19 M/E P.C.O. 4 outlet temp TIAH PT100 0 200 Deg.C 70 1 5 2 TA M/E 4 Slowdown:75
ML20 M/E P.C.O. 5 outlet temp TIAH PT100 0 200 Deg.C 70 1 5 2 TA M/E 4 Slowdown:75
ML21 M/E P.C.O. 6 outlet temp TIAH PT100 0 200 Deg.C 70 1 5 2 TA M/E 4 Slowdown:75
ML22 M/E P.C.O. 1 non flow FAL B/I(NC) 1 1 9 15 RV M/E 4 Slowdown
ML23 M/E P.C.O. 2 non flow FAL B/I(NC) 1 1 9 15 RV M/E 4 Slowdown
ML24 M/E P.C.O. 3 non flow FAL B/I(NC) 1 1 9 15 RV M/E 4 Slowdown
ML25 M/E P.C.O. 4 non flow FAL B/I(NC) 1 1 9 15 RV M/E 4 Slowdown
ML26 M/E P.C.O. 5 non flow FAL B/I(NC) 1 1 9 15 RV M/E 4 Slowdown
ML27 M/E P.C.O. 6 non flow FAL B/I(NC) 1 1 9 15 RV M/E 4 Slowdown
ML28 M/E crank case oil mist high OMH B/I(NC) 1 15 2 RV M/E 1 Slowdown by BMS
ML29 M/E oil mist detect system failure XA B/I(NC) 2 2 RV M/E 1
ML30 M/E cyl. Lubricator system common abnormal XA B/I(NC) 2 14 2 RV M/E 1 Slowdown by BMS
ML31 M/E cyl. Lubricator system MCU power failure XA B/I(NC) 2 2 RV M/E 1
ML32 M/E cyl. Lubricator system BCU power failure XA B/I(NC) 2 2 RV M/E 1
ML33 M/E cyl. Lubricator system MCU failure XA B/I(NC) 2 2 RV M/E 1
ML34 M/E cyl. Lubricator system BCU failure XA B/I(NC) 2 2 RV M/E 1
ML35 M/E T/C L.O. outlet temperature TIAH PT100 0 200 Deg.C 95 2 2 TA M/E 4

9
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
ML36 M/E Main L.O pump St-by start XA B/I(NC) 3 2 RV 3
ML37 M/E L.O settling tank high level LAH B/I(NC) 3 15 LR 3
ML38 M/E cyl. Oil service tank low level LAL B/I(NC) 3 15 LR 3
ML39 M/E cyl. Oil service tank high level LAH B/I(NC) 3 15 LR 3
ML40 M/E Main L.O filter diff. Press high DPAH B/I(NC) 2 2 PR 4
ML41 M/E L.O sump tank low level LAL B/I(NC) 3 15 LP 4
ML42
ML43
ML44
ML45

10
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
MF01 M/E F.O inlet press PIAL 4-20mA 0 16 Kg/cm2 6.5 2 1 2 PA M/E 4 W/ IND ON ECC
MF02 M/E F.O inlet temp TIAHL PT100 0 200 Deg.C 95 160 2 1 2 TA M/E 4
MF03 M/E F.O high press. pipe leak LAH B/I(NC) 3 15 LR M/E 4
MF04 M/E F.O viscosity VIAHL 4-20mA 0 50 cst 3 3 20 RV 3
MF05 M/E F.O auto filter diff. Press high DPAH B/I(NC) 3 2 PR 3
MF06 M/E F.O supply unit mixing tank low level LAL B/I(NC) 3 15 LR 3
MF07 M/E F.O supply unit common abnormal XA B/I(NC) 3 2 RV 3
MF08 M/E F.O supply pump st-by start XA B/I(NC) 3 2 RV 3
MF09 M/E F.O circ. pump st-by start XA B/I(NC) 3 2 RV 3
MF10 M/E D.O use signal BL B/I(NC) 1 BLOCK'G 3
MF11
MF12
MF13
MF14
MF15
MF16
MF17
MF18
MF19
MF20

11
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
MC01 M/E A/C C.F.W inlet press PIAL 4-20mA 0 6 Kg/cm2 1 3 1 2 PA M/E 4 W/IND ON ECC
MC02 M/E Jacket C.F.W across engine differential pressure DPAH B/I(NC) 3 2 PR M/E 4
MC03 M/E Jacket C.F.W inlet pressure PIAL 4-20mA 0 6 Kg/cm2 2 1 1 2 2 PA M/E 4 SLD:1.5 W /IND ON ECC

MC04 M/E Jacket C.F.W inlet temp TIAL PT100 0 200 Deg.C 57 2 2 TA M/E 4
MC05 M/E Jacket No.1 C.F.W outlet temp TIAH PT100 0 200 Deg.C 90 1 6 2 TA M/E 4 Slowdown:95
MC06 M/E Jacket No.2 C.F.W outlet temp TIAH PT100 0 200 Deg.C 90 1 6 2 TA M/E 4 Slowdown:95
MC07 M/E Jacket No.3 C.F.W outlet temp TIAH PT100 0 200 Deg.C 90 1 6 2 TA M/E 4 Slowdown:95
MC08 M/E Jacket No.4 C.F.W outlet temp TIAH PT100 0 200 Deg.C 90 1 6 2 TA M/E 4 Slowdown:95
MC09 M/E Jacket No.5 C.F.W outlet temp TIAH PT100 0 200 Deg.C 90 1 6 2 TA M/E 4 Slowdown:95
MC10 M/E Jacket No.6 C.F.W outlet temp TIAH PT100 0 200 Deg.C 90 1 6 2 TA M/E 4 Slowdown:95
MC11 M/E J.C.F W pump st-by start XA B/I(NC) 3 2 RV 3
MC12 M/E C.F.W Exp. tank low level LAL B/I(NC) 3 15 LR 3
MC13 C.F.W de-aerating tank low level LAL B/I(NC) 3 15 LR 3
MC14 No.1 Low temp cooler C.S.W inlet temp TIAH PT100 0 200 Deg.C 57 3 2 TA 4
MC15 No.2 Low temp cooler C.S.W inlet temp TIAH PT100 0 200 Deg.C 57 3 2 TA 4
MC16 Low temp cooler C.S.W inlet pressure PIAL 4-20mA 0 6 Kg/cm2 3 1 2 PA 4
MC17 Low temp C.F.W pump st-by start XA B/I(NC) 3 2 RV 3
MC18 Main C S.W pump st-by start XA B/I(NC) 3 2 RV 3
MC19 .
MC20
MC21
MC22
MC23
MC24
MC25

12
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
ME01 M/E no.1 cyl. Exh. Gas outlet temp TIAH 4-20mA 0 600 Deg.C 430 1 12 2 TA M/E 4 Slowdown:450
ME02 M/E no.2 cyl. Exh. Gas outlet temp TIAH 4-20mA 0 600 Deg.C 430 1 12 2 TA M/E 4 Slowdown:450
ME03 M/E no.3 cyl. Exh. Gas outlet temp TIAH 4-20mA 0 600 Deg.C 430 1 12 2 TA M/E 4 Slowdown:450
ME04 M/E no.4 cyl. Exh. Gas outlet temp TIAH 4-20mA 0 600 Deg.C 430 1 12 2 TA M/E 4 Slowdown:450
ME05 M/E no.5 cyl. Exh. Gas outlet temp TIAH 4-20mA 0 600 Deg.C 430 1 12 2 TA M/E 4 Slowdown:450
ME06 M/E no.6 cyl. Exh. Gas outlet temp TIAH 4-20mA 0 600 Deg.C 430 1 12 2 TA M/E 4 Slowdown:450
ME07 M/E Cyl. Exh. Gas mean temp TI - 0 600 Deg.C - AMS - By software
ME08 M/E no.1 cyl. Exh. Gas Dev. temp TDIAH - 0 600 Deg.C -50 50 1 12 2 AMS -
ME09 M/E no.2 cyl. Exh. Gas Dev. temp TDIAH - 0 600 Deg.C -50 50 1 12 2 AMS -
ME10 M/E no.3 cyl. Exh. Gas Dev. temp TDIAH - 0 600 Deg.C -50 50 1 12 2 AMS - Slowdown+,- 50 By
ME11 M/E no.4 cyl. Exh. Gas Dev. temp TDIAH - 0 600 Deg.C -50 50 1 12 2 AMS - software
ME12 M/E no.5 cyl. Exh. Gas Dev. temp TDIAH - 0 600 Deg.C -50 50 1 12 2 AMS -
ME13 M/E no.6 cyl. Exh. Gas Dev. temp TDIAH - 0 600 Deg.C -50 50 1 12 2 AMS -
ME14 M/E T/C Exh. Gas inlet temp TIAH 4-20mA 0 600 Deg.C 520 1 13 2 TA M/E 4 Slowdown:550
ME15 M/E T/C Exh. Gas outlet temp TIAH 4-20mA 0 600 Deg.C 350 2 2 TA M/E 4
ME16

13
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
MA01 M/E Cyl. 1 Scavenge air fire detection TIAH PT100 0 200 Deg.C 80 1 7 2 TA M/E 4 Slowdown:120
MA02 M/E Cyl. 2 Scavenge air fire detection TIAH PT100 0 200 Deg.C 80 1 7 2 TA M/E 4 Slowdown:120
MA03 M/E Cyl. 3 Scavenge air fire detection TIAH PT100 0 200 Deg.C 80 1 7 2 TA M/E 4 Slowdown:120
MA04 M/E Cyl. 4 Scavenge air fire detection TIAH PT100 0 200 Deg.C 80 1 7 2 TA M/E 4 Slowdown:120
MA05 M/E Cyl. 5 Scavenge air fire detection TIAH PT100 0 200 Deg.C 80 1 7 2 TA M/E 4 Slowdown:120
MA06 M/E Cyl. 6 Scavenge air fire detection TIAH PT100 0 200 Deg.C 80 1 7 2 TA M/E 4 Slowdown:120
MA07 M/E Scav. Air inlet press PI 4-20mA 0 4 Kg/cm2 PA M/E 4 W/IND ON ECC
MA08 Scav. Air water mist catcher level high LAH B/I(NC) 3 15 LR M/E 4
MA09 Scav. Air box drain tank water level high LAH B/I(NC) 3 15 LR 4
MA10 No.1 aux. blower abnormal XA B/I(NC) 3 2 RV M/E 4
MA11 No.2 aux. blower abnormal XA B/I(NC) 3 2 RV M/E 4
MA12
MA13
MA14
MA15

14
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
MS01 M/E shut down SHD B/I(NC) 1 2 RV BMS 1
MS02 M/E slow down SLD B/I(NC) 1 2 RV BMS 1
MS03 M/E over speed TRIP SHD B/I(NC) 1 2 RV BMS 1
MS04 M/E manual em’cy stop XA B/I(NC) 1 2 RV BMS 1
MS05 M/E em'cy shut down prewarning XA B/I(NC) 2 2 RV BMS 1
MS06 M/E em'cy slow down prewarning XA B/I(NC) 3 2 RV BMS 1
MS07 M/E wrong way XA B/I(NC) 2 2 RV BMS 1
MS08 M/E start blocked XA B/I(NC) 3 2 RV BMS 1
MS09 M/E critical speed XA B/I(NC) 2 2 RV BMS 1
MS10 M/E start failure XA B/I(NC) 3 2 RV BMS 1
MS11 M/E not ready XA B/I(NC) 2 2 RV BMS 1
MS12 M/E control system abnormal XA B/I(NC) 2 2 RV BMS 1
MS13 M/E safety system abnormal XA B/I(NC) 2 2 RV BMS 1
MS14 M/E bridge control imperfect XA B/I(NC) 2 2 RV BMS 1
MS15 M/E slow down request XA B/I(NC) 3 2 RV BMS 1
MS16 M/E slow down cancelled XA B/I(NC) 3 2 RV BMS 1
MS17 M/E shut down cancelled XA B/I(NC) 3 2 RV BMS 1
MS18 M/E F.W.E signal BL B/I(NC) BMS 1 BLOCK'G 1
MS19 M/E stop signal(standstill) BL B/I(NC) BMS 1 BLOCK'G 2
MS20 M/E fuel cam position abnormal XA B/I(NC) 3 2 RV BMS 1
MS21 M/E Starting air press PIAL 4-20mA 0 40 Kg/cm2 15 2 2 2 PA M/E 4 W/IND ON ECC
MS22 M/E Control air press PIAL 4-20mA 0 10 Kg/cm2 5.5 2 2 2 PA M/E 4 W/IND ON ECC
MS23 M/E Safety air low press PAL B/I(NC) 0 10 Kg/cm2 5.5 2 2 2 PR M/E 4
MS24 M/E exh valve spring air press PIAL 4-20mA 0 10 Kg/cm2 5.5 2 2 2 PA M/E 4
MS25 M/E Axial vabration monitor system failure XA B/I(NC) 3 2 RV M/E 4
MS26 M/E Axial vabration level VIAH 4-20mA 0 10 mm 2.46 1 16 2 RV M/E 4 Slowdown by BMS
MS27 M/E telegraph power failure XA B/I(NC) 3 2 RV BMS 1
MS28 M/E telegraph system abnormal XA B/I(NC) 3 2 RV BMS 1
MS29 M/E governor system abnormal XA B/I(NC) 2 2 RV BMS 1
MS30 M/E VIT control abnormal XA B/I(NC) 2 2 RV BMS 1
MS31 M/E bridge control panel source failure XA B/I(NC) 2 2 RV BMS 1
MS32 M/E control room control source failure XA B/I(NC) 2 2 RV BMS 1
MS33 M/E control room safety source failure XA B/I(NC) 2 2 RV BMS 1
MS34 M/E control main(AC)l source failure XA B/I(NC) 2 2 RV BMS 1
MS35 M/E control em'cy(DC)l source failure XA B/I(NC) 2 2 RV BMS 1

15
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
MS36 M/E remote control relay panel power failure XA B/I(NC) 2 2 RV BMS 1
MS37 M/E T/C RPM high XA B/I(NC) 2 2 RV M/E 1

16
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
ST01 Inter. Shaft bearing temperature TIAH PT100 0 200 Deg.C 65 2 2 TA 4
ST02 Stern tube AFT bearing temperature TIAH PT100 0 200 Deg.C 60 2 2 TA 4
ST03 Stern tube FWD seal tank low level LAL B/I(NC) 3 15 LR 4
ST04 Stern tube AFT seal tank high level LAH B/I(NC) 3 15 LR 4
ST05 Stern tube AFT seal tank low level LAL B/I(NC) 3 15 LR 4
ST06 Stern tube L.O gravity tank low level LAL B/I(NC) 3 15 LR 4
ST07 Stern tube L.O sump tank low level LAL B/I(NC) 3 15 LR 4
ST08 Stern tube L.O pump St-by start XA B/I(NC) 3 2 RV 3

17
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
GA01 No 1 A/E common shut down SHT B/I(NC) 2 2 RV A/E 2
(overspeed trip, C.F.W outlet high temperature trip,
L.O inlet low pressure trip, each cylinder Exhaust
gas high temperature trip)
GA02 No 1 A/E H.T C.F.W inlet pressure PIAL 4-20mA 0 6 Kg/cm2 1.3 3 5 2 PA A/E 2
GA03 No 1 A/E L.O inlet pressure PIAL 4-20mA 0 10 Kg/cm2 3.5 2 5 2 PA A/E 2
GA04 No 1 A/E F.O inlet low pressure PAL B/I(NC) 4.6 2 4,5 2 PR A/E 2
GA05 No.1 A/E H.T C.F.W outlet temperature TIAH PT100 0 200 Deg.C 95 2 2 TA A/E 2
GA06 No.1 A/E L.O inlet temperature TIAH PT100 0 200 Deg.C 75 3 2 TA A/E 2
GA07 No.1 A/E pre-lub. L.O inlet low pressure PAL B/I(NC) 3 2 PR A/E 2
GA08 No.1 A/E L.O sump tank low level LAL B/I(NC) 3 15 LR A/E 2
GA09 No.1 A/E F.O leak tank high level LAH B/I(NC) 3 15 LR A/E 2
GA10 No.1 A/E Starting air inlet low press PAL B/I(NC) 8 3 2 PR A/E 2
GA11 No.1 A/E control air low press PAL B/I(NC) 6 2 2 PR A/E 2
GA12 No.1 A/E L.O strainer high diff. press. DPAH B/I(NC) 1 2 PR A/E 2
GA13 No.1 A/E exh. gas T/C outlet temperature TIAH PT100 0 700 Deg.C 500 2 2 TA A/E 2
GA14 No.1 A/E exh. gas T/C inlet temperature(no.1 ~ no.3 cyl.) TIAH PT100 0 700 Deg.C 580 2 2 TA A/E 2
GA15 No.1 A/E exh. gas T/C inlet temperature(no.4 ~ no.6 cyl.) TIAH PT100 0 700 Deg.C 580 2 2 TA A/E 2
GA16 No.1 A/E no.1 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA1 2 TA A/E 2 GA1 : Shutdown
GA17 No.1 A/E no.2 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA1 2 TA A/E 2 GA1 : Shutdown
GA18 No.1 A/E no.3 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA1 2 TA A/E 2 GA1 : Shutdown
GA19 No.1 A/E no.4 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA1 2 TA A/E 2 GA1 : Shutdown
GA20 No.1 A/E no.5 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA1 2 TA A/E 2 GA1 : Shutdown
GA21 No.1 A/E no.6 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA1 2 TA A/E 2 GA1 : Shutdown
GA22 No.1 A/E Cyl. Exh. Gas mean temp TI - 0 Deg.C - AMS - By software
GA23 No.1 A/E no.1 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GA24 No.1 A/E no.2 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GA25 No.1 A/E no.3 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
+, - '50 By software
GA26 No.1 A/E no.4 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GA27 No.1 A/E no.5 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GA28 No.1 A/E no.6 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GA29 No 1 A/E start failure XA B/I(NC) 3 2 RV A/E 2
GA30 No 1 A/E shut down system failure XA B/I(NC) 3 2 RV A/E 2
GA31 No 1 A/E electric power failure XA B/I(NC) 2 2 RV A/E 2
GA32 No 1 A/E CPU fault XA B/I(NC) 2 2 RV A/E 2

18
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
GA36 No.1 D/G Stator “R” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GA37 No.1 D/G Stator “S” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GA38 No.1 D/G Stator “T” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GA39 No.1 D/G fore bearing temperature TIAH PT100 0 200 Deg.C 90 3 2 TA D/G 2
GA40 No.1 D/G after bearing temperature TIAH PT100 0 200 Deg.C 90 3 2 TA D/G 2
GA41 No.1 A/E stop signal BL B/I(NC) A/E 2 BLOCK'G 5
GA42
GA43
GA44
GA45
GA46
GA47 A/E F.O viscosity VIAHL 4-20mA 0 50 cst 3 3 20 RV 3
GA48 A/E F.O auto filter diff. press high DPAH B/I(NC) 3 2 RV 3
GA49 A/E F.O supply unit mixing tank low level LAL B/I(NC) 3 15 LR 3
GA50 A/E F.O supply unit common abnormal XA B/I(NC) 3 2 RV 3
GA51 A/E F.O supply pump st-by start XA B/I(NC) 3 2 RV 3
GA52 A/E F.O circ. pump st-by start XA B/I(NC) 3 2 RV 3
GA53 A/E L.O settling tank high level LAH B/I(NC) 3 15 LR 2
GA54 A/E D.O use signal BL B/I(NC) 1 BLOCK'G 4

19
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
GB01 No 2 A/E common shut down SHT B/I(NC) 2 2 RV A/E 2
(overspeed trip, C.F.W outlet high temperature trip,
L.O inlet low pressure trip, each cylinder Exhaust
gas high temperature trip)
GB02 No 2 A/E H.T C.F.W inlet pressure PIAL 4-20mA 0 6 Kg/cm2 1.3 3 6 2 PA A/E 2
GB03 No 2 A/E L.O inlet pressure PIAL 4-20mA 0 10 Kg/cm2 3.5 2 6 2 PA A/E 2
GB04 No 2 A/E F.O inlet low pressure PAL B/I(NC) 4.6 2 4,6 2 PR A/E 2
GB05 No.2 A/E H.T C.F.W outlet temperature TIAH PT100 0 200 Deg.C 95 2 2 TA A/E 2
GB06 No.2 A/E L.O inlet temperature TIAH PT100 0 200 Deg.C 75 3 2 TA A/E 2
GB07 No.2 A/E pre-lub. L.O inlet low pressure PAL B/I(NC) 3 2 PR A/E 2
GB08 No.2 A/E L.O sump tank low level LAL B/I(NC) 3 15 LR A/E 2
GB09 No.2 A/E F.O leak tank high level LAH B/I(NC) 3 15 LR A/E 2
GB10 No.2 A/E Starting air inlet low press PAL B/I(NC) 8 3 2 PR A/E 2
GB11 No.2 A/E control air low press PAL B/I(NC) 6 2 2 PR A/E 2
GB12 No.2 A/E L.O strainer high diff. press. DPAH B/I(NC) 1 2 PR A/E 2
GB13 No.2 A/E exh. gas T/C outlet temperature TIAH PT100 0 700 Deg.C 500 2 2 TA A/E 2
GB14 No.2 A/E exh. gas T/C inlet temperature(no.1 ~ no.3 cyl.) TIAH PT100 0 700 Deg.C 580 2 2 TA A/E 2
GB15 No.2 A/E exh. gas T/C inlet temperature(no.4 ~ no.6 cyl.) TIAH PT100 0 700 Deg.C 580 2 2 TA A/E 2
GB16 No.2 A/E no.1 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA2 2 TA A/E 2 GA2 : Shutdown
GB17 No.2 A/E no.2 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA2 2 TA A/E 2 GA2 : Shutdown
GB18 No.2 A/E no.3 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA2 2 TA A/E 2 GA2 : Shutdown
GB19 No.2 A/E no.4 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA2 2 TA A/E 2 GA2 : Shutdown
GB20 No.2 A/E no.5 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA2 2 TA A/E 2 GA2 : Shutdown
GB21 No.2 A/E no.6 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA2 2 TA A/E 2 GA2 : Shutdown
GB22 No.2 A/E Cyl. Exh. Gas mean temp TI - 0 Deg.C - AMS - By software
GB23 No.2 A/E no.1 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GB24 No.2 A/E no.2 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GB25 No.2 A/E no.3 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
+, - '50 By software
GB26 No.2 A/E no.4 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GB27 No.2 A/E no.5 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GB28 No.2 A/E no.6 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GB29 No 2 A/E start failure XA B/I(NC) 3 2 RV A/E 2
GB30 No 2 A/E shut down system failure XA B/I(NC) 3 2 RV A/E 2
GB31 No 2 A/E electric power failure XA B/I(NC) 2 2 RV A/E 2
GB32 No 2 A/E CPU fault XA B/I(NC) 2 2 RV A/E 2

20
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
GB36 No.2 D/G Stator “R” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GB37 No.2 D/G Stator “S” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GB38 No.2 D/G Stator “T” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GB39 No.2 D/G fore bearing temperature TIAH PT100 0 200 Deg.C 90 3 2 TA D/G 2
GB40 No.2 D/G after bearing temperature TIAH PT100 0 200 Deg.C 90 3 2 TA D/G 2
GB41 No.2 A/E stop signal BL B/I(NC) A/E 2 BLOCK'G 6

21
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
GC01 No 3 A/E common shut down SHT B/I(NC) 2 2 RV A/E 2
(overspeed trip, C.F.W outlet high temperature trip,
L.O inlet low pressure trip, each cylinder Exhaust
gas high temperature trip)
GC02 No 3 A/E H.T C.F.W inlet pressure PIAL 4-20mA 0 6 Kg/cm2 1.3 3 7 2 PA A/E 2
GC03 No 3 A/E L.O inlet pressure PIAL 4-20mA 0 10 Kg/cm2 3.5 2 7 2 PA A/E 2
GC04 No 3 A/E F.O inlet low pressure PAL B/I(NC) 4.6 2 4,7 2 PR A/E 2
GC05 No.3 A/E H.T C.F.W outlet temperature TIAH PT100 0 200 Deg.C 95 2 2 TA A/E 2
GC06 No.3 A/E L.O inlet temperature TIAH PT100 0 200 Deg.C 75 3 2 TA A/E 2
GC07 No.3 A/E pre-lub. L.O inlet low pressure PAL B/I(NC) 3 2 PR A/E 2
GC08 No.3 A/E L.O sump tank low level LAL B/I(NC) 3 15 LR A/E 2
GC09 No.3 A/E F.O leak tank high level LAH B/I(NC) 3 15 LR A/E 2
GC10 No.3 A/E Starting air inlet low press PAL B/I(NC) 8 3 2 PR A/E 2
GC11 No.3 A/E control air low press PAL B/I(NC) 6 2 2 PR A/E 2
GC12 No.3 A/E L.O strainer high diff. press. DPAH B/I(NC) 1 2 PR A/E 2
GC13 No.3 A/E exh. gas T/C outlet temperature TIAH PT100 0 700 Deg.C 500 2 2 TA A/E 2
GC14 No.3 A/E exh. gas T/C inlet temperature(no.1 ~ no.3 cyl.) TIAH PT100 0 700 Deg.C 580 2 2 TA A/E 2
GC15 No.3 A/E exh. gas T/C inlet temperature(no.4 ~ no.6 cyl.) TIAH PT100 0 700 Deg.C 580 2 2 TA A/E 2
GC16 No.3 A/E no.1 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA3 2 TA A/E 2 GA3 : Shutdown
GC17 No.3 A/E no.2 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA3 2 TA A/E 2 GA3 : Shutdown
GC18 No.3 A/E no.3 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA3 2 TA A/E 2 GA3 : Shutdown
GC19 No.3 A/E no.4 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA3 2 TA A/E 2 GA3 : Shutdown
GC20 No.3 A/E no.5 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA3 2 TA A/E 2 GA3 : Shutdown
GC21 No.3 A/E no.6 cyl.exh. gas outlet temperature TIAH PT100 0 700 Deg.C 500 2 GA3 2 TA A/E 2 GA3 : Shutdown
GC22 No.3 A/E Cyl. Exh. Gas mean temp TI - 0 Deg.C - AMS - By software
GC23 No.3 A/E no.1 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GC24 No.3 A/E no.2 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GC25 No.3 A/E no.3 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
+, - '50 By software
GC26 No.3 A/E no.4 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GC27 No.3 A/E no.5 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GC28 No.3 A/E no.6 cyl. Exh. Gas Dev. temp TDIAH - 0 Deg.C -50 50 2 2 AMS -
GC29 No 3 A/E start failure XA B/I(NC) 3 2 RV A/E 2
GC30 No 3 A/E shut down system failure XA B/I(NC) 3 2 RV A/E 2
GC31 No 3 A/E electric power failure XA B/I(NC) 2 2 RV A/E 2
GC32 No 3 A/E CPU fault XA B/I(NC) 2 2 RV A/E 2

22
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
GC36 No.3 D/G Stator “R” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GC37 No.3 D/G Stator “S” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GC38 No.3 D/G Stator “T” temp TIAH PT100 0 200 Deg.C 150 3 2 TA D/G 2
GC39 No.3 D/G fore bearing temperature TIAH PT100 0 200 Deg.C 90 3 2 TA D/G 2
GC40 No.3 D/G after bearing temperature TIAH PT100 0 200 Deg.C 90 3 2 TA D/G 2
GC41 No.3 A/E stop signal BL B/I(NC) A/E 2 BLOCK'G 7
GC42
GC43
GC44

23
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
AB01 No.1 Aux. boiler common abnormal XA B/I(NC) 2 2 RV BLR 3
AB02 No.1 Aux. boiler common trip XA B/I(NC) 2 2 RV BLR 3
AB03 No.1 Aux. boiler frame failure XA B/I(NC) 2 2 RV BLR 3
AB04 No.1 Aux. boiler control power failure XA B/I(NC) 2 2 RV BLR 3
AB05 No.1 Aux. boiler combust. air fan abnormal stop XA B/I(NC) 2 2 RV BLR 3
AB06 No.1 Aux. boiler drum water level LIAHL 4-20mA -170 360 mm -100 150 3 8 15 PA BLR 3 W/IND ON ECC
AB07 No.1 Aux. boiler drum steam press PIAHL 4-20mA 0 25 Kg/cm2 4 17 3 8 2 PA BLR 3
AB08
AB09
AB10 No.1 Aux. Boiler smoke density high DAH B/I(NC) 2 2 RV BLR 3
AB11 No.1 Aux. boiler exhaust gas temp TIAH PT100 0 500 Deg.C 420 3 2 TA BLR 3
AB12 No.2 Aux. boiler common abnormal XA B/I(NC) 2 2 RV BLR 3
AB13 No.2 Aux. boiler common trip XA B/I(NC) 2 2 RV BLR 3
AB14 No.2 Aux. boiler frame failure XA B/I(NC) 2 2 RV BLR 3
AB15 No.2 Aux. boiler control power failure XA B/I(NC) 2 2 RV BLR 3
AB16 No.2 Aux. boiler combust. air fan abnormal stop XA B/I(NC) 2 2 RV BLR 3
AB17 No.2 Aux. boiler drum water level LIAHL 4-20mA -170 360 mm -100 150 3 9 15 PA BLR 3 W/IND ON ECC
AB18 No.2 Aux. boiler drum steam press PIAHL 4-20mA 0 25 Kg/cm2 4 17 3 9 2 PA BLR 3
AB19 No.2 Aux. Boiler smoke density high DAH B/I(NC) 2 2 RV BLR 3
AB20 No.2 Aux. boiler exhaust gas temp TIAH PT100 0 500 Deg.C 420 3 2 TA BLR 3
AB21 Aux. boiler F.O inlet low press XA B/I(NC) 2 2 RV BLR 3
AB22 Aux. boiler F.O inlet temp TIAHL 4-20mA 0 160 Deg.C 110 150 3 9 2 TA BLR 3
AB23 Aux. boiler F.O pump st-by start XA B/I(NC) 3 2 RV 3
AB24 Aux. boiler feeder water pump st-by start XA B/I(NC) 3 2 RV 3
AB25 Aux. boiler water circ. pump st-by start XA B/I(NC) 3 2 RV 3
AB26 Aux. boiler no.1 D.O ignition pump abnormal XA B/I(NC) 3 2 RV 3
AB27 Aux. boiler no.2 D.O ignition pump abnormal XA B/I(NC) 3 2 RV 3
AB28 Aux. boiler F.W cascade tank low level LAL B/I(NC) 3 15 LR BLR 3
AB29 Aux. boiler F.W cascade tank high level LAH B/I(NC) 3 15 LR BLR 3
AB30 Aux. boiler F.W observ. tank oil content high DAH B/I(NC) 3 2 RV BLR 3
AB31 Aux. boiler feed water salinity high SAH B/I(NC) 3 2 PR BLR 3 W/IND ON ECC
AB32 Economizer exh gas diff. Press high DPAH B/I(NC) 3 2 PR BLR 1 W/IND ON ECC
AB33 Economizer exh gas inlet temp TI PT100 0 500 Deg.C 3 2 TA BLR 3 W/IND ON ECC
AB34 Economizer exh gas outlet temp TI PT100 0 500 Deg.C 3 2 TA BLR 3 W/IND ON ECC
AB35

24
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
AB32 No.1 Aux. boiler stop BL B/I(NC) BLR 3 BLOCK'G 8
AB33 No.2 Aux. boiler stop BL B/I(NC) BLR 3 BLOCK'G 9
AB34
AB32
AB33
AB34
AB32
AB33
AB34
AB32
AB33
AB34
AB32
AB33
AB34
AB32
AB33
AB34
AB32
AB33
AB34
AB32
AB33
AB34
AB32
AB33
AB34
AB32
AB33
AB34
AB32
AB33
AB32
AB33
AB34

25
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
PU01 No.1 L.O Purifier run XI B/I(NO) 2 RV 3
PU02 No.2 L.O Purifier run XI B/I(NO) 2 RV 3
PU03 No.1 L.O Purifier common abnormal XA B/I(NC) 3 2 RV 3
PU04 No.2 L.O Purifier common abnormal XA B/I(NC) 3 2 RV 3
PU05 No.1 H.F.O/D.O Purifier run XI B/I(NO) 2 RV 3
PU06 No.2 H.F.O/D.O Purifier run XI B/I(NO) 2 RV 3
PU07 No.1 H.F.O/D.O Purifier common abnormal XA B/I(NC) 3 2 RV 3
PU08 No.2 H.F.O/D.O Purifier common abnormal XA B/I(NC) 3 2 RV 3
PU09 H.F.O sludge tank high level LAH B/I(NC) 3 15 LR 3
PU10 L.O sludge tank high level LAH B/I(NC) 3 15 LR 3
PU11
PU12
PU13
PU14
PU15
PU16

27
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
ES01 MSBD common abnormal XA B/I(NC) 3 2 RV 1
Bus high/low voltage, high/low frequency, pref. trip, over
current trip, ACB abnormal trip, em'cy trip circuit
failure,reverser power trip,ACB non close, auto synchro
failure
ES02 ESBD common abnormal XA B/I(NC) 3 2 RV 1
ES03 Em’cy generator common abnormal XA B/I(NC) 3 2 RV 1
ES04 Battery charger abnormal XA B/I(NC) 3 2 RV 3
ES05 MSBD AC 440V low insulation XA B/I(NC) 3 2 RV 1
ES06 MSBD AC 220V low insulation XA B/I(NC) 3 2 RV 1
ES07 Forecastle AC 220V low insulation XA B/I(NC) 3 2 RV 4
ES08 DC 24V low insulation XA B/I(NC) 3 2 RV 3
ES09 E.C.C AC 220V power failure XA B/I(NC) 3 2 RV 1
ES10 E.C.C DC 24V power failure XA B/I(NC) 3 2 RV 1
ES11 AMS UPS1 power failure(ECC) XA B/I(NC) 3 2 RV 1
ES12 AMS UPS2 power failure(ECC) XA B/I(NC) 3 2 RV 1
ES13 BMS UPS power failure XA B/I(NC) 3 2 RV 1
ES14 W/H control console AC power failure XA B/I(NC) 3 2 RV 3
ES15 W/H control console DC power failure XA B/I(NC) 3 2 RV 3
ES16 Cargo control console AC power failure XA B/I(NC) 3 2 RV 3
ES17 Cargo control console DC power failure XA B/I(NC) 3 2 RV 3
ES18 Nautical equipment power dist.(AC 220V) power failure XA B/I(NC) 3 2 RV 3
ES19 Nautical equipment power dist.(DC 24V) power failure XA B/I(NC) 3 2 RV 3
ES20 ESBD AC 440V low insulation XA B/I(NC) 3 2 RV 1
ES21 ESBD AC 220V low insulation XA B/I(NC) 3 2 RV 1
ES22
ES23
ES28
ES29
ES30
ES31
ES32
ES33
ES31
ES32
ES33

26
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
MP01 No.1 Main air compressor abnormal XA B/I(NC) 3 2 RV 3
MP02 No.2 Main air compressor abnormal XA B/I(NC) 3 2 RV 3
MP03 No.1 Main air reservoir press PIAL 4-20mA 0 40 Kg/cm2 15 2 2 PA 3 W/IND ON ECC
MP04 No.2 Main air reservoir press PIAL 4-20mA 0 40 Kg/cm2 15 2 2 PA 3 W/IND ON ECC
MP05 Em'cy air comp. abnormal XA B/I(NC) 3 2 RV 2
MP06 Control air comp. abnormal XA B/I(NC) 3 2 RV 2
MP07 Service air comp. abnormal XA B/I(NC) 3 2 RV 2
MP08 Incinerator run XI B/I(NO) 2 RV 3
MP09 Incinerator common abnormal XA B/I(NC) 3 2 RV 3
MP10 Incinerator W.O tank high levrl LAH B/I(NC) 3 15 LR 3
MP11 Incinerator W.O tank common abnormal XA B/I(NC) 3 2 RV 3
MP12 Sewage treatment unit common abnormal XA B/I(NC) 3 2 RV 2
MP13 Sewage collecting tank high level LAH B/I(NC) 3 15 LR 2
MP14 Bilge water separator run XI B/I(NO) 3 2 RV 4
MP15 Bilge water separator abnormal XA B/I(NC) 3 2 RV 4
MP16 Bilge water separator oil content high OAH B/I(NC) 3 2 RV 4
MP17 MGPS abnormal XA B/I(NC) 3 2 RV 4
MP18 ICCP(FWD) abnormal XA B/I(NC) 3 2 RV 4
MP19 ICCP(AFT) abnormal XA B/I(NC) 3 2 RV 4
MP20 Em’cy quick closing V/V air reservoir low press PAL B/I(NC) 3 2 PR 3
MP21 No.1 Control air dryer abnormal XA B/I(NC) 3 2 RV 2
MP22 No.2 Control air dryer abnormal XA B/I(NC) 3 2 RV 2
MP23 Waste oil tank high levrl LAH B/I(NC) 3 15 LR 4
MP24 E.C.R unit cooler abnormal XA B/I(NC) 3 2 RV 3
MP25 Air cond. Plant no.1 compressor run XI B/I(NO) 2 RV 3
MP26 Air cond. Plant no.2 compressor run XI B/I(NO) 2 RV 3
MP27 Air cond. Plant no.1 compressor abnormal XA B/I(NC) 3 2 RV 3
MP28 Air cond. Plant no.2 compressor abnormal XA B/I(NC) 3 2 RV 3
MP29 Air cond. Plant no.1 AHU fan abnormal XA B/I(NC) 3 2 RV 3
MP30 Air cond. Plant no.2 AHU fan abnormal XA B/I(NC) 3 2 RV 3
MP31 Prov. Ref. plant no.1 compressor abnormal XA B/I(NC) 3 2 RV 3
MP32 Prov. Ref. plant no.2 compressor abnormal XA B/I(NC) 3 2 RV 3
MP33 Prov. Ref. plant fan control panel abnormal XA B/I(NC) 3 2 RV 3
MP34 COPT condensate pump st'by start XA B/I(NC) 3 2 RV 4
MP35 Deck water seal pump st'by start XA B/I(NC) 3 2 RV 4

28
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
MP36 Signal light column power fail XA B/I(NC) 3 2 RV 1
MP37 Extension alarm system failure XA INT COM 7 2 RV AMS
MP38 Data logger failure XA INT COM 7 2 RV AMS
MP39 Auto pilot power failure XA B/I(NC) 2 2 RV 3
MP40 Auto pilot no.1 control motor failure(hyd. Lock) XA B/I(NC) 2 2 RV 3
MP41 Auto pilot no.2 control motor failure(hyd. Lock) XA B/I(NC) 2 2 RV 3
MP42 Gyro compass system abnormal XA B/I(NC) 2 2 RV 3
MP43 Public addressor main unit Power failure XA B/I(NC) 2 2 RV 3
MP44 Public addressor main unit system failure XA B/I(NC) 2 2 RV 3
MP45 VRC hyd. Power pack common abnormal XA B/I(NC) 3 2 RV 3
MP46 Oil discharge monitoring system abnormal XA B/I(NC) 3 2 RV 3
MP47 COPT vacuum condenser high level LAH B/I(NC) 3 15 LR 3
MP48 COPT vacuum condenser low level LAL B/I(NC) 3 15 LR 3
MP49 Inert gas system common abnomal XA B/I(NC) 3 2 RV 3
MP50 Co2 alarm reley box power failure XA B/I(NC) 3 2 RV 3
MP51 E/R Co2 release XA B/I(NC) 5 2 RV 3
MP52 Pump room Co2 release XA B/I(NC) 5 2 RV 3
MP53 Fire detection system common fault XA B/I(NC) 2 2 RV 3
MP54 Fire alarm XA B/I(NC) 5 2 RV 3
MP55 Local fire fighting system(LFFS) common abnormal XA B/I(NC) 3 2 RV 3
MP56 Local fire fighting system(LFFS) release XA B/I(NC) 5 2 RV 3
MP57 H.F.O Transfer pump abnormal XA B/I(NC) 3 2 RV 3
MP58 M.D.O Transfer pump abnormal XA B/I(NC) 3 2 RV 3
MP59 L.O Transfer pump abnormal XA B/I(NC) 3 2 RV 4
MP60 H.W circulating pump abnormal XA B/I(NC) 3 2 RV 3
MP61 Fresh water generator run XI B/I(NO) 2 RV 4
MP62 Fresh water generator salinity high SAH B/I(NC) 3 2 RV 4
MP63 Fresh water generator common abnormal XA B/I(NC) 3 2 RV 4
MP64 Fire main line press PI 4-20mA 0 10 Kg/cm2 PA 3 W/IND ON BCC,CCC

MP65 Meat room temp TIAH PT100 -50 50 Deg.C -18 3 30 TA 2


MP66 Fish room temp TIAH PT100 -50 50 Deg.C -18 3 30 TA 2
MP67 Vegetable room temp TIAH PT100 -50 50 Deg.C 6 3 30 TA 2
MP68 Dairy room temp TIAH PT100 -50 50 Deg.C 4 3 30 TA 2
MP69 Personnal alarm XA B/I(NC) 4 2 RV 1
MP70 Bilge holding tank high temperature TAH B/I(NC) 3 2 TR 4

29
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
MP71 No.1 Steering gear common abnormal XA B/I(NC) 2 2 RV 2
No.1 Steering gear overload
No.1 Steering gear motor phase fail
No.1 Steering gear no voltage
No.1 Steering gear control power fail
No.1 Steering gear Hyd. oil tank low level

MP72 No.2 Steering gear common abnormal XA B/I(NC) 2 2 RV 2


No.2 Steering gear overload
No.2 Steering gear motor phase fail
No.2 Steering gear no voltage
No.2 Steering gear control power fail
No.2 Steering gear Hyd. oil tank low level
MP73 Gas sampling system failure(pump room) XA B/I(NC) 3 2 RV 2
MP74 Gas sampling system failure(ballast tanks) XA B/I(NC) 3 2 RV 2
MP75 Gas sampling system gas detection(pump room) XA B/I(NC) 3 2 RV 2
MP76 Gas sampling system gas detection(ballast tanks) XA B/I(NC) 3 2 RV 2
MP77 Prov. Ref. plant no.1 compressor run XI B/I(NO) 2 RV 4
MP78 Prov. Ref. plant no.2 compressor run XI B/I(NO) 2 RV 4
MP79 L.O drain tank high level LAH B/I(NC) 3 15 LR 4
MP80 Automatic valve control system power failure XA B/I(NC) 3 2 RV 1
MP81 COPT vacuum condenser high pressure PAH B/I(NC) 3 2 PR 4

30
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
FT01 H.F.O overflow tank high level LAH B/I(NC) 3 15 LR 4
FT02 No.1 H.F.O bunker tank(port) high level LAH B/I(NC) 3 15 LR 3 W/IND ON ECC
FT03 No.1 H.F.O bunker tank(stbd) high level LAH B/I(NC) 3 15 LR 3 W/IND ON ECC
FT04 No.2 H.F.O bunker tank(port) high level LAH B/I(NC) 3 15 LR 3 W/IND ON ECC
FT05 H.F.O L.S bunker tank(stbd) high level LAH B/I(NC) 3 15 LR 3 W/IND ON ECC
FT06 H.F.O settl'g tank low level LAL B/I(NC) 3 15 LR 3
FT07 H.F.O settl'g tank high level LAH B/I(NC) 3 15 LR 3
FT08 H.F.O settl'g tank high temp TAH B/I(NC) 3 2 TR 3
FT09 H.F.O L.S settl'g tank low level LAL B/I(NC) 3 15 LR 3
FT10 H.F.O L.S settl'g tank high level LAH B/I(NC) 3 15 LR 3
FT11 H.F.O L.S settl'g tank high temp TAH B/I(NC) 3 2 TR 3
FT12 H.F.O Service tank low level LAL B/I(NC) 3 15 LP 3
FT13 H.F.O Service tank high temp TAH B/I(NC) 3 2 TR 3
FT14 H.F.O L.S Service tank low level LAL B/I(NC) 3 15 LP 3
FT15 H.F.O L.S Service tank high temp TAH B/I(NC) 3 2 TR 3
FT16 D.O settl'g tank low level LAL B/I(NC) 3 15 LR 3
FT17 D.O settl'g tank high level LAH B/I(NC) 3 15 LR 3
FT18 D.O service tank low level LAL B/I(NC) 3 15 LR 3
FT19 M.D.O Storage tank(stbd) high level LAH B/I(NC) 3 15 LP 3 W/IND ON ECC
FT20 Em'cy Gen. D.O tank low level LAL B/I(NC) 3 15 LR 3
FT21
FT22
FT23
FT24
FT25

31
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.
BS01 E/R FWD Port bilge high level LAH B/I(NC) 6 15 LR 4
BS02 E/R FWD Stbd bilge high level LAH B/I(NC) 6 15 LR 4
BS03 E/R AFT Bilge high level LAH B/I(NC) 6 15 LR 4
BS04 Bilge holding tank high level LAH B/I(NC) 6 15 LR 4
BS05 E/R M/E sunken area bilge high level LAH B/I(NC) 3 15 LR 4
BS06 Hull part bilge high level(common) LAH B/I(NC) 6 15 LR 4
Bosun store bilge high level(port) alarm on CCC
Bosun store bilge high level(stbd) alarm on CCC
Bosun store bilge high level(center) alarm on CCC
EM'CY fire pump room bilge high level alarm on CCC
Steering gear room bilge high level(port) alarm on CCC
Steering gear room bilge high level(stbd) alarm on CCC
Pump room bilge high level(port) alarm on CCC
Pump room bilge high level(stbd)) alarm on CCC
BS07
BS08
BS09
BS10

32
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.

Output signal for BMS (slow down signal)

BO01 M/E Main L.O inlet low pressure XO B/O(NO) RV AMS 1


BO02 M/E P.C.O inlet low pressure XO B/O(NO) RV AMS 1
BO03 M/E Jacket C.F.W inlet low pressure XO B/O(NO) RV AMS 1
BO04 M/E thrust pad high temperature XO B/O(NO) RV AMS 1
BO05 M/E Main L.O inlet high temperature XO B/O(NO) RV AMS 1
BO06 M/E P.C.O inlet high temperature XO B/O(NO) RV AMS 1
BO07 M/E P.C.O outlet high temperature XO B/O(NO) RV AMS 1
BO08 M/E Jacket C.F.W outlet high temperature XO B/O(NO) RV AMS 1
BO09 M/E cyl. Scavenge air outlet high temperature XO B/O(NO) RV AMS 1
BO10 M/E camshaft bearing high temperature XO B/O(NO) RV AMS 1
BO11 M/E P.C.O. non flow XO B/O(NO) RV AMS 1
BO12 M/E thrust radial bearing high temperature XO B/O(NO) RV AMS 1
BO13 M/E Main bearing temperature(cylinder) XO B/O(NO) RV AMS 1
BO14 M/E T/C L.O inlet low pressure XO B/O(NO) RV AMS 1
BO15 M/E cyl. Exh. Gas outlet high temperature XO B/O(NO) RV AMS 1
BO16 M/E cyl. Exh. Gas Dev. high/low temperature XO B/O(NO) RV AMS 1
BO17 M/E T/C Exh. Gas inlet high temperature XO B/O(NO) RV AMS 1

Output signal for misc.

BO18 E/R alarm(for signal light column) XO B/O(NO) RV AMS 1


BO19 personnal alarm auto start XO B/O(NO) RV AMS 1

Output signal for A/E (shut down signal)

BO20 No.1 A/E cyl. Exh. Gas outlet high temperature XO B/O(NO) RV AMS 1
BO21 No.1 A/E cyl. Exh. Gas outlet high temperature XO B/O(NO) RV AMS 1
BO22 No.1 A/E cyl. Exh. Gas outlet high temperature XO B/O(NO) RV AMS 1

33
LIST OF ALARM / MONITORING POINTS
TAG Signal Range Alarm (set value) AL. BL. AC. Time Test DPU
Description Code Unit Supplier Remarks
NO. Type Min Max L.L L H H.H GRP. GRP. GRP. Delay method no.

Output signal for ECC (press/temp/level gauge)

AO01 M/E Main L.O inlet pressure (TAG. NO. ML01) AO 4-20mA RV AMS 1
AO02 M/E Main P.C.O inlet pressure (TAG. NO. ML02) AO 4-20mA RV AMS 1
AO03 M/E F.O inlet pressure (TAG. NO. MF01) AO 4-20mA RV AMS 1
AO04 M/E A/C C.F.W inlet pressure (TAG. NO. MC01) AO 4-20mA RV AMS 1
AO05 M/E Jacket C.F.W inlet pressure (TAG. NO.MC03) AO 4-20mA RV AMS 1
AO06 M/E Scav. Air inlet pressure (TAG NO. MA07) AO 4-20mA RV AMS 1
AO07 M/E Starting air press (TAG NO. MS21) AO 4-20mA RV AMS 1
AO08 M/E Control air pressure (TAG NO. MS22) AO 4-20mA RV AMS 1
AO09 NO.1 Aux. boiler drum water level (TAG NO. AB06) AO 4-20mA RV AMS 1
AO10 NO.2 Aux. boiler drum water level (TAG NO. AB17) AO 4-20mA RV AMS 1
AO11 No.1 Main air reservoir press (TAG NO. MP03) AO 4-20mA RV AMS 1
AO12 No.2 Main air reservoir press (TAG NO. MP04) AO 4-20mA RV AMS 1
AO13 Economizer exh gas diff. pressure(TAG NO. AB32) AO 4-20mA RV AMS 1
AO14 Economizer exh gas inlet temperature(TAG NO. AB33) AO 4-20mA RV AMS 1
AO15 Economizer exh gas outlet temperature9TAG NO. AB34) AO 4-20mA RV AMS 1

AO16 Fire main line pressure (TAG NO. MP64) for CCC AO 4-20mA RV AMS 1 loop circuit
Fire main line pressure (TAG NO. MP64) for W/H C.C loop circuit

34